Variable speed drive, Altivar Process ATV600, ATV630, 22kW/30 hp, 200...240 V, IP21/UL type Main Range of product Altivar Process ATV600 Product or component type Variable speed drive Product specific application Process and utilities Device short name ATV630 Variant Standard version Product destination Synchronous motors Asynchronous motors EMC filter Without EMC filter IP degree of protection IP21 conforming to IEC 61800-5-1 IP21 conforming to IEC 60529 Degree of protection UL type 1 conforming to UL 508C Type of cooling Forced convection Motor power kW 22 kW (normal duty) 18.5 kW (heavy duty) Motor power hp 30 hp normal duty 25 hp heavy duty Line current 76 A at 200 V (normal duty)
64.3 A at 240 V (normal duty)
64.8 A at 200 V (heavy duty)
54.5 A at 240 V (heavy duty)
Prospective line Isc 50 kA Apparent power 26.7 kVA at 240 V (normal duty) 22.7 kVA at 240 V (heavy duty) Continuous output current 92.6 A at 4 kHz for normal duty
78.4 A at 4 kHz for heavy duty
Maximum transient current 101.9 A during 60 s (normal duty) Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 14, 2021
117.6 A during 60 s (heavy duty)
Asynchronous motor control profile Variable torque standard Constant torque standard Optimized torque mode Synchronous motor control profile Permanent magnet motor Synchronous reluctance motor Output frequency 0.0001…0.5 kHz Speed drive output frequency 0.1…599 Hz Nominal switching frequency 4 kHz Switching frequency 2...12 kHz adjustable 4...12 kHz with derating factor Safety function STO (safe torque off) SIL 3 Discrete input logic 16 preset speeds Communication port protocol Modbus TCP Ethernet Modbus serial Option card Slot A: communication module, Profibus DP V1 Slot A: communication module, Profinet Slot A: communication module, DeviceNet Slot A: communication module, Modbus TCP/EtherNet/IP Slot A: communication module, CANopen daisy chain RJ45 Slot A: communication module, CANopen SUB-D 9 Slot A: communication module, CANopen screw terminals Slot A/slot B: digital and analog I/O extension module Slot A/slot B: output relay extension module Slot A: communication module, Ethernet IP/Modbus TCP/MD-Link Communication module, BACnet MS/TP Communication module, Ethernet Powerlink Complementary Mounting mode Wall mount Output voltage <= power supply voltage Permissible temporary current boost 1.1 x In during 60 s (normal duty) 1.5 x In during 60 s (heavy duty) Motor slip compensation Adjustable Automatic whatever the load Not available in permanent magnet motor law Can be suppressed Acceleration and deceleration ramps Linear adjustable separately from 0.01...9999 s Braking to standstill By DC injection Protection type Thermal protection: motor Safe torque off: motor Motor phase break: motor Thermal protection: drive Safe torque off: drive Overheating: drive Overcurrent between output phases and earth: drive Overload of output voltage: drive Short-circuit protection: drive Motor phase break: drive Overvoltages on the DC bus: drive Line supply overvoltage: drive Line supply undervoltage: drive Line supply phase loss: drive Overspeed: drive Break on the control circuit: drive Frequency resolution Display unit: 0.1 Hz Analog input: 0.012/50 Hz Motor: screw terminal 50 mm²/AWG 1 Connector type RJ45 (on the remote graphic terminal) for Ethernet/Modbus TCP RJ45 (on the remote graphic terminal) for Modbus serial Exchange mode Half duplex, full duplex, autonegotiation Ethernet/Modbus TCP Number of addresses 1…247 for Modbus serial
Method of access Slave Modbus TCP Supply External supply for digital inputs: 24 V DC (19…30 V), <1.25 mA, protection type: overload and short- circuit protection Internal supply for reference potentiometer (1 to 10 kOhm): 10.5 V DC +/- 5 %, <10 mA, protection type: overload and short-circuit protection Internal supply for digital inputs and STO: 24 V DC (21…27 V), <200 mA, protection type: overload and short-circuit protection Local signalling 3 LEDs for local diagnostic
3 LEDs (dual colour) for embedded communication status
4 LEDs (dual colour) for communication module status
1 LED (red) for presence of voltage
Net weight 14.3 kg Analogue input number 3 Analogue input type AI1, AI2, AI3 software-configurable voltage: 0...10 V DC, impedance: 30 kOhm, resolution 12 bits bits Discrete input number 8 Discrete input type DI1...DI6 programmable, 24 V DC (<= 30 V), impedance: 3.5 kOhm DI5, DI6 programmable as pulse input: 0…30 kHz, 24 V DC (<= 30 V) STOA, STOB safe torque off, 24 V DC (<= 30 V), impedance: > 2.2 kOhm Input compatibility DI1...DI6: discrete input level 1 PLC conforming to EN/IEC 61131-2 DI5, DI6: discrete input level 1 PLC conforming to IEC 65A-68 STOA, STOB: discrete input level 1 PLC conforming to EN/IEC 61131-2 Discrete input logic Positive logic (source) (DI1...DI6), < 5 V (state 0), > 11 V (state 1) Negative logic (sink) (DI1...DI6), > 16 V (state 0), < 10 V (state 1) Positive logic (source) (DI5, DI6), < 0.6 V (state 0), > 2.5 V (state 1) Positive logic (source) (STOA, STOB), < 5 V (state 0), > 11 V (state 1) Analogue output number 2 Analogue output type Software-configurable voltage AO1, AO2: 0...10 V DC impedance 470 Ohm, resolution 10 bits Software-configurable current AO1, AO2: 0...20 mA, resolution 10 bits Sampling duration 2 ms +/- 0.5 ms (DI1...DI4) - discrete input 5 ms +/- 1 ms (DI5, DI6) - discrete input 5 ms +/- 0.1 ms (AI1, AI2, AI3) - analog input 10 ms +/- 1 ms (AO1) - analog output Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output Linearity error AI1, AI2, AI3: +/- 0.15 % of maximum value for analog input AO1, AO2: +/- 0.2 % for analog output Relay output number 3 Relay output type Configurable relay logic R1: fault relay NO/NC electrical durability 100000 cycles Configurable relay logic R2: sequence relay NO electrical durability 100000 cycles Configurable relay logic R3: sequence relay NO electrical durability 100000 cycles Refresh time Relay output (R1, R2, R3): 5 ms (+/- 0.5 ms) Minimum switching current Relay output R1, R2, R3: 5 mA at 24 V DC Maximum switching current Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 250 V AC Relay output R1, R2, R3 on resistive load, cos phi = 1: 3 A at 30 V DC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 250 V AC Relay output R1, R2, R3 on inductive load, cos phi = 0.4 and L/R = 7 ms: 2 A at 30 V DC Isolation Between power and control terminals Variable speed drive application selection Building - HVAC Compressor centrifugal Food and beverage processing Other application Mining mineral and metal Fan Mining mineral and metal Pump Oil and gas Fan Water and waste water Other application Building - HVAC Screw compressor Food and beverage processing Pump Food and beverage processing Fan Food and beverage processing Atomization Oil and gas Electro submersible pump (ESP) Oil and gas Water injection pump Oil and gas Jet fuel pump
Oil and gas Compressor for refinery Water and waste water Centrifuge pump Water and waste water Positive displacement pump Water and waste water Electro submersible pump (ESP) Water and waste water Screw pump Water and waste water Lobe compressor Water and waste water Screw compressor Water and waste water Compressor centrifugal Water and waste water Fan Water and waste water Conveyor Water and waste water Mixer Motor power range AC-3 15…25 kW at 200…240 V 3 phases Environment Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth Noise level 63.5 dB conforming to 86/188/EEC Power dissipation in W Natural convection: 107 W at 200 V, switching frequency 4 kHz Forced convection: 707 W at 200 V, switching frequency 4 kHz Volume of cooling air 240 m3/h Operating position Vertical +/- 10 degree Maximum THDI <48 % from 80...100 % of load conforming to IEC 61000-3-12 Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Pollution degree 2 conforming to EN/IEC 61800-5-1 Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6 1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6 Shock resistance 15 gn for 11 ms conforming to IEC 60068-2-27 Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3 Ambient air temperature for operation -15…50 °C (without derating) 50…60 °C (with derating factor) Ambient air temperature for storage -40…70 °C Operating altitude <= 1000 m without derating 1000...4800 m with current derating 1 % per 100 m Standards UL 508C EN/IEC 61800-3 Environment 1 category C2 EN/IEC 61800-3 Environment 2 category C3 EN/IEC 61800-3 EN/IEC 61800-5-1 IEC 61000-3-12 IEC 60721-3 IEC 61508 IEC 13849-1 Product certifications DNV-GL ATEX zone 2/22 CSA TÜV UL ATEX INERIS Marking CE Packing Units Package 1 Weight 25.000 kg Package 1 Height 5.200 dm Package 1 width 3.500 dm Package 1 Length 8.100 dm Offer Sustainability Sustainable offer status Green Premium product
REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration Environmental Disclosure Product Environmental Profile Circularity Profile End of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov Upgradeability Upgraded components available
Drives with IP21 Top Cover Front, Left and Rear Views Drives Without IP21 Top Cover Left and Rear Views
Mounting Type A: Individual IP21 Mounting Type B: Side by Side IP20 (Possible, 2 Drives Only) Mounting Type C: Individual IP20
Three-Phase Power Supply with Upstream Breaking via Line Contactor Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1 (1) Line choke if used (2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive KM1 : Line Contactor Q2, Q3 : Circuit breakers S1, S2 : Pushbuttons T1 : Transformer for control part
Three-Phase Power Supply with Downstream Breaking via Contactor Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping category 0 in accordance with standard IEC/EN 60204-1 (1) Line choke if used (2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected. A1 : Drive KM1 : Contactor
Control Block Wiring Diagram (1) Safe Torque Off (2) Analog Output (3) Digital Input (4) Reference potentiometer (5) Analog Input R1A, R1B, R1C :Fault relay R2A, R2C :Sequence relay R3A, R3C :Sequence relay Sensor Connection It is possible to connect either 1 or 3 sensors on terminals AI2 or AI3.
Sink / Source Switch Configuration The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
- Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
- Set the switch to Ext if using PLC outputs with NPN transistors. Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs Switch Set to EXT Position Using an External Power Supply for the DIs
40 °C (104 °F) - Mounting type A, B and C 50 °C (122 °F) - Mounting type A, B and C 60 °C (140 °F) - Mounting type B and C In : Nominal Drive Current SF : Switching Frequency