AS9024 GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- Approvals include: - UL Standard 1971 - UL Standard 464 - New York City (MEA) - California State Fire Marshall (CSFM)
- ADA/NFPA/UFC/AN SI compliant
- Wall-mounted models are available with field multi- candela settings of 15, 30, 75, or 110 cd
- Ceiling mounted models are available with field select- able multi-candela settings of 15, 30, 75, or 95 cd
- Single candela models are available in 15/75 cd
- Weatherproof models are available for outdoor use (ASWP)
- Selected continuous horn or temporal pattern (ANSI 3.41)
- Three (3) field dBA settings adjusted to 90, 95, or 99 dBA for both tones
- Silenceable horns and non-silenceable strobes installed over the same wires
- Strobes flash once per second over the regulated volt- age range
- 12 & 24 VDC models with wide UL “regulated voltage range” using filtered DC or unfiltered FWR input voltage
- Synchronize with SM or DSM synchronization modules
- Fast installation with In/Ou t screw terminals using 12 to
18 AWG wires
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com 9020-0572 Rev. C1 page 2 of 4 Description (Continued) General Notes:
- Strobes are designed to flash at one flash per second minimum over the Regulated Voltage Range. Note that NFPA-72 (1999) specifies a flash rate of one to two flashes per second and ADA guidelines specify a flash rate of one to three flashes per second.
- All candela ratings represent minimum effective strobe intensity based on UL Standard 1971.
- Series AS strobe products are Listed under UL Standard 1971 for indoor use with a temperature range of 32 ° F to 120° F (0 ° C to 49 ° C) and a maximum humidity of 93% (+/- 2%).
- Series AH horns are Listed under UL Standard 464 for audible signal appliances (indoor use only).
- Series AH-24WP audible appliances are Listed under UL Standard 464 for indoor/outdoor use with a temperature range of –31° F to 150° F (-35 ° C to 66° C) and a maximum humidity of 95%.
- “Regulated Voltage Range” is the state-of-the-art technol- ogy used by UL to identify the voltage range. Prior to this technology, UL used the term, “Listed Voltage Range.” Table 5:dBA Ratings for 12 VDC & 24 VDC Series AS/AH 12 & 24 VDC Horns
Description
per UL 464 @ 10 pt. Anchoic dBA @ 10 pt. Continuous Horn High 91 99 Medium 88 95 Low 83 90 Temporal Pattern High 87 99 Medium 84 95 Low 79 90 Table 6: Average RM S Current* for AS-24 M CC Ceil- ing Models @ each Candela Setting Average Current with High dBA Setting (99 dBA) Voltage 15 cd 30 cd 75 cd 95 cd Average Current with Medium dBA Setting (95 dBA) Average Current with Low dBA Setting (90 dBA) Table 7: Average Mean Current* Series AS-241575 Voltage High Medium Low 8.0 VDC 0.320 0.276 0.286 0.250 0.195 0.175 12.0 VDC 17.5 VDC 0.205 0.105 0.130 Table 1: Ratings per UL 1971 Model Input Voltage VDC Regulated Voltage Range VDC/FW R Strobe Candela (cd) AS-24MCW-FA 24 160-330 15/30/75/110 AS-241575W-FR 24 160-330 15 (75 or Axis) AS-121575W-FR 12 80-175 15 (75 or Axis) AS-24M C C –FW 24 160-330 15/30 /75 /95 AS WP-2475W-FR 24 160-330 75 @ -31° F Table 2: Average RMS Current* fir AS-24 MCW Wall- Models @ each Candela Setting Average Current with High dBA Setting (99 dBA) Voltage 15 cd 30 cd 75 cd 110 cd Average Current with Medium dBA Setting (95 dBA) Average Current with Low dBA Setting (90dBA) Table 3: Average Mean Current * Series AH-24R/W & AH-12-R/W * W P (Horn only) Voltage High Medium Low 16.0 VDC 0.035 0.020 0.14 24.0 VDC 0.050 0.026 0.017 33.0 VDC 0.089 0.035 0.021 8.0 VDC 0.093 0.037 0.080 12.0 VDC 0.108 0.049 0.085 17.5 VDC 0.128 0.069 0.042 Table 4: Avereage RM* Current Series AS0241575 Voltage High Medium Low 16.0 VDC 0.130 0.114 0.108 24.0 VDC 0.107 0.085 0.075 33.0 VDC 0.105 0.075 0.060
www.gamewell-fci.com 9020-0572 Rev. C1 page 3 of 4 # SM Sync Module is rated for 3.0 amps @ 24 VDC ## DSM Sync Module is rated for 3.0 amps per circuit. The maximum number of interconnected DSM Modules is 20. SYNC MODULES MODEL ORDER CODE INPUT VOLTAGE (VDC) AVERAGE MEAN CURRENT@ 24VDC SM-12/24-R # 6369 24VDC 0.028A SM-12/24-R ## 6374 24VDC 0.035A STROBE NAC CIRCUIT RETURN + OUT 1 + IN 1 MINUS 1 + AUDIBLE - AUDIBLE MINUS 2 + IN 2 + OUT 2 ASAS AS AS AS AS F A C P STROBE NAC CIRCUIT AUDIBLE NAC CIRCUIT DSM #1 DSM #2 DSM #3 - SYNC + SYNC AUDIBLE NAC CIRCUIT AUDIBLE NAC CIRCUIT STROBE NAC CIRCUIT STROBE NAC CIRCUIT DSM INTERCONNECTING WIRING SHOWN. MAXIUMUM OF TWENTY (20) MODULES WIRING DIAGRAMS + SYNC - SYNC - SYNC + SYNC AS AS ASAS AS AS STROBE NAC CIRCUIT SM NAC CIRCUIT AUDIBLE SERIES AS APPLIANCES NON-SYNCHRONIZED + - FROM PRECEDING APPLIANCE OR FACP TO NEXT APPLIANCE OR EOLR +- +- SERIES AS APPLIANCES SYNCHRONIZED WITH MUTIPLE DSM MODULES SERIES AS APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE CLASS "A" NAC CIRCUIT WITH NO AUDIBLE SILENCE FEATURE F A C P STROBE NAC CIRCUIT OUT DSM + SYNC - SYNC SERIES AS APPLIANCES SYNCHRONIZED WITH SM MODULE SINGLE CLASS "B" NAC CIRCUIT WITH AUDIBLE SILENCE FEATURE F A C P + STROBE - STROBE + AUDIBLE - AUDIBLE EOLR AS AS
www.gamewell-fci.com 9020-0572 Rev. C1 page 4 of 4 Architects and Engineers Specifications The notification appliances shall be Cooper-Wheelock Series AS audible/strobe appliances and Series AH audible appliances or approved equals. The Series AS appliance shall be listed under UL Standard 1971 (Emergency Devices for the Hearing Impaired) for indoor Fire Protection Service. The Series AH Audible shal l be UL Listed under Standard 464 (Fire Protective Signaling). Bo th shall meet the requirements of FCC Part 15 Class B. All inputs shall be compatible with standard reverse polarity supervision o f circuit wiring by a fire alarm control panel (FACP). The audible portion of the appliance shall have a minimum of th ree (3) field selectable settings for dBA levels and shall have a choice of continuous or temporal pattern audible output. The strobe portion of the appliance shall produce a flash rate of one (1) flash per second over the Regulated Voltage Range and shall incorporate a Xenon flashtube enclosed in a rugged Lexan ® lens. The series AS shall be of low current design. Where Multi- Candela appliances are specified, the strobe intensity shall have a minimum of four (4) field selectable settings and shall be rated per UL Standard 1971 at: 15, 30, 75, and 110 candela for wall mount, or 15, 30, 75, and 95 candela for ceiling mount. The selector switch for selecting the candela shall be ta mper resistant and not accessible from t he front of the applianc e. The 15/75 candel a strobe shall be specified when 15 cd UL Standard 1971 Listing with 75 cd on-axis is required (e.g. ADA compliance). When synchronization is required, the appliance shall be compat ible with Cooper-Wheelock’s SM and DSM Sync Modules. The strobes shall not drift out of synchronizati on at any time during operatio n. If the sync module fails to operate, i.e. contacts remain closed), the strobe shall revert to a non-synchronized flash-rate . The appliance shall also be designed so that the audible sig nal may be silenced while maintaining strobe activation. The Series AS audible/strobe and Series AH audible shall incor porate a patented universal mounting plate that shall allow mount - ing on a single-gang, double-gang, 4-inch square, 100 mm Eur opean type backbox, or the SHBB surface backbox. If required, an NATP (Notification Appliance Trimplate) shall be provided. All notification appliances shall be backward compatible. Specifications Model Strobe Candela Non-Sync Sync w SM/ or DSM VDC VDC Wall Mount Ceiling Mount UL MEA CSFM FM BFP AS-24MCW-FR 15/30/75/110 X X X - X - X X X X X AS-24M CW –FW 15/30/75/110 X X X - X - X X X X X AS-241575W - FR 15 (75 on Axis) X X X - X - X X X X X AS-121575W –FR 15 (75 on Axis) X X X - X - X X X X X AS-24MCC –FW 15/30/75/95 X X X - - X X * * * * ASW-P-2475W –FR 75 @ -31° F X X X - X - X X X X * AH –24-R - X X X - X X X X X X X AH –24W P-R - X X X - X X X X AH –12W P-R - X X - X X X X X