Regenerative unit - 15 kW - for Altivar variable speed drive Main Range of product Altivar Product or component type Power module Device short name ATVR Device application Energy regeneration Complementary Range compatibility Altivar Machine ATV340 Altivar Machine ATV320 Altivar Process ATV900 Fixing mode By screws Network number of phases 3 phases Network frequency 45...65 Hz Rated power 13.5 kW DC bus operating voltage 456...778 V DC DC bus voltage limits 300...880 V DC Input power 13.5 kW at 380...500 V AC for voltage inputs (continuous) 20.3 kW at 380...500 V AC for voltage inputs (transient for 60 s) Input current 31.8 A at 380 V AC for voltage inputs (continuous)

27.9 A at 500 V AC for voltage inputs (continuous)

43.1 A at 380 V AC for voltage inputs (transient for 60 s)

36.3 A at 500 V AC for voltage inputs (transient for 60 s)

Output current 25.9 A at 380 V AC (continuous)

23.2 A at 500 V AC (continuous)

36.5 A at 380 V AC (transient for 60 s)

29.7 A at 500 V AC (transient for 60 s)

Power supply: removable screw terminal block: 6 mm², AWG 8 (top) DC bus: removable screw terminal block: 6 mm², AWG 8 (bottom) Maximum voltage drop at rated load 3 % Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Sep 20, 2021

Operating position Vertical or horizontal position Height 399 mm Width 105 mm Depth 235 mm Product weight 11.5 kg Type of cooling Fan Environment Environmental characteristic Chemical pollution resistance class 3C3 conforming to EN/IEC 60721-3-3 Dust pollution resistance class 3S2 conforming to EN/IEC 60721-3-3 Ambient air temperature for operation -10…50 °C without derating 50…60 °C with derating factor Ambient air temperature for storage -40…70 °C Operating altitude <= 1000 m without derating 1000...3000 m with power derating 1 % per 100 m Pollution degree 2 conforming to EN/IEC 61800-5-1 IP degree of protection IP20 Standards IEC 61800-3 IEC 61800-5-1 Product certifications cUL Packing Units Unit Type of Package 1 PCE Number of Units in Package 1 1 Package 1 Weight 13.565 kg Package 1 Height 21 cm Package 1 width 32 cm Package 1 Length 61 cm Unit Type of Package 2 P06 Number of Units in Package 2 4 Package 2 Weight 67.26 kg Package 2 Height 73.5 cm Package 2 width 60 cm Package 2 Length 80 cm Offer Sustainability Sustainable offer status Green Premium product REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov

(1) : Fixing holes for ATV320

Drive and Regenerative Unit (1) : AC protection fuses (2) : Optional additional EMC input Filter (see drive catalog) (3) : Optional AC Choke (see drive catalog) (4) : DC bus link (5) : DC protection fuses (6) : Altivar Regenerative Unit