MODEL: B3HU B3HU SPECIFICATIONS ES-7502 Rev.14 Page 1/5 http://www.m-system.co.jp/ Space-saving Two-wire Signal Conditioners B3-UNIT 2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER (HART communication, intrinsically safe) Functions & Features
- Universal input: mV, V, T/C, RTD, resistance, potentiometer and DC voltage
- High accuracy
- HART communication
- Intrinsically safe approval
- Programming via hand-held communicator or via PC
- A wide variety of T/C and RTD types
- User’s temperature table can be used
- Self diagnostics
- Input-output isolated mm (inch) 110.5 (4.35) 18 (.71) 106 (4.17) MODEL: B3HU–[1]/A
ORDERING INFORMATION
- Code number: B3HU-[1]/A Specify a code from below for [1]. (e.g. B3HU-0/A)
- Use Ordering Information Sheet (No. ESU-7502). Factory standard setting will be used if not otherwise specified.
- Specify the country in which the product is to be used with the Safety Approval code 2. [1] SAFETY APPROVAL 0: None 1: FM intrinsically safe 2: ATEX intrinsic safety OPTIONS CJC Sensor /A: External Sensor (must be specified)
RELATED PRODUCTS
- USB interface Bell202 modem (model: COP-HU) Usable in ‘non-hazardous’ area only.
- Hand-held communicator (Consult HART Communication Foundation (HCF) web site: www.hartcomm.org. )
- AMS (version 6.0 or higher)
- Simatic PDM (version 6.0 or higher)
- PC configurator software (model: B3HUCFG) Downloadable at M-System’s web site. GENERAL SPECIFICATIONS Construction: Small-sized front terminal structure Connection: Euro type connector terminal (Applicable wire size: 0.2 - 2.5 mm2 (pin terminals: 0.2 - 1.5 mm2), stripped length 8 mm) Housing material: Flame-resistant resin (gray) Isolation: Input to output Burnout (except DC voltage input): Upscale, downscale or no burnout selectable (standard: upscale); Also detects wire breakdown and overrange input exceeding the electrical design limit for DC voltage input. Cold junction compensation (T/C): CJC sensor (included) to be attached to the input terminals User-configurable items:
- Input sensor type
- Number of wires (RTD & resistance)
- Input range
- Inverted output
- Burnout
- Damping time (via HART only, standard: 0)
- Sensor calibration (via HART only)
- Output calibration
- Special linearization data (via HART only)
- HART communication mode HART COMMUNICATION Protocol: HART communication protocol HART address range: 0 – 15 (factory set to 0) Transmission speed: 1200 bps Digital current: Approx. 1 mAp-p when communicating Character format: 1 Start Bit, 8 Data Bits, 1 Odd Parity Bit,
1 Stop Bit
Distance: 1.5 km (0.9 miles) HART communication mode: Master-Slave Mode and Burst Mode (factory set to Master-Slave) HART network mode: Point-to-Point Mode and Multi-drop Mode; automatically set to Multi-drop Mode when the address is set to other than 0.
MODEL: B3HU B3HU SPECIFICATIONS ES-7502 Rev.14 Page 2/5 http://www.m-system.co.jp/ INPUT SPECIFICATIONS The input type is factory-set to K thermocouple, and the input range to 0 to 100°C. See Table 1 for the available input type, the minimum span, and the maximum range. ■ DC mV & V Input resistance: ≥ 1 MΩ ■ Thermocouple Input resistance: ≥ 1 MΩ Burnout sensing: 130 nA ±10 % ■ RTD (2-wire, 3-wire or 4-wire) Excitation: 0.2 mA ± 10 % Allowable leadwire resistance: Max. 20 Ω per wire ■ Resistance (2-wire, 3-wire or 4-wire) Excitation: 0.2 mA ±10 % Allowable leadwire resistance: Max. 20 Ω per wire ■ Potentiometer Excitation: 0.2 mA ±10% Allowable leadwire resistance: Max. 20 Ω per wire OUTPUT SPECIFICATIONS Output range: 4 – 20 mA DC Operational range: 3.8 – 21.6 mA Load resistance vs. supply voltage: Load Resistance (Ω) = (Supply Voltage (V) – 12 (V)) ÷ 0.024 (A) (including leadwire resistance) INSTALLATION Supply voltage
- 12 – 42 V DC (non-approved)
- 12 – 28 V DC (approved) Operating temperature: -40 to +85°C (-40 to +185°F) (See Safety Parameters for use in a hazardous location.) Operating humidity: 0 to 95 %RH (non-condensing) Mounting: DIN rail Weight: 80 g (2.8 oz) PERFORMANCE Accuracy: See Table 1 and ‘Explanations of Terms.’ Cold junction compensation error: ±0.5℃ (±0.9°F) Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) of max. span at -5 to +55°C [23 to 131°F] Start-up time: Approx. 8 sec. Response time: ≤ 2 sec. (0 – 90 %) with damping time set to 0 and when not communicating via HART. Supply voltage effect: ±0.003 % × [Output Span] / 1 V Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @1 minute (input to output to ground) EXPLANATIONS OF TERMS ■ ACCURACY This transmitter’s accuracy is theoretically defined as the addition of A/D and D/A conversion errors: Accuracy = A/D Conversion Error + D/A Conversion Error The A/D conversion error means that measured as HART signal which is A/D converted from the analog input signal. The D/A conversion error of this transmitter is relatively very small so that it does not really affect the unit’s overall performance. The “Accuracies” given in Table 1 therefore equals the A/D conversion error. The temperature drift (coefficient) or the cold junction compensation error is not included in the “Accuracy.” ■ CALCULATION EXAMPLES OF OVERALL ACCURACY IN %
- DC Voltage 1) 0 – 200 mV Absolute value accuracy (Table 1): 40 μV 40 μV ÷ 200000 μV × 100 = 0.02 % < 0.1 % ➠ Overall accuracy = ±0.1% of span 2) 0 – 4 mV Absolute value accuracy (Table 1): 10 μV 10 μV ÷ 4000 μV × 100 = 0.25 % > 0.1% ➠ Overall accuracy = ±0.25 % of span
- Thermocouple 1) K thermocouple, 0 – 1000°C Absolute value accuracy (Table 1): 0.25°C CJC error (0.5°C) added: 1 + 0.5 = 1.5°C ➠ Overall accuracy including CJC error = ±0.15 % of span 2) K thermocouple, 50 – 150°C Absolute value accuracy (Table 1): 0.25°C CJC error (0.5°C) added: 0.25 + 0.5 = 0.75°C ➠ Overall accuracy including CJC error = ±0.75 % of span
- RTD 1) Pt 100, -200 – 800°C Absolute value accuracy (Table 1): 0.15°C ➠ Overall accuracy = ±0.1 % of span 2) Pt 100, 0 – 100°C Absolute value accuracy (Table 1): 0.15°C ➠ Overall accuracy = ±0.15 % of span
MODEL: B3HU B3HU SPECIFICATIONS ES-7502 Rev.14 Page 3/5 http://www.m-system.co.jp/ STANDARDS & APPROVALS EU conformity: ATEX Directive Ex ia EN 60079-11 EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 RoHS Directive EN 50581 Safety approval: FM: Intrinsically safe Class I, Div. 1, Groups A, B, C and D Class I, Zone 0, AEx ia IIC T4 and T5 (Class 3610) ATEX: Intrinsic safety II 1G, Ex ia II C; T4 and T5 (EN 60079-0) (EN 60079-11) SAFETY PARAMETERS Operating temperature For ATEX / FM: T4: -40 to +80°C T5: -40 to +55°C Ex-data:
- Output circuit Ui (Vmax): 30 V DC Ii (Imax): 96 mA DC Pi (Pmax): 0.72 W Ci: 1 nF Li: 0 mH
- Sensor circuit Uo (Voc): 6.4 V DC Io (Isc): 30 mA DC Po: 48 mW Co (Ca): 20 μF Lo (La): 10 mH
MODEL: B3HU B3HU SPECIFICATIONS ES-7502 Rev.14 Page 4/5 http://www.m-system.co.jp/ INPUT TYPE, RANGE & ACCURACY ■ INPUT TYPE, RANGE & ACCURACY INPUT TYPE MIN. SPAN MAXIMUM RANGE ACCURACY DC mV & V 4 mV -50 to +1000 mV ±0.1 % or ±10 μV, whichever is greater (F .S. input ≤ 50 mV) ±0.1 % or ±40μV, whichever is greater (F .S. input ≤ 200 mV) ±0.1 % or ±60μV, whichever is greater (F .S. input ≤ 500 mV) ±0.1 % or ±80μV, whichever is greater (F .S. input > 500 mV) Potentiometer 2 % Total resicetance 150 to 4000Ω ±0.1 % Resistance 10Ω 0 to 4000Ω ±0.1 % or ±0.1Ω, whichever is greater.* 2 THERMOCOUPLE °C °F MIN. SPAN MAXIMUM RANGE CONFORMANCE RANG ACCURACY MIN. SPAN MAXIMUM RANGE CONFORMANCE RANG ACCURACY (PR) K (CA) E (CRC) 0 to 1760 -270 to +1370 -270 to +1000 0 to 1760 -150 to +1370 -170 to +1000 ±1.00 ±0.25 ±0.20 32 to 3200 -454 to +2498 -454 to +1832 32 to 3200 -238 to +2498 -274 to +1832 ±1.80 ±0.45 ±0.36 J (IC) T (CC) B (RH) -210 to +1200 -270 to +400 100 to 1820 -180 to +1200 -170 to +400 400 to 1760 ±0.25 ±0.25 ±0.75 +346 to +2192 -454 to +752 212 to 3308 -292 to +2192 -274 to +752 752 to 3200 ±0.45 ±0.45 ±1.35 R S C (WRe 5-26) -50 to +1760 -50 to +1760 0 to 2315 200 to 1760 0 to 1760 0 to 2315 ±0.50 ±0.50 ±0.25 -58 to +3200 -58 to +3200 32 to 4199 392 to 3200 32 to 3200 32 to 4199 ±0.90 ±0.90 ±0.45 N U L P (Platinel II) -270 to +1300 -200 to +600 -200 to +900 0 to 1395 -130 to +1300 -200 to +600 -200 to +900 0 to 1395 ±0.30 ±0.20 ±0.25 ±0.25 -454 to +2372 -328 to +1112 -328 to +1652 32 to 2543 -202 to +2372 -328 to +1112 -328 to +1652 32 to 2543 ±0.54 ±0.36 ±0.45 ±0.45 RTD °C °F MIN. SPAN MAXIMUM RANGE ACCURACY MIN. SPAN MAXIMUM RANGE ACCURACY Pt 100 (JIS ’97, IEC) Pt 200 Pt 300 -200 to +850 -200 to +850 -200 to +850 ±0.15 ±0.15 ±0.15 -328 to +1562 -328 to +1562 -328 to +1562 ±0.27 ±0.27 ±0.27 Pt 400 Pt 500 Pt 1000 -200 to +850 -200 to +850 -200 to +850 ±0.15 ±0.15 ±0.15 -328 to +1562 -328 to +1562 -328 to +1562 ±0.27 ±0.27 ±0.27 Pt 50 Ω (JIS ’81) JPt 100 (JIS ’89) Ni 100 -200 to +649 -200 to +510 -80 to +260 ±0.15 ±0.15 ±0.15 -328 to +1200 -328 to +950 -112 to +500 ±0.27 ±0.27 ±0.27 Ni 120 Ni 508.4 Ω Ni-Fe 604 CU10 @ 25°C -80 to +260 -50 to +200 -200 to +200 -50 to +250 ±0.15 ±0.15 ±0.15 ±0.50 -112 to +500 -58 to +392 -328 to +392 -58 to +482 ±0.27 ±0.27 ±0.27 ±0.90 *1. [Accuracy or ±0.1% of span, whichever is greater] + Cold Junction Compensation Error. *2. Or ±0.1% of span, whichever is greater. (For 2- or 3-wire resistance or RTD, the value is valid by the sensor calibration after the wiring is done.)
MODEL: B3HU B3HU SPECIFICATIONS ES-7502 Rev.14 Page 5/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 10 11 12 4 5 6 1 2 3 7 8 9 106 (4.17) 110.5 (4.35) 62 (2.44) [5 (.20)] DIN RAIL 35mm wide
- When mounting, no extra space is needed between units. 18 (.71) (.28) CJC SENSOR* (model: CJM) *Used only with a thermocouple input SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM POTDC mV A A B B RTD & Resistance 4-wire T/C3-wire2-wire A B B A B Output Driver Output Computation Input Computation HART Comm. Low Drift Amplifier *1*1 Isolation LOADOUTPUT 24V DC 4 – 20mA DC Hazardous Area Safe Area Safety Barrier Close across the terminals 1 & 2 for a resistance or RTD input. Limited to 250 – 1100Ω for HART communication. A safety barrier must be installed for the intrinsic safety. The safety barrier must meet the Ex-data of this unit and must be approved for the hazardous location. CJC *1. *2. *3. *4. Replace the Terminal Block (4 – 5 – 6) with the one connected with the CJC Sensor, included in the package. Specifications are subject to change without notice.