ATV71EXA2C50N SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
enclosed variable speed drive ATV71 Plus - 500 kW - 500V - IP23 To be discontinued Commercial status To be discontinued on: 31 December 2023 To be end-of-service on: 31 December 2031 Main Range of product Altivar 71 Plus Product or component type Variable speed drive Device short name ATV71 Plus Product destination Synchronous motors Asynchronous motors Product specific application Complex, high-power machines Assembly style With integrated cooling circuit In floor-standing enclosure with separate air flows Product composition Integrated drive system ATV71EC63YE1 Terminals/bars for motor connection Control transformer for 230 V A switch and fast-acting fuses An IP65 remote mounting kit for graphic display terminal A wired ready-assembled Sarel Spacial 6000 enclosure EMC filter Integrated Network number of phases 3 phases Rated supply voltage 500...525 V +/- 10 % Supply voltage limits 450…578 V Supply frequency 50...60 Hz +/- 5 % Network frequency 47.5...63 Hz Motor power kW 500 kW, 3 phases at 500 V Line current 698 A for 500 V / 500 kW Complementary Apparent power 604 kVA for 500 V / 500 kW Prospective line Isc 100 kA with external fuses Continuous output current 740 A at 2.5 kHz, 500 V / 500 kW Maximum transient current 1110 A for 60 s / 500 kW Speed drive output frequency 0.1…500 Hz Nominal switching frequency 2.5 kHz Switching frequency 2...4.9 kHz adjustable Speed range 1…100 for asynchronous motor in open-loop mode, without speed feedback 1…50 for synchronous motor in open-loop mode, without speed feedback Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 18, 2021
1…1000 for asynchronous motor in closed-loop mode with encoder feedback Speed accuracy +/- 0.01 % of nominal speed in closed-loop mode with encoder feedback 0.2 Tn to Tn +/- 10 % of nominal slip without speed feedback 0.2 Tn to Tn Torque accuracy +/- 5 % in closed-loop mode with encoder feedback +/- 15 % in open-loop mode, without speed feedback Transient overtorque 170 % of nominal motor torque for 60 s 220 % of nominal motor torque for 2 s Braking torque 30 % without braking resistor <= 150 % with braking or hoist resistor Asynchronous motor control profile Voltage/frequency ratio, 2 points Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 5 points Flux vector control without sensor, 2 points Flux vector control without sensor, ENA (energy Adaptation) system Flux vector control without sensor, standard Flux vector control with sensor, standard Synchronous motor control profile Vector control without sensor, standard Vector control with sensor, standard Regulation loop Adjustable PI regulator Motor slip compensation Suppressable Not available in voltage/frequency ratio (2 or 5 points) Adjustable Automatic whatever the load Overvoltage category Class 3 conforming to EN 50178 Local signalling LCD display unit for operation function, status and configuration - mounted in the front door Output voltage <= supply voltage Isolation Electrical between power and control Type of cable for external connection IEC cable at 40 °C, copper 70 °C / PVC UL 508 cable at 40 °C, copper 75 °C / PVC Electrical connection Bar M12 - 10 x 240 mm² (L1/R, L2/S, L3/T) bottom entry at 6-pulse operation Bar M12 - 4 x 240 mm² (L1/R, L2/S, L3/T) bottom entry at 12-pulse operation Bar M12 - 16 x 240 mm² (U/T1, V/T2, W/T3) bottom entry Terminal - 2.5 mm² / AWG 14 (R1A, R1B, R1C, R2A, R2B) bottom entry Screw clamp terminals - 1.5 mm² (AI1-/AI1+, AI2, AO1, LI1...LI6, PWR) bottom entry Motor recommanded cable cross section 3 (3 x 185) mm² Short-circuit protection 1000 A fuse protection type gI - power supply upstream - at 6-pulse operation
500 A fuse protection type gI - power supply upstream - at 12-pulse operation
Supply External supply: 24 V DC (19…30 V), <1 A Internal supply for reference potentiometer: 10 V DC (10…11 V), <10 mA Internal supply: 24 V DC (21…27 V), <100 mA Analogue input number 2 Analogue input type AI2 software-configurable voltage: 0...10 V DC, 24 V max, impedance: 30000 Ohm, sampling time: 1.5…2.5 ms, resolution: 11 bits AI1-/Al1+ bipolar differential voltage: +/- 10 V DC, 24 V max, sampling time: 1.5…2.5 ms, resolution: 11 bits + sign 2.5 ms, resolution: 11 bits Analogue output number 1 resolution: 10 bits resolution: 10 bits Discrete output number 2 Minimum switching current 3 mA at 24 V DC (configurable relay logic) Maximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 (R1, R2)
5 A at 30 V DC on resistive load - L/R = 0 ms (R1, R2)
2 A at 250 V AC on inductive load - cos phi = 0.4 (R1, R2)
2 A at 30 V DC on inductive load - L/R = 7 ms
Switch-configurable (LI6) at 24 V DC <= 30 V level 1 PLC 1.5 kOhm (duration=1.5…2.5 ms)
Safety input (PWR) at 24 V DC <= 30 V 1.5 kOhm Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s S, U or customized Braking to standstill By DC injection Protection type Overheating protection: drive Thermal protection: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply undervoltage: drive Line supply overvoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor Power removal: motor Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance > 1 mOhm 500 V DC for 1 minute to earth Frequency resolution Display unit: 0.1 Hz Analog input: 0.024/50 Hz Communication port protocol CANopen Modbus Connector type 1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen Physical interface 2-wire RS 485 for Modbus Transmission frame RTU for Modbus Transmission rate 9600 bps, 19200 bps for Modbus on front face 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen Data format 8 bits, 1 stop, even parity for Modbus on front face 8 bits, odd even or no configurable parity for Modbus on terminal Type of polarization No impedance for Modbus Number of addresses 1…247 for Modbus 1…127 for CANopen Method of access Slave CANopen Option card Communication card for Modbus TCP/IP Communication card for Fipio Communication card for Modbus/Uni-Telway Communication card for Modbus Plus Communication card for EtherNet/IP Communication card for DeviceNet Communication card for Profibus DP Communication card for Profibus DP V1 Communication card for Interbus-S Communication card for CC-Link Basic I/O extension card Extended I/O extension card Controller inside programmable card Encoder interface cards Options for enclosure configuration Safe standstill for power circuit PTC relay for power circuit Pt100 relay for power circuit Insulation monitoring for power circuit Design for IT networks for power circuit External 230 V supply terminals for power circuit Buffer voltage 24 V DC power supply for power circuit External 24 V DC supply terminals for power circuit Enclosure lighting for power circuit Key switch (local/remote) for power circuit Motor heating for power circuit External motor fan for power circuit
Voltmeter for power circuit Door handle for main switch for power circuit Circuit breaker for power circuit Line contactor for power circuit 12-pulse supply for power circuit Line reactor for power circuit Ammeter for power circuit Enclosure heating for power circuit Motor choke for power circuit Cable entry via the top for power circuit Enclosure plinth for power circuit Door handle for circuit breaker for power circuit Control terminals for control circuit Adaptor for 115 V logic inputs for control circuit Relay output C/O for control circuit Isolated amplifier for control circuit Operating position Vertical +/- 10 degree Colour of enclosure Light grey (RAL 7035) Colour of base of enclosure Dark grey (RAL 7022) Height 2009 mm Width 1800 mm Depth 642 mm Net weight 950 kg Environment Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Pollution degree 2 conforming to EN/IEC 61800-5-1 IP degree of protection IP23 Vibration resistance 1.5 mm peak to peak (f= 3…10 Hz) conforming to EN/IEC 60068-2-6 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6 3M3 conforming to EN/IEC 60721-3-3 Shock resistance 4 gn for 11 ms conforming to EN/IEC 60068-2-27 3M2 conforming to EN/IEC 60721-3-3 Noise level 77 dB conforming to 86/188/EEC Environmental characteristic Without condensation: 3C2 conforming to IEC 60721-3-3 Without condensation: 3S2 conforming to IEC 60721-3-3 Without condensation: 3K3 conforming to IEC 60721-3-3 Relative humidity 0…95 % Ambient air temperature for operation 0…40 °C (without derating) 40…50 °C (with current derating of 1.2 % per °C) Ambient air temperature for storage -25…70 °C Volume of cooling air 5500 m3/h Operating altitude <= 1000 m without derating 1000...3000 m with current derating 1 % per 100 m Standards EN/IEC 61800-3 EN 61800-3 environments 2 category C3 EN 61800-3 environments 1 category C3 EN/IEC 61800-5-1 EN 55011 class A group 2 Product certifications GOST ATEX Marking CE Packing Units Package 1 Weight 900.000 kg Package 1 Height 20.000 dm Package 1 width 6.600 dm
Package 1 Length 18.300 dm Contractual warranty Warranty 18 months
IP 23 Floor-Standing Enclosure with Separate Air Flows Dimensions NOTE: For each floor-standing enclosure added, allow a 4 mm/0.15 in. space for the seal.
Floor-Standing Enclosure with Separate Air Flows Standard 6-pulse Design A1 Drive A2 Enclosure F1 Fuses IL1 Optional line choke KM1 Optional line contactor M Motor Q1 Switch Q2 Optional circuit breaker (1) Filter (2) Control (3) Relay control (4) Reference potentiometer (5) PLC (6) Optional motor choke Optional 12-pulse Design A1 Drive A2 Enclosure F1 Fuses IL1 Optional line choke KM1 Optional line contactor M Motor Q1 Switch (1) Filter (2) Control (3) Relay control (4) Reference potentiometer (5) PLC (6) Optional motor choke
IP 23 Floor-Standing Enclosure with Separate Air Flows Derating Curves The derating curves for the drive nominal current (In) are dependent on the temperature and switching frequency. For intermediate temperatures, interpolate between 2 curves. NOTE: The drive will reduce the switching frequency automatically in the event of excessive temperature rise. X Switching frequency (kHz) NOTE: The temperatures shown correspond to the temperature of the air entering the enclosure.