ATV630C22N4MN, C25N4MN, C31N4MN ATV930C22N4MN, C22N4CMN C25N4CMN, C31N4CMN QGH5721601 DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
- The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.
- Many components of the product, including the printed circuit boards, operate with mains voltage.
- Only use properly rated, electrically insulated tools and measuring equipment.
- Do not touch unshielded components or terminals with voltage present.
- Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to prevent rotation.
- AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
- Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
- Before performing work on the drive system: - Disconnect all power, including external control power that may be present. Take into account that the circuit breaker or main switch does not de-energize all circuits. - Place a "Do Not Turn On" label on all power switches related to the drive system. - Lock all power switches in the open position. - Wait 15 minutes to allow the DC bus capacitors to discharge. - Follow the instructions given in the chapter “Verifying the Absence of Voltage” in the installation manual of the product.
- Before applying voltage to the drive system: - Verify that the work has been completed and that the entire installation cannot cause hazards. - If the mains input terminals and the motor output terminals have been grounded and short-circuited, remove the ground and the short circuits on the mains input terminals and the motor output terminals. - Verify proper grounding of all equipment. - Verify that all protective equipment such as covers, doors, grids is installed and/or closed. Failure to follow these instructions will result in death or serious injury. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. © 2017 Schneider Electric. All Rights Reserved. You must have detailed information to be able to carry out the installation and commissioning. This information can be found in the following manuals that can be downloaded on: www.schneider-electric.com/drives - ATV630-650 Installation manual (EAV64301) - ATV930-950 lnstallation manual (NHA80932)
QGH57216-01 www.schneider-electric.com2/4 mm in. mm in. 430 16.9 377 14.86 350 13.78 5.9 950 37.4 920 36.22 377.38 14.88 950 37.4 585 23.03 540 21.26 5.9 920 36.22 ATV630C25N4MN, ATV930C25N4CMN, ATV630C31N4MN, ATV930C31N4CMN weight: 150 kg / 330.7 lb ATV630C22N4MN, ATV930C22N4MN, ATV930C22N4CMN weight: 108 kg / 238.1 lb IP20 IP20
QGH57216-01 www.schneider-electric.com3/4 Line Chokes to wire Power dissipated at nominal load ATV630pppppMN ATV930pppppMN ATV630C22N4MN ATV630C25N4MN ATV930C22N4MN ATV930C22N4CMN ATV930C25N4CMN ATV630C22N4MN ATV930C22N4MN ATV930C22N4CMN ATV630C22N4MN ATV930C22N4MN ATV930C22N4CMN ATV630C31N4MN ATV630C31N4CMN Inductance (mH) Wiring diagram ATV630C31N4MN ATV930C31N4CMN 0.06 0.038 M 3 a 3 aL2 U/T1 V/T2 W/T3 www.schneider-electric.com EAV64301 NHA80932 Forced Cooled Area (W) 4635 451 5381 606 6602 769 Natural Cooled Area (W) S1E1 S2E2 S3E3
QGH57216-01 www.schneider-electric.com4/4 Short-Circuit Current Ratings (SCCR) and Branch Circuit Protection The combinations in the table below have been tested per UL508C. (Reference UL file E116875). These ratings allow proper coordination of short circuit protection. The product would exceed a 100 kA interrupt rating on the output. Altivar Process drives are provided with integral overload and over-speed monitoring and can provide motor overload protection at 100% of the full load motor current. The motor thermal current [Motor Th Current]ItH must be set to the rated current indicated on the motor nameplate. For more information refer to the ATV600 programming manual (EAV64318) or ATV900 programming manual (NHA80757). The opening of the branch circuit protective device may be an indication that a fault current has been interrupted. 75°C (167°F) copper conductor with the AWG wire size shown on nameplate for all sizes. Suitable for use on a circuit capable of delivering not more than __X__ rms symmetrical kiloAmperes, __Y__ Volts maximum, when protected by __Z1__ with a maximum rating of __Z2_. (a) The amp rating of the short circuit protection devices in the table are maximum values. Smaller amp sizes may be used; particularly for Heavy Duty ratings. Branch circuit protection must be provided in accordance with the National Electrical Code and any additional local codes. (b) The maximum prospective short circuit current value that cannot be exceeded is 100 kA. Electrical distribution systems with a higher prospective short circuit will cause higher input currents in the front end of the drive. (c) Ratings apply to the Altivar Process Type 1 product when mounted on a wall or when mounting in a Type 1, 12, 3R, or 4X rated enclosure. (d) Use Class CC or J fast acting or time delay. (e) Use Class CC or J fast acting. (f) Ratings apply to an Altivar Process mounted in a Type 1, 12, 3R or 4(X) rated enclosure. (g) Without braking unit (h) With braking unit (i) Bussmann number: LPJ500SP, do not substitute. (j) Bussmann number: LPJ600SP, do not substitute Altivar Process Short Circuit Current Ratings (a) (b) Input Voltage 50/60 Hz Y Power Ratings in Normal Duty Catalog Number With Fuses (d) SCCR X = 100 kA With Circuit Breaker (f) SCCR X = 100 kA (kW) (HP) Fuse Ampere Rating (A) Z1, Z2 Minimum Enclosure Volume (cu. in.) Power Pact Z1, Z2 Minimum Enclosure Volume (cu. in.) 400/480 Vac Three-phase With Fuses (d) SCCR X = 18 kA 220 350 ATV630C22N4MN ATV930C22N4MN ATV930C22N4CMN 500 (c) order VW3A9212 – – 250 400 ATV630C25N4MN 600 (c) order VW3A9213 – – ATV930C25N4MN ATV930C25N4CMN 600 (c) order VW3A9213 (g) order VW3A9214 (h) –– With Fuses (e) SCCR X = 30 kA 315 500 ATV630C31N4MN 600 (c) order VW3A9213 – – ATV930C31CN4MN 600 (c) order VW3A9213 (g) order VW3A9214 (h) –– Altivar Process Short Circuit Current Ratings (a) (b) Input Voltage 50/60 Hz Y Power Ratings in Normal Duty Catalog Number With Fuses, SCCR X = 100 kA (kW) (HP) Line Reactor Minimum Value (mH) Fuse Ampere Rating (A) Z1, Z2 Minimum Enclosure Volume (cu. in.) 400/480 Vac Three-phase 220 350 ATV630C22N4MN ATV930C22N4MN ATV930C22N4CMN )i( 00550.0 53550250 400 ATV630C25N4MN ATV930C25N4CMN 0.05 600 (j) 315 500 ATV630C31N4MN ATV930C31N4CMN 0.04 DANGER HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
- Current-carrying parts and other components of the cont roller should be examined and replaced if damaged.
- If burnout of the current element of an overload relay occurs, the complete overload relay must be replaced. Failure to follow these instructions will result in death or serious injury.