B25832F4105K001 EPCOS | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 10
Technical content
Ordering code: B25832 Date: September 2005 © EPCOS AG 2005. Reproduction, publication and disseminat ion of this data sheet, enclosures hereto and the information contained therein without EPCO S' prior express consent is prohibited.
Please read Cautions and warnings and 2 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832
Features
■ Compact design ■ Long-term stability and reliability
Applications
■ For commutation in the low-frequency range Construction ■ Self-healing ■ Plastic dielectric ■ Oil-impregnated tubular windings (no PCB) ■ Metal-sprayed end faces ensure reliable contacting ■ Cylindrical aluminum case ■ Ceramic or plastic lead-throughs ■ Mounting bolts M8 or M12 Terminals ■ Tab connectors 6.3 mm ■ Dual tab connectors 6.3 mm Mounting ■ If the vibration stress is ≤ 5 g and the capacitors are ≤ 60 mm in diameter, the bolt is used for mounting. Grounding ■ Mounting bolts for grounding in accordance with VDE 0100 ■ Grounding identification in accordance with DIN 40 011 Individual data sheets Individual data sheets contain detailed specification incl. thermal data. Upon request, these data sheets are available for each capacitor type.
Please read Cautions and warnings and 3 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 Technical data Standards IEC 1071-1/2 EN 61071-1/2 VDE 0560 part 120 and 121 Dielectric dissipation factor tan δ0 2 · 10–4 Capacitance tolerance ± 10 % Max. repetitive rate of voltage rise (dv/dt) max Max. non-repetitive rate of voltage rise (dv/dt) s Climatic data: Min. operating temperature T min – 25 °C Max. operating temperature T max + 85 °C Average relative humidity ≤ 75 % Failure quota αFQ(co) 1000 failures per 109 component hours Load duration t LD(co) up to 30 000 h Storage temperature limit T stg – 55/+ 85 °C IEC climatic category (IEC 68-1 and 2) 25/085/56 Test data: AC test voltage between terminals V TT 1.25 x VR, 50 Hz, 10 s (or DC 1.75 x VR, 10 s) between terminals and case V TC 2 · Vi + 1000 V, 50 Hz, 10 s Insulating voltage Vi = max. recurrent peak voltage / Insulation resistance R ins ≤ 1 μF: ≥ 3000 MΩ Self-discharge time constant τ =R ins x C > 1 μF: ≥ 3000 s Dissipation factor tan δ≤ 3 . 10–4 î C---- IS C---- vˆ 2
Please read Cautions and warnings and 4 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 Characteristics and ordering codes CR1) μF Imax A î A Is A RS 20 °C mΩ Lself nH Dimensions d × l mm Fig. Appr. weight g Ordering code VR = AC 640 V = 800 V vs = 1100 V VTT = AC 800 V, 10 s VTC = AC 2200 V, 10 s 1.0 10 40 100 24.0 50 25 × 48 3 30 B25832F4105K001 1.5 10 25 60 54.0 90 25 × 80 3 50 B25832F4155K001 1.6 16 60 160 16.0 50 30 × 48 4 50 B25832F4165K001 2.0 16 80 200 13.0 50 30 × 48 4 50 B25832F4205K001 2.2 10 35 90 39.0 90 25 × 80 3 50 B25832F4225K001 2.5 16 100 250 12.0 50 35 × 48 5 60 B25832F4255K001 3.0 10 50 120 30.0 90 25 × 80 3 50 B25832F4305K001 3.0 16 120 300 11.0 50 35 × 48 5 60 B25832F4305K011 3.3 10 50 130 28.0 90 25 × 80 3 50 B25832F4335K001 4.0 16 60 160 24.0 90 30 × 80 4 70 B25832F4405K001 4.7 16 75 190 21.0 90 30 × 80 4 70 B25832F4475K001 5.0 16 80 200 20.0 90 30 × 80 4 70 B25832F4505K001 6.0 18 240 600 5.6 70 45 × 57 1 110 B25832C4605K009 6.8 16 110 270 17.0 90 35 × 80 5 100 B25832F4685K001 7.0 16 110 280 16.0 90 35 × 80 5 100 B25832F4705K001 8.0 18 130 320 12.0 90 40 × 86 1 130 B25832C4805K009 10 18 160 400 10.0 90 40 × 86 1 130 B25832C4106K009 12 18 190 480 9.4 90 45 × 86 1 160 B25832C4126K009 14 18 220 560 8.6 90 50 × 86 1 200 B25832C4146K009 15 18 240 600 8.1 90 50 × 86 1 200 B25832C4156K009 16 18 260 640 7.8 90 50 × 86 1 200 B25832C4166K009 20 18 320 800 7.0 90 55 × 86 1 250 B25832C4206K009 22 18 350 880 6.7 90 60 × 86 1 300 B25832C4226K009 25 18 400 1000 6.2 90 60 × 86 1 300 B25832C4256K009 30 18 480 1200 6.8 140 50 × 156 1 370 B25832C4306K009 33 18 530 1300 6.6 140 50 × 156 1 370 B25832C4336K009 40 18 640 1600 6.2 140 55 × 156 1 450 B25832C4406K009 47 18 750 1900 6.1 140 60 × 156 1 550 B25832C4476K009 50 18 800 2000 5.9 140 60 × 156 1 550 B25832C4506K009 1) Other capacitance values upon request vˆ
Please read Cautions and warnings and 5 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 VR = AC 930 V = 1200 V vs = 1600 V VTT = AC 1200 V, 10 s VTC = AC 2700 V, 10 s 1.5 10 45 110 33.0 90 30 × 80 4 70 B25832F6155K001 2.0 10 60 150 26.0 90 30 × 80 4 70 B25832F6205K001 2.5 16 75 190 22.0 90 35 × 80 5 100 B25832F6255K001 3.0 18 90 230 17.0 90 40 × 86 1 130 B25832C6305K009 4.0 18 120 300 14.0 90 40 × 86 1 130 B25832C6405K009 5.0 18 150 380 12.0 90 45 × 86 1 160 B25832C6505K009 5.5 18 170 410 11.0 90 45 × 86 1 160 B25832C6555K009 6.0 18 180 450 10.0 90 50 × 86 1 200 B25832C6605K009 7.0 18 210 530 9.2 90 50 × 86 1 200 B25832C6705K009 8.0 18 240 600 8.5 90 55 × 86 1 250 B25832C6805K009 10 18 300 750 7.5 90 60 × 86 1 300 B25832C6106K009 12 18 360 900 6.7 90 60 × 86 1 300 B25832C6126K009 15 18 450 1100 7.0 110 79.2 × 104 2 600 B25832C6156K009 18 18 540 1400 6.5 110 79.2 × 104 2 600 B25832C6186K009 20 18 600 1500 6.3 110 89.3 × 104 2 800 B25832C6206K009 22 18 660 1700 6.2 110 89.3 × 104 2 800 B25832C6226K009 Characteristics and ordering codes CR1) μF Imax A î A Is A RS 20 °C mΩ Lself nH Dimensions d × l mm Fig. Appr. weight g Ordering code 1) Other capacitance values upon request vˆ
Please read Cautions and warnings and 6 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 Dimensional drawing 1 Dual tab connectors 6.3 mm Dimensions in mm Mounting parts (included in delivery) dll 1+1*) Creepage distance Clearance 40 86 8 45 57 8 45 86 8 50 86 12 50 156 12 55 86 12 55 156 12 60 86 12 60 156 12 Threaded bolt Max. torque Toothed washer Hex nut M8 4 Nm J 8.2 DIN 6797 M 8 DIN 439 M12 10 Nm J 12.5 DIN 6797 M12 DIN 439 KLK0908-V 8+0,5 6,3±0,1 l 13,5 max.l1 0,8±0,04 6,8+0,2 d +0.5 –0.2 Dimensional drawing 2 Dual tab connectors 6.3 mm Dimensions in mm *) 8 mm = threaded bolt M8 12 mm = threaded bolt M12 d–1 . 2 l–4 ∅ d1–0.4 Creepage distance Clear- ance 79.2 104 75.2 7589.3 104 85.2 KLK1264-3 8+0,5 6,3±0,1 l 13,5 max.16+1 0,8±0,04 6,8+0,2 d M12 ød 1
Please read Cautions and warnings and 7 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 Dimensional drawing 4 Tab connectors 6.3 mm Dimensions in mm dl ± 2 Creepage distance Clearance 30 48 9730 80 KLK1416-V 18 max. Tab connector 8+1 A 6,3 x 0,8 DIN 46 244 ld 15,5±0,5 +0.5 –0.2 Dimensional drawing 3 Tab connectors 6.3 mm Dimensions in mm Mounting parts (included in delivery) dl ± 2 Creepage distance Clearance 25 48 9725 80 Threaded bolt Max. torque Toothed washer Hex nut M8 4 Nm J 8.2 DIN 6797 M8 DIN 439 KLK1415-M 18 max. Tab connector 8+1 A 6,3 x 0,8 DIN 46 244 ld 15,5±0,5 +0.5 –0.2
Please read Cautions and warnings and 8 09/05 Important notes at the end of this document. MKV AC Capacitors General AC Applications B25832 Dimensional drawing 5 Tab connectors 6.3 mm Dimensions in mm Mounting parts (included in delivery) dl ± 2 Creepage distance Clearance 35 48 6635 80 Threaded bolt Max. torque Toothed washer Hex nut M8 4 Nm J 8.2 DIN 6797 M8 ISO 4035 KLK1418-C 13 max. Tab connector 8+1 A 6,3 x 0,8 DIN 46 244 ld 15,5±0,5 +0.5 –0.2
■ In case of dents of more than 1 mm depth or any other mechanical damage, capacitors must not be used at all. This applies also in cases of oil leakage. ■ Electrical or mechanical misapplication of capacitors may be hazardous. Personal injury or prop- erty damage may result from bursting of the capacitor or from expulsion of oil or melted material due to mechanical disruption of the capacitor. ■ Ensure good, effective grounding for capacitor enclosures. ■ Observe appropriate safety prec autions during operation (self-recharging phenomena and the high energy contained in capacitors). ■ Handle capacitors carefully, because they may still be charged even after disconnection. ■ The terminals of capacitors, connected bus bars and cables as well as other devices may also be energized. ■ Follow good engineering practice. ■ Failure to follow cautions may result, worst case, in premature failures, bursting and fire. Thermal load After installation of the capacitor it is necessary to verify that maximum hot-spot temperature is not exceeded at extreme service conditions (see www.epcos.com/thermal_design). Mechanical protection The capacitor has to be installed in a way that mechanical damages and dents in the aluminum can are avoided. Storage and Operating Conditions Do not use or store capacitors in corrosive atmosphere especially where chloride gas, sulfide gas, acid, alkali, salt or the like are present. In dusty environments, regular maintenance and cleaning especially of the terminals is required to avoid conductive path between phases and/or phases and ground. Overpressure disconnector To ensure full functionality of an overpressure disconnector, the following must be observed: ■ The elastic elements must not be hindered, i.e. – connecting lines must be flexible leads (cables), – there must be sufficient space (minimum 12 mm) above the connections for expansion of the overpressure disconnector, – folding crimps must not be retained by clamps. ■ Stress parameters of the capacitor must be within the IEC61071 specification. Service life expectancy Electrical components do not have an unlimited service life expectancy; this applies to self-healing capacitors too. The maximum service life expect ancy may vary depending on the application the capacitor is used in.
The following applies to all products named in this publication: 1. Some parts of this publication contain statements about the suitability of our products for certain areas of application. These statements are based on our knowledge of typical require- ments that are often placed on our products in the areas of application concerned. We neverthe- less expressly point out that such statements cannot be regarded as binding statements about the suitability of our products for a particular customer application. As a rule, EPCOS is either unfamiliar with indivi dual customer applications or less familiar with them than the customers themselves. For these reasons, it is always ultimately incumbent on the customer to check and decide whether an EPCOS pr oduct with the properties described in the product specification is suitable for use in a particular customer application. 2. We also point out that in individual cases, a malfunction of passive electronic components or failure before the end of their usual servi ce life cannot be completely ruled out in the current state of the art, even if they are operated as specified. In customer applications re- quiring a very high level of operational safety and especially in customer applications in which the malfunction or failure of a pa ssive electronic com ponent could endanger human life or health (e.g. in accident prevention or life-saving systems), it must therefore be ensured by means of suit- able design of the customer application or other action taken by the customer (e.g. installation of protective circuitry or redundancy) that no injury or damage is sustained by third parties in the event of malfunction or failure of a passive electronic component. 3. The warnings, cautions and product-specific notes must be observed. 4. In order to satisfy certain technical requirements, some of the products described in this pub- lication may contain substances subject to restrictions in certain jurisdictions (e.g. be- cause they are classed as “hazardous”). Useful information on this will be found in our Material Data Sheets on the Inte rnet (www.epcos.com/material). Shou ld you have any more detailed questions, please contact our sales offices. 5. We constantly strive to improve our products. Consequently, the products described in this publication may change from time to time . The same is true of the corresponding product specifications. Please check therefore to what extent product descript ions and specifications contained in this publication are still applicable before or when you place an order. We also reserve the right to discontinue production and delivery of products. Consequent- ly, we cannot guarantee that all products named in this publication will always be available. 6. Unless otherwise agreed in individual contracts, all orders are subject to the current version of the “General Terms of Delivery for Produc ts and Services in the Electrical Industry” published by the German Electrical and Electronics Industry Association (ZVEI). 7. The trade names EPCOS, CeraDiode, CSSP, PhaseCap, PhaseMod, SilverCap, SIFI, SIMID, SIKOREL, SIOV, SIP5D, SIP5K, TOPcap, UltraCap, WindCap are trademarks registered or pending in Europe and in other countries. Further information will be found on the Internet at www.epcos.com/trademarks.