ATV630D45N4 SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 13
Technical content
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Aug 9, 2019 Product data sheet Characteristics ATV630D45N4 variable speed drive ATV630 - 45kW/60HP - 380...480V - IP21/UL type 1
Product availability: Non-Stock - Not normally stocked in distribution facility Main Range of product Altivar Process ATV600 Product or component type Variable speed drive Product specific applica- tion Process and utilities Device short name ATV630 Variant Standard version Product destination Synchronous motors Asynchronous motors Mounting mode Wall mount EMC filter Integrated EN/IEC 61800-3 category C3 <= 150 m Integrated EN/IEC 61800-3 category C2 <= 50 m IP degree of protection IP21 conforming to IEC 61800-5-1 IP21 conforming to IEC 60529 Degree of protection UL type 1 UL 508C Type of cooling Forced convection Network number of phases 3 phases [Us] rated supply volt- age Motor power kW 45 kW normal duty 37 kW heavy duty Motor power hp 60 hp normal duty 50 hp heavy duty Line current 79.8 A 380 V normal duty
69.1 A 480 V normal duty
67.1 A 380 V heavy duty
59 A 480 V heavy duty
Prospective line Isc 50 kA Apparent power 57.4 kVA 480 V normal duty 49.1 kVA 480 V heavy duty Continuous output cur- rent
88 A 4 kHz normal duty
74.5 A 4 kHz heavy duty
96.8 A 60 s normal duty
111.8 A 60 s heavy duty
Synchronous reluctance motor Permanent magnet motor Speed drive output fre- quency 0.1...599 Hz Nominal switching fre- quency 4 kHz Switching frequency 2...12 kHz adjustable 4...12 kHz with derating factor Safety function STO (safe torque off) SIL 3 Discrete input logic 16 preset speeds
Option card Communication module Profibus DP V1 slot A Communication module Profinet slot A Communication module DeviceNet slot A Communication module Modbus TCP/EtherNet/IP slot A Communication module CANopen daisy chain RJ45 slot A Communication module CANopen SUB-D 9 slot A Communication module CANopen screw terminals slot A Digital and analog I/O extension module slot A/slot B Output relay extension module slot A/slot B Communication module Ethernet IP/Modbus TCP/ MD-Link slot A Communication module BACnet MS/TP Communication module Ethernet Powerlink Complementary Output voltage <= power supply voltage Permissible temporary current boost 1.1 x In 60 s normal duty 1.5 x In 60 s heavy duty Motor slip compensation Not available in permanent magnet motor law Adjustable Automatic whatever the load Can be suppressed Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s Braking to standstill By DC injection Protection type Safe torque off motor Motor phase break motor Safe torque off drive Overheating drive Short-circuit protection drive Motor phase break drive Overspeed drive Break on the control circuit drive Overvoltages on the DC bus drive Overload of output voltage drive Line supply overvoltage drive Line supply phase loss drive Line supply undervoltage drive Overcurrent between output phases and earth drive Thermal protection motor Thermal protection drive Frequency resolution Display unit Analog input Screw terminal 50 mm² AWG 1 motor Connector type RJ45 Ethernet/Modbus TCP on the remote graphic terminal RJ45 Modbus serial on the remote graphic terminal Physical interface 2-wire RS 485 Modbus serial Transmission frame RTU Modbus serial Transmission rate 10/100 Mbit/s Ethernet IP/Modbus TCP 4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP Data format 8 bits, configurable odd, even or no parity Modbus serial Type of polarization No impedance Modbus serial Number of addresses Modbus serial Method of access Slave Modbus TCP Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <= 10 mA overload and short-circuit protection External supply for digital inputs 24 V DC 19...30 V <= 1.25 mA overload and short-circuit protection Internal supply for digital inputs and STO 24 V DC 21...27 V <= 200 mA overload and short-circuit protection
Local signalling 3 LEDs local diagnostic
3 LEDs dual colour embedded communication status
4 LEDs dual colour communication module status
1 LED red presence of voltage
Width 8.9 in (226 mm) Height 26.5 in (673 mm) Depth 10.67 in (271 mm) Product weight 63.27 lb(US) (28.7 kg) Analogue input number 3 Analogue input type Software-configurable voltage AI1, AI2, AI3 0...10 V DC 30 kOhm 12 bits Discrete input number 8 Discrete input type Programmable DI1...DI6 24 V DC 3.5 kOhm Programmable as pulse input DI5, DI6 0...30 kHz 24 V DC Safe torque off STOA, STOB 24 V DC > 2.2 kOhm Input compatibility Level 1 PLC EN/IEC 61131-2 DI1...DI6 discrete input Level 1 PLC IEC 65A-68 DI5, DI6 discrete input Level 1 PLC EN/IEC 61131-2 STOA, STOB discrete input Discrete input logic Positive logic (source) DI1...DI6 < 5 V > 11 V Negative logic (sink) DI1...DI6 > 16 V < 10 V Positive logic (source) DI5, DI6 < 0.6 V > 2.5 V Positive logic (source) STOA, STOB < 5 V > 11 V Analogue output number 2 Analogue output type Software-configurable voltage AO1, AO2 0...10 V DC 470 Ohm 10 bits Software-configurable current AO1, AO2 0...20 mA 10 bits Sampling duration 2 ms +/- 0.5 ms DI1...DI4 discrete input 5 ms +/- 1 ms DI5, DI6 discrete input 5 ms +/- 0.1 ms AI1, AI2, AI3 analog input 10 ms +/- 1 ms AO1 analog output Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output Linearity error +/- 0.15 % of maximum value analog input AI1, AI2, AI3 +/- 0.2 % analog output AO1, AO2 Relay output number 3 Relay output type Configurable relay logic R1 fault relay NO/NC 100000 cycles Configurable relay logic R2 sequence relay NO 100000 cycles Configurable relay logic R3 sequence relay NO 100000 cycles Refresh time 5 ms +/- 0.5 ms R1, R2, R3 relay output Minimum switching current 5 mA 24 V DC R1, R2, R3 relay output Maximum switching current 3 A 250 V AC resistive 1 R1, R2, R3 relay output
3 A 30 V DC resistive 1 R1, R2, R3 relay output
2 A 250 V AC inductive 0.4 7 ms R1, R2, R3 relay output 2 A 30 V DC inductive 0.4 7 ms R1, R2, R3 relay output Isolation Between power and control terminals Functionality Full Specific application Utility IP degree of protection IP21
Variable speed drive application selection Building - HVAC compressor centrifugal Food and beverage processing other application Mining mineral and metal fan Mining mineral and metal pump Oil and gas fan Water and waste water other application Building - HVAC screw compressor Food and beverage processing pump Food and beverage processing fan Food and beverage processing atomization Oil and gas electro submersible pump (ESP) Oil and gas water injection pump Oil and gas jet fuel pump Oil and gas compressor for refinery Water and waste water centrifuge pump Water and waste water positive displacement pump Water and waste water electro submersible pump (ESP) Water and waste water screw pump Water and waste water lobe compressor Water and waste water screw compressor Water and waste water compressor centrifugal Water and waste water fan Water and waste water conveyor Water and waste water mixer Motor starter type Variable speed drive Environment Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth Noise level 63.5 dB 86/188/EEC Power dissipation in W 121 W natural convection 380 V 4 kHz
943 W forced convection 380 V 4 kHz
Volume of cooling air 63402.43 Gal/hr(US) (240 m3/h) Operating position Vertical +/- 10 degree THDI <= 48 % from 80...100 % of load IEC 61000-3-12 Electromagnetic compatibility Conducted radio-frequency immunity test level 3 IEC 61000-4-6 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Pollution degree 2 EN/IEC 61800-5-1 Vibration resistance 1.5 mm peak to peak 2...13 Hz IEC 60068-2-6 1 gn 13...200 Hz IEC 60068-2-6 Shock resistance 15 gn 11 ms IEC 60068-2-27 Relative humidity 5...95 % without condensation IEC 60068-2-3 Ambient air temperature for operation -15...50 °C without Operating altitude 1000...4800 m with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without Environmental characteristic Chemical pollution resistance class 3C3 EN/IEC 60721-3-3 Dust pollution resistance class 3S3 EN/IEC 60721-3-3 Standards EN/IEC 61800-3 EN/IEC 61800-3 environment 1 category C2 EN/IEC 61800-3 environment 2 category C3 UL 508C EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 Product certifications ATEX zone 2/22 DNV-GL TÜV UL REACH ATEX INERIS CSA Marking CE
Ordering and shipping details Category 22206 - ATV630 FRAMES 3 & 4 Discount Schedule CP4E GTIN 00785901949589 Nbr. of units in pkg. 1 Package weight(Lbs) 78 Returnability Y Country of origin IN Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1426 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference not containing SVHC above the threshold Product environmental profile Available Product Environmental Profile Product end of life instructions Available End Of Life Information California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov
Drives with IP21 Top Cover Front, Left and Rear Views Drives Without IP21 Top Cover Left and Rear Views
Mounting Type A: Individual IP21
Mounting Type B: Side by Side IP20 (Possible, 2 Drives Only) Mounting Type C: Individual IP20
Three-Phase Power Supply with Upstream Breaking via Line Contactor Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1 (1) Line choke if used (2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive KM1 :Line Contactor Q2, Q3 : Circuit breakers S1, S2 : Pushbuttons T1 : Transformer for control part Three-Phase Power Supply with Downstream Breaking via Contactor Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1 (1) Line choke if used (2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive KM1 :Contactor
Control Block Wiring Diagram (1) Safe Torque Off (2) Analog Output (3) Digital Input (4) Reference potentiometer (5) Analog Input R1A, R1B, R1C : Fault relay R2A, R2C : Sequence relay R3A, R3C : Sequence relay Sensor Connection It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3. Sink / Source Switch Configuration The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
- Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
- Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs Switch Set to EXT Position Using an External Power Supply for the DIs
40 °C (104 °F) - Mounting type A, B and C 50 °C (122 °F) - Mounting type A, B and C 60 °C (140 °F) - Mounting type B and C In : Nominal Drive Current SF : Switching Frequency