BD-SS GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- Transmitter/receiver built into same unit.
- Six user-selectable sensitivity levels.
- 16' to 328' (use BEAMLRK beyond 230') protection range.
- Removable plug-in terminal blocks.
- Digital display — no special tools required.
- Built-in automatic gain control compen- sates for signal deterioration from dust buildup.
- Optional remote test station.
- Optional long-range kit (BEAMLRK) for applications in excess of 230' (70 m).
- Optional multi-mount kit (BEAMMMK) providing ceiling or wall mount capability with increased angular adjustment.
- Optional heater kits (BEAMHK and BEAMHKR) for prevention of condensa- tion (not intended to increase or reduce the specified operating temperature).ing service. Listings Listings and approvals below apply to the basic BD-SS and BDT-SS beam smoke detectors. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
- UL Listed: file S1195.
- FM approved.
- MEA approved: file 269-04-E.
- CSFM approved: file 7260-1288:171. BD-SS and BDT-SS Single-Ended, Reflected-Type, Addressable Beam Smoke Detector with SmartScan™ BD-SS with reflective plate (top); and with BEAMMMK
BD-SS and BDT-SS CS-2516 09/01/06Page 2 of 4 digital display will illuminate and read the current sensitivity setting in percent obscuration. To change the sensitivity, continue to depress the sensitivity switch until the desired setting is achieved. The digital display will turn off automatically if no further switch presses occur. In addition to the four standard sensitivity selections, the detector has two Acclimate™ settings. When either Acclimate™ setting is chosen, the detec- tor will automatically adjust its sensitivity using advanced software algo- rithms to select the optimum sensitivity for the environment. The sensitiv- ity will be continuously adjusted within the ranges specified in the chart above. Total obscuration can be converted to percent per foot, assuming uniform smoke density for the entire length of the beam. The chart below converts total obscuration percent per foot for all acceptable sensitivity settings. Specifications Operational Specifications Protection range 16 to 230 feet (5 to 70 m), 230 to 328 feet (70 to 100 m) using optional BEAMLRK kit. Adjustment angle ±10° horizontal and vertical. Note that the optics move independently of the unit. Sensitivity (6 levels)
- Level 1 — 25%.
- Level 2 — 30%.
- Level 3 — 40%.
- Level 4 — 50%.
- Acclimate™ Level 5 — 30% to 50%.
- Acclimate™ Level 6 — 40% to 50%. Fault condition (trouble)
- 96% or more obscuration blockage.
- In alignment mode.
- Improper initial alignment.
- Self-compensation limit reached. Alignment aid
- Optical gunsight.
- Integral signal strength indication.
- Two-digit display. Indicators
- Alarm — local red LED and remote alarm.
- Trouble — local yellow LED and remote trouble.
- Normal — local flashing green LED. Test/reset features
- Integral sensitivity test filter (BDT-SS only, requires external power supply).
- Sensitivity filter (incremental scale on reflector).
- Local alarm test switch.
- Local alarm reset switch.
- Remote test and reset switch (compatible with RTS451 and RTS451KEY test stations). Smoke detector spacing On smooth ceilings, 30 – 60 feet (9.1 to 18.3 m) between projected beams and not more than one-half that spacing between a projected beam and a sidewall. Other spacing may be used depending on ceiling height, airflow characteristics, and response requirements. See NFPA 72. Sensitivity Setting Percent Obscuration Display Reading Acceptable DISTANCE between detector and reflector (ft) Acceptable DISTANCE between detector and reflector (m) Level 1 25% 25 16.4 to 120 5.0 to 36.6 Level 2 30% 30 25 to 150 7.6 to 45.7 Level 3 40% 40 60 to 220 18.3 to 67 Level 4 50% 50 80 to 328 24.4 to 100 Acclimate™ Level 1 30% to 50% A1 80 to 150 24.4 to 45.7 Acclimate™ Level 2 40% to 50% A2 80 to 220 24.4 to 67 6985sens.tbl Reflector Mounting Guidelines 6985mt2.wmf 6985mt1.wmf
BD-SS and BDT-SS CS-2516 09/01/06 Page 3 of 4 Specifications Environmental Specifications Temperature –22°F to 131°F (–30°C to 55°C). Humidity 10 – 93% RH noncondensing. Electrical Specifications Voltage 15 to 32 VDC. Average standby current
24 VDC: 2 mA maximum (LED flashing,
SLC @ 24 V). LED current 6.5 mA maximum. Remote annunciator current 11.2 mA maximum. Average current during testing 500 mA maximum. Alarm current 24 VDC; 8.5 mA maximum (LED on). Trouble/fault current 24 VDC; 4.5 mA maximum (LED on). Fault condition current Add to standby current; 100 mA maximum. Alignment mode current 24 VDC; 20 mA maximum. External supply (BDT-SS only) Voltage: 15 to 32 VDC. Current: 0.5 A maximum. Remote output (alarm) Voltage: 15 to 32 VDC. NOTE: Output voltage is the same as device input voltage. Current: 15 mA maximum, 6 mA minimum. NOTE: Output current is limited by 2.2K ohm resistor. Heater kit BEAMHK Voltage: 15 to 32 V. Current: 92 mA maximum @ 32 V (heater only). Power consumption: nominal 1.6 W @ 24 V; maximum 3.0 W @ 32 V. Heater kit BEAMHKR Voltage: 15 to 32 V. Current: 450 mA maximum @ 32 V (per reflector). Power consumption (per reflector): nominal 7.7 W @ 24 V; maximum 15.0 W @ 32 V. Mechanical Specifications Detector dimensions 10.0" H x 7.5" W x 3.3" D (254 mm H x 191 mm W x 84 mm D). Reflector dimensions For 16' to 230' (5 to 70 m) applications: For applications beyond 230'/70 m: 15.7" x 18.1" (400 x 460 mm). Switch Locations Wiring Diagram Wiring Diagram (with RTS451/KEY) g2516w1.wmf 6985swlo.wmf BD-SS / BDT-SS
BD-SS and BDT-SS CS-2516 09/01/06Page 4 of 4 Gamewell-FCI
12 Clintonville Road
Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Alignment Adjustment Locations Housing Screw Locations
Ordering Information
BD-SS Intelligent beam smoke detector BD-SSA Same as BD-SS with ULC Listing. BDT-SS Intelligent beam smoke detector with integral sensitivity test. BDT-SSA Same as BDT-SS with ULC Listing. BEAMLRK Long range accessory kit (required for applica- tions in excess of 230 ft/70 m) . BEAMMMK Multi-mount kit (provides ceiling or wall mount capability with increased angular adjustment). BEAMSMK Surface-mount kit. RTS451 Remote test station. RTS451KEY Remote test station with key lock. BEAMHK Heating kit for use with the transmitter/receiver unit of BDT-SS. For prevention of condensation. BEAMHRK Heating kit for use with the reflector of BDT-SS. For prevention of condensation. Parts List Item Quantity Acclimate™ is a trademark of System Sensor, a Honeywell company. SmartScan™ is a trademark of Gamewell.