ATV61EXS5C40Y SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 8
Technical content
enclosed variable speed drive ATV61 Plus - 400 kW - 690V - IP54 SA To be discontinued Main Range of product Altivar 61 Plus Product or component type Variable speed drive Device short name ATV61 Product destination Asynchronous motors Synchronous motors Product specific application Pumping and ventilation machine Assembly style In floor-standing enclosure with separate air flows Product composition A wired ready-assembled Sarel Spacial 6000 enclosure A plinth A switch and fast-acting fuses A line choke in an additional enclosure ATV61HC40Y standard drive IP00 An IP65 remote mounting kit for graphic display terminal Terminals/bars for motor connection EMC filter Integrated Network number of phases 3 phases Rated supply voltage 690 V +/- 10 % Supply frequency 50...60 Hz Motor power kW 400 kW, 3 phases at 690 V Line current 394 A at 690 V3 phases / 400 kW IP degree of protection IP54 Complementary Apparent power 471 kVA for 690 V, 3 phases 400 kW Prospective line Isc 100 kA with external fuses Continuous output current 420 A, 2.5 kHz at 690 V 3 phases Maximum transient current 504 A for 60 s, 3 phases Speed drive output frequency 0.1…500 Hz Nominal switching frequency 2.5 kHz 2...4.9 kHz adjustable Speed range 1…100 in open-loop mode, without speed feedback Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 18, 2021
Torque accuracy +/- 15 % in open-loop mode, without speed feedback Transient overtorque 120 % of nominal motor torque for 60 s 135 % of nominal motor torque for 2 s Braking torque 30 % without braking resistor <= 125 % with braking resistor Asynchronous motor control profile Voltage/frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, 5 points Flux vector control without sensor, standard Voltage/frequency ratio, 2 points Synchronous motor control profile Vector control without sensor, standard Regulation loop Adjustable PI regulator Motor slip compensation Suppressable Adjustable Automatic whatever the load Not available in voltage/frequency ratio (2 or 5 points) Supply voltage limits 621…759 V Network frequency limits 47.5…63 Hz Overvoltage category Class 3 conforming to EN 50178 Local signalling LCD display unit for operation function, status and configuration - mounted in the front door Output voltage <= supply voltage Isolation Electrical between power and control Type of cable for external connection IEC cable at 40 °C, copper 70 °C / PVC entry from the bottom Terminal M12 - 4 x 240 mm² (U/T1, V/T2, W/T3) entry from the bottom Terminal M12 - 3 x 185 mm² (L1/R, L2/S, L3/T) entry from the bottom Motor recommanded cable cross section 2 (3 x 150) mm² Short-circuit protection 630 A fuse protection type gI - power supply upstream Supply External supply: 24 V (19…30 V)DC, <1 A Internal supply for reference potentiometer: 10 V (10…11 V)DC, <10 mA Internal supply: 24 V (21…27 V)DC, <100 mA Analogue input number 2 Analogue input type AI2 software-configurable voltage: 0...10 V DC, 24 V max, impedance: 30 kOhm, sampling time: 1.5…2.5 ms, resolution: 11 bits AI1-/Al1+ bipolar differential voltage: +/- 10 V DC, 24 V max, sampling time: 1.5…2.5 ms, resolution: 11 bits + sign 2.5 ms, resolution: 11 bits Analogue output number 1 resolution: 10 bits resolution: 10 bits Discrete output number 2 Minimum switching current 3 mA at 24 V DC (configurable relay logic) Maximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 for configurable relay logic
2 A at 30 V DC on inductive load - L/R = 7 ms for configurable relay logic
5 A at 30 V DC on resistive load - L/R = 0 ms for configurable relay logic
2 A at 250 V AC on inductive load - cos phi = 0.4 for configurable relay logic Discrete input number 7 Switch-configurable (LI6) at 24 V DC <= 30 V level 1 PLC 1.5 kOhm (duration=1.5…2.5 ms) Safety input (PWR) at 24 V DC <= 30 V 1.5 kOhm Acceleration and deceleration ramps S, U or customized Linear adjustable separately from 0.01 to 9000 s Braking to standstill By DC injection, <60 s
Protection type Against exceeding limit speed: drive Against input phase loss: drive Break on the control circuit: drive Input phase breaks: drive Line supply overvoltage: drive Line supply undervoltage: drive Overcurrent between output phases and earth: drive Overheating protection: drive Overvoltages on the DC bus: drive Power removal: drive Short-circuit between motor phases: drive Thermal protection: drive Motor phase break: motor Power removal: motor Thermal protection: motor Dielectric strength 3110 V DC between earth and power terminals
5345 V DC between control and power terminals
Insulation resistance > 1 mOhm 500 V DC for 1 minute Frequency resolution Analog input: 0.024/50 Hz Display unit: 0.1 Hz Communication port protocol Modbus CANopen Connector type 1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen Physical interface 2-wire RS 485 for Modbus Transmission frame RTU for Modbus Transmission rate 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal 9600 bps, 19200 bps for Modbus on front face 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen Data format 8 bits, 1 stop, even parity for Modbus on front face 8 bits, odd even or no configurable parity for Modbus on terminal Type of polarization No impedance for Modbus Number of addresses 1…127 for CANopen 1…247 for Modbus Method of access Slave CANopen Options for enclosure configuration Safe standstill for power circuit PTC relay for power circuit Pt100 relay for power circuit Insulation monitoring for power circuit Design for IT networks for power circuit External 230 V supply terminals for power circuit Buffer voltage 24 V DC power supply for power circuit Enclosure lighting for power circuit Key switch (local/remote) for power circuit Motor heating for power circuit External motor fan for power circuit Voltmeter for power circuit Door handle for main switch for power circuit Line contactor for power circuit Ammeter for power circuit Enclosure heating for power circuit Motor choke for power circuit Cable entry via the top for power circuit Braking unit for power circuit Relay output C/O for control circuit External 24 V DC supply terminals for power circuit Control terminals for control circuit Adaptor for 115 V logic inputs for control circuit Isolated amplifier for control circuit Circuit breaker for control circuit Enclosure plinth for control circuit Option card Communication card for APOGEE FLN Communication card for BACnet Communication card for CC-Link Communication card for DeviceNet Communication card for Ethernet/IP Communication card for Fipio Communication card for Interbus-S Communication card for LonWorks
Communication card for METASYS N2 Communication card for Modbus Plus Communication card for Modbus TCP Communication card for Modbus/Uni-Telway Communication card for Profibus DP Communication card for Profibus DP V1 Controller inside programmable card Multi-pump card Basic I/O extension card Extended I/O extension card Encoder interface cards Operating position Vertical +/- 10 degree Colour of enclosure Light grey (RAL 7035) Colour of base of enclosure Dark grey (RAL 7022) Width 1200 mm Height 2362 mm Depth 642 mm Net weight 620 kg Environment Electromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Standards EN 61800-3 environments 1 category C3 EN 55011 class A group 2 EN/IEC 61800-3 EN 61800-3 environments 2 category C3 EN/IEC 61800-5-1 Product certifications ATEX GOST Marking CE Noise level 72 dB Pollution degree 3 conforming to EN/IEC 61800-5-1 Vibration resistance 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 3…10 Hz) conforming to EN/IEC 60068-2-6 3M3 conforming to EN/IEC 60721-3-3 Shock resistance 4 gn for 11 ms conforming to EN/IEC 60068-2-27 3M2 conforming to EN/IEC 60721-3-3 Environmental characteristic 3C2 without condensation conforming to IEC 60721-3-3 3S2 without condensation conforming to IEC 60721-3-3 3K3 without condensation conforming to IEC 60721-3-3 Relative humidity 0…95 % Ambient air temperature for operation 0…40 °C (without derating) 40…50 °C (with current derating of 1 % per °C) Ambient air temperature for storage -25…70 °C Volume of cooling air 1400 m3/h Operating altitude <= 1000 m without derating 1000...2260 m with current derating 1 % per 100 m Packing Units Package 1 Weight 580.000 kg Package 1 Height 21.600 dm Package 1 width 6.600 dm Package 1 Length 10.160 dm Contractual warranty Warranty 18 months
IP 54 Floor-Standing Enclosure with Separate Air Flows Standard Floor-Standing Enclosure Standard Compact Floor-Standing Enclosure + Additional Floor-Standing Enclosures, According to the Configuration (1) Seal. For each floor-standing enclosure added, allow a 4 mm/0.15 in. space for the seal. (2) Standard version floor-standing enclosure. NOTE: The position of the enclosures must be complied with during installation. The number of additional enclosures can vary according to the chosen configuration. Options a a1 a2 a3 a4 With or without common options or options dependent on the drive rating 808 mm/31.8 in. – – 408 mm/16 in. 1220 mm/48 in. Cable entry via the top option 808 mm/31.8 in. – – 408 mm/16 in. 1220 mm/48 in.
Motor choke + braking unit + cable entry via the top option (3) Except sinus filter option, which requires an additional enclosure. The sinus filter option is not compatible with the cable entry via the top option. (4) The cable entry via the top option is not compatible with the sinus filter option.
IP 54 Floor-Standing Enclosure with Separate Air Flows Wiring Diagram A1 Drive A2 Enclosure F1 Fast-acting semi-conductor fuse IL1 Line choke L1 DC choke Q1 Switch (1) Fault relay contacts. For remote signalling of drive status.
Floor-Standing Enclosure Compact Version Derating Curves The derating curves for the drive nominal current (In) are dependent on the temperature and switching frequency. For intermediate temperatures, interpolate between 2 curves. NOTE: The drive will reduce the switching frequency automatically in the event of excessive temperature rise. X Switching frequency (kHz) NOTE: The temperatures shown correspond to the temperature of the air entering the enclosure.