enclosed variable speed drive ATV31 - 11 kW - 380..500 V - 3-phase supply Main Range of product Altivar 31 Product or component type Variable speed drive Product destination Asynchronous motors Product specific application Wire guiding Simple machine Assembly style Enclosed Component name ATV31 EMC filter Integrated Network number of phases 3 phases Motor power kW 11 kW Motor power hp 15 hp Line current 28.4 A 500 V 1 kA
37.2 A 380 V 1 kA
Maximum prospective line Isc 22 kA Nominal output current 27.7 A 4 kHz Maximum transient current 41.6 A for 60 s Power dissipation in W 397 W at nominal load Speed range 1…50 Transient overtorque 150…170 % of nominal motor torque Asynchronous motor control profile Sensorless flux vector control with PWM type motor control signal Factory set : constant torque Analogue input number 3 IP degree of protection IP55 Complementary Power supply voltage limit 323…550 V Power supply frequency limits 47.5…63 Hz Speed drive output frequency 0.5…500 Hz Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications May 18, 2021
Nominal switching frequency 4 kHz Switching frequency 2...16 kHz adjustable Braking torque <= 150 % during 60 s with braking resistor 100 % with braking resistor continuously 30 % without braking resistor Regulation loop Frequency PI regulator Motor slip compensation Suppressable Automatic whatever the load Adjustable Output voltage <= power supply voltage L1, L2, L3, U, V, W, PA, PB, PA/+, PC/- terminal 2.5 mm² AWG 14 L1, L2, L3, U, V, W, PA, PB, PA/+, PC/-: 0.8 N.m Insulation Electrical between power and control Supply Internal supply for logic inputs 19…30 V, <100 mA overload protection Internal supply for logic inputs 19…30 V, <100 mA short-circuit protection Internal supply for reference potentiometer 10…10.8 V, <10 mA overload protection Internal supply for reference potentiometer 10…10.8 V, <10 mA short-circuit protection Analogue input type AI3 configurable current 0...20 mA, impedance: 250 Ohm AI1 configurable voltage 0...10 V, input voltage 30 V max, impedance: 30000 Ohm AI2 configurable voltage +/- 10 V, input voltage 30 V max, impedance: 30000 Ohm Input sampling time LI1...LI6: 4 ms discrete AI1, AI2, AI3: 8 ms analog Output response time AOV, AOC 8 ms for analog R1A, R1B, R1C, R2A, R2B 8 ms for discrete Linearity error +/- 0.2 % for output Analogue output number 2 Analogue output type AOC configurable current: 0...20 mA, impedance: 800 Ohm, resolution: 8 bits AOV configurable voltage: 0...10 V, impedance: 470 Ohm, resolution: 8 bits Discrete input logic Positive logic (source) (LI1...LI6), < 5 V (state 0), > 11 V (state 1) Logic input not wired (LI1...LI4), < 13 V (state 1) Negative logic (source) (LI1...LI6), > 19 V (state 0) Discrete output number 2 Discrete output type Configurable relay logic: (R1A, R1B, R1C) 1 NO + 1 NC - 100000 cycles Configurable relay logic: (R2A, R2B) NC - 100000 cycles Minimum switching current 10 mA 5 V DC R1-R2 Maximum switching current 2 A at 250 V AC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1-R2) 2 A at 30 V DC on inductive load - cos phi = 0.4 - L/R = 7 ms (R1-R2)
5 A at 250 V AC on resistive load - cos phi = 1 - L/R = 0 ms (R1-R2)
5 A at 30 V DC on resistive load - cos phi = 1 - L/R = 0 ms (R1-R2)
Discrete input type (LI1...LI6) programmable at 24 V, 0…100 mA for PLC, impedance: 3500 Ohm Acceleration and deceleration ramps Linear adjustable separately from 0.1 to 999.9 s S, U or customized Braking to standstill By DC injection Protection type Input phase breaks: drive Line supply overvoltage and undervoltage safety circuits: drive Line supply phase loss safety function, for three phases supply: drive Motor phase breaks: drive Overcurrent between output phases and earth (on power up only): drive Overheating protection: drive Short-circuit between motor phases: drive Thermal protection: motor Insulation resistance >= 500 mOhm 500 V DC for 1 minute Local signalling 1 LED (red) for drive voltage Four 7-segment display units for CANopen bus status Time constant 5 ms for reference change Frequency resolution Display unit: 0.1 Hz Analog input: 0.1...100 Hz Communication port protocol CANopen Modbus
Connector type 1 RJ45 for CANopen via VW3 CANTAP2 adaptor
1 RJ45 for Modbus
Physical interface RS485 multidrop serial link for Modbus Transmission frame RTU for Modbus Transmission rate 10, 20, 50, 125, 250, 500 kbps or 1 Mbps for CANopen via VW3 CANTAP2 adaptor 4800, 9600 or 19200 bps for Modbus Number of addresses 1…127 for CANopen via VW3 CANTAP2 adaptor 1…247 for Modbus Number of drive 127 for CANopen via VW3 CANTAP2 adaptor 31 for Modbus Marking CE Operating position Vertical +/- 10 degree Net weight 32.5 kg Environment Dielectric strength 2410 V DC between earth and power terminals
3400 V AC between control and power terminals
Electromagnetic compatibility 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4 Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3 Standards EN 50178 Product certifications C-Tick Pollution degree 2 Protective treatment TC Vibration resistance 1 gn (f= 13…150 Hz) conforming to EN/IEC 60068-2-6 1.5 mm (f= 3…13 Hz) conforming to EN/IEC 60068-2-6 Shock resistance 15 gn for 11 ms conforming to EN/IEC 60068-2-27 Relative humidity 5…95 % without condensation conforming to IEC 60068-2-3 5…95 % without dripping water conforming to IEC 60068-2-3 Ambient air temperature for storage -25…70 °C Ambient air temperature for operation -10…50 °C without derating (with protective cover on top of the drive) -10…60 °C with derating factor (without protective cover on top of the drive) Operating altitude <= 1000 m without derating >= 1000 m with current derating 1 % per 100 m Contractual warranty Warranty 18 months