Fused and non-fused HVAC disconnects Catalog symbol:

  • B22__ Description: Fused and non-fused pullout HVAC disconnects in NEMA 3R enclosures. Fused versions are available in 30 and 60 amp ratings with or without self- testing GFCI receptacles. Non-fused versions are available in 60 amp versions with or without self- testing GFCI receptacles. Specifications: Ratings
  • Volts
  • 120 Vac single-phase
  • 240 Vac split-phase
  • Amps 30 or 60 A Catalog numbers
  • See table on page 2. Agency Information
  • UL® Listed to UL 1429, cUL Certified, UL Guide WGEW Conductors - AWG
  • 14-3 Cu/Al Enclosures
  • Metallic NEMA 3R housing with weather resistant coating Dimensions
  • See catalog numbers table Features and benefits
  • A/C disconnects meet NEC® Code requirements under articles 440.14.
  • Self-testing GFCI units meet NEC Code requirements under articles 210.63, 210.8, and 406.8(B)(1).
  • NEMA 3R enclosures withstand outdoor environment.
  • Padlockable with two-position pullout handle to lock safety shield when in the ON position. (Not available on GFCI or 60 A switched units.) For added safety, pullout handle can be stored in the compartment in the OFF position. Typical applications:
  • Residential, light industrial/commercial A/C and heat pump service
  • Spas/whirlpools, swimming pools, pump houses
  • Suitable for service entrance equipment applications with field installed ground bar — order catalog number DPFG Fused disconnect Non-fused disconnect with GFCI receptacle. Non-fused disconnect

Eaton.com/bussmannseries Fused and non-fused HVAC disconnects Technical Data 1143 Effective June 2017 Follow us on social media to get the latest product and support information. The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton and Bussmann are valuable trademarks of Eaton in the U.S. and other countries. Y ou are not permitted to use the Eaton trademarks without prior written consent of Eaton. NEC is a registered trademark of the National Fire Protection Association, Inc. UL is a registered trademark of the Underwriters Laboratories, Inc. Eaton

1000 Eaton Boulevard

Cleveland, OH 44122 Eaton.com Bussmann Division

114 Old State Road

Ellisville, MO 63021 United States Eaton.com/bussmannseries © 2017 Eaton All Rights Reserved Printed in USA Publication No. 1143 — BU-SB04150 June 2017 Catalog numbers Cat. nos. Description Amp rating Max Hp rating Fuse class Approximate dimensions (in)

120 V 240 V Height Width Depth

B221-30F 30 amp, pullout 30 1. 5 3 H or R 8-3/4 5-3/8 2-7/8 B221-30FGFST 30 amp, pullout with GFCI 30 1. 5 3 H or R 13 7-1/2 4-3/4 B221-30FGFWTST 30 amp, pullout with weather-resistant/tamper-resistant rated GFCI 30 1. 5 3 H or R 13 7-1/2 4-3/4 B222-60F 60 amp, pullout 60 3 10 H or R 8-3/4 5-3/8 2-7/8 B222-60FGFST 60 amp, pullout with GFCI 60 3 10 H or R 13 7-1/2 4-3/4 B222-60FGFWTST 60 amp, pullout with weather-resistant/tamper-resistant rated GFCI 60 3 10 H or R 13 7-1/2 4-3/4 Non-fused disconnects B222-60NF 60 amp, pullout 60 3 10 * 8-3/4 5-3/8 2-7/8 B222-60NFGFST 60 amp, pullout with GFCI 60 3 10 * 11-3/4 6-1/2 4-1/2 B222-60NFGFWTST 60 amp, pullout with weather-resistant/tamper-resistant rated GFCI 60 3 10 * 11-3/4 6-1/2 4-1/2 B222-60NFNA 60 amp, switch 60 — 10 * 8-3/4 5-3/8 3-5/8 * Upstream overcurrent protective device (OPCD) not to exceed 60 A. For 30 and 60 amp pullout replacement handles, order catalog number 96-3258-4. Recommended Bussmann series fuses Fuse class Catalog symbol Operation Available amps Data sheet no. H NON-(amp) One time, general purpose 1/8 to 60 1030 R FRN-R-(amp) Dual element, time-delay 1/10 to 60 1019 LPN-RK-(amp)SP (non-indicating) 1/10 to 60 1003 LPN-RK-(amp)SPI (indicating 35 to 60 1003