The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Aug 9, 2019 Product data sheet Characteristics ATV212HD30N4 variable speed drive ATV212 - 30kW - 40hp - 480V - 3ph - EMC - IP21 Product availability: Stock - Normally stocked in distribution facility Main Range of product Altivar 212 Product or component type Variable speed drive Device short name ATV212 Product destination Asynchronous motors Product specific applica- tion Pumps and fans in HVAC Assembly style With heat sink Phase 3 phases Motor power kW 30 kW Motor power hp 40 hp [Us] rated supply volt- age Supply voltage limits 323...528 V Network frequency 47.5...63 Hz EMC filter Class C2 EMC filter integrated Line current 44.7 A 480 V
56.7 A 380 V
Apparent power 44.6 kVA 380 V Prospective line Isc 22 kA Continuous output current 58.5 A 380 V
58.5 A 460 V
Maximum transient current 64.4 A 60 s Speed drive output frequency 0.5...200 Hz Nominal switching frequency 8 kHz Switching frequency 6...16 kHz adjustable 8...16 kHz with derating factor Speed range 1...10 Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn Torque accuracy +/- 15 % Transient overtorque 120 % of nominal motor torque +/- 10 % 60 s Asynchronous motor control profile Voltage/Frequency ratio, 2 points Voltage/Frequency ratio, 5 points Flux vector control without sensor, standard Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Regulation loop Adjustable PI regulator Motor slip compensation Adjustable Automatic whatever the load Not available in voltage/frequency ratio motor control Local signalling 1 LED red DC bus energized Output voltage <= power supply voltage Isolation Electrical between power and control Type of cable IEC cable without mounting kit 1 113 °F (45 °C) copper 90 °C XLPE/EPR IEC cable without mounting kit 1 45 °C copper 70 °C PVC UL 508 cable with UL Type 1 kit 3 40 °C copper 75 °C PVC
Electrical connection Terminal 0 in² (2.5 mm²) AWG 14 VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES Terminal 50 mm² AWG 1/0 L1/R, L2/S, L3/T Tightening torque 212.39 lbf.in (24 N.m) 212 lb.in L1/R, L2/S, L3/T 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 % <=
10 A overload and short-circuit protection
Internal supply 24 V DC 21...27 V <= 200 A overload and short-circuit protection Analogue input number 2 Analogue input type Switch-configurable voltage VIA 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable voltage VIB 0...10 V DC 24 V max 30000 Ohm 10 bits Configurable PTC probe VIB 0...6 probes 1500 Ohm Switch-configurable current VIA 0...20 mA 250 Ohm 10 bits Sampling duration 2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog Response time 2 ms +/- 0.5 ms FM analog 7 ms +/- 0.5 ms FLA, FLC discrete 7 ms +/- 0.5 ms FLB, FLC discrete 7 ms +/- 0.5 ms RY, RC discrete Accuracy +/- 0.6 % VIA for a temperature variation 60 °C +/- 0.6 % VIB for a temperature variation 60 °C +/- 1 % FM for a temperature variation 60 °C Linearity error +/- 0.15 % of maximum value input VIA +/- 0.15 % of maximum value input VIB +/- 0.2 % output FM Analogue output number 1 Analogue output type Switch-configurable voltage FM 0...10 V DC 7620 Ohm 10 bits Switch-configurable current FM 0...20 mA 970 Ohm 10 bits Discrete output number 2 Discrete output type Configurable relay logic FLA, FLC NO 100000 cycles Configurable relay logic FLB, FLC NC 100000 cycles Configurable relay logic RY, RC NO 100000 cycles Minimum switching current 3 mA 24 V DC configurable relay logic Maximum switching current 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R Discrete input type Programmable F 24 V DC level 1 PLC 4700 Ohm Programmable R 24 V DC level 1 PLC 4700 Ohm Programmable RES 24 V DC level 1 PLC 4700 Ohm Discrete input logic Positive logic (source) F, R, RES <= 5 V >= 11 V Negative logic (sink) F, R, RES >= 16 V <= 10 V Acceleration and deceleration ramps Automatic based on the load Linear adjustable separately from 0.01 to 3200 s Braking to standstill By DC injection Protection type Motor phase break motor Break on the control circuit drive Thermal power stage drive Overvoltages on the DC bus drive Against exceeding limit speed drive Against input phase loss drive With PTC probes motor Input phase breaks drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Overcurrent between output phases and earth drive Overheating protection drive Short-circuit between motor phases drive Thermal protection motor Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance >= 1 MOhm 500 V DC for 1 minute Frequency resolution 0.024/50 Hz analog input
0.1 Hz display unit
Communication port protocol APOGEE FLN BACnet LonWorks METASYS N2 Modbus Connector type 1 RJ45 1 open style Physical interface 2-wire RS 485 Transmission frame RTU Transmission rate 9600 bps or 19200 bps Data format 8 bits, 1 stop, odd even or no configurable parity Type of polarization No impedance Number of addresses 1...247 Communication service Monitoring inhibitable Read device identification (43) Read holding registers (03) 2 words maximum Time out setting from 0.1 to 100 s Write multiple registers (16) 2 words maximum Write single register (06) Option card Communication card LonWorks Operating position Vertical +/- 10 degree Width 9.45 in (240 mm) Height 16.54 in (420 mm) Depth 8.43 in (214 mm) Product weight 58.2 lb(US) (26.4 kg) Power dissipation in W 847 W Air flow 76611.27 Gal/hr(US) (290 m3/h) Functionality Mid Specific application HVAC IP degree of protection IP21 Variable speed drive application selection Building - HVAC : compressor for scroll Building - HVAC : fan Building - HVAC : pump Motor starter type Variable speed drive Environment Electromagnetic compatibility Conducted radio-frequency immunity test level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test IEC 61000-4-11 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Pollution degree 3 IEC 61800-5-1 IP degree of protection IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 Vibration resistance 1 gn 13...200 Hz EN/IEC 60068-2-8 1.5 mm 3...13 Hz EN/IEC 60068-2-6 Shock resistance 15 gn 11 ms IEC 60068-2-27 Environmental characteristic Classes 3C1 IEC 60721-3-3 Classes 3S2 IEC 60721-3-3 Noise level 59.9 dB 86/188/EEC distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating Relative humidity 5...95 % without condensation IEC 60068-2-3 5...95 % without dripping water IEC 60068-2-3
Standards EN 55011 class A group 1 EN 61800-3 EN 61800-3 category C2 EN 61800-3 category C3 EN 61800-3 environments 1 category C1 EN 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C1 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C3 EN 61800-5-1 IEC 61800-3 IEC 61800-3 category C2 IEC 61800-3 category C3 IEC 61800-3 environments 1 category C1 IEC 61800-3 environments 1 category C2 IEC 61800-3 environments 1 category C3 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 UL Type 1 Product certifications CSA C-Tick NOM 117 UL Marking CE Ordering and shipping details Category 22158 - ATV212 30 - 100 HP 460 VOLT Discount Schedule CP4D GTIN 00785901921554 Nbr. of units in pkg. 1 Package weight(Lbs) 68.200000000000003 Returnability Y Country of origin CN Offer Sustainability Sustainable offer status Green Premium product RoHS (date code: YYWW) Compliant - since 1050 - Schneider Electric declaration of conformity Schnei- der Electric declaration of conformity REACh Reference not containing SVHC above the threshold Product environmental profile Available Product end of life instructions Available California proposition 65 WARNING: This product can expose you to chemicals including: - - - - - - - Substance 1 Lead and lead compounds, which is known to the State of California to cause can- cer and birth defects or other reproductive harm. - - - - - - - Substance 2 Bisphenol A (BPA), which is known to the State of California to cause birth defects or other reproductive harm. - - - - - - - More information For more information go to www.p65warnings.ca.gov Contractual warranty Warranty period 18 months
ATV212H a b c G H K Ø D22M3X D22N4, D30N4 240 420 214 206 403 10 6 D37N4, D45N4 240 550 244 206 529 10 6 Dimensions in in. ATV212H a b c G H K Ø D22M3X D22N4, D30N4 EMC mounting plate (supplied with drive) Dimensions in mm ATV212H b1 c1 D22M3X D22N4, D30N4 122 120 D37N4, D45N4 113 127 Dimensions in in. ATV212H b1 c1 D22M3X D22N4, D30N4 4.80 4.72 D37N4, D45N4 4.45 5.00
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit. Mounting Types Type A mounting Type B mounting Type C mounting By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite. Specific Recommendations for Mounting in an Enclosure To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Recommended Wiring Diagram 3-Phase Power Supply A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, S2: XB4 B or XB5 A pushbuttons T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Switches (Factory Settings) Voltage/current selection for analog I/O (VIA and VIB) Voltage/current selection for analog I/O (FM) Selection of logic type (1) negative logic (2) positive logic Other Possible Wiring Diagrams
Logic Inputs According to the Position of the Logic Type Switch “Source” position “Sink” position “PLC” position with PLC transistor outputs (1) PLC (1) PLC 2-wire control F: Forward R: Preset speed (2) ATV 212 control terminals 3-wire control F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals PTC probe (2) ATV 212 control terminals (3) Motor Analog Inputs Voltage analog inputs External +10 V (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ (2) ATV 212 control terminals
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA (2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA Analog input VIA configured as positive logic input (“Source” position) (2) ATV 212 control terminals Analog input VIA configured as negative logic input (“Sink” position) (2) ATV 212 control terminals
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves. X Switching frequency