INI-VGC GAMEWELL-FCI | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 4
Technical content
Features
- All communication signals and control-by-event sequences over twisted, unshielded pair of wires or fiber-optic cable including:
- Distributed architecture, including Style 7 wiring configurations, allow system components to continue normal operation with NO loss of function during single line fault conditions.
- Integrates with IN X transponders and addi tional INCC command centers to create a complete audio evacuation system with up to 64 nodes.
- Each INI-VGC supports up to sixteen (16), ASM-16 switch modules for a total of 256 switches.
- INI-VGC connects to a voice page microphone and fire fighter’s handset.
- Redundant command centers with microphone and fire fighter’s handset easily configured by adding additional INCCs.
- Advance Boolean logic-based programming such as AND, OR, NOT, NOR, time delay, and calendar functions configurable through computer programming.
- Advanced digital signal processor (DSP) technology for efficient audio compression and filtering. Uses network data transfer rate at 625K baud.
- Listed under UL Standard 864, 9th Edition. - Audio Evacuation - Fan Control & Damper Shutdown - Voice Paging - Door Closures - Fire Fighter Intercom - Fire Alarm and Control Devices - Elevator Control - Horn/Strove Circuit Activation An ISO 9001-2000 Company INCC
Each Addressable Switch Module (ASM-16) has sixteen (16), push-button switches that can be programmed to serve any function the application demands. An ASM-16 switch can be programmed as a Speaker Circuit switch, Fire Fighter Phone switch, an Auxiliary Contro l switch using a bank of three (3), switches (one switch each for On-Off- Auto functions), or switches with custom defined functions (e.g. System Reset, System Silence, System Acknowledge, All-Call, Phone Patch, Lamp Test, Alarm Tone On, Manual Select, etc.). Each ASM-16 switch also has three (3), fully programmable status-indicating LEDs in Red, Yellow, and Green. The INCC assembly is enclosed in one or more compact 19” wall-mounted enclosures. Its modular construction provides comple te flexibility in system design. Each cabinet can contain the INI-VGC and up to six (6), ASM-16 modules. If more ASM-16 modules are required, they may be mounted in additional INCC cabinets. As many as six (6), ASM-16 modules can fit in the INCC cabinet. If a Microphone module is required, it would take the place of one ASM-16 position. A Fire Fighter handset would take the place of two ASM-16 positions. An INI-VGC can support as many as sixteen (16), ASM-16s for a total of 256 completely programmable switches. The INCC operates on 24 VDC that can be sourced from the non-rese ttable auxiliary output of its associated power supply such as the PM-9. A complete E3 Audio Evacuation System can be assembled from three (3) different panels: one or more E3 Series™ fire alarm control panels, one or more INCC Audio Evacuation Command Centers, and one or more INX transponders. This modular approach greatly simplifies the design and installation process and can be configured to meet the exact needs of the project. GAMEWELL-FCI
12 Clintonville Road, Northford, CT 06472 - Tel: (203) 484-7161 - Fax: (203) 484-7118
www.gamewell-fci.com 9020-0542 Rev. G page 2 of 4 Figure 1 INCC with MIC and Handset Figure 2 INCC with Six (6) ASM-16s
www.gamewell-fci.com 9020-0542 Rev. G page 3 of 4
Description
Operating Voltage: 24 VDC (nominal) Operating Current: 0.150 amp. supervisory and alarm Operating Temperature: 32˚ to 120˚ F (0˚ to 49˚ C) Relative Humidity: 0 to 93% (non-condensing) Protocol Asynchronous with half-duplex data flow Speed RS-232 up to 64 KBps RS-485 up to 128 KBps St connectors Up to 200 microns (multimode), optimized for 62.5/125 microns ASM-16 Operating Voltage: 24 VDC (nominal) Operating Current: 0.005 amp supervisory 0.005 amp alarm plus 0.003 amp per LED activated (0.195 amp max.) Operating Temperature: 32˚ to 120˚ F (0 to 49˚ C) Relative Humidity: 0 to 93% (non-condensing) GAMEWELL-FCI www.gamewell-fci.com 9020-0542 Rev. G page 4 of 4
Ordering Information
Intelligent Network Command Center INI-VGC Command center voice gateway ASM-16 Programmable switch module (occupies one single slot of inner door) INCC-IDT Inner door with one double slot for INCC=TEL fire fighter handset and 4 single slots INCC-ID Inner door with six (6), single slots INCC-CAB INCC backbox (black) with black outer door. 19” W x 19” H x 4” D (48 x 48 x 10 cm) INCC-CABR INCC backbox (black) with red outer door 19” W x 19” H x 4” D (48 x 48 x 10 cm) Optional Accessories INCC-TEL Fire fighter telephone handset (requires INCC-IDT Inner Door) INCC-MIC Paging microphone module (occupies one single slot of Inner Door) INCC-BP Command center blank face plate (occupies one single slot of inner door)