rev 12.01.01 America’s (USA): 1-888-41-ASTEC Europe (UK): 44 (1384) 842-211 Asia (HK): 852-2437-9662182 Special Features Electrical Specs INPUT DC input -40 VDC to –75 VDC Transients ANSI T1.315-1994, FTZ19, BTR2511 Input feeds 4 x 100A each 4 x 150A each (available in the future) OUTPUT DC output 20 x 25A breakers total Four breaker modules, each with 5 x 25A breakers Alarm signals Critical, major, minor alarms 48V 400-600 Amp Breaker Panel (BIP) AP6C64AA
- L o w p r o f i l e :
- Fits in 2U height,
- 3.47", 88.1 mm
- 23" width
- 4 x 100 A input feeds, upgradeable to 4 x 150A input feeds
- supports A & B redundant input feeds
- 4 hot swappable Breaker Modules + one Alarm Module
- Breaker Modules available in various configurations, all come equipped with:
- 28,200 µF capacitor bank
- automatic inrush current limiting
- hot swappable, field replaceable without service interruption
- Breaker Module configurations:
- 5A 5A 5A 5A 5A
- 20A 20A 20A 20A 20A
- 25A 25A 5A 25A 25A
- 10A 5A 30A 5A 10A
- 25A 25A 25A 25A 25A
- 30A 30A 5A 30A 30A
- other configurations available on request, please consult your Astec representative
- Standard Alarm module comes equipped with:
- isolated alarm contacts
- input feed fail alarm
- output breaker trip alarm
- critical, major, minor alarms
- end aisle lamp drive
- fully programmable, 6 bit, shelf ID
- LED test switch
- connections for voice and data jacks
- Enhanced, customized alarm modules available by special order EMC/EMI: No switching components, inherently EMI/EMC benign ESD: Bellcore GR-1089-CORE, ETSI 300 386-1, (15kV) Operating Temperature and Humidity -5°C to +55°C normal, 5% to 85% RH, non-condensing -8°C to +65°C short term Shock and Vibration: Bellcore GR-063-CORE and ETSI 300 019 Zone 4 earthquake Fire Resistance: UL94V-0 UULL 1950 CCSSAA C22.2 950 EENN 60850, 41003 BBeellllccoorree GR-063-CORE Environmental Safety A breaker interface panel, also knows as a power distribution unit (PDU), or frame supervisory panel (FSP), improves system power stability and provides a convenient centralized location for all customer load circuit breakers, alarms, and filtering. AASSIIAA UUnniittss 22111111--22111166,, LLeevveell 2211 TToowweerr11,, MMeettrrooppllaazzaa 222233,, HHiinngg FFoonngg RRooaadd FFwwaaii FFoonngg,, NNeeww TTeerrrriittoorriieess HHoonngg KKoonngg TTeelleepphhoonnee:: 885522--22443377--99666622 FFaaccssiimmiillee:: 885522--22440022--44442266 EEUURROOPPEE AAsstteecc HHoouussee,, WWaatteerrffrroonntt BBuussiinneessss PPaarrkk MMeerrrryy HHiillll,, DDuuddlleeyy WWeesstt MMiiddllaannddss,, DDYY55 11LLXX,, UUKK TTeelleepphhoonnee:: 4444 ((11338844)) 884422--221111 FFaaccssiimmiillee:: 4444 ((11338844)) 884433--335555 AAMMEERRIICCAASS
55881100 VVaann AAlllleenn WWaayy