6827377 TURCK | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 4

Technical content

Edition • 2023-07-21T16:18:53+02:00 Gateway for the BL20 I/O System High-Feature Interface for PROFINET (IRT) BL20-E-GW-PN Type BL20-E-GW-PN ID 6827377 Supply voltage 24 VDC System power supply 24 VDC / 5 VDC Field supply 24 VDC Admissible range 18…30 VDC Nominal current from module bus ð 200 mA Max. field supply current 8 A Max. system supply current 0.8 A Voltage supply connection Push-in terminals System data Max. number of I/O modules 72 Transmission rate 10/100 Mbps; full/half duplex; auto negotiation; auto crossing Connection technology Ethernet 2 × RJ45 female connector Service interface Mini USB PROFINET Addressing DCP Conformance class C (IRT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) not supported Dimensions (W x L x H) 33.5 x 129.5 x 74.4 mm Approvals CE Ambient temperature 0…+55 °C Storage temperature -25…+85 °C Relative humidity 15…95 %, no condensation allowed Vibration test Acc. to EN 61131 Shock test Acc. to IEC 60068-2-27 Drop and topple acc. to IEC 68-2-31 and free fall to IEC 68-2-32 Electromagnetic compatibility Acc. to EN 50082-2 Protection class IP20 ■ Protection class IP20 ■ 2 x end brackets BL20-WEW35/2-SW ■ 1 x end plate BL20-ABPL ■ LEDs for display of supply voltage, group and bus errors ■ Gateway between the BL20 system and PROFINET (IRT) ■ Supports topology recognition and LLDP ■ 10/100 Mbps, Auto MDIX ■ 2 x RJ45 port Attention: This gateway is nearing the end of the product life cycle Field/System Supply Functional principle BL20 gateways are the head component of a BL20 station. They are designed to inter- face the modular fieldbus nodes to the high- er level fieldbus (PROFIBUS-DP, DeviceNet, CANopen, Ethernet). All BL20 electronic modules communicate over the internal module bus, the data of which is transferred to the fieldbus via the gateway, so that all I/O modules can be con- figured independently of the bus system.

Edition • 2023-07-21T16:18:53+02:00 Included in delivery 2 x end brackets BL20-WEW-35/2-SW, 1 x end plate BL20-ABPL

Edition • 2023-07-21T16:18:53+02:00 Anschlussübersicht PROFINET Fieldbus cable (example): RJ45S-RJ45S-441-2M (ident no. 6932517) or RJ45-FKSDD-441-0,5M/S2174 (ident no. 6914221) Pin Assignment Power Supply The USYS system supply feeds power to the gateway and the I/O modules. The UL field supply feeds power to the sensors and actuators. Pin Assignment

Edition • 2023-07-21T16:18:53+02:00 Accessories Type code Ident-No. Dimension drawing BL20-ABPL (2 PCS.) 6827123 End plate for a BL20 station after the last I/O module (2 pieces) BL20-WEW-35/2-SW (10 PCS.)

6827124 End bracket for fixation of a BL20 station (10 pieces)