enclosed variable speed drive ATV61 Plus - 630 kW - 500V - IP23 To be discontinued Commercial status To be discontinued on: 31 December 2023 To be end-of-service on: 31 December 2031 Main Range of product Altivar 61 Plus Product or component type Variable speed drive Device short name ATV61 Product destination Synchronous motors Asynchronous motors Product specific application Pumping and ventilation machine Assembly style In floor-standing enclosure with separate air flows Product composition Control transformer for 230 V A wired ready-assembled Sarel Spacial 6000 enclosure Integrated drive system ATV61EC80YE1 A plinth A switch and fast-acting fuses Terminals/bars for motor connection An IP65 remote mounting kit for graphic display terminal EMC filter Integrated Network number of phases 3 phases Rated supply voltage 500...525 V +/- 10 % Supply frequency 50...60 Hz Motor power kW 630 kW, 3 phases at 500...525 V Line current 862 A at 500 V3 phases / 630 kW IP degree of protection IP23 Complementary Apparent power 747 kVA for 500 V3 phases / 630 kW Prospective line Isc 100 kA with external fuses Continuous output current 920 A at 2.5 kHz, 500 V3 phases Maximum transient current 1104 A for 60 s 3 phases Speed drive output frequency 0.1…500 Hz Nominal switching frequency 2.5 kHz Switching frequency 2...4.9 kHz adjustable Speed range 1…100 in open-loop mode, without speed feedback Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn without speed feedback Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 18, 2021
Torque accuracy +/- 15 % in open-loop mode, without speed feedback Transient overtorque 120 % of nominal motor torque for 60 s 135 % of nominal motor torque for 2 s Braking torque 30 % without braking resistor <= 125 % with braking resistor Asynchronous motor control profile Voltage/frequency ratio, 2 points Voltage/frequency ratio, 5 points Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, standard Synchronous motor control profile Vector control without sensor, standard Regulation loop Adjustable PI regulator Motor slip compensation Not available in voltage/frequency ratio (2 or 5 points) Automatic whatever the load Suppressable Adjustable Supply voltage limits 450…578 V Network frequency limits 47.5…63 Hz Overvoltage category Class 3 conforming to EN 50178 Local signalling LCD display unit for operation function, status and configuration Output voltage <= supply voltage Isolation Electrical between power and control Type of cable for external connection IEC cable at 40 °C, copper 70 °C / PVC Electrical connection Bar M12 - 16 x 240 mm² 41 N.m (U/T1, V/T2, W/T3) entry from the bottom Terminal - 2.5 mm² / AWG 14 0.6 N.m (R1A, R1B, R1C, R2A, R2B) entry from the bottom bottom Bar M12 - 10 x 240 mm² 41 N.m (L1/R, L2/S, L3/T) entry from the bottom at 6-pulse operation Bar M12 - 4 x 240 mm² 41 N.m (L1/R, L2/S, L3/T) entry from the bottom at 12-pulse operation Motor recommanded cable cross section 3 (3 x 240) mm² 4 (3 x 185) mm² Short-circuit protection 1250 A fuse protection type gI - power supply upstream - at 6-pulse operation
630 A fuse protection type gI - power supply upstream - at 12-pulse operation
Supply External supply: 24 V (19…30 V)DC, <1 A Internal supply for reference potentiometer: 10 V (10…11 V)DC, <10 A Internal supply: 24 V (21…27 V)DC, <100 A Analogue input number 2 Analogue input type AI2 software-configurable voltage: 0...10 V DC, 24 V max, impedance: 30 kOhm, sampling time: 1.5…2.5 ms, resolution: 11 bits AI1-/Al1+ bipolar differential voltage: +/- 10 V DC, 24 V max, sampling time: 1.5…2.5 ms, resolution: 11 bits + sign 2.5 ms, resolution: 11 bits Analogue output number 1 resolution: 10 bits resolution: 10 bits Discrete output number 2 Minimum switching current 3 mA at 24 V DC (configurable relay logic) Maximum switching current 5 A at 250 V AC on resistive load - cos phi = 1 for configurable relay logic
5 A at 30 V DC on inductive load - L/R = 7 ms for configurable relay logic
5 A at 30 V DC on resistive load - L/R = 0 ms for configurable relay logic
5 A at 250 V AC on inductive load - cos phi = 0.4 for configurable relay logic Discrete input number 7 Switch-configurable (LI6) at 24 V DC <= 30 V level 1 PLC 1.5 kOhm (duration=1.5…2.5 ms) Safety input (PWR) at 24 V DC <= 30 V 1.5 kOhm Acceleration and deceleration ramps Linear adjustable separately from 0.01 to 9000 s
S, U or customized Braking to standstill By DC injection, <60 s Protection type Overheating protection: drive Thermal protection: drive Short-circuit between motor phases: drive Input phase breaks: drive Overcurrent between output phases and earth: drive Overvoltages on the DC bus: drive Break on the control circuit: drive Against exceeding limit speed: drive Line supply undervoltage: drive Line supply overvoltage: drive Against input phase loss: drive Thermal protection: motor Motor phase break: motor Power removal: drive Power removal: motor Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance > 1 mOhm 500 V DC for 1 minute Frequency resolution Display unit: 0.1 Hz Analog input: 0.024/50 Hz Communication port protocol Modbus CANopen Connector type 1 RJ45 (on front face) for Modbus
1 RJ45 (on terminal) for Modbus
Male SUB-D 9 on RJ45 for CANopen Physical interface 2-wire RS 485 for Modbus Transmission frame RTU for Modbus Transmission rate 9600 bps, 19200 bps for Modbus on front face 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps for Modbus on terminal 20 kbps, 50 kbps, 125 kbps, 250 kbps, 500 kbps, 1 Mbps for CANopen Data format 8 bits, 1 stop, even parity for Modbus on front face 8 bits, odd even or no configurable parity for Modbus on terminal Type of polarization No impedance for Modbus Number of addresses 1…247 for Modbus 1…127 for CANopen Method of access Slave CANopen Options for enclosure configuration Safe standstill for power circuit PTC relay for power circuit Pt100 relay for power circuit Insulation monitoring for power circuit Design for IT networks for power circuit External 230 V supply terminals for power circuit Buffer voltage 24 V DC power supply for power circuit Enclosure lighting for power circuit Key switch (local/remote) for power circuit Motor heating for power circuit External motor fan for power circuit Voltmeter for power circuit Door handle for main switch for power circuit Line contactor for power circuit 12-pulse supply for power circuit Ammeter for power circuit Enclosure heating for power circuit Motor choke for power circuit Cable entry via the top for power circuit Enclosure plinth for power circuit Relay output C/O for control circuit External 24 V DC supply terminals for power circuit Circuit breaker for power circuit Line reactor for power circuit Control terminals for control circuit Adaptor for 115 V logic inputs for control circuit Isolated amplifier for control circuit Option card Communication card for Modbus TCP/IP Communication card for Fipio Communication card for Modbus/Uni-Telway Communication card for Modbus Plus
Communication card for EtherNet/IP Communication card for DeviceNet Communication card for Profibus DP Communication card for Profibus DP V1 Communication card for Interbus-S Communication card for CC-Link Communication card for LonWorks Communication card for METASYS N2 Communication card for APOGEE FLN Communication card for BACnet Basic I/O extension card Extended I/O extension card Controller inside programmable card Multi-pump card Encoder interface cards Operating position Vertical +/- 10 degree Colour of enclosure Light grey (RAL 7035) Colour of base of enclosure Dark grey (RAL 7022) Width 1800 mm Height 2009 mm Depth 642 mm Net weight 950 kg Environment Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Voltage dips and interruptions immunity test conforming to IEC 61000-4-11 Standards EN 61800-3 environments 2 category C3 EN 55011 class A group 2 EN/IEC 61800-3 EN 61800-3 environments 1 category C3 EN/IEC 61800-5-1 Product certifications ATEX GOST Marking CE Pollution degree 2 conforming to EN/IEC 61800-5-1 Noise level 77 dB Vibration resistance 1.5 mm (f= 3…10 Hz) conforming to EN/IEC 60068-2-6 0.6 gn (f= 10…200 Hz) conforming to EN/IEC 60068-2-6 3M3 conforming to EN/IEC 60721-3-3 Shock resistance 4 gn for 11 ms conforming to EN/IEC 60068-2-27 3M2 conforming to EN/IEC 60721-3-3 Environmental characteristic 3C2 without condensation conforming to IEC 60721-3-3 3S2 without condensation conforming to IEC 60721-3-3 3K3 without condensation conforming to IEC 60721-3-3 Relative humidity 0…95 % Ambient air temperature for operation 0…40 °C (without derating) 40…50 °C (with current derating of 1.2 % per °C) Ambient air temperature for storage -25…70 °C Volume of cooling air 5500 m3/h Operating altitude <= 1000 m without derating 1000...3000 m with current derating 1 % per 100 m Packing Units Package 1 Weight 900.000 kg Package 1 Height 20.000 dm Package 1 width 6.600 dm Package 1 Length 18.300 dm
IP 23 Floor-Standing Enclosure with Separate Air Flows Dimensions NOTE: For each floor-standing enclosure added, allow a 4 mm/0.15 in. space for the seal.
Floor-Standing Enclosure with Separate Air Flows Standard 6-pulse Design A1 Drive A2 Enclosure F1 Fuses IL1 Optional line choke KM1 Optional line contactor M Motor Q1 Switch Q2 Optional circuit breaker (1) Filter (2) Control (3) Relay control (4) Reference potentiometer (5) PLC (6) Optional motor choke Optional 12-pulse Design A1 Drive A2 Enclosure F1 Fuses IL1 Optional line choke KM1 Optional line contactor M Motor Q1 Switch (1) Filter (2) Control (3) Relay control (4) Reference potentiometer (5) PLC (6) Optional motor choke
IP 23 Floor-Standing Enclosure with Separate Air Flows Derating Curves The derating curves for the drive nominal current (In) are dependent on the temperature and switching frequency. For intermediate temperatures, interpolate between 2 curves. NOTE: The drive will reduce the switching frequency automatically in the event of excessive temperature rise. X Switching frequency (kHz) NOTE: The temperatures shown correspond to the temperature of the air entering the enclosure.