Features

  • Compatible with Gamewell-FCI Analog Addressable Control Panels.
  • Operates in the Velociti ® or CLIP mode.
  • High Sensitivity for both sm oldering and fast flaming fires.
  • Includes patented algorithms that ignore transient smoke and dust particles.
  • Provides low profile construction and an easy plug-in of the head to base.
  • Offers the following built-in features: - Signal processing - Tamper-resistant - Test switch
  • Supports a remote test feature (originating from the panel).
  • 360° view angle of dual alarm LEDs.
  • Optional bases for auxiliary functions.
  • Maximum air velocity 4,000 FPM. ASD-LS

12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118

9020-0525 Rev. G page 2 of 2 www.gamewell-fci.com Installation Place the sensor into the s ensor base. Turn the sensor clockwise until the sensor locks into place. To use the tamper-proof feature, break the smaller tab on the base as shown in the inst allation instru ctions. Install the sensor. To remove the sensor from the base when using the tamper-proof feature, insert the blade of a small screwdriver into the hole on the side of the base and push the plastic lever away from the detector head. This will allow the sensor to be rotated counterclockwise for removal. NOTE: When you use the tamper-proof feature, remove the decorative ring before removing the head. For information on spacing, the location of the sensors and other guidelines, refer to NFPA72, Chapter 5-3 “Smoke Sensing Fire Detectors.” Testing Sensors may be tested locally in the following ways: A. Place a test magnet against the sensor housing per the instructions. The sensor should go into alarm within 30 seconds. B. Aerosol Generator - The Gemini Model 501 aerosol generator may be used to perform a Functional Test. This test should be performed immediately following the Magnet Test. The Magnet test initiates an approxi- mately ten minute period when the detector's signal processing software routines are not active. Failure to first perform the Magnet Test will introduce a time delay before the detector alarms. Follow instructions in the Generator Instruction Manual. Maintenance Cleaning programs should be adapted to the individual environment in conformance with the National Fire Alarm Code, NFPA, 72. We recommend, at the least, an annual cleaning of the unit. The sensor screen and cover assem- bly can be removed, revealing the sensing chamber. A vacuum cleaner can be used to remove the dust from the screen, cover and sensing chamber. For the complete pro- cedure, refer to the Installation and Maintenance Instruc- tions furnished with each sensor. Specifications Sensitivity: .02 - 2.0%/ft. Operating Voltage: 15-32 VDC Standby Current: .00033 amp @ 24 VDC Alarm Current (max.): .0065 amp @ 24 VDC Operating/Installation Temperature: 32° to 100° F (0° to 38° C) Operating Humidity: 10% to 93% relative humidity (non-condensing) Dimensions: 1.7” (4.3 cm) height 4.1” (10.4 cm) installed in the B501 base 6.1” (15.5 cm) installed in the B210LP base Weight: 5 oz. (142 gm.)

Ordering Information

ASD-LS L o w P r o f i l e A n a l o g L a s e r S e n s o r B501 Plug-in sensor base without flange Dimensions: 4.1” (10.4 cm) diameter B210LP Flanged mounting base Dimensions: 6.1” (15.5 cm) diameter B210LPBP Flanged mounting base bulk pack Dimensions: 6.1” (15.5 cm) diameter B224RB Plug-in sensor base with auxiliary relay, SPDT, rated 2 amps. @ 30 VDC (resistive) 2 coil latching relay 1 Form C Contact UL/ CSA Rating:

0.9 A @ 125 VAC inductive

0.9 A @ 110 VDC inductive

3 A @ 30 VDC resistive

Dimensions: 6.1” (15.5 cm) diameter B224BI Plug-in sensor isolator base for Style 7 operation Dimensions: 6.1” (15.5 cm) diameter B200S Intelligent sensor sounder base Dimensions: 6.875” (17.5 cm) diameter B200SR Standard sounder base, UL 864 9th Edition compliant, ULC Listed Dimensions: 6.875” (17.5 cm) diameter RA-100Z Remote LED Annunciator XR2B Extractor Test