The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications. It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof. Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein. Jan 12, 2022 Product data sheet Characteristics ATV212H075N4 variable speed drive ATV212 - 0.75kW - 1hp - 480V - 3ph - EMC - IP21 Main Device short name ATV212 Product destination Asynchronous motors Phase 3 phase Motor power kW 0.75 kW Maximum Horse Power Rating 1 hp Supply voltage limits 323…528 V Line current 1.4 A 480 V
1.7 A 380 V
Range of Product Altivar 212 Product or Component Type Variable speed drive Product Specific Application Pumps and fans in HVAC Communication Port Protocol Modbus METASYS N2 APOGEE FLN LonWorks BACnet [Us] rated supply voltage EMC filter Class C2 EMC filter integrated IP degree of protection IP21 Complementary Apparent power 1.6 kVA 380 V Continuous output current 2.2 A 380 V
2.2 A 460 V
Maximum transient current 2.4 A 60 s Speed drive output frequency 0.5…200 Hz Speed range 1…10 Speed accuracy +/- 10 % of nominal slip 0.2 Tn to Tn Local signalling For DC bus energized 1 LED (red) Output voltage <= power supply voltage Isolation Electrical between power and control Type of cable Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC Electrical connection VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00 in² (2.5 mm²) / AWG 14 L1/R, L2/S, L3/T terminal 0.01 in² (6 mm²) / AWG 10 5.31 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) Supply Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection Sampling duration 2 Ms +/- 0.5 ms F discrete 2 Ms +/- 0.5 ms R discrete 2 Ms +/- 0.5 ms RES discrete 3.5 Ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog
Response time FM 2 ms +/- 0.5 ms analog FLA, FLC 7 ms +/- 0.5 ms discrete FLB, FLC 7 ms +/- 0.5 ms discrete RY, RC 7 ms +/- 0.5 ms discrete Accuracy +/- 0.6 % VIA) for a temperature variation 60 °C +/- 0.6 % VIB) for a temperature variation 60 °C +/- 1 % FM) for a temperature variation 60 °C Linearity error VIA +/- 0.15 % of maximum value input VIB +/- 0.15 % of maximum value input FM +/- 0.2 % output Analogue output type FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits FM switch-configurable current 0...20 mA 970 Ohm 10 bits Discrete output type Configurable relay logic FLA, FLC) NO - 100000 cycles Configurable relay logic FLB, FLC) NC - 100000 cycles Configurable relay logic RY, RC) NO - 100000 cycles Minimum switching current 3 mA 24 V DC configurable relay logic Maximum switching current 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)
2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) Discrete input type F programmable 24 V DC level 1 PLC 4700 Ohm R programmable 24 V DC level 1 PLC 4700 Ohm RES programmable 24 V DC level 1 PLC 4700 Ohm Discrete input logic Positive logic (source) F, R, RES), <= 5 V, >= 11 V Negative logic (sink) F, R, RES), >= 16 V, <= 10 V Dielectric strength 3535 V DC between earth and power terminals
5092 V DC between control and power terminals
Insulation resistance >= 1 mOhm 500 V DC for 1 minute Frequency resolution Display unit 0.1 Hz Analog input 0.024/50 Hz Communication Service Read device identification (43) Time out setting from 0.1 to 100 s Write single register (06) Write multiple registers (16) 2 words maximum Monitoring inhibitable Read holding registers (03) 2 words maximum Option card Communication card LonWorks Power dissipation in W 55 W Air flow 5019.36 Gal/hr(US) (19 m3/h) Functionality Mid Specific application HVAC Variable speed drive application selection Compressor for scroll Building - HVAC Fan Building - HVAC Pump Building - HVAC Motor power range AC-3 0.55…1 KW 380…440 V 3 phase 0.55…1 kW 480…500 V 3 phase Motor starter type Variable speed drive Discrete output number 2 Analogue input number 2 Analogue input type VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable PTC probe 0...6 probes 1500 Ohm VIA switch-configurable current 0...20 mA 250 Ohm 10 bits Analogue output number 1 Physical interface 2-wire RS 485 Connector type 1 open style
1 RJ45
Transmission Rate 9600 bps or 19200 bps Transmission frame RTU Number of addresses 1…247 Data format 8 bits, 1 stop, odd even or no configurable parity Type of polarization No impedance
Asynchronous motor control profile Voltage/Frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/Frequency ratio - Energy Saving, quadratic U/f Voltage/Frequency ratio, 2 points Flux vector control without sensor, standard Voltage/frequency ratio, 5 points Torque accuracy +/- 15 % Transient overtorque 120 % of nominal motor torque +/- 10 % 60 s Acceleration and deceleration ramps Automatic based on the load Linear adjustable separately from 0.01 to 3200 s Motor slip compensation Not available in voltage/frequency ratio motor control Automatic whatever the load Adjustable Switching frequency 6...16 kHz adjustable 12...16 kHz with derating factor Nominal switching frequency 12 kHz Braking to standstill By DC injection Network Frequency 47.5...63 Hz Prospective line Isc 5 kA Protection type Overheating protection drive Thermal power stage drive Short-circuit between motor phases drive Input phase breaks drive Overcurrent between output phases and earth drive Overvoltages on the DC bus drive Break on the control circuit drive Against exceeding limit speed drive Line supply overvoltage and undervoltage drive Line supply undervoltage drive Against input phase loss drive Thermal protection motor Motor phase break motor With PTC probes motor Width 4.21 in (107 mm) Height 5.63 in (143 mm) Depth 5.91 in (150 mm) Net Weight 4.41 lb(US) (2 kg) Environment Pollution degree 2 IEC 61800-5-1 IP degree of protection IP20 on upper part without blanking plate on cover EN/IEC 61800-5-1 IP20 on upper part without blanking plate on cover EN/IEC 60529 IP21 EN/IEC 61800-5-1 IP21 EN/IEC 60529 IP41 on upper part EN/IEC 61800-5-1 IP41 on upper part EN/IEC 60529 Vibration resistance 1.5 mm 3…13 Hz)EN/IEC 60068-2-6 1 gn 13…200 Hz)EN/IEC 60068-2-8 Shock resistance 15 gn 11 ms IEC 60068-2-27 Environmental characteristic Classes 3C1 IEC 60721-3-3 Classes 3S2 IEC 60721-3-3 Noise level 51 dB 86/188/EEC distribution network with current derating 1 % per 100 m <= 3280.84 ft (1000 m) without derating Relative humidity 5…95 % without condensation IEC 60068-2-3 5…95 % without dripping water IEC 60068-2-3 Ambient air temperature for operation 14…104 °F (-10…40 °C) without derating) 104…122 °F (40…50 °C) with derating factor) Operating position Vertical +/- 10 degree Product Certifications UL NOM 117 CSA C-tick Marking CE
Standards EN 55011 class A group 1 EN 61800-3 environments 1 category C3 EN 61800-3 environments 2 category C2 EN 61800-3 environments 2 category C1 EN 61800-3 category C3 IEC 61800-3 environments 1 category C2 EN 61800-3 environments 1 category C2 IEC 61800-3 environments 2 category C3 IEC 61800-5-1 EN 61800-3 environments 1 category C1 UL Type 1 IEC 61800-3 category C2 EN 61800-3 IEC 61800-3 IEC 61800-3 environments 1 category C1 EN 61800-3 category C2 IEC 61800-3 environments 2 category C1 IEC 61800-3 environments 2 category C2 IEC 61800-3 category C3 EN 61800-3 environments 2 category C3 IEC 61800-3 environments 1 category C3 EN 61800-5-1 Assembly style With heat sink Electromagnetic compatibility Electrostatic discharge immunity test level 3 IEC 61000-4-2 Radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 Electrical fast transient/burst immunity test level 4 IEC 61000-4-4 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5 Conducted radio-frequency immunity test level 3 IEC 61000-4-6 Voltage dips and interruptions immunity test IEC 61000-4-11 Regulation loop Adjustable PI regulator Ambient Air Temperature for Storage -13…158 °F (-25…70 °C) Ordering and shipping details Category 22157 - ATV212 1 - 25 HP 460 VOLT Discount Schedule CP4D GTIN 3606480322440 Nbr. of units in pkg. 1 Package weight(Lbs) 4.27 lb(US) (1.937 kg) Returnability Yes Country of origin ID Packing Units Unit Type of Package 1 PCE Package 1 Height 7.28 in (18.5 cm) Package 1 width 7.09 in (18 cm) Package 1 Length 8.46 in (21.5 cm) Unit Type of Package 2 P06 Number of Units in Package 2 27 Package 2 Weight 143.54 lb(US) (65.11 kg) Package 2 Height 28.94 in (73.5 cm) Package 2 width 23.62 in (60 cm) Package 2 Length 31.50 in (80 cm) Offer Sustainability Sustainable offer status Green Premium product California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes
RoHS exemption information Yes China RoHS Regulation China RoHS Declaration Environmental Disclosure Product Environmental Profile Circularity Profile End Of Life Information WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. Contractual warranty Warranty 18 months
Plate for EMC mounting (supplied with the drive) (1) 2 x M5 screws
Depending on the conditions in which the drive is to be used, its installation will require certain precautions and the use of appropriate accessories. Install the unit vertically:
- Do not place it close to heating elements.
- Leave sufficient free space to ensure that the air required for cooling purposes can circulate from bottom to the top of the unit. Mounting Types Type A mounting Type B mounting Type C mounting By removing the protective blanking cover from the top of the drive, the degree of protection for the drive becomes IP21. The protective blanking cover may vary according to the drive model, see opposite. Specific Recommendations for Mounting in an Enclosure To help ensure proper air circulation in the drive:
- Fit ventilation grilles.
- Check that there is sufficient ventilation. If there is not, install a forced ventilation unit with a filter. The openings and/or fans must provide a flow rate at least equal to that of the drive fans (refer to the product characteristics).
- Use special filters with UL Type 12/IP54 protection.
- Remove the blanking cover from the top of the drive.
Sealed Metal Enclosure (IP54 Degree of Protection) The drive must be mounted in a dust and damp proof enclosure in certain environmental conditions, such as dust, corrosive gases, high humidity with risk of condensation and dripping water, splashing liquid, etc.This enables the drive to be used in an enclosure where the maximum internal temperature reaches 50°C.
Recommended Wiring Diagram 3-Phase Power Supply A1: ATV 212 drive KM1: Contactor Q1: Circuit breaker Q2: GV2 L rated at twice the nominal primary current of T1 Q3: GB2CB05 S1, S2: XB4 B or XB5 A pushbuttons T1: 100 VA transformer 220 V secondary (1) Fault relay contacts for remote signalling of the drive status (2) Connection of the common for the logic inputs depends on the positioning of the switch (Source, PLC, Sink) (3) Reference potentiometer SZ1RV1202 NOTE: All terminals are located at the bottom of the drive. Install interference suppressors on all inductive circuits near the drive or connected on the same circuit, such as relays, contactors, solenoid valves, fluorescent lighting, etc. Switches (Factory Settings) Voltage/current selection for analog I/O (VIA and VIB) Voltage/current selection for analog I/O (FM) Selection of logic type (1) negative logic (2) positive logic Other Possible Wiring Diagrams
Logic Inputs According to the Position of the Logic Type Switch “Source” position “Sink” position “PLC” position with PLC transistor outputs (1) PLC (1) PLC 2-wire control F: Forward R: Preset speed (2) ATV 212 control terminals 3-wire control F: Forward R: Stop RES: Reverse (2) ATV 212 control terminals PTC probe (2) ATV 212 control terminals (3) Motor Analog Inputs Voltage analog inputs External +10 V (2) ATV 212 control terminals (4) Speed reference potentiometer 2.2 to 10 kΩ (2) ATV 212 control terminals
Analog input configured for current: 0-20 mA, 4-20 mA, X-Y mA (2) ATV 212 control terminals (5) Source 0-20 mA, 4-20 mA, X-Y mA Analog input VIA configured as positive logic input (“Source” position) (2) ATV 212 control terminals Analog input VIA configured as negative logic input (“Sink” position) (2) ATV 212 control terminals
The derating curves for the drive nominal current (In) depend on the temperature, the switching frequency and the mounting type (A, B or C). For intermediate temperatures (45°C for example), interpolate between 2 curves. X Switching frequency