F2C-ARH-T ABB | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 786

Technical content

System pro M compact ® DIN Rail components for low voltage installation Technical catalogue - Edition 201 1 Contact us 2CSC400002D0209 - January 2011 - 14.000 ABB SACE a division of ABB S.p.A. ABB STOTZ-KONTAKT GmbH In consideration of modifications to Standards and materials, the characteristics and overall dimensions indicated in this catalogue may be considered binding only following confirmation by ABB Copyright 2011 ABB. All rights reserved. System pro M compact® DIN Rail components for low voltage installation

Miniature circuit-breakers Residual current devices Auxiliary elements and accessories Other modular devices Command devices Measurement devices SUMMARY Other functions Protection devices Application sheets 12 Overall dimensions 13 Load management devices Worldwide marks and approvals 14 Technical details Plug-in systems

2 Introduction | System pro M compact ®

System pro M compact® News SPD+MCB The OVR Plus range (SPD+MCB) is now complete with the 3Ph+N version in 15 and 40kA (Imax). Also available in 1Ph+N version, the compact OVR Plus range cover now all applications from domestic to industrial. MeMo4 A new memory size is available for the MeMo range of modular data memories: MeMo4 with 4 GB of storage available. F2C-ARH-T The new autoreclosing unit for domestic and similar application F2C-ARH-T periodically performs the auto test of the associated 2P RCCB F202 30 mA. The product range is growing and growing. New functions, new characteristics, new possibilities.

System pro M compact ® | Introduction 3 ANR96PRF The ANR range of network analyzers has been widened with the introduction of two versions, ANR96PRF-24 and ANR96PRF-230, with Profibus DP protocol built in. Modular sockets New modular sockets to be used worldwide: − M1363 to take the British standard BS1363 plugs up to 13 A; − M1176 to take Australian/New Zealand standard AS/NZS 3112 plugs up to 10 A and 15 A; − M2071 to take Argentine standard IRAM 2071 plugs up to 10 A. CTO The range of current transformers for measurement devices has been broadened with CTO split core current transformer with through primary: this type of current transformers is typically used in distribution panels or power centers for maintenance reasons or system enlargment. They can be installed easily and they allows to save a lot of time, avoiding bar disconnection. EPD24 The protection devices EPD24 extend the ABB product range of modular DIN rail components by electronic overcurrent protection modules for selective protection of 24V DC load circuits. If a fault occurs in a load circuit, the protection device EPD24 will detect this rapidly and reliably, disable the power output transistor and hence interrupt the current flow in the defective circuit.

4 Introduction | System pro M compact ®

A wide product range suitable for all applications For all applications in residential, industrial and commercial installations ABB System pro M compact ® range offers many functionalities like: − protection and switching − checking and monitoring − control and programming Moreover, shape and dimensions of the devices allow a perfect integration in existing installations. The technologically innovative bidirectional cylinder-lift terminal available in the System pro M compact ® devices enables synchronous closing of the front and rear wiring input. Highest safety standard for the installer thanks to protection against electric shock according to EN 41140. Marking of devices is reliable and clear. Both supply and connection with busbars from top or bottom is admitted. System pro M compact® Presentation

System pro M compact ® | Introduction 5 The System pro M compact ® range MCBs Miniature circuit-breakers. RCDs − Residual current circuit-breakers (RCCBs); − RCD-blocks; − Residual current circuit-breakers with overcurrent protec- tion (RCBOs); − Residual current relays (modular and front panel) with external toroid. Auxiliary elements A whole range of accessories and auxiliary elements. SPDs Surge protective devices. Protection devices In addition to MCBs and RCDs, ABB supplies other modular devices for protection such as fuse holders, fuses, switch disconnectors, insulation monitoring devices etc. Command devices This category includes devices that are operated manually to command the electric system: contactors, latching relays, switch-isolators, switches, pushbuttons etc. Typically they are installed to control lights from severeal points of the same circuit or to pilot user devices with a high number of operations. Load management devices Overload relays, load management switches, anti black-out lamps, time switches and the other modular devices in this category react automatically to variations of parameters and other events in the system to allow for plant optimisation. Measurement devices The range of devices in this category is very wide, including a great number of auxiliary components and accessories that make installation in switchboards and consumer units practical and economic. Other devices The System pro M compact ® range also includes bells, transformers, modular sockets etc. Various accessories

6 Introduction | System pro M compact ®

System pro M compact® Advantages Supply from top or bottom either with cables or busbars. Universal signal/auxiliary and auxiliary contacts fit on S 200, F 200 and DS 200. RCD-blocks DDA 200 2P , 3P , 4P up to 40 A fit into two modules. Versions in 63 A sizes are supplied with two additional terminals for remote tripping. Availability of a wide range of RCBOs. Safety connections between DDA 200 and S 200 thanks to a safe plastic key system. MCBs are also available with an integrated auxiliary contact (1 NO or 1 NC). Existing installations can be easily upgraded to include auxiliary switch functionality. The System pro M compact ® range offers enormous advantages in relation to installation. Advanced and smart solutions allow a far easier and safer installation and guarantee time saving.

System pro M compact ® | Introduction 7 More working space between component rows. Special quick fastening for an easy removal of the devices from the assembly pressing upwards, both for MCBs S 200 and RCCBs F 200: the only in the market that can be removed without a screwdriver. Without busbars two terminal spaces can be used for cables with different cross sections: incoming supply with supplementary terminal up to 50 mm from the front side. The bi-directional cylinder-lift terminal allows easier and quicker connections. In addition it avoids errors because it prevents the use of free cable seats. This high protection level against errors eliminates right from the start industrial accidents deriving from incorrect wiring. The terminal guarantees a very high tightening torque for cables with a section up to 25 mm The housing of connection busbars in the rear seat guarantees easier wiring. Safe terminal technology: the terminals offer protection from misconnection. Error proof terminals: they avoid the use of free cable seats. Supply from top or bottom also possible with busbars.

2CSC400259F02012CSC400556F0201

Miniature circuit-breakers

Characteristics B,C,D, K,Z B,C,D, K,Z B,C,D, K,Z B,C,D, K,Z B,C,D, K,Z K,Z K,Z K,Z K,Z B,C B,C,D B,C B,C Rated current [A] 0.5 ≤ In ≤ 63 0.5 ≤ In ≤ 63 0.2 ≤ In ≤ 25 32 ≤ In ≤ 40 50 ≤ In ≤ 63 0.2 ≤ In ≤ 25 32 ≤ In ≤ 40 50 ≤ In ≤ 63 0.2 ≤ In ≤ 25 2 ≤ In ≤ 40 2 ≤ In ≤ 40 2 ≤ In ≤ 40 80 ≤ In ≤ 100 Breaking capacity [kA] Reference standard Nr. poles Ue[V] IEC 23-3/EN 60898 Icn 230/400 6 1 02 51 51 5 4 . 5 6 1 0 6 IEC/EN 60947-2 Alternating current Icu 1, 1P+N 133 20 25 /L5471340 25 25 40 25 25 40 10 15 20 15 230 10 15 /L5471325 15 15 25 15 15 25 6 10 10 6 2, 3, 4 230 20 25 /L5471340 25 25 40 25 25 40 10 400 10 15 /L5471325 15 15 25 15 15 25 6 2, 3, 4 500 690 2, 3, 4 500 690 IEC/EN 60947-2 Direct current T=I/R≤5ms for all series, except S280 UC and S800S-UC, where T=I/R<15ms Icu 1, 1P+N 24 20 60 10 10 15 10 10 15 10 10 15 10 15 15 10 125 250 2 48 20 125 10 10 15 10 10 15 10 10 15 10 15 15 10 250 500 600 800 3,4 375 500 750 1000 1200 Ics 1, 1P+N 24 20 60 10 10 15 10 10 15 10 10 15 10 15 15 10 125 250 2 48 20 125 10 10 15 10 10 15 10 10 15 10 15 15 10 250 500 600 800 3,4 375 500 750 1000 1200 UL 1077/ C22.2 No 235 Alternating current Int. cap. 1, 1P+N 120 10 10 10 10 277 6 1 01 01 0 2, 3, 4 240 10 10 10 10

480 Y/277 6 1 01 01 0

UL 1077/ C22.2 No 235 Direct current Int. cap. 1, 1P+N 60 10 2, 3, 4 125 10 UL 489/ C22.2 No 5 Alternating current Int. cap. 240 10 10 10 10 277 10 2, 3, 4 240 10 10 10 10

480 Y/277 10

3, 4 1200 /L54706 only up to 40 A; 10 kA up to 50/63 A /L54707 only for “D” characteristic /L54708 values are not for all rated currents /L54709 600 V DC for 100, 125 A /L54710 1000 V DC for 100, 125 A General features and breaking capacities System pro M compact® MCBs NOTE: All the MCBs of S200 series present two values of breaking capacities marked on the product: on the front I cn according to IEC/EN 60898 on the side I cu/Ics according to IEC/EN 60947-2 dependig on the rated current, if not otherwise specified.

B,K,Z K,Z B,C,D,K E,K /L54714B,C,D K KM UCB UCK B,C,D B,C,D,K Z,K PV-S K adjustable K adjustable 0.2 ≤ In ≤ 40 50 ≤ In ≤ 63 80 ≤ In ≤ 125 10 ≤ In ≤ 100 6 ≤ In ≤ 125 6 ≤ In ≤ 125 20 ≤ In ≤ 80 10 ≤ In ≤ 125 10 ≤ In ≤ 125 10 ≤ In ≤ 125 10 ≤ In ≤ 125 10 ≤ In ≤ 100 10 ≤ In ≤ 125 125 0.1 ≤ In ≤ 3 2.8 ≤ In ≤ 11 10 ≤ In ≤ 45 0.1 ≤ In ≤ 45 10 25 /L54714 25 20 15 10 6 6 4.5 20 (15) /L54707 50 50 50 36 25 30 100 50 30 1 0 6 2 5 5 05 05 0 3 62 55 0 6 4.5 20 (15) /L54707 50 50 50 36 25 50 100 50 30 15 /L5470815 /L5470815 /L54708 10 /L54708 100 20 15 6 /L547086 /L547086 /L54708 4.5 100 6 6 7.5 6 6 4.5 10 (7.5) /L5470712.5 /L5471440 40 40 30 18 25 7.5 6 12.5 40 40 40 30 18 40 100 30 25 6 4.5 10 (7.5) /L5470712.5 /L5471440 40 40 30 18 100 30 25 11 /L5470811 /L5470811 /L54708 8 /L54708 100 15 11 4 /L547084 /L547084 /L54708 3 100 3 3 6 4.5 30 30 30 20 10 50 50 30 6 4.5 30 30 30 20 10 50 50 30 5 /L54709 30 /L5471130 /L5471130 /L5471130 /L5471130 /L5471120 /L5471110 /L54711 30 /L5471230 /L5471230 /L5471230 /L5471230 /L5471220 /L5471210 /L54712 50 50 30 5 /L54710 12.5 6 4.5 30 30 30 20 10 50 50 6 4.5 30 30 30 20 10 50 50 5 /L54709 30 /L5471130 /L5471130 /L5471130 /L5471130 /L5471120 /L5471110 /L54711 30 /L5471230 /L5471230 /L5471230 /L5471230 /L5471220 /L5471210 /L54712 50 50 5 /L54709 14 30 /L54718 18 /L54719 5 14 /L54718 14 /L54719 14 30 /L54718 18 /L54719 5 /L54720 14 /L54718 14 /L54719 0.4 30 /L54715 0.6 30 /L54717 1.5 1.5 /L54711 3 poles /L54712 4 poles /L54713 < 50 A /L54714 relevant product standard: E /L54715 by 250 V DC 1-pole /L54717 by 600 V DC 2-pole /L54718 ≤ 25 A /L54719 > 25 A /L54720 480/277 V DIN VDE 0645 (based 600 V 3- and 4-pole on IEC/EN 60898-1 and IEC/EN 60947-2) General features and breaking capacities System pro M compact® MCBs /L54712

MCBs protect installations against overload and short- circuit, warranting reliability and safety for operations. New System pro M compact S 200 series satisfies most common requirements in terms of MCBs, allowing the usage of them for domestic, industrial and commercial applications. Three series – S 200, S 200 M and S 200 P – with three different breaking capacities up to 25 kA are available, in all characteristics (B, C, D, K and Z) and configurations (1P , 1P+N, 2P , 3P , 3P+N and 4P), in all the sizes up to 63 A. All these MCBs comply to IEC/EN 60898 and IEC/EN 60947-2 Standards. The range includes also the new S 200 U and S 200 UP in accordance to UL 489/CSA- C22.2 N 05 Standard. It is also available the new integrated auxiliary contact on the bottom side which per- mits to save 50% space. Thought to be advanced, MCBs range also offers all the “plus” advantages which characterized the whole new System pro M compact range. S 200 series devices obtained a lot of marks and approvals, so they can be used in all world’s markets. 2CSC400230F02012CSC400260F02012CSC400259F0201 2CSC400261F0201

Miniature circuit-breakers S 200 series Index Selection tables of MCBs S 200 series Selection tables of MCBs S 200 in accordance to UL 489/CSA-C22.2 N 05

pro M compact® S 200 Electrical Data Standards IEC/EN UL/CSA Poles Tripping characteristics Rated current I n A Rated voltage Un IEC/EN 60898-1 V Rated voltage Ue IEC/EN 60947-2 V Rated voltage UL/CSA V Insulation voltage Ui IEC/EN 60898-1 / 60947-2 V Max. operating voltage UBmax. V Min. operating voltage UBmin. V Rated frequency f Hz Rated short-circuit capacity Icn IEC/EN 60898-1 kA Ultimate short-circuit capacity Icu IEC/EN 60947-2 kA Service short-circuit capacity Ics IEC/EN 60947-2 kA Rated interrupting capacity UL 1077, CSA 22.2 No. 235 kA Short-circuit current rating SCCR UL 489, CSA 22.2 No. 5 kA Energy limiting class IEC/EN 60898-1 Overvoltage category IEC/EN 60898-1 / 60947-2 Pollution degree IEC/EN 60898-1 IEC/EN 60947-2 Rated impulse withstand voltage U imp. (1.2/50 μs) IEC/EN 60898-1 / 60947-2 kV Dielectric test voltage IEC/EN 60898-1 kV Mechanical Data Housing Toggle Contact position indication Protection degree EN 60529 Electrical endurance ops. Mechanical endurance ops. Shock resistance IEC/EN 60068-2-27 Vibration resistance IEC/EN 60068-2-6 Tropicalization (damp heat cyclic) IEC/EN 60068-2-30 °C/RH Ambient temperature °C Storage temperature °C Reference temperature for tripping characteristics IEC/EN 60898-1 IEC/EN 60947-2 Installation Terminal Cross-section of conductors (top / bottom) IEC/EN 60898-1 / 60947-2 mm UL/CSA AWG Cross-section of busbars (top / bottom) IEC/EN 60898-1 / 60947-2 mm 2 UL/CSA AWG Torque IEC/EN Nm UL/CSA in-Ibs. Screwdriver Mounting Mounting position Supply Dimensions and weight Mounting dimensions DIN 43880 Pole dimensions (H x D x W) mm Pole weight g Combination with aux. elements Auxiliary contact Signal contact/auxiliary switch Shunt trip Undervoltage release

pro M compact® S 200 S 200 S 200 M S 200 P S 200 U S 200 UP S 200 UDC IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60898-1, IEC/EN 60947-2 IEC/EN 60947-2 – 1P , 2P , 3P , 4P , 1P+N, 3P+N 1P , 2P , 3P , 4P 1P , 2P B, C, D, K, Z K, Z 1P: 230/400 V AC; 1P+N: 230 V AC ; 2...4P: 400 V AC; 3P+N: 400 V AC – 480Y / 277 V AC – 480Y / 277 V AC 1P: 240 V AC 2...4P: 240 V AC 1P: 277 V AC 2...4P: 480Y / 277 V AC 1P: 60 V DC 2P: 125 V DC

250 V AC (phase to ground), 500 V AC (phase to phase) –

1P: 253 V AC; 1P+N: 253 V AC; 2P: 440 V AC; 3...4P: 440 V AC; 3P+N: 440 V AC 1P: 72 V DC; 2P: 125 V DC 1P: 253/440 V AC; 2...4P: 440 V AC –

12 V AC - 12 V DC 12 V AC 12 V DC

6 kA 10 kA ≤ 25 A: 25 kA > 25 A: 15 kA 10 kA ≤ 40 A: 15 kA 50, 63 A: 10 kA ≤ 25 A: 25 kA ≥ 32 A: 15 kA 10 kA – 7.5 kA ≤ 40 A: 11.2 kA 50, 63 A: 7.5 kA ≤ 25 A: 12.5 kA ≤ 32…40 A: 11.2 kA 50, 63 A: 7.5 kA 7.5 kA 6 kA – 10 kA – – 10 kA 14 kA (UL) 3 – III – 2 – 3 – 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) – 2 kV (50 / 60Hz, 1 min.) – Insulation group I, RAL 7035 Insulation group II, black, sealable Marking on toggle, I ON / 0 OFF Marking on toggle (I ON / 0 OFF), Real CPI (red ON / green OFF) IP20 / IPXXB, IP40 in enclosure with cover In < 32 A: 20,000 ops AC, In ≥ 32 A: 10,000 ops. AC 1,000 ops. DC 6,000 ops. 20,000 ops. 30 g - 3 shocks - 11 ms 5g - 20 cycles at 5…150…5 Hz with load 0.8In 28 cycles with 55°C/90-96% and 25°C/95-100% -25 … +55°C -40 … +70°C B, C, D: 30°C K, Z: 20°C 25°C (UL/CSA) 25°C (UL) Failsafe bi-directional cylinder-lift terminal 25 mm 2 / 25 mm2 – 18 - 4 AWG – 18 - 4 AWG 10 mm2 / 10 mm2 – 18 - 8 AWG – 18 - 8 AWG 2.8 Nm 25 in-Ibs. – 25 in-Ibs. No. 2 Pozidrive On DIN rail 35 mm acc. to EN 60715 by fast clip any optional Please note polarity of device Mounting dimension 1 – 88 x 69 x 17.5 mm 92 x 71 x 17.5 mm 100 x 71 x 17.5 mm 92 x 71 x 17.5 mm ca. 125 g ca. 140 g Yes Yes Yes Yes no

pro M compact® S 200-B B S 200 B characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201-B 6 2CDS 251 001 R0065 46490 1 0.125 10 10 S 201-B 10 2CDS 251 001 R0105 46380 5 0.125 10 13 S 201-B 13 2CDS 251 001 R0135 46500 7 0.125 10 16 S 201-B 16 2CDS 251 001 R1165 57863 9 0.125 10 20 /L54706 S 201-B 20 2CDS 251 001 R0205 46510 6 0.125 10 25 S 201-B 25 2CDS 251 001 R0255 46520 5 0.125 10 32 /L54707 S 201-B 32 2CDS 251 001 R0325 46530 4 0.125 10 40 /L54708 S 201-B 40 2CDS 251 001 R0405 46540 3 0.125 10 50 S 201-B 50 2CDS 251 001 R0505 55092 5 0.125 10 63 S 201-B 63 2CDS 251 001 R0635 55093 2 0.125 10 2 6 S 202-B 6 2CDS 252 001 R0065 46640 0 0.250 5 10 S 202-B 10 2CDS 252 001 R0105 46660 8 0.250 5 13 S 202-B 13 2CDS 252 001 R0135 46670 7 0.250 5 16 S 202-B 16 2CDS 252 001 R0165 46690 5 0.250 5 20 S 202-B 20 2CDS 252 001 R0205 46700 1 0.250 5

25 S 202-B 25

2CDS 252 001 R0255 46710 0 0.250 5 32 S 202-B 32 2CDS 252 001 R0325 46720 9 0.250 5 40 S 202-B 40 2CDS 252 001 R0405 46740 7 0.250 5 50 S 202-B 50 2CDS 252 001 R0505 55094 9 0.250 5 63 S 202-B 63 2CDS 252 001 R0635 55095 6 0.250 5 3 6 S 203-B 6 2CDS 253 001 R0065 46860 2 0.375 1 10 S 203-B 10 2CDS 253 001 R0105 46870 1 0.375 1 13 S 203-B 13 2CDS 253 001 R0135 46890 9 0.375 1 16 S 203-B 16 2CDS 253 001 R0165 46900 5 0.375 1 20 /L54706 S 203-B 20 2CDS 253 001 R0205 46910 4 0.375 1 25 S 203-B 25 2CDS 253 001 R0255 46920 3 0.375 1 32 /L54707 S 203-B 32 2CDS 253 001 R0325 46930 2 0.375 1 40 /L54708 S 203-B 40 2CDS 253 001 R0405 46940 1 0.375 1 50 S 203-B 50 2CDS 253 001 R0505 55096 3 0.375 1 63 S 203-B 63 2CDS 253 001 R0635 55097 0 0.375 1 4 6 S 204-B 6 2CDS 254 001 R0065 52895 5 0.500 1 10 S 204-B 10 2CDS 254 001 R0105 52896 2 0.500 1 13 S 204-B 13 2CDS 254 001 R0135 52897 9 0.500 1 16 S 204-B 16 2CDS 254 001 R0165 52898 6 0.500 1 20 S 204-B 20 2CDS 254 001 R0205 52899 3 0.500 1 25 S 204-B 25 2CDS 254 001 R0255 52900 6 0.500 1 32 S 204-B 32 2CDS 254 001 R0325 52901 3 0.500 1 40 S 204-B 40 2CDS 254 001 R0405 52902 0 0.500 1 50 S 204-B 50 2CDS 254 001 R0505 55098 7 0.500 1 63 S 204-B 63 2CDS 254 001 R0635 55099 4 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 UBmax 125 V ... with 2 poles connected in series UBmax

253 V /L50513

72 V ... UBmax

440 V /L50513

125 V ... /L54709 UBmax 125 V ... /L54709 Selection tables MCBs S 200 series 6000 2CSC400411F02012CSC400413F02012CSC400415F02012CSC400443F0201

pro M compact® S 200-B B With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201-B 6 NA 2CDS 251 103 R0065 53158 0 0.250 5 + 10 S 201-B 10 NA 2CDS 251 103 R0105 53159 7 0.250 5 NA 13 S 201-B 13 NA 2CDS 251 103 R0135 53160 3 0.250 5 16 S 201-B 16 NA 2CDS 251 103 R0165 53161 0 0.250 5 20 /L54706 S 201-B 20 NA 2CDS 251 103 R0205 53162 7 0.250 5 25 S 201-B 25 NA 2CDS 251 103 R0255 53163 4 0.250 5 32 /L54707 S 201-B 32 NA 2CDS 251 103 R0325 53164 1 0.250 5 40 /L54708 S 201-B 40 NA 2CDS 251 103 R0405 53165 8 0.250 5 50 S 201-B 50 NA 2CDS 251 103 R0505 53615 8 0.250 5 63 S 201-B 63 NA 2CDS 251 103 R0635 53614 1 0.250 5 3 6 S 203-B 6 NA 2CDS 253 103 R0065 53228 0 0.500 1 + 10 S 203-B 10 NA 2CDS 253 103 R0105 53229 7 0.500 1 NA 13 S 203-B 13 NA 2CDS 253 103 R0135 53230 3 0.500 1 16 S 203-B 16 NA 2CDS 253 103 R0165 53231 0 0.500 1 20 /L54706 S 203-B 20 NA 2CDS 253 103 R0205 53232 7 0.500 1 25 S 203-B 25 NA 2CDS 253 103 R0255 53233 4 0.500 1 32 /L54707 S 203-B 32 NA 2CDS 253 103 R0325 53234 1 0.500 1 40 /L54708 S 203-B 40 NA 2CDS 253 103 R0405 53235 8 0.500 1 50 S 203-B 50 NA 2CDS 253 103 R0505 53616 5 0.580 1 63 S 203-B 63 NA 2CDS 253 103 R0635 53617 2 0.580 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 2CSC400421F02012CSC400418F0201

pro M compact® S 200-C C S 200 C characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-C 0.5 2CDS 251 001 R0984 52329 5 0.125 10 1 S 201-C 1 2CDS 251 001 R0014 52331 8 0.125 10 1.6 S 201-C 1.6 2CDS 251 001 R0974 52330 1 0.125 10 2 S 201-C 2 2CDS 251 001 R0024 52332 5 0.125 10 3 S 201-C 3 2CDS 251 001 R0034 52333 2 0.125 10 4 S 201-C 4 2CDS 251 001 R0044 52334 9 0.125 10 6 S 201-C 6 2CDS 251 001 R0064 46400 0 0.125 10 8 S 201-C 8 2CDS 251 001 R0084 46410 9 0.125 10 10 S 201-C 10 2CDS 251 001 R0104 46420 8 0.125 10 13 S 201-C 13 2CDS 251 001 R0134 46430 7 0.125 10 16 S 201-C 16 2CDS 251 001 R0164 46440 6 0.125 10 20 /L54706 S 201-C 20 2CDS 251 001 R0204 46450 5 0.125 10 25 S 201-C 25 2CDS 251 001 R0254 46460 4 0.125 10 32 /L54707 S 201-C 32 2CDS 251 001 R0324 46470 3 0.125 10 40 /L54708 S 201-C 40 2CDS 251 001 R0404 46480 2 0.125 10

50 S 201-C 50 2CDS 251 001 R0504 55100 7

0.125 10 63 S 201-C 63 2CDS 251 001 R0634 55101 4 0.125 10 2 0.5 S 202-C 0.5 2CDS 252 001 R0984 52335 6 0.250 5 1 S 202-C 1 2CDS 252 001 R0014 52336 3 0.250 5 1.6 S 202-C 1.6 2CDS 252 001 R0974 52337 0 0.250 5 2 S 202-C 2 2CDS 252 001 R0024 52338 7 0.250 5 3 S 202-C 3 2CDS 252 001 R0034 52339 4 0.250 5 4 S 202-C 4 2CDS 252 001 R0044 52340 0 0.250 5 6 S 202-C 6 2CDS 252 001 R0064 46550 2 0.250 5 8 S 202-C 8 2CDS 252 001 R0084 46560 1 0.250 5 10 S 202-C 10 2CDS 252 001 R0104 46570 0 0.250 5 13 S 202-C 13 2CDS 252 001 R0134 46580 9 0.250 5 16 S 202-C 16 2CDS 252 001 R0164 46590 8 0.250 5 20 S 202-C 20 2CDS 252 001 R0204 46600 4 0.250 5 25 S 202-C 25 2CDS 252 001 R0254 46610 3 0.250 5 32 S 202-C 32 2CDS 252 001 R0324 46620 2 0.250 5 40 S 202-C 40 2CDS 252 001 R0404 46630 1 0.250 5 50 S 202-C 50 2CDS 252 001 R0504 55104 5 0.250 5 63 S 202-C 63 2CDS 252 001 R0634 55105 2 0.250 5 3 0.5 S 203-C 0.5 2CDS 253 001 R0984 52341 7 0.375 1 1 S 203-C 1 2CDS 253 001 R0014 52342 4 0.375 1 1.6 S 203-C 1.6 2CDS 253 001 R0974 52343 1 0.375 1 2 S 203-C 2 2CDS 253 001 R0024 52344 8 0.375 1 3 S 203-C 3 2CDS 253 001 R0034 52345 5 0.375 1 4 S 203-C 4 2CDS 253 001 R0044 52346 2 0.375 1 6 S 203-C 6 2CDS 253 001 R0064 46750 6 0.375 1 8 S 203-C 8 2CDS 253 001 R0084 46760 5 0.375 1 10 S 203-C 10 2CDS 253 001 R0104 46780 3 0.375 1 13 S 203-C 13 2CDS 253 001 R0134 46790 2 0.375 1 16 S 203-C 16 2CDS 253 001 R0164 46800 8 0.375 1 20 /L54706 S 203-C 20 2CDS 253 001 R0204 46810 7 0.375 1 25 S 203-C 25 2CDS 253 001 R0254 46820 6 0.375 1 32 /L54707 S 203-C 32 2CDS 253 001 R0324 46830 5 0.375 1 40 /L54708 S 203-C 40 2CDS 253 001 R0404 46840 4 0.375 1 50 S 203-C 50 2CDS 253 001 R0504 55106 9 0.375 1 63 S 203-C 63 2CDS 253 001 R0634 55107 6 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax 2CSC400409F0201 2CSC400408F02012CSC400412F0201

pro M compact® S 200-C C With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-C 0.5 NA 2CDS 251 103 R0984 53166 5 0.250 5 + 1 S 201-C 1 NA 2CDS 251 103 R0014 53167 2 0.250 5 NA 1.6 S 201-C 1.6 NA 2CDS 251 103 R0974 53168 9 0.250 5 2 S 201-C 2 NA 2CDS 251 103 R0024 53169 6 0.250 5 3 S 201-C 3 NA 2CDS 251 103 R0034 53170 2 0.250 5 4 S 201-C 4 NA 2CDS 251 103 R0044 53172 6 0.250 5 6 S 201-C 6 NA 2CDS 251 103 R0064 53173 3 0.250 5 8 S 201-C 8 NA 2CDS 251 103 R0084 53174 0 0.250 5 10 S 201-C 10 NA 2CDS 251 103 R0104 53175 7 0.250 5 13 S 201-C 13 NA 2CDS 251 103 R0134 53176 4 0.250 5 16 S 201-C 16 NA 2CDS 251 103 R0164 53177 1 0.250 5 20 /L54706 S 201-C 20 NA 2CDS 251 103 R0204 53178 8 0.250 5 25 S 201-C 25 NA 2CDS 251 103 R0254 53179 5 0.250 5 32 /L54707 S 201-C 32 NA 2CDS 251 103 R0324 53180 1 0.250 5 40 /L54708 S 201-C 40 NA 2CDS 251 103 R0404 53181 8 0.250 5

50 S 201-C 50 NA 2CDS 251 103 R0504 55102 1

0.290 5 63 S 201-C 63 NA 2CDS 251 103 R0634 55103 8 0.290 5 3 0.5 S 203-C 0.5 NA 2CDS 253 103 R0984 53236 5 0.500 1 + 1 S 203-C 1 NA 2CDS 253 103 R0014 53237 2 0.500 1 NA 1.6 S 203-C 1.6 NA 2CDS 253 103 R0974 53238 9 0.500 1 2 S 203-C 2 NA 2CDS 253 103 R0024 53240 2 0.500 1 3 S 203-C 3 NA 2CDS 253 103 R0034 53241 9 0.500 1 4 S 203-C 4 NA 2CDS 253 103 R0044 53242 6 0.500 1 6 S 203-C 6 NA 2CDS 253 103 R0064 53243 3 0.500 1 8 S 203-C 8 NA 2CDS 253 103 R0084 53244 0 0.500 1 10 S 203-C 10 NA 2CDS 253 103 R0104 53245 7 0.500 1 13 S 203-C 13 NA 2CDS 253 103 R0134 53246 4 0.500 1 16 S 203-C 16 NA 2CDS 253 103 R0164 53247 1 0.500 1 20 /L54706 S 203-C 20 NA 2CDS 253 103 R0204 53248 8 0.500 1 25 S 203-C 25 NA 2CDS 253 103 R0254 53249 5 0.500 1 32 /L54707 S 203-C 32 NA 2CDS 253 103 R0324 53250 1 0.500 1 40 /L54708 S 203-C 40 NA 2CDS 253 103 R0404 53251 8 0.500 1 50 S 203-C 50 NA 2CDS 253 103 R0504 55108 3 0.580 1 63 S 203-C 63 NA 2CDS 253 103 R0634 55109 0 0.580 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204-C 0.5 2CDS 254 001 R0984 52911 2 0.500 1 1 S 204-C 1 2CDS 254 001 R0014 52912 9 0.500 1 1.6 S 204-C 1.6 2CDS 254 001 R0974 52913 6 0.500 1 2 S 204-C 2 2CDS 254 001 R0024 52914 3 0.500 1 3 S 204-C 3 2CDS 254 001 R0034 52915 0 0.500 1 4 S 204-C 4 2CDS 254 001 R0044 52916 7 0.500 1 6 S 204-C 6 2CDS 254 001 R0064 52917 4 0.500 1 8 S 204-C 8 2CDS 254 001 R0084 52918 1 0.500 1 10 S 204-C 10 2CDS 254 001 R0104 52919 8 0.500 1 13 S 204-C 13 2CDS 254 001 R0134 52920 4 0.500 1 16 S 204-C 16 2CDS 254 001 R0164 52921 1 0.500 1 20 S 204-C 20 2CDS 254 001 R0204 52922 8 0.500 1 25 S 204-C 25 2CDS 254 001 R0254 52923 5 0.500 1 32 S 204-C 32 2CDS 254 001 R0324 52924 2 0.500 1 40 S 204-C 40 2CDS 254 001 R0404 52925 9 0.500 1 50 S 204-C 50 2CDS 254 001 R0504 55110 6 0.500 1 63 S 204-C 63 2CDS 254 001 R0634 55111 3 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series 6000 2CSC400418F0201 2CSC400421F0201 2CSC400419F0201

pro M compact® S 200-D D S 200 D characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-D 0.5 2CDS 251 001 R0981 52993 8 0.125 10 1 S 201-D 1 2CDS 251 001 R0011 52994 5 0.125 10 1.6 S 201-D 1.6 2CDS 251 001 R0971 52995 2 0.125 10 2 S 201-D 2 2CDS 251 001 R0021 52996 9 0.125 10 3 S 201-D 3 2CDS 251 001 R0031 52997 6 0.125 10 4 S 201-D 4 2CDS 251 001 R0041 52998 3 0.125 10 6 S 201-D 6 2CDS 251 001 R0061 52999 0 0.125 10 8 S 201-D 8 2CDS 251 001 R0081 53000 2 0.125 10 10 S 201-D 10 2CDS 251 001 R0101 53001 9 0.125 10 13 S 201-D 13 2CDS 251 001 R0131 53002 6 0.125 10 16 S 201-D 16 2CDS 251 001 R0161 53003 3 0.125 10 20 /L54706 S 201-D 20 2CDS 251 001 R0201 53004 0 0.125 10 25 S 201-D 25 2CDS 251 001 R0251 53005 7 0.125 10 32 /L54707 S 201-D 32 2CDS 251 001 R0321 53006 4 0.125 10 40 /L54708 S 201-D 40 2CDS 251 001 R0401 53007 1 0.125 10

50 S 201-D 50 2CDS 251 001 R0501 55199 1

0.125 10 63 S 201-D 63 2CDS 251 001 R0631 55200 4 0.125 10 2 0.5 S 202-D 0.5 2CDS 252 001 R0981 53048 4 0.250 5 1 S 202-D 1 2CDS 252 001 R0011 53049 1 0.250 5 1.6 S 202-D 1.6 2CDS 252 001 R0971 53050 7 0.250 5 2 S 202-D 2 2CDS 252 001 R0021 53051 4 0.250 5 3 S 202-D 3 2CDS 252 001 R0031 53052 1 0.250 5 4 S 202-D 4 2CDS 252 001 R0041 53053 8 0.250 5 6 S 202-D 6 2CDS 252 001 R0061 53054 5 0.250 5 8 S 202-D 8 2CDS 252 001 R0081 53055 2 0.250 5 10 S 202-D 10 2CDS 252 001 R0101 53058 3 0.250 5 13 S 202-D 13 2CDS 252 001 R0131 53060 6 0.250 5 16 S 202-D 16 2CDS 252 001 R0161 53061 3 0.250 5 20 S 202-D 20 2CDS 252 001 R0201 53063 7 0.250 5 25 S 202-D 25 2CDS 252 001 R0251 53064 4 0.250 5 32 S 202-D 32 2CDS 252 001 R0321 53065 1 0.250 5 40 S 202-D 40 2CDS 252 001 R0401 53066 8 0.250 5 50 S 202-D 50 2CDS 252 001 R0501 55203 5 0.250 5 63 S 202-D 63 2CDS 252 001 R0631 55204 2 0.250 5 3 0.5 S 203-D 0.5 2CDS 253 001 R0981 53081 1 0.375 1 1 S 203-D 1 2CDS 253 001 R0011 53082 8 0.375 1 1.6 S 203-D 1.6 2CDS 253 001 R0971 53083 5 0.375 1 2 S 203-D 2 2CDS 253 001 R0021 53084 2 0.375 1 3 S 203-D 3 2CDS 253 001 R0031 53085 9 0.375 1 4 S 203-D 4 2CDS 253 001 R0041 53086 6 0.375 1 6 S 203-D 6 2CDS 253 001 R0061 53088 0 0.375 1 8 S 203-D 8 2CDS 253 001 R0081 53089 7 0.375 1 10 S 203-D 10 2CDS 253 001 R0101 53090 3 0.375 1 13 S 203-D 13 2CDS 253 001 R0131 53091 0 0.375 1 16 S 203-D 16 2CDS 253 001 R0161 53092 7 0.375 1 20 /L54706 S 203-D 20 2CDS 253 001 R0201 53093 4 0.375 1 25 S 203-D 25 2CDS 253 001 R0251 53094 1 0.375 1 32 /L54707 S 203-D 32 2CDS 253 001 R0321 53095 8 0.375 1 40 /L54708 S 203-D 40 2CDS 253 001 R0401 53096 5 0.375 1 50 S 203-D 50 2CDS 253 001 R0501 55205 9 0.375 1 63 S 203-D 63 2CDS 253 001 R0631 55206 6 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax 2CSC400409F0201 2CSC400408F02012CSC400412F0201

pro M compact® S 200-D D With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-D 0.5 NA 2CDS 251 103 R0981 53197 9 0.250 5 + 1 S 201-D 1 NA 2CDS 251 103 R0011 53198 6 0.250 5 NA 1.6 S 201-D 1.6 NA 2CDS 251 103 R0971 53199 3 0.250 5 2 S 201-D 2 NA 2CDS 251 103 R0021 53200 6 0.250 5 3 S 201-D 3 NA 2CDS 251 103 R0031 53201 3 0.250 5 4 S 201-D 4 NA 2CDS 251 103 R0041 53202 0 0.250 5 6 S 201-D 6 NA 2CDS 251 103 R0061 53203 7 0.250 5 8 S 201-D 8 NA 2CDS 251 103 R0081 53204 4 0.250 5 10 S 201-D 10 NA 2CDS 251 103 R0101 53205 1 0.250 5 13 S 201-D 13 NA 2CDS 251 103 R0131 53206 8 0.250 5 16 S 201-D 16 NA 2CDS 251 103 R0161 53209 9 0.250 5 20 /L54706 S 201-D 20 NA 2CDS 251 103 R0201 53210 5 0.250 5 25 S 201-D 25 NA 2CDS 251 103 R0251 53211 2 0.250 5 32 /L54707 S 201-D 32 NA 2CDS 251 103 R0321 53212 9 0.250 5 40 /L54708 S 201-D 40 NA 2CDS 251 103 R0401 53213 6 0.250 5

50 S 201-D 50 NA 2CDS 251 103 R0501 55201 1

0.290 5 63 S 201-D 63 NA 2CDS 251 103 R0631 55202 8 0.290 5 3 0.5 S 203-D 0.5 NA 2CDS 253 103 R0981 53276 1 0.500 2 + 1 S 203-D 1 NA 2CDS 253 103 R0011 53277 8 0.500 2 NA 1.6 S 203-D 1.6 NA 2CDS 253 103 R0971 53278 5 0.500 2 2 S 203-D 2 NA 2CDS 253 103 R0021 53279 2 0.500 2 3 S 203-D 3 NA 2CDS 253 103 R0031 53280 8 0.500 2 4 S 203-D 4 NA 2CDS 253 103 R0041 53281 5 0.500 2 6 S 203-D 6 NA 2CDS 253 103 R0061 53282 2 0.500 2 8 S 203-D 8 NA 2CDS 253 103 R0081 53283 9 0.500 2 10 S 203-D 10 NA 2CDS 253 103 R0101 53284 6 0.500 2 13 S 203-D 13 NA 2CDS 253 103 R0131 53286 0 0.500 2 16 S 203-D 16 NA 2CDS 253 103 R0161 53287 7 0.500 2 20 /L54706 S 203-D 20 NA 2CDS 253 103 R0201 53288 4 0.500 2 25 S 203-D 25 NA 2CDS 253 103 R0251 53289 1 0.500 2 32 /L54707 S 203-D 32 NA 2CDS 253 103 R0321 53290 7 0.500 2 40 /L54708 S 203-D 40 NA 2CDS 253 103 R0401 53291 4 0.500 2 50 S 203-D 50 NA 2CDS 253 103 R0501 55207 3 0.580 2 63 S 203-D 63 NA 2CDS 253 103 R0631 55208 0 0.580 2 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204-D 0.5 2CDS 254 001 R0981 53112 2 0.500 1 1 S 204-D 1 2CDS 254 001 R0011 53113 9 0.500 1 1.6 S 204-D 1.6 2CDS 254 001 R0971 53114 6 0.500 1 2 S 204-D 2 2CDS 254 001 R0021 53115 3 0.500 1 3 S 204-D 3 2CDS 254 001 R0031 53116 0 0.500 1 4 S 204-D 4 2CDS 254 001 R0041 53117 7 0.500 1 6 S 204-D 6 2CDS 254 001 R0061 53118 4 0.500 1 8 S 204-D 8 2CDS 254 001 R0081 53119 1 0.500 1 10 S 204-D 10 2CDS 254 001 R0101 53120 7 0.500 1 13 S 204-D 13 2CDS 254 001 R0131 53121 4 0.500 1 16 S 204-D 16 2CDS 254 001 R0161 53122 1 0.500 1 20 S 204-D 20 2CDS 254 001 R0201 53123 8 0.500 1 25 S 204-D 25 2CDS 254 001 R0251 53129 0 0.500 1 32 S 204-D 32 2CDS 254 001 R0321 53130 6 0.500 1 40 S 204-D 40 2CDS 254 001 R0401 53131 3 0.500 1 50 S 204-D 50 2CDS 254 001 R0501 55209 7 0.500 1 63 S 204-D 63 2CDS 254 001 R0631 55210 3 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series 6000 2CSC400421F0201 2CSC400419F02012CSC400418F0201

pro M compact® S 200-K K 2CSC400416F0201 2CSC400414F02012CSC400417F0201 S 200 K (power) characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=6 kA (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-K 0.5 2CDS 251 001 R0157 50719 6 0.125 10 1 S 201-K 1 2CDS 251 001 R0217 50720 2 0.125 10 1.6 S 201-K 1.6 2CDS 251 001 R0257 50721 9 0.125 10 2 S 201-K 2 2CDS 251 001 R0277 50722 6 0.125 10 3 S 201-K 3 2CDS 251 001 R0317 50723 3 0.125 10 4 S 201-K 4 2CDS 251 001 R0337 50724 0 0.125 10 6 S 201-K 6 2CDS 251 001 R0377 50725 7 0.125 10 8 S 201-K 8 2CDS 251 001 R0407 50726 4 0.125 10 10 S 201-K 10 2CDS 251 001 R0427 49611 7 0.125 10 13 S 201-K 13 2CDS 251 001 R0447 50727 1 0.125 10 16 S 201-K 16 2CDS 251 001 R0467 49612 4 0.125 10 20 S 201-K 20 2CDS 251 001 R0487 50728 8 0.125 10 25 S 201-K 25 2CDS 251 001 R0517 50729 5 0.125 10 32 S 201-K 32 2CDS 251 001 R0537 49613 1 0.125 10 40 S 201-K 40 2CDS 251 001 R0557 50730 1 0.125 10 50 S 201-K 50 2CDS 251 001 R0577 55112 0 0.125 10 63 S 201-K 63 2CDS 251 001 R0607 55113 7 0.125 10 2 0.5 S 202-K 0.5 2CDS 252 001 R0157 50731 8 0.250 5 1 S 202-K 1 2CDS 252 001 R0217 50732 5 0.250 5 1.6 S 202-K 1.6 2CDS 252 001 R0257 50733 2 0.250 5 2 S 202-K 2 2CDS 252 001 R0277 50734 9 0.250 5 3 S 202-K 3 2CDS 252 001 R0317 50735 6 0.250 5 4 S 202-K 4 2CDS 252 001 R0337 50736 3 0.250 5 6 S 202-K 6 2CDS 252 001 R0377 50737 0 0.250 5 8 S 202-K 8 2CDS 252 001 R0407 50738 7 0.250 5 10 S 202-K 10 2CDS 252 001 R0427 50739 4 0.250 5 13 S 202-K 13 2CDS 252 001 R0447 50740 0 0.250 5 16 S 202-K 16 2CDS 252 001 R0467 50741 7 0.250 5 20 S 202-K 20 2CDS 252 001 R0487 50742 4 0.250 5 25 S 202-K 25 2CDS 252 001 R0517 50743 1 0.250 5 32 S 202-K 32 2CDS 252 001 R0537 50744 8 0.250 5 40 S 202-K 40 2CDS 252 001 R0557 50745 5 0.250 5 50 S 202-K 50 2CDS 252 001 R0577 55116 8 0.250 5 63 S 202-K 63 2CDS 252 001 R0607 55117 5 0.250 5 3 0.5 S 203-K 0.5 2CDS 253 001 R0157 50746 2 0.375 1 1 S 203-K 1 2CDS 253 001 R0217 50747 9 0.375 1 1.6 S 203-K 1.6 2CDS 253 001 R0257 50748 6 0.375 1 2 S 203-K 2 2CDS 253 001 R0277 50749 3 0.375 1 3 S 203-K 3 2CDS 253 001 R0317 50750 9 0.375 1 4 S 203-K 4 2CDS 253 001 R0337 50751 6 0.375 1 6 S 203-K 6 2CDS 253 001 R0377 50752 3 0.375 1 8 S 203-K 8 2CDS 253 001 R0407 50753 0 0.375 1 10 S 203-K 10 2CDS 253 001 R0427 49614 8 0.375 1 13 S 203-K 13 2CDS 253 001 R0447 50754 7 0.375 1 16 S 203-K 16 2CDS 253 001 R0467 49615 5 0.375 1 20 S 203-K 20 2CDS 253 001 R0487 50755 4 0.375 1 25 S 203-K 25 2CDS 253 001 R0517 50756 1 0.375 1 32 S 203-K 32 2CDS 253 001 R0537 49616 2 0.375 1 40 S 203-K 40 2CDS 253 001 R0557 50757 8 0.375 1 50 S 203-K 50 2CDS 253 001 R0577 55118 2 0.375 1 63 S 203-K 63 2CDS 253 001 R0607 55119 9 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54706 UBmax

pro M compact® S 200-K K 4 0.5 S 204-K 0.5 2CDS 254 001 R0157 52926 6 0.500 1 1 S 204-K 1 2CDS 254 001 R0217 52927 3 0.500 1 1.6 S 204-K 1.6 2CDS 254 001 R0257 52928 0 0.500 1 2 S 204-K 2 2CDS 254 001 R0277 52929 7 0.500 1 3 S 204-K 3 2CDS 254 001 R0317 52930 3 0.500 1 4 S 204-K 4 2CDS 254 001 R0337 52931 0 0.500 1 6 S 204-K 6 2CDS 254 001 R0377 52932 7 0.500 1 8 S 204-K 8 2CDS 254 001 R0407 52933 4 0.500 1 10 S 204-K 10 2CDS 254 001 R0427 52934 1 0.500 1 13 S 204-K 13 2CDS 254 001 R0447 52935 8 0.500 1 16 S 204-K 16 2CDS 254 001 R0467 52936 5 0.500 1 20 S 204-K 20 2CDS 254 001 R0487 52937 2 0.500 1 25 S 204-K 25 2CDS 254 001 R0517 52938 9 0.500 1 32 S 204-K 32 2CDS 254 001 R0537 52939 6 0.500 1 40 S 204-K 40 2CDS 254 001 R0557 52940 2 0.500 1 50 S 204-K 50 2CDS 254 001 R0577 55122 9 0.500 1 63 S 204-K 63 2CDS 254 001 R0607 55123 6 0.500 1 /L54706 UBmax 125 V ... with 2 poles connected in series UBmax 60 V ... With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-K 0.5 NA 2CDS 251 103 R0157 53182 5 0.250 5 + 1 S 201-K 1 NA 2CDS 251 103 R0217 53183 2 0.250 5 NA 1.6 S 201-K 1.6 NA 2CDS 251 103 R0257 53184 9 0.250 5 2 S 201-K 2 NA 2CDS 251 103 R0277 53185 6 0.250 5 3 S 201-K 3 NA 2CDS 251 103 R0317 53186 3 0.250 5 4 S 201-K 4 NA 2CDS 251 103 R0337 53187 0 0.250 5 6 S 201-K 6 NA 2CDS 251 103 R0377 53188 7 0.250 5 8 S 201-K 8 NA 2CDS 251 103 R0407 53189 4 0.250 5 10 S 201-K 10 NA 2CDS 251 103 R0427 53190 0 0.250 5 13 S 201-K 13 NA 2CDS 251 103 R0447 53191 7 0.250 5 16 S 201-K 16 NA 2CDS 251 103 R0467 53192 4 0.250 5 20 S 201-K 20 NA 2CDS 251 103 R0487 53193 1 0.250 5 25 S 201-K 25 NA 2CDS 251 103 R0517 53194 8 0.250 5 32 S 201-K 32 NA 2CDS 251 103 R0537 53195 5 0.250 5 40 S 201-K 40 NA 2CDS 251 103 R0557 53196 2 0.250 5 50 S 201-K 50 NA 2CDS 251 103 R0577 55114 4 0.250 5 63 S 201-K 63 NA 2CDS 251 103 R0607 55115 1 0.250 5 3 0.5 S 203-K 0.5 NA 2CDS 253 103 R0157 53261 7 0.500 1 + 1 S 203-K 1 NA 2CDS 253 103 R0217 53262 4 0.500 1 NA 1.6 S 203-K 1.6 NA 2CDS 253 103 R0257 53263 1 0.500 1 2 S 203-K 2 NA 2CDS 253 103 R0277 53264 8 0.500 1 3 S 203-K 3 NA 2CDS 253 103 R0317 53265 5 0.500 1 4 S 203-K 4 NA 2CDS 253 103 R0337 53266 2 0.500 1 6 S 203-K 6 NA 2CDS 253 103 R0377 53267 9 0.500 1 8 S 203-K 8 NA 2CDS 253 103 R0407 53268 6 0.500 1 10 S 203-K 10 NA 2CDS 253 103 R0427 53269 3 0.500 1 13 S 203-K 13 NA 2CDS 253 103 R0447 53270 9 0.500 1 16 S 203-K 16 NA 2CDS 253 103 R0467 53271 6 0.500 1 20 S 203-K 20 NA 2CDS 253 103 R0487 53272 3 0.500 1 25 S 203-K 25 NA 2CDS 253 103 R0517 53273 0 0.500 1 32 S 203-K 32 NA 2CDS 253 103 R0537 53274 7 0.500 1 40 S 203-K 40 NA 2CDS 253 103 R0557 53275 4 0.500 1 50 S 203-K 50 NA 2CDS 253 103 R0577 55120 5 0.500 1 63 S 203-K 63 NA 2CDS 253 103 R0607 55121 2 0.500 1 UBmax 72 V ... UBmax 2CSC400421F0201 2CSC400419F02012CSC400418F0201

pro M compact® S 200-Z Z S 200 Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=6 kA (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-Z 0.5 2CDS 251 001 R0158 53030 9 0.125 10 1 S 201-Z 1 2CDS 251 001 R0218 53033 0 0.125 10 1.6 S 201-Z 1.6 2CDS 251 001 R0258 53034 7 0.125 10 2 S 201-Z 2 2CDS 251 001 R0278 53035 4 0.125 10 3 S 201-Z 3 2CDS 251 001 R0318 53036 1 0.125 10 4 S 201-Z 4 2CDS 251 001 R0338 53037 8 0.125 10 6 S 201-Z 6 2CDS 251 001 R0378 53040 8 0.125 10 8 S 201-Z 8 2CDS 251 001 R0408 53041 5 0.125 10 10 S 201-Z 10 2CDS 251 001 R0428 53042 2 0.125 10 16 S 201-Z 16 2CDS 251 001 R0468 53043 9 0.125 10 20 S 201-Z 20 2CDS 251 001 R0488 53044 6 0.125 10 25 S 201-Z 25 2CDS 251 001 R0518 53045 3 0.125 10 32 S 201-Z 32 2CDS 251 001 R0538 53046 0 0.125 10 40 S 201-Z 40 2CDS 251 001 R0558 53047 7 0.125 10 50 S 201-Z 50 2CDS 251 001 R0578 55191 5 0.125 10 63 S 201-Z 63 2CDS 251 001 R0608 55192 2 0.125 10 2 0.5 S 202-Z 0.5 2CDS 252 001 R0158 53068 2 0.250 5 1 S 202-Z 1 2CDS 252 001 R0218 53067 5 0.250 5 1.6 S 202-Z 1.6 2CDS 252 001 R0258 53069 9 0.250 5 2 S 202-Z 2 2CDS 252 001 R0278 53070 5 0.250 5 3 S 202-Z 3 2CDS 252 001 R0318 53071 2 0.250 5 4 S 202-Z 4 2CDS 252 001 R0338 53072 9 0.250 5 6 S 202-Z 6 2CDS 252 001 R0378 53073 6 0.250 5 8 S 202-Z 8 2CDS 252 001 R0408 53074 3 0.250 5 10 S 202-Z 10 2CDS 252 001 R0428 53075 0 0.250 5 16 S 202-Z 16 2CDS 252 001 R0468 53076 7 0.250 5 20 S 202-Z 20 2CDS 252 001 R0488 53077 4 0.250 5 25 S 202-Z 25 2CDS 252 001 R0518 53078 1 0.250 5 32 S 202-Z 32 2CDS 252 001 R0538 53079 8 0.250 5 40 S 202-Z 40 2CDS 252 001 R0558 53080 4 0.250 5 50 S 202-Z 50 2CDS 252 001 R0578 55193 9 0.250 5 63 S 202-Z 63 2CDS 252 001 R0608 55194 6 0.250 5 3 0.5 S 203-Z 0.5 2CDS 253 001 R0158 53097 2 0.375 1 1 S 203-Z 1 2CDS 253 001 R0218 53098 9 0.375 1 1.6 S 203-Z 1.6 2CDS 253 001 R0258 53099 6 0.375 1 2 S 203-Z 2 2CDS 253 001 R0278 53100 9 0.375 1 3 S 203-Z 3 2CDS 253 001 R0318 53101 6 0.375 1 4 S 203-Z 4 2CDS 253 001 R0338 53102 3 0.375 1 6 S 203-Z 6 2CDS 253 001 R0378 53103 0 0.375 1 8 S 203-Z 8 2CDS 253 001 R0408 53104 7 0.375 1 10 S 203-Z 10 2CDS 253 001 R0428 53105 4 0.375 1 16 S 203-Z 16 2CDS 253 001 R0468 53106 1 0.375 1 20 S 203-Z 20 2CDS 253 001 R0488 53107 8 0.375 1 25 S 203-Z 25 2CDS 253 001 R0518 53108 5 0.375 1 32 S 203-Z 32 2CDS 253 001 R0538 53109 2 0.375 1 40 S 203-Z 40 2CDS 253 001 R0558 53110 8 0.375 1 50 S 203-Z 50 2CDS 253 001 R0578 55195 3 0.375 1 63 S 203-Z 63 2CDS 253 001 R0608 55196 0 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54706 UBmax 2CSC400416F0201 2CSC400423F02012CSC400417F0201

pro M compact® S 200-Z Z With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201-Z 0.5 NA 2CDS 251 103 R0158 53214 3 0.260 5 + 1 S 201-Z 1 NA 2CDS 251 103 R0218 53215 0 0.260 5 NA 1.6 S 201-Z 1.6 NA 2CDS 251 103 R0258 53216 7 0.260 5 2 S 201-Z 2 NA 2CDS 251 103 R0278 53217 4 0.260 5 3 S 201-Z 3 NA 2CDS 251 103 R0318 53218 1 0.260 5 4 S 201-Z 4 NA 2CDS 251 103 R0338 53219 8 0.260 5 6 S 201-Z 6 NA 2CDS 251 103 R0378 53220 4 0.260 5 8 S 201-Z 8 NA 2CDS 251 103 R0408 53221 1 0.260 5 10 S 201-Z 10 NA 2CDS 251 103 R0428 53222 8 0.260 5 16 S 201-Z 16 NA 2CDS 251 103 R0468 53223 5 0.260 5 20 S 201-Z 20 NA 2CDS 251 103 R0488 53224 2 0.260 5 25 S 201-Z 25 NA 2CDS 251 103 R0518 53225 9 0.260 5 32 S 201-Z 32 NA 2CDS 251 103 R0538 53226 6 0.260 5 40 S 201-Z 40 NA 2CDS 251 103 R0558 53227 3 0.260 5 50 S 201-Z 50 NA 2CDS 251 103 R0578 55212 7 0.320 5 63 S 201-Z 63 NA 2CDS 251 103 R0608 55213 4 0.320 5 3 0.5 S 203-Z 0.5 NA 2CDS 253 103 R0158 53292 1 0.520 1 + 1 S 203-Z 1 NA 2CDS 253 103 R0218 53293 8 0.520 1 NA 1.6 S 203-Z 1.6 NA 2CDS 253 103 R0258 53294 5 0.520 1 2 S 203-Z 2 NA 2CDS 253 103 R0278 53295 2 0.520 1 3 S 203-Z 3 NA 2CDS 253 103 R0318 53297 6 0.520 1 4 S 203-Z 4 NA 2CDS 253 103 R0338 53298 3 0.520 1 6 S 203-Z 6 NA 2CDS 253 103 R0378 53299 0 0.520 1 8 S 203-Z 8 NA 2CDS 253 103 R0408 53300 3 0.520 1 10 S 203-Z 10 NA 2CDS 253 103 R0428 53301 0 0.520 1 16 S 203-Z 16 NA 2CDS 253 103 R0468 53302 7 0.520 1 20 S 203-Z 20 NA 2CDS 253 103 R0488 53305 8 0.520 1 25 S 203-Z 25 NA 2CDS 253 103 R0518 53306 5 0.520 1 32 S 203-Z 32 NA 2CDS 253 103 R0538 53307 2 0.520 1 40 S 203-Z 40 NA 2CDS 253 103 R0558 53308 9 0.520 1 50 S 203-Z 50 NA 2CDS 253 103 R0578 55214 1 0.640 1 63 S 203-Z 63 NA 2CDS 253 103 R0608 55216 5 0.640 1 UBmax 72 V ... UBmax 125 V ... /L54706 4 0.5 S 204-Z 0.5 2CDS 254 001 R0158 53024 8 0.500 1 1 S 204-Z 1 2CDS 254 001 R0218 53132 0 0.500 1 1.6 S 204-Z 1.6 2CDS 254 001 R0258 53144 3 0.500 1 2 S 204-Z 2 2CDS 254 001 R0278 53143 6 0.500 1 3 S 204-Z 3 2CDS 254 001 R0318 53133 7 0.500 1 4 S 204-Z 4 2CDS 254 001 R0338 53134 4 0.500 1 6 S 204-Z 6 2CDS 254 001 R0378 53135 1 0.500 1 8 S 204-Z 8 2CDS 254 001 R0408 53136 8 0.500 1 10 S 204-Z 10 2CDS 254 001 R0428 53137 5 0.500 1 16 S 204-Z 16 2CDS 254 001 R0468 53138 2 0.500 1 20 S 204-Z 20 2CDS 254 001 R0488 53139 9 0.500 1 25 S 204-Z 25 2CDS 254 001 R0518 53140 5 0.500 1 32 S 204-Z 32 2CDS 254 001 R0538 53141 2 0.500 1 40 S 204-Z 40 2CDS 254 001 R0558 53142 9 0.500 1 50 S 204-Z 50 2CDS 254 001 R0578 55197 7 0.500 1 63 S 204-Z 63 2CDS 254 001 R0608 55198 4 0.500 1 /L54706 UBmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series 6000 2CSC400421F0201 2CSC400419F02012CSC400418F0201

pro M compact® S 200 M-B B S 200 M-B characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201 M-B 6 2CDS 271 001 R0065 54942 4 0.125 10 10 S 201 M-B 10 2CDS 271 001 R0105 54943 1 0.125 10 13 S 201 M-B 13 2CDS 271 001 R0135 54944 8 0.125 10 16 S 201 M-B 16 2CDS 271 001 R0165 54945 5 0.125 10 20 /L54706 S 201 M-B 20 2CDS 271 001 R0205 54946 2 0.125 10 25 S 201 M-B 25 2CDS 271 001 R0255 54947 9 0.125 10 32 /L54707 S 201 M-B 32 2CDS 271 001 R0325 54948 6 0.125 10 40 /L54708 S 201 M-B 40 2CDS 271 001 R0405 54949 3 0.125 10 50 S 201 M-B 50 2CDS 271 001 R0505 54381 1 0.125 10 63 S 201 M-B 63 2CDS 271 001 R0635 54382 8 0.125 10 2 6 S 202 M-B 6 2CDS 272 001 R0065 54958 5 0.250 5 10 S 202 M-B 10 2CDS 272 001 R0105 54959 2 0.250 5 13 S 202 M-B 13 2CDS 272 001 R0135 54960 8 0.250 5 16 S 202 M-B 16 2CDS 272 001 R0165 54961 5 0.250 5 20 S 202 M-B 20 2CDS 272 001 R0205 54962 2 0.250 5

25 S 202 M-B 25 2CDS 272 001 R0255 54963 9

0.250 5 32 S 202 M-B 32 2CDS 272 001 R0325 54964 6 0.250 5 40 S 202 M-B 40 2CDS 272 001 R0405 54965 3 0.250 5 50 S 202 M-B 50 2CDS 272 001 R0505 54385 9 0.250 5 63 S 202 M-B 63 2CDS 272 001 R0635 54386 6 0.250 5 3 6 S 203 M-B 6 2CDS 273 001 R0065 54966 0 0.375 1 10 S 203 M-B 10 2CDS 273 001 R0105 54967 7 0.375 1 13 S 203 M-B 13 2CDS 273 001 R0135 54968 4 0.375 1 16 S 203 M-B 16 2CDS 273 001 R0165 54969 1 0.375 1 20 /L54706 S 203 M-B 20 2CDS 273 001 R0205 54970 7 0.375 1 25 S 203 M-B 25 2CDS 273 001 R0255 54971 4 0.375 1 32 /L54707 S 203 M-B 32 2CDS 273 001 R0325 54972 1 0.375 1 40 /L54708 S 203 M-B 40 2CDS 273 001 R0405 54973 8 0.375 1 50 S 203 M-B 50 2CDS 273 001 R0505 54387 3 0.375 1 63 S 203 M-B 63 2CDS 273 001 R0635 54388 0 0.375 1 4 6 S 204 M-B 6 2CDS 274 001 R0065 54982 0 0.500 1 10 S 204 M-B 10 2CDS 274 001 R0105 54983 7 0.500 1 13 S 204 M-B 13 2CDS 274 001 R0135 54984 4 0.500 1 16 S 204 M-B 16 2CDS 274 001 R0165 54985 1 0.500 1 20 S 204 M-B 20 2CDS 274 001 R0205 54986 8 0.500 1 25 S 204 M-B 25 2CDS 274 001 R0255 54987 5 0.500 1 32 S 204 M-B 32 2CDS 274 001 R0325 54988 2 0.500 1 40 S 204 M-B 40 2CDS 274 001 R0405 54989 9 0.500 1 50 S 204 M-B 50 2CDS 274 001 R0505 54391 0 0.500 1 63 S 204 M-B 63 2CDS 274 001 R0635 54392 7 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series UBmax 72 V ... UBmax 125 V ... /L54709 UBmax 125 V ... /L54709 UBmax 2CSC400413F0201 2CSC400411F02012CSC400415F02012CSC400443F0201

pro M compact® S 200 M-B B With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201 M-B 6 NA 2CDS 271 103 R0065 54950 9 0.250 5 + 10 S 201 M-B 10 NA 2CDS 271 103 R0105 54951 6 0.250 5 NA 13 S 201 M-B 13 NA 2CDS 271 103 R0135 54952 3 0.250 5 16 S 201 M-B 16 NA 2CDS 271 103 R0165 54953 0 0.250 5 20 /L54706 S 201 M-B 20 NA 2CDS 271 103 R0205 54954 7 0.250 5 25 S 201 M-B 25 NA 2CDS 271 103 R0255 54955 4 0.250 5 32 /L54707 S 201 M-B 32 NA 2CDS 271 103 R0325 54956 1 0.250 5 40 /L54708 S 201 M-B 40 NA 2CDS 271 103 R0405 54957 8 0.250 5 50 S 201 M-B 50 NA 2CDS 271 103 R0505 54383 5 0.250 5 63 S 201 M-B 63 NA 2CDS 271 103 R0635 54384 2 0.250 5 3 6 S 203 M-B 6 NA 2CDS 273 103 R0065 54974 5 0.500 1 + 10 S 203 M-B 10 NA 2CDS 273 103 R0105 54975 2 0.500 1 NA 13 S 203 M-B 13 NA 2CDS 273 103 R0135 54976 9 0.500 1 16 S 203 M-B 16 NA 2CDS 273 103 R0165 54977 6 0.500 1 20 /L54706 S 203 M-B 20 NA 2CDS 273 103 R0205 54978 3 0.500 1

25 S 203 M-B 25 NA

2CDS 273 103 R0255 54979 0 0.500 1 32 /L54707 S 203 M-B 32 NA 2CDS 273 103 R0325 54980 6 0.500 1 40 /L54708 S 203 M-B 40 NA 2CDS 273 103 R0405 54981 3 0.500 1 50 S 203 M-B 50 NA 2CDS 273 103 R0505 54389 7 0.500 1 63 S 203 M-B 63 NA 2CDS 273 103 R0635 54390 3 0.580 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 2CSC400418F0201 2CSC400421F0201

pro M compact® S 200 M-C C S 200 M-C characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-C 0.5 2CDS 271 001 R0984 54990 5 0.125 10 1 S 201 M-C 1 2CDS 271 001 R0014 54992 9 0.125 10 1.6 S 201 M-C 1.6 2CDS 271 001 R0974 54991 2 0.125 10 2 S 201 M-C 2 2CDS 271 001 R0024 54993 6 0.125 10 3 S 201 M-C 3 2CDS 271 001 R0034 54994 3 0.125 10 4 S 201 M-C 4 2CDS 271 001 R0044 54995 0 0.125 10 6 S 201 M-C 6 2CDS 271 001 R0064 54996 7 0.125 10 8 S 201 M-C 8 2CDS 271 001 R0084 54997 4 0.125 10 10 S 201 M-C 10 2CDS 271 001 R0104 54998 1 0.125 10 13 S 201 M-C 13 2CDS 271 001 R0134 54999 8 0.125 10 16 S 201 M-C 16 2CDS 271 001 R0164 55000 0 0.125 10 20 /L54706 S 201 M-C 20 2CDS 271 001 R0204 55001 7 0.125 10 25 S 201 M-C 25 2CDS 271 001 R0254 55002 4 0.125 10 32 /L54707 S 201 M-C 32 2CDS 271 001 R0324 55003 1 0.125 10 40 /L54708 S 201 M-C 40 2CDS 271 001 R0404 55004 8 0.125 10

50 S 201 M-C 50 2CDS 271 001 R0504 54393 4

0.125 10 63 S 201 M-C 63 2CDS 271 001 R0634 54394 1 0.125 10 2 0.5 S 202 M-C 0.5 2CDS 272 001 R0984 55020 8 0.250 5 1 S 202 M-C 1 2CDS 272 001 R0014 55022 2 0.250 5 1.6 S 202 M-C 1.6 2CDS 272 001 R0974 55021 5 0.250 5 2 S 202 M-C 2 2CDS 272 001 R0024 55023 9 0.250 5 3 S 202 M-C 3 2CDS 272 001 R0034 55024 6 0.250 5 4 S 202 M-C 4 2CDS 272 001 R0044 55025 3 0.250 5 6 S 202 M-C 6 2CDS 272 001 R0064 55026 0 0.250 5 8 S 202 M-C 8 2CDS 272 001 R0084 55027 7 0.250 5 10 S 202 M-C 10 2CDS 272 001 R0104 55028 4 0.250 5 13 S 202 M-C 13 2CDS 272 001 R0134 55029 1 0.250 5 16 S 202 M-C 16 2CDS 272 001 R0164 55030 7 0.250 5 20 S 202 M-C 20 2CDS 272 001 R0204 55031 4 0.250 5 25 S 202 M-C 25 2CDS 272 001 R0254 55032 1 0.250 5 32 S 202 M-C 32 2CDS 272 001 R0324 55033 8 0.250 5 40 S 202 M-C 40 2CDS 272 001 R0404 55034 5 0.250 5 50 S 202 M-C 50 2CDS 272 001 R0504 54397 2 0.250 5 63 S 202 M-C 63 2CDS 272 001 R0634 54398 9 0.250 5 3 0.5 S 203 M-C 0.5 2CDS 273 001 R0984 55035 2 0.375 1 1 S 203 M-C 1 2CDS 273 001 R0014 55037 6 0.375 1 1.6 S 203 M-C 1.6 2CDS 273 001 R0974 55036 9 0.375 1 2 S 203 M-C 2 2CDS 273 001 R0024 55038 3 0.375 1 3 S 203 M-C 3 2CDS 273 001 R0034 55039 0 0.375 1 4 S 203 M-C 4 2CDS 273 001 R0044 55040 6 0.375 1 6 S 203 M-C 6 2CDS 273 001 R0064 55041 3 0.375 1 8 S 203 M-C 8 2CDS 273 001 R0084 55042 0 0.375 1 10 S 203 M-C 10 2CDS 273 001 R0104 55043 7 0.375 1 13 S 203 M-C 13 2CDS 273 001 R0134 55044 4 0.375 1 16 S 203 M-C 16 2CDS 273 001 R0164 55045 1 0.375 1 20 /L54706 S 203 M-C 20 2CDS 273 001 R0204 55046 8 0.375 1 25 S 203 M-C 25 2CDS 273 001 R0254 55047 5 0.375 1 32 /L54707 S 203 M-C 32 2CDS 273 001 R0324 55048 2 0.375 1 40 /L54708 S 203 M-C 40 2CDS 273 001 R0404 55049 9 0.375 1 50 S 203 M-C 50 2CDS 273 001 R0504 54399 6 0.375 1 63 S 203 M-C 63 2CDS 273 001 R0634 54400 9 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax 2CSC400425F0201 2CSC400424F02012CSC400426F0201

pro M compact® S 200 M-C C With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-C 0.5 NA 2CDS 271 103 R0984 55005 5 0.250 5 + 1 S 201 M-C 1 NA 2CDS 271 103 R0014 55007 9 0.250 5 NA 1.6 S 201 M-C 1.6 NA 2CDS 271 103 R0974 55006 2 0.250 5 2 S 201 M-C 2 NA 2CDS 271 103 R0024 55008 6 0.250 5 3 S 201 M-C 3 NA 2CDS 271 103 R0034 55009 3 0.250 5 4 S 201 M-C 4 NA 2CDS 271 103 R0044 55010 9 0.250 5 6 S 201 M-C 6 NA 2CDS 271 103 R0064 55011 6 0.250 5 8 S 201 M-C 8 NA 2CDS 271 103 R0084 55012 3 0.250 5 10 S 201 M-C 10 NA 2CDS 271 103 R0104 55013 0 0.250 5 13 S 201 M-C 13 NA 2CDS 271 103 R0134 55014 7 0.250 5 16 S 201 M-C 16 NA 2CDS 271 103 R0164 55015 4 0.250 5 20 /L54706 S 201 M-C 20 NA 2CDS 271 103 R0204 55016 1 0.250 5 25 S 201 M-C 25 NA 2CDS 271 103 R0254 55017 8 0.250 5 32 /L54707 S 201 M-C 32 NA 2CDS 271 103 R0324 55018 5 0.250 5 40 /L54708 S 201 M-C 40 NA 2CDS 271 103 R0404 55019 2 0.250 5

50 S 201 M-C 50 NA 2CDS 271 103 R0504 54395 8

0.250 5 63 S 201 M-C 63 NA 2CDS 271 103 R0634 54396 5 0.250 5 3 0.5 S 203 M-C 0.5 NA 2CDS 273 103 R0984 55051 2 0.500 1 + 1 S 203 M-C 1 NA 2CDS 273 103 R0014 55052 9 0.500 1 NA 1.6 S 203 M-C 1.6 NA 2CDS 273 103 R0974 55050 5 0.500 1 2 S 203 M-C 2 NA 2CDS 273 103 R0024 55053 6 0.500 1 3 S 203 M-C 3 NA 2CDS 273 103 R0034 55054 3 0.500 1 4 S 203 M-C 4 NA 2CDS 273 103 R0044 55055 0 0.500 1 6 S 203 M-C 6 NA 2CDS 273 103 R0064 55056 7 0.500 1 8 S 203 M-C 8 NA 2CDS 273 103 R0084 55057 4 0.500 1 10 S 203 M-C 10 NA 2CDS 273 103 R0104 55058 1 0.500 1 13 S 203 M-C 13 NA 2CDS 273 103 R0134 55059 8 0.500 1 16 S 203 M-C 16 NA 2CDS 273 103 R0164 55060 4 0.500 1 20 /L54706 S 203 M-C 20 NA 2CDS 273 103 R0204 55061 1 0.500 1 25 S 203 M-C 25 NA 2CDS 273 103 R0254 55062 8 0.500 1 32 /L54707 S 203 M-C 32 NA 2CDS 273 103 R0324 55063 5 0.500 1 40 /L54708 S 203 M-C 40 NA 2CDS 273 103 R0404 55064 2 0.500 1 50 S 203 M-C 50 NA 2CDS 273 103 R0504 54401 6 0.580 1 63 S 203 M-C 63 NA 2CDS 273 103 R0634 54402 3 0.580 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204 M-C 0.5 2CDS 274 001 R0984 55065 9 0.500 1 1 S 204 M-C 1 2CDS 274 001 R0014 55067 3 0.500 1 1.6 S 204 M-C 1.6 2CDS 274 001 R0974 55066 6 0.500 1 2 S 204 M-C 2 2CDS 274 001 R0024 55068 0 0.500 1 3 S 204 M-C 3 2CDS 274 001 R0034 55069 7 0.500 1 4 S 204 M-C 4 2CDS 274 001 R0044 55070 3 0.500 1 6 S 204 M-C 6 2CDS 274 001 R0064 55071 0 0.500 1 8 S 204 M-C 8 2CDS 274 001 R0084 55072 7 0.500 1 10 S 204 M-C 10 2CDS 274 001 R0104 55073 4 0.500 1 13 S 204 M-C 13 2CDS 274 001 R0134 55074 1 0.500 1 16 S 204 M-C 16 2CDS 274 001 R0164 55075 8 0.500 1 20 S 204 M-C 20 2CDS 274 001 R0204 55076 5 0.500 1 25 S 204 M-C 25 2CDS 274 001 R0254 55077 2 0.500 1 32 S 204 M-C 32 2CDS 274 001 R0324 55078 9 0.500 1 40 S 204 M-C 40 2CDS 274 001 R0404 55079 6 0.500 1 50 S 204 M-C 50 2CDS 274 001 R0504 54403 0 0.500 1 63 S 204 M-C 63 2CDS 274 001 R0634 54404 7 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series M 10000 2CSC400420F0201 2CSC400443F02012CSC400418F0201

pro M compact® D 2CSC400425F0201 2CSC400424F02012CSC400426F0201 S 200 M-D S 200 M-D characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, break- down lamps). Applications: residential, commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-D 0.5 2CDS 271 001 R0981 59983 2 0.125 10 1 S 201 M-D 1 2CDS 271 001 R0011 50031 3 0.125 10 1.6 S 201 M-D 1.6 2CDS 271 001 R0971 59982 5 0.125 10 2 S 201 M-D 2 2CDS 271 001 R0021 59933 7 0.125 10 3 S 201 M-D 3 2CDS 271 001 R0031 59935 1 0.125 10 4 S 201 M-D 4 2CDS 271 001 R0041 59935 7 0.125 10 6 S 201 M-D 6 2CDS 271 001 R0061 59939 9 0.125 10 8 S 201 M-D 8 2CDS 271 001 R0081 59940 5 0.125 10 10 S 201 M-D 10 2CDS 271 001 R0101 59942 9 0.125 10 13 S 201 M-D 13 2CDS 271 001 R0131 66326 7 0.125 10 16 S 201 M-D 16 2CDS 271 001 R0161 59945 0 0.125 10 20 /L54706 S 201 M-D 20 2CDS 271 001 R0201 50046 7 0.125 10 25 S 201 M-D 25 2CDS 271 001 R0251 59949 8 0.125 10 32 /L54707 S 201 M-D 32 2CDS 271 001 R0321 59956 6 0.125 10 40 /L54708 S 201 M-D 40 2CDS 271 001 R0401 59961 0 0.125 10

50 S 201 M-D 50 2CDS 271 001 R0501 59970 2

0.125 10 63 S 201 M-D 63 2CDS 271 001 R0631 59981 8 0.125 10 2 0.5 S 202 M-D 0.5 2CDS 272 001 R0981 60088 0 0.250 5 1 S 202 M-D 1 2CDS 272 001 R0011 60036 1 0.250 5 1.6 S 202 M-D 1.6 2CDS 272 001 R0971 60087 3 0.250 5 2 S 202 M-D 2 2CDS 272 001 R0021 60038 5 0.250 5 3 S 202 M-D 3 2CDS 272 001 R0031 60040 8 0.250 5 4 S 202 M-D 4 2CDS 272 001 R0041 60042 2 0.250 5 6 S 202 M-D 6 2CDS 272 001 R0061 60044 6 0.250 5 8 S 202 M-D 8 2CDS 272 001 R0081 60045 3 0.250 5 10 S 202 M-D 10 2CDS 272 001 R0101 60047 7 0.250 5 13 S 202 M-D 13 2CDS 272 001 R0131 66327 4 0.250 5 16 S 202 M-D 16 2CDS 272 001 R0161 60050 7 0.250 5 20 S 202 M-D 20 2CDS 272 001 R0201 60051 4 0.250 5 25 S 202 M-D 25 2CDS 272 001 R0251 60054 5 0.250 5 32 S 202 M-D 32 2CDS 272 001 R0321 60061 3 0.250 5 40 S 202 M-D 40 2CDS 272 001 R0401 60066 8 0.250 5 50 S 202 M-D 50 2CDS 272 001 R0501 60075 0 0.250 5 63 S 202 M-D 63 2CDS 272 001 R0631 60086 6 0.250 5 3 0.5 S 203 M-D 0.5 2CDS 273 001 R0981 60141 2 0.375 1 1 S 203 M-D 1 2CDS 273 001 R0011 60089 7 0.375 1 1.6 S 203 M-D 1.6 2CDS 273 001 R0971 60140 5 0.375 1 2 S 203 M-D 2 2CDS 273 001 R0021 60091 0 0.375 1 3 S 203 M-D 3 2CDS 273 001 R0031 60093 4 0.375 1 4 S 203 M-D 4 2CDS 273 001 R0041 60095 8 0.375 1 6 S 203 M-D 6 2CDS 273 001 R0061 60097 2 0.375 1 8 S 203 M-D 8 2CDS 273 001 R0081 60098 9 0.375 1 10 S 203 M-D 10 2CDS 273 001 R0101 60100 9 0.375 1 13 S 203 M-D 13 2CDS 273 001 R0131 66328 1 0.375 1 16 S 203 M-D 16 2CDS 273 001 R0161 60103 0 0.375 1 20 /L54706 S 203 M-D 20 2CDS 273 001 R0201 60104 7 0.375 1 25 S 203 M-D 25 2CDS 273 001 R0251 60107 8 0.375 1 32 /L54707 S 203 M-D 32 2CDS 273 001 R0321 60114 6 0.375 1 40 /L54708 S 203 M-D 40 2CDS 273 001 R0401 60119 1 0.375 1 50 S 203 M-D 50 2CDS 273 001 R0501 60128 3 0.375 1 63 S 203 M-D 63 2CDS 273 001 R0631 60139 9 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax

pro M compact® D 2CSC400420F0201 2CSC400443F02012CSC400418F0201 S 200 M-D With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-D 0.5 NA 2CDS 271 103 R0981 60035 4 0.250 5 + 1 S 201 M-D 1 NA 2CDS 271 103 R0011 59984 9 0.250 5 NA 1.6 S 201-M D 1.6 NA 2CDS 271 103 R0971 60034 7 0.250 5 2 S 201 M-D 2 NA 2CDS 271 103 R0021 59986 3 0.250 5 3 S 201 M-D 3 NA 2CDS 271 103 R0031 59988 7 0.250 5 4 S 201 M-D 4 NA 2CDS 271 103 R0041 59990 0 0.250 5 6 S 201 M-D 6 NA 2CDS 271 103 R0061 59992 4 0.250 5 8 S 201 M-D 8 NA 2CDS 271 103 R0081 59993 1 0.250 5 10 S 201 M-D 10 NA 2CDS 271 103 R0101 59994 8 0.250 5 13 S 201 M-D 13 NA 2CDS 271 103 R0131 66330 4 0.250 5 16 S 201 M-D 16 NA 2CDS 271 103 R0161 59997 9 0.250 5 20 /L54706 S 201 M-D 20 NA 2CDS 271 103 R0201 59998 6 0.250 5 25 S 201 M-D 25 NA 2CDS 271 103 R0251 60001 9 0.250 5 32 /L54707 S 201 M-D 32 NA 2CDS 271 103 R0321 60008 8 0.250 5 40 /L54708 S 201 M-D 40 NA 2CDS 271 103 R0401 60013 2 0.250 5

50 S 201 M-D 50 NA 2CDS 271 103 R0501 60022 4

0.290 5 63 S 201 M-D 63 NA 2CDS 271 103 R0631 60033 0 0.290 5 3 0.5 S 203 M-D 0.5 NA 2CDS 273 103 R0981 66331 1 0.500 1 + 1 S 203 M-D 1 NA 2CDS 273 103 R0011 66332 8 0.500 1 NA 1.6 S 203 M-D 1.6 NA 2CDS 273 103 R0971 66333 5 0.500 1 2 S 203 M-D 2 NA 2CDS 273 103 R0021 66334 2 0.500 1 3 S 203 M-D 3 NA 2CDS 273 103 R0031 66335 9 0.500 1 4 S 203 M-D 4 NA 2CDS 273 103 R0041 66336 6 0.500 1 6 S 203 M-D 6 NA 2CDS 273 103 R0061 66337 3 0.500 1 8 S 203 M-D 8 NA 2CDS 273 103 R0081 663380 0.500 1 10 S 203 M-D 10 NA 2CDS 273 103 R0101 66339 7 0.500 1 13 S 203 M-D 13 NA 2CDS 273 103 R0131 66340 3 0.500 1 16 S 203 M-D 16 NA 2CDS 273 103 R0161 66341 0 0.500 1 20 /L54706 S 203 M-D 20 NA 2CDS 273 103 R0201 66342 7 0.500 1 25 S 203 M-D 25 NA 2CDS 273 103 R0251 66343 4 0.500 1 32 /L54707 S 203 M-D 32 NA 2CDS 273 103 R0321 66344 1 0.500 1 40 /L54708 S 203 M-D 40 NA 2CDS 273 103 R0401 66345 8 0.500 1 50 S 203 M-D 50 NA 2CDS 273 103 R0501 66346 5 0.580 1 63 S 203 M-D 63 NA 2CDS 273 103 R0631 66347 2 0.580 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204 M-D 0.5 2CDS 274 001 R0981 60214 3 0.500 1 1 S 204 M-D 1 2CDS 274 001 R0011 60163 4 0.500 1 1.6 S 204 M-D 1.6 2CDS 274 001 R0971 60213 6 0.500 1 2 S 204 M-D 2 2CDS 274 001 R0021 60165 8 0.500 1 3 S 204 M-D 3 2CDS 274 001 R0031 60167 2 0.500 1 4 S 204 M-D 4 2CDS 274 001 R0041 60169 6 0.500 1 6 S 204 M-D 6 2CDS 274 001 R0061 60171 9 0.500 1 8 S 204 M-D 8 2CDS 274 001 R0081 60172 6 0.500 1 10 S 204 M-D 10 2CDS 274 001 R0101 60174 0 0.500 1 13 S 204 M-D 13 2CDS 274 001 R0131 66329 8 0.500 1 16 S 204 M-D 16 2CDS 274 001 R0161 60177 1 0.500 1 20 S 204 M-D 20 2CDS 274 001 R0201 60178 8 0.500 1 25 S 204 M-D 25 2CDS 274 001 R0251 60181 8 0.500 1 32 S 204 M-D 32 2CDS 274 001 R0321 60188 7 0.500 1 40 S 204 M-D 40 2CDS 274 001 R0401 60193 1 0.500 1 50 S 204 M-D 50 2CDS 274 001 R0501 60201 3 0.500 1 63 S 204 M-D 63 2CDS 274 001 R0631 60212 9 0.500 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series M 10000

pro M compact® K 2CDC021171F0006 2CSC400424F02012CSC400426F0201 S 200 M-K S 200 M-K (power) characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=10 kA (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-K 0.5 2CDS 271 001 R0157 59943 6 0.125 10 1 S 201 M-K 1 2CDS 271 001 R0217 59947 4 0.125 10 1.6 S 201 M-K 1.6 2CDS 271 001 R0257 59950 4 0.125 10 2 S 201 M-K 2 2CDS 271 001 R0277 59952 8 0.125 10 3 S 201 M-K 3 2CDS 271 001 R0317 59954 2 0.125 10 4 S 201 M-K 4 2CDS 271 001 R0337 59957 3 0.125 10 6 S 201 M-K 6 2CDS 271 001 R0377 59959 7 0.125 10 8 S 201 M-K 8 2CDS 271 001 R0407 59962 7 0.125 10 10 S 201 M-K 10 2CDS 271 001 R0427 59964 1 0.125 10 13 S 201 M-K 13 2CDS 271 001 R0447 65939 0 0.125 10 16 S 201 M-K 16 2CDS 271 001 R0467 59966 5 0.125 10 20 S 201 M-K 20 2CDS 271 001 R0487 59968 9 0.125 10 25 S 201 M-K 25 2CDS 271 001 R0517 59971 9 0.125 10 32 S 201 M-K 32 2CDS 271 001 R0537 59973 3 0.125 10 40 S 201 M-K 40 2CDS 271 001 R0557 59975 7 0.125 10 50 S 201 M-K 50 2CDS 271 001 R0577 59977 1 0.125 10 63 S 201 M-K 63 2CDS 271 001 R0607 59979 5 0.125 10 2 0.5 S 202 M-K 0.5 2CDS 272 001 R0157 60048 4 0.250 5 1 S 202 M-K 1 2CDS 272 001 R0217 60052 1 0.250 5 1.6 S 202 M-K 1.6 2CDS 272 001 R0257 60055 2 0.250 5 2 S 202 M-K 2 2CDS 272 001 R0277 60057 6 0.250 5 3 S 202 M-K 3 2CDS 272 001 R0317 60059 0 0.250 5 4 S 202 M-K 4 2CDS 272 001 R0337 60062 0 0.250 5 6 S 202 M-K 6 2CDS 272 001 R0377 60064 4 0.250 5 8 S 202 M-K 8 2CDS 272 001 R0407 60067 5 0.250 5 10 S 202 M-K 10 2CDS 272 001 R0427 60069 9 0.250 5 13 S 202 M-K 13 2CDS 272 001 R0447 65940 6 0.250 5 16 S 202 M-K 16 2CDS 272 001 R0467 60071 2 0.250 5 20 S 202 M-K 20 2CDS 272 001 R0487 60073 6 0.250 5 25 S 202 M-K 25 2CDS 272 001 R0517 60076 7 0.250 5 32 S 202 M-K 32 2CDS 272 001 R0537 60078 1 0.250 5 40 S 202 M-K 40 2CDS 272 001 R0557 60080 4 0.250 5 50 S 202 M-K 50 2CDS 272 001 R0577 60082 8 0.250 5 63 S 202 M-K 63 2CDS 272 001 R0607 60084 2 0.250 5 3 0.5 S 203 M-K 0.5 2CDS 273 001 R0157 60101 6 0.375 1 1 S 203 M-K 1 2CDS 273 001 R0217 60105 4 0.375 1 1.6 S 203 M-K 1.6 2CDS 273 001 R0257 60108 5 0.375 1 2 S 203 M-K 2 2CDS 273 001 R0277 60110 8 0.375 1 3 S 203 M-K 3 2CDS 273 001 R0317 60112 2 0.375 1 4 S 203 M-K 4 2CDS 273 001 R0337 60115 3 0.375 1 6 S 203 M-K 6 2CDS 273 001 R0377 60117 7 0.375 1 8 S 203 M-K 8 2CDS 273 001 R0407 60120 7 0.375 1 10 S 203 M-K 10 2CDS 273 001 R0427 60122 1 0.375 1 13 S 203 M-K 13 2CDS 273 001 R0447 65941 3 0.375 1 16 S 203 M-K 16 2CDS 273 001 R0467 60124 5 0.375 1 20 S 203 M-K 20 2CDS 273 001 R0487 60126 9 0.375 1 25 S 203 M-K 25 2CDS 273 001 R0517 60129 0 0.375 1 32 S 203 M-K 32 2CDS 273 001 R0537 60131 3 0.375 1 40 S 203 M-K 40 2CDS 273 001 R0557 60133 7 0.375 1 50 S 203 M-K 50 2CDS 273 001 R0577 60135 1 0.375 1 63 S 203 M-K 63 2CDS 273 001 R0607 60137 5 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54706 UBmax

pro M compact® K 2CDC021170F0006 2CSC400443F02012CSC400418F0201 S 200 M-K 4 0.5 S 204 M-K 0.5 2CDS 274 001 R0157 60175 7 0.500 1 1 S 204 M-K 1 2CDS 274 001 R0217 60179 5 0.500 1 1.6 S 204 M-K 1.6 2CDS 274 001 R0257 60182 5 0.500 1 2 S 204 M-K 2 2CDS 274 001 R0277 60184 9 0.500 1 3 S 204 M-K 3 2CDS 274 001 R0317 60186 3 0.500 1 4 S 204 M-K 4 2CDS 274 001 R0337 60189 4 0.500 1 6 S 204 M-K 6 2CDS 274 001 R0377 60191 7 0.500 1 8 S 204 M-K 8 2CDS 274 001 R0407 60194 8 0.500 1 10 S 204 M-K 10 2CDS 274 001 R0427 60196 2 0.500 1 13 S 204 M-K 13 2CDS 274 001 R0447 65942 0 0.500 1 16 S 204 M-K 16 2CDS 274 001 R0467 60198 6 0.500 1 20 S 204 M-K 20 2CDS 274 001 R0487 60200 6 0.500 1 25 S 204 M-K 25 2CDS 274 001 R0517 60202 0 0.500 1 32 S 204 M-K 32 2CDS 274 001 R0537 60204 4 0.500 1 40 S 204 M-K 40 2CDS 274 001 R0557 60206 8 0.500 1 50 S 204 M-K 50 2CDS 274 001 R0577 60208 2 0.500 1 63 S 204 M-K 63 2CDS 274 001 R0607 60210 5 0.500 1 /L54706 UBmax 125 V ... with 2 poles connected in series UBmax 125 V ... With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-K 0.5 NA 2CDS 271 103 R0157 59995 5 0.250 5 + 1 S 201 M-K 1 NA 2CDS 271 103 R0217 59999 3 0.250 5 NA 1.6 S 201 M-K 1.6 NA 2CDS 271 103 R0257 60002 6 0.250 5 2 S 201 M-K 2 NA 2CDS 271 103 R0277 60004 0 0.250 5 3 S 201 M-K 3 NA 2CDS 271 103 R0317 60006 4 0.250 5 4 S 201 M-K 4 NA 2CDS 271 103 R0337 60009 5 0.250 5 6 S 201 M-K 6 NA 2CDS 271 103 R0377 60011 8 0.250 5 8 S 201 M-K 8 NA 2CDS 271 103 R0407 60014 9 0.250 5 10 S 201 M-K 10 NA 2CDS 271 103 R0427 60016 3 0.250 5 13 S 201 M-K 13 NA 2CDS 271 103 R0447 65943 7 0.250 5 16 S 201 M-K 16 NA 2CDS 271 103 R0467 60018 7 0.250 5 20 S 201 M-K 20 NA 2CDS 271 103 R0487 60020 0 0.250 5 25 S 201 M-K 25 NA 2CDS 271 103 R0517 60023 1 0.250 5 32 S 201 M-K 32 NA 2CDS 271 103 R0537 60025 5 0.250 5 40 S 201 M-K 40 NA 2CDS 271 103 R0557 60027 9 0.250 5 50 S 201 M-K 50 NA 2CDS 271 103 R0577 60029 3 0.250 5 63 S 201 M-K 63 NA 2CDS 271 103 R0607 60031 6 0.250 5 3 0.5 S 203 M-K 0.5 NA 2CDS 273 103 R0157 65944 4 0.500 1 + 1 S 203 M-K 1 NA 2CDS 273 103 R0217 65045 1 0.500 1 NA 1.6 S 203 M-K 1.6 NA 2CDS 273 103 R0257 65946 8 0.500 1 2 S 203 M-K 2 NA 2CDS 273 103 R0277 65947 5 0.500 1 3 S 203 M-K 3 NA 2CDS 273 103 R0317 65948 2 0.500 1 4 S 203 M-K 4 NA 2CDS 273 103 R0337 65949 9 0.500 1 6 S 203 M-K 6 NA 2CDS 273 103 R0377 65950 5 0.500 1 8 S 203 M-K 8 NA 2CDS 273 103 R0407 65951 2 0.500 1 10 S 203 M-K 10 NA 2CDS 273 103 R0427 65952 9 0.500 1 13 S 203 M-K 13 NA 2CDS 273 103 R0447 65953 6 0.500 1 16 S 203 M-K 16 NA 2CDS 273 103 R0467 65954 3 0.500 1 20 S 203 M-K 20 NA 2CDS 273 103 R0487 65955 0 0.500 1 25 S 203 M-K 25 NA 2CDS 273 103 R0517 65956 7 0.500 1 32 S 203 M-K 32 NA 2CDS 273 103 R0537 65957 4 0.500 1 40 S 203 M-K 40 NA 2CDS 273 103 R0557 65958 1 0.500 1 50 S 203 M-K 50 NA 2CDS 273 103 R0577 65960 4 0.500 1 63 S 203 M-K 63 NA 2CDS 273 103 R0607 65961 1 0.500 1 UBmax 72 V ... UBmax

pro M compact® Z 2CDC021205F0006 2CSC400424F02012CSC400426F0201 S 200 M-Z S 200 M-Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=10 kA (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-Z 0.5 2CDS 271 001 R0158 59944 3 0.125 10 1 S 201 M-Z 1 2CDS 271 001 R0218 59948 1 0.125 10 1.6 S 201 M-Z 1.6 2CDS 271 001 R0258 59951 1 0.125 10 2 S 201 M-Z 2 2CDS 271 001 R0278 59953 5 0.125 10 3 S 201 M-Z 3 2CDS 271 001 R0318 59955 9 0.125 10 4 S 201 M-Z 4 2CDS 271 001 R0338 59958 0 0.125 10 6 S 201 M-Z 6 2CDS 271 001 R0378 59960 3 0.125 10 8 S 201 M-Z 8 2CDS 271 001 R0408 59963 4 0.125 10 10 S 201 M-Z 10 2CDS 271 001 R0428 59965 8 0.125 10 16 S 201 M-Z 16 2CDS 271 001 R0468 59967 2 0.125 10 20 S 201 M-Z 20 2CDS 271 001 R0488 59969 6 0.125 10 25 S 201 M-Z 25 2CDS 271 001 R0518 59972 6 0.125 10 32 S 201 M-Z 32 2CDS 271 001 R0538 59974 0 0.125 10 40 S 201 M-Z 40 2CDS 271 001 R0558 59976 4 0.125 10 50 S 201 M-Z 50 2CDS 271 001 R0578 59978 8 0.125 10 63 S 201 M-Z 63 2CDS 271 001 R0608 59980 1 0.125 10 2 0.5 S 202 M-Z 0.5 2CDS 272 001 R0158 60049 1 0.250 5 1 S 202 M-Z 1 2CDS 272 001 R0218 60053 8 0.250 5 1.6 S 202 M-Z 1.6 2CDS 272 001 R0258 60056 9 0.250 5 2 S 202 M-Z 2 2CDS 272 001 R0278 60058 3 0.250 5 3 S 202 M-Z 3 2CDS 272 001 R0318 60060 6 0.250 5 4 S 202 M-Z 4 2CDS 272 001 R0338 60063 7 0.250 5 6 S 202 M-Z 6 2CDS 272 001 R0378 60065 1 0.250 5 8 S 202 M-Z 8 2CDS 272 001 R0408 60068 2 0.250 5 10 S 202 M-Z 10 2CDS 272 001 R0428 60070 5 0.250 5 16 S 202 M-Z 16 2CDS 272 001 R0468 60072 9 0.250 5 20 S 202 M-Z 20 2CDS 272 001 R0488 60074 3 0.250 5 25 S 202 M-Z 25 2CDS 272 001 R0518 60077 4 0.250 5 32 S 202 M-Z 32 2CDS 272 001 R0538 60079 8 0.250 5 40 S 202 M-Z 40 2CDS 272 001 R0558 60081 1 0.250 5 50 S 202-M Z 50 2CDS 272 001 R0578 60083 5 0.250 5 63 S 202 M-Z 63 2CDS 272 001 R0608 60085 9 0.250 5 3 0.5 S 203 M-Z 0.5 2CDS 273 001 R0158 60102 3 0.375 1 1 S 203 M-Z 1 2CDS 273 001 R0218 60106 1 0.375 1 1.6 S 203 M-Z 1.6 2CDS 273 001 R0258 60109 2 0.375 1 2 S 203 M-Z 2 2CDS 273 001 R0278 60111 5 0.375 1 3 S 203 M-Z 3 2CDS 273 001 R0318 60113 9 0.375 1 4 S 203 M-Z 4 2CDS 273 001 R0338 60116 0 0.375 1 6 S 203 M-Z 6 2CDS 273 001 R0378 60118 4 0.375 1 8 S 203 M-Z 8 2CDS 273 001 R0408 60121 4 0.375 1 10 S 203 M-Z 10 2CDS 273 001 R0428 60123 8 0.375 1 16 S 203 M-Z 16 2CDS 273 001 R0468 60125 2 0.375 1 20 S 203 M-Z 20 2CDS 273 001 R0488 60127 6 0.375 1 25 S 203 M-Z 25 2CDS 273 001 R0518 60130 6 0.375 1 32 S 203 M-Z 32 2CDS 273 001 R0538 60132 0 0.375 1 40 S 203 M-Z 40 2CDS 273 001 R0558 60134 4 0.375 1 50 S 203 M-Z 50 2CDS 273 001 R0578 60136 8 0.375 1 63 S 203 M-Z 63 2CDS 273 001 R0608 60138 2 0.375 1 UBmax 72 V ... UBmax 125 V ... /L54706 UBmax

pro M compact® Z 2CDC021204F0006 2CSC400443F02012CSC400418F0201 S 200 M-Z With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 M-Z 0.5 NA 2CDS 271 103 R0158 59996 2 0.260 5 + 1 S 201 M-Z 1 NA 2CDS 271 103 R0218 60000 2 0.260 5 NA 1.6 S 201 M-Z 1.6 NA 2CDS 271 103 R0258 60003 3 0.260 5 2 S 201 M-Z 2 NA 2CDS 271 103 R0278 60005 7 0.260 5 3 S 201 M-Z 3 NA 2CDS 271 103 R0318 60007 1 0.260 5 4 S 201 M-Z 4 NA 2CDS 271 103 R0338 60010 1 0.260 5 6 S 201 M-Z 6 NA 2CDS 271 103 R0378 60012 5 0.260 5 8 S 201 M-Z 8 NA 2CDS 271 103 R0408 60015 6 0.260 5 10 S 201 M-Z 10 NA 2CDS 271 103 R0428 60017 0 0.260 5 16 S 201 M-Z 16 NA 2CDS 271 103 R0468 60019 4 0.260 5 20 S 201 M-Z 20 NA 2CDS 271 103 R0488 60021 7 0.260 5 25 S 201 M-Z 25 NA 2CDS 271 103 R0518 60024 8 0.260 5 32 S 201 M-Z 32 NA 2CDS 271 103 R0538 60026 2 0.260 5 40 S 201 M-Z 40 NA 2CDS 271 103 R0558 60028 6 0.260 5 50 S 201 M-Z 50 NA 2CDS 271 103 R0578 60030 9 0.320 5 63 S 201 M-Z 63 NA 2CDS 271 103 R0608 60032 3 0.320 5 3 0.5 S 203 M-Z 0.5 NA 2CDS 273 103 R0158 60147 4 0.520 1 + 1 S 203 M-Z 1 NA 2CDS 273 103 R0218 60148 1 0.520 1 NA 1.6 S 203 M-Z 1.6 NA 2CDS 273 103 R0258 60149 8 0.520 1 2 S 203 M-Z 2 NA 2CDS 273 103 R0278 60150 4 0.520 1 3 S 203 M-Z 3 NA 2CDS 273 103 R0318 60151 1 0.520 1 4 S 203 M-Z 4 NA 2CDS 273 103 R0338 60152 8 0.520 1 6 S 203 M-Z 6 NA 2CDS 273 103 R0378 60153 5 0.520 1 8 S 203 M-Z 8 NA 2CDS 273 103 R0408 60154 2 0.520 1 10 S 203 M-Z 10 NA 2CDS 273 103 R0428 60155 9 0.520 1 16 S 203 M-Z 16 NA 2CDS 273 103 R0468 60156 6 0.520 1 20 S 203 M-Z 20 NA 2CDS 273 103 R0488 60157 3 0.520 1 25 S 203 M-Z 25 NA 2CDS 273 103 R0518 60158 0 0.520 1 32 S 203 M-Z 32 NA 2CDS 273 103 R0538 60159 7 0.520 1 40 S 203 M-Z 40 NA 2CDS 273 103 R0558 60160 3 0.520 1 50 S 203 M-Z 50 NA 2CDS 273 103 R0578 60161 0 0.640 1 63 S 203 M-Z 63 NA 2CDS 273 103 R0608 60162 7 0.640 1 UBmax 72 V ... UBmax 125 V ... /L54706 4 0.5 S 204 M-Z 0.5 2CDS 274 001 R0158 60176 4 0.500 1 1 S 204 M-Z 1 2CDS 274 001 R0218 60181 0 0.500 1 1.6 S 204 M-Z 1.6 2CDS 274 001 R0258 60183 2 0.500 1 2 S 204 M-Z 2 2CDS 274 001 R0278 60185 6 0.500 1 3 S 204 M-Z 3 2CDS 274 001 R0318 60187 0 0.500 1 4 S 204 M-Z 4 2CDS 274 001 R0338 60190 0 0.500 1 6 S 204 M-Z 6 2CDS 274 001 R0378 60192 4 0.500 1 8 S 204 M-Z 8 2CDS 274 001 R0408 60195 5 0.500 1 10 S 204 M-Z 10 2CDS 274 001 R0428 60197 9 0.500 1 16 S 204 M-Z 16 2CDS 274 001 R0468 60199 3 0.500 1 20 S 204 M-Z 20 2CDS 274 001 R0488 65962 8 0.500 1 25 S 204 M-Z 25 2CDS 274 001 R0518 60203 7 0.500 1 32 S 204 M-Z 32 2CDS 274 001 R0538 60205 1 0.500 1 40 S 204 M-Z 40 2CDS 274 001 R0558 60207 5 0.500 1 50 S 204 M-Z 50 2CDS 274 001 R0578 60209 9 0.500 1 63 S 204 M-Z 63 2CDS 274 001 R0608 60211 2 0.500 1 /L54706 UBmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series M 10000

pro M compact® S 200 P-B B S 200 P-B characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. Applications: commercial and industrial. Standard: IEC/EN 60898 Icn=25 kA for 0.5 A≤In≤25 A Icn=15 kA for 32 A≤In≤63 A Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201 P-B 6 2CDS 281 001 R0065 589574 0.14 10 10 S 201 P-B 10 2CDS 281 001 R0105 589581 0.14 10 13 S 201 P-B 13 2CDS 281 001 R0135 589598 0.14 10 16 S 201 P-B 16 2CDS 281 001 R0165 589260 0.14 10 20 S 201 P-B 20 2CDS 281 001 R0205 589604 0.14 10 25 S 201 P-B 25 2CDS 281 001 R0255 589611 0.14 10 32 S 201 P-B 32 2CDS 281 001 R0325 589628 0.14 10 40 S 201 P-B 40 2CDS 281 001 R0405 589635 0.14 10 50 S 201 P-B 50 2CDS 281 001 R0505 589659 0.14 10 63 S 201 P-B 63 2CDS 281 001 R0635 589666 0.14 10 2 6 S 202 P-B 6 2CDS 282 001 R0065 589673 0.28 5 10 S 202 P-B 10 2CDS 282 001 R0105 589680 0.28 5 13 S 202 P-B 13 2CDS 282 001 R0135 589697 0.28 5 16 S 202 P-B 16 2CDS 282 001 R0165 589703 0.28 5 20 S 202 P-B 20 2CDS 282 001 R0205 589710 0.28 5 25 S 202 P-B 25 2CDS 282 001 R0255 589727 0.28 5

32 S 202 P-B 32 2CDS 282 001 R0325

589734 0.28 5 40 S 202 P-B 40 2CDS 282 001 R0405 589741 0.28 5 50 S 202 P-B 50 2CDS 282 001 R0505 589758 0.28 5 63 S 202 P-B 63 2CDS 282 001 R0635 589765 0.28 5 3 6 S 203 P-B 6 2CDS 283 001 R0065 589772 0.42 1 10 S 203 P-B 10 2CDS 283 001 R0105 589789 0.42 1 13 S 203 P-B 13 2CDS 283 001 R0135 589796 0.42 1 16 S 203 P-B 16 2CDS 283 001 R0165 589802 0.42 1 20 S 203 P-B 20 2CDS 283 001 R0205 589819 0.42 1 25 S 203 P-B 25 2CDS 283 001 R0255 589826 0.42 1 32 S 203 P-B 32 2CDS 283 001 R0325 589833 0.42 1 40 S 203 P-B 40 2CDS 283 001 R0405 589840 0.42 1 50 S 203 P-B 50 2CDS 283 001 R0505 589857 0.42 1 63 S 203 P-B 63 2CDS 283 001 R0635 589864 0.42 1 4 6 S 204 P-B 6 2CDS 284 001 R0065 589871 0.56 1 10 S 204 P-B 10 2CDS 284 001 R0105 589888 0.56 1 13 S 204 P-B 13 2CDS 284 001 R0135 589895 0.56 1 16 S 204 P-B 16 2CDS 284 001 R0165 589901 0.56 1 20 S 204 P-B 20 2CDS 284 001 R0205 589918 0.56 1 25 S 204 P-B 25 2CDS 284 001 R0255 589925 0.56 1 32 S 204 P-B 32 2CDS 284 001 R0325 589932 0.56 1 40 S 204 P-B 40 2CDS 284 001 R0405 589949 0.56 1 50 S 204 P-B 50 2CDS 284 001 R0505 589956 0.56 1 63 S 204 P-B 63 2CDS 284 001 R0635 589963 0.56 1 /L54706 UBmax 125 V ... with 2 poles connected in series UBmax 72 V ... UBmax 125 V ... /L54706 UBmax 125 V ... /L54706 Selection tables MCBs S 200 series P 25000 - 15000 2CSC400057F0201 2CSC400056F02012CSC400058F02012CSC400059F0201

pro M compact® S 200 P-B B With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S 201 P-B 6 NA 2CDS 281 103 R0065 589970 0.28 5 + 10 S 201 P-B 10 NA 2CDS 281 103 R0105 589987 0.28 5 NA 13 S 201 P-B 13 NA 2CDS 281 103 R0135 589994 0.28 5 16 S 201 P-B 16 NA 2CDS 281 103 R0165 590006 0.28 5 20 S 201 P-B 20 NA 2CDS 281 103 R0205 590013 0.28 5 25 S 201 P-B 25 NA 2CDS 281 103 R0255 590020 0.28 5 32 S 201 P-B 32 NA 2CDS 281 103 R0325 590037 0.28 5 40 S 201 P-B 40 NA 2CDS 281 103 R0405 590044 0.28 5 50 S 201 P-B 50 NA 2CDS 281 103 R0505 590051 0.28 5 63 S 201 P-B 63 NA 2CDS 281 103 R0635 590068 0.28 5 3 6 S 203 P-B 6 NA 2CDS 283 103 R0065 590075 0.56 1 + 10 S 203 P-B 10 NA 2CDS 283 103 R0105 590082 0.56 1 NA 13 S 203 P-B 13 NA 2CDS 283 103 R0135 590099 0.56 1 16 S 203 P-B 16 NA 2CDS 283 103 R0165 590105 0.56 1 20 S 203 P-B 20 NA 2CDS 283 103 R0205 590112 0.56 1 25 S 203 P-B 25 NA 2CDS 283 103 R0255 590129 0.56 1 32 S 203 P-B 32 NA 2CDS 283 103 R0325 590136 0.56 1 40 S 203 P-B 40 NA 2CDS 283 103 R0405 590143 0.56 1 50 S 203 P-B 50 NA 2CDS 283 103 R0505 590150 0.56 1 63 S 203 P-B 63 NA 2CDS 283 103 R0635 590167 0.56 1 UBmax 72 V ... UBmax 2CSC400062F0201 2CSC400060F0201

pro M compact® S 200 P-C C S 200 P-C characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. Applications: commercial and industrial. Standard: IEC/EN 60898 Icn=25 kA for 0.5 A≤In≤25 A Icn=15 kA for 32 A≤In≤63 A Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-C 0.5 2CDS 281 001 R0984 590174 0.14 10 1 S 201 P-C 1 2CDS 281 001 R0014 590181 0.14 10 1.6 S 201 P-C 1.6 2CDS 281 001 R0974 590198 0.14 10 2 S 201 P-C 2 2CDS 281 001 R0024 590204 0.14 10 3 S 201 P-C 3 2CDS 281 001 R0034 590211 0.14 10 4 S 201 P-C 4 2CDS 281 001 R0044 590228 0.14 10 6 S 201 P-C 6 2CDS 281 001 R0064 590235 0.14 10 8 S 201 P-C 8 2CDS 281 001 R0084 590242 0.14 10 10 S 201 P-C 10 2CDS 281 001 R0104 590259 0.14 10 13 S 201 P-C 13 2CDS 281 001 R0134 590266 0.14 10 16 S 201 P-C 16 2CDS 281 001 R0164 590273 0.14 10 20 S 201 P-C 20 2CDS 281 001 R0204 590280 0.14 10 25 S 201 P-C 25 2CDS 281 001 R0254 590297 0.14 10 32 S 201 P-C 32 2CDS 281 001 R0324 590303 0.14 10

40 S 201 P-C 40

2CDS 281 001 R0404 590310 0.14 10 50 S 201 P-C 50 2CDS 281 001 R0504 590327 0.14 10 63 S 201 P-C 63 2CDS 281 001 R0634 590334 0.14 10 2 0.5 S 202 P-C 0.5 2CDS 282 001 R0984 590341 0.28 5 1 S 202 P-C 1 2CDS 282 001 R0014 590358 0.28 5 1.6 S 202 P-C 1.6 2CDS 282 001 R0974 590365 0.28 5 2 S 202 P-C 2 2CDS 282 001 R0024 590372 0.28 5 3 S 202 P-C 3 2CDS 282 001 R0034 590389 0.28 5 4 S 202 P-C 4 2CDS 282 001 R0044 590396 0.28 5 6 S 202 P-C 6 2CDS 282 001 R0064 590402 0.28 5 8 S 202 P-C 8 2CDS 282 001 R0084 590419 0.28 5 10 S 202 P-C 10 2CDS 282 001 R0104 590426 0.28 5 13 S 202 P-C 13 2CDS 282 001 R0134 590433 0.28 5 16 S 202 P-C 16 2CDS 282 001 R0164 590440 0.28 5 20 S 202 P-C 20 2CDS 282 001 R0204 590457 0.28 5 25 S 202 P-C 25 2CDS 282 001 R0254 590464 0.28 5 32 S 202 P-C 32 2CDS 282 001 R0324 590471 0.28 5 40 S 202 P-C 40 2CDS 282 001 R0404 590488 0.28 5 50 S 202 P-C 50 2CDS 282 001 R0504 590495 0.28 5 63 S 202 P-C 63 2CDS 282 001 R0634 590501 0.28 5 3 0.5 S 203 P-C 0.5 2CDS 283 001 R0984 590518 0.42 1 1 S 203 P-C 1 2CDS 283 001 R0014 590525 0.42 1 1.6 S 203 P-C 1.6 2CDS 283 001 R0974 590532 0.42 1 2 S 203 P-C 2 2CDS 283 001 R0024 590549 0.42 1 3 S 203 P-C 3 2CDS 283 001 R0034 590556 0.42 1 4 S 203 P-C 4 2CDS 283 001 R0044 590563 0.42 1 6 S 203 P-C 6 2CDS 283 001 R0064 590570 0.42 1 8 S 203 P-C 8 2CDS 283 001 R0084 590587 0.42 1 10 S 203 P-C 10 2CDS 283 001 R0104 590594 0.42 1 13 S 203 P-C 13 2CDS 283 001 R0134 590600 0.42 1 16 S 203 P-C 16 2CDS 283 001 R0164 590617 0.42 1 20 S 203 P-C 20 2CDS 283 001 R0204 590624 0.42 1 25 S 203 P-C 25 2CDS 283 001 R0254 590631 0.42 1 32 S 203 P-C 32 2CDS 283 001 R0324 590648 0.42 1 40 S 203 P-C 40 2CDS 283 001 R0404 590655 0.42 1 50 S 203 P-C50 2CDS 283 001 R0504 590662 0.42 1 63 S 203 P-C63 2CDS 283 001 R0634 590679 0.42 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax 2CSC400057F0201 2CSC400056F02012CSC400058F0201

pro M compact® S 200 P-C C With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-C 0.5 NA 2CDS 281 103 R0984 590853 0.28 5 + 1 S 201 P-C 1 NA 2CDS 281 103 R0014 590860 0.28 5 NA 1.6 S 201 P-C 1.6 NA 2CDS 281 103 R0974 590877 0.28 5 2 S 201 P-C 2 NA 2CDS 281 103 R0024 590884 0.28 5 3 S 201 P-C 3 NA 2CDS 281 103 R0034 590891 0.28 5 4 S 201 P-C 4 NA 2CDS 281 103 R0044 590907 0.28 5 6 S 201 P-C 6 NA 2CDS 281 103 R0064 590914 0.28 5 8 S 201 P-C 8 NA 2CDS 281 103 R0084 590921 0.28 5 10 S 201 P-C 10 NA 2CDS 281 103 R0104 590938 0.28 5 13 S 201 P-C 13 NA 2CDS 281 103 R0134 590945 0.28 5 16 S 201 P-C 16 NA 2CDS 281 103 R0164 590952 0.28 5 20 S 201 P-C 20 NA 2CDS 281 103 R0204 590969 0.28 5 25 S 201 P-C 25 NA 2CDS 281 103 R0254 590976 0.28 5 32 S 201 P-C 32 NA 2CDS 281 103 R0324 590983 0.28 5 S 201 P-C 40 NA 2CDS 281 103 R0404 590990 0.28 5 50 S 201 P-C 50 NA 2CDS 281 103 R0504 591003 0.28 5 63 S 201 P-C 63 NA 2CDS 281 103 R0634 591010 0.28 5 3 0.5 S 203 P-C 0.5 NA 2CDS 283 103 R0984 591027 0.56 1 + 1 S 203 P-C 1 NA 2CDS 283 103 R0014 591034 0.56 1 NA 1.6 S 203 P-C 1.6 NA 2CDS 283 103 R0974 591041 0.56 1 2 S 203 P-C 2 NA 2CDS 283 103 R0024 591058 0.56 1 3 S 203 P-C 3 NA 2CDS 283 103 R0034 591065 0.56 1 4 S 203 P-C 4 NA 2CDS 283 103 R0044 591072 0.56 1 6 S 203 P-C 6 NA 2CDS 283 103 R0064 591089 0.56 1 8 S 203 P-C 8 NA 2CDS 283 103 R0084 591096 0.56 1 10 S 203 P-C 10 NA 2CDS 283 103 R0104 591102 0.56 1 13 S 203 P-C 13 NA 2CDS 283 103 R0134 591119 0.56 1 16 S 203 P-C 16 NA 2CDS 283 103 R0164 591126 0.56 1 20 S 203 P-C 20 NA 2CDS 283 103 R0204 591133 0.56 1 25 S 203 P-C 25 NA 2CDS 283 103 R0254 591140 0.56 1 32 S 203 P-C 32 NA 2CDS 283 103 R0324 591157 0.56 1 40 S 203 P-C 40 NA 2CDS 283 103 R0404 591164 0.56 1 50 S 203 P-C 50 NA 2CDS 283 103 R0504 591171 0.56 1 63 S 203 P-C 63 NA 2CDS 283 103 R0634 591188 0.56 1 UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204 P-C 0.5 2CDS 284 001 R0984 590686 0.56 1 1 S 204 P-C 1 2CDS 284 001 R0014 590693 0.56 1 1.6 S 204 P-C 1.6 2CDS 284 001 R0974 590709 0.56 1 2 S 204 P-C 2 2CDS 284 001 R0024 590716 0.56 1 3 S 204 P-C 3 2CDS 284 001 R0034 590723 0.56 1 4 S 204 P-C 4 2CDS 284 001 R0044 590730 0.56 1 6 S 204 P-C 6 2CDS 284 001 R0064 590747 0.56 1 8 S 204 P-C 8 2CDS 284 001 R0084 590754 0.56 1 10 S 204 P-C 10 2CDS 284 001 R0104 590761 0.56 1 13 S 204 P-C 13 2CDS 284 001 R0134 590778 0.56 1 16 S 204 P-C 16 2CDS 284 001 R0164 590785 0.56 1 20 S 204 P-C 20 2CDS 284 001 R0204 590792 0.56 1 25 S 204 P-C 25 2CDS 284 001 R0254 590808 0.56 1 32 S 204 P-C 32 2CDS 284 001 R0324 590815 0.56 1 40 S 204 P-C 40 2CDS 284 001 R0404 590822 0.56 1 50 S 204 P-C 50 2CDS 284 001 R0504 590839 0.56 1 63 S 204 P-C 63 2CDS 284 001 R0634 590846 0.56 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series P 25000 - 15000 2CSC400060F0201 2CSC400059F02012CSC400062F0201

pro M compact® S 200 P-D S 200 P-D characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for circuits which supply loads with high inrush current at the circuit closing (LV/LV transformers, breakdown lamps). Applications: commercial and industrial. Standard: IEC/EN 60898 Icn=25 kA for 0.5 A≤In≤25 A Icn=15 kA for 32 A≤In≤63 A Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-D 0.5 2CDS 281 001 R0981 591195 0.14 10 1 S 201 P-D 1 2CDS 281 001 R0011 591201 0.14 10 1.6 S 201 P-D 1.6 2CDS 281 001 R0971 591218 0.14 10 2 S 201 P-D 2 2CDS 281 001 R0021 591225 0.14 10 3 S 201 P-D 3 2CDS 281 001 R0031 591232 0.14 10 4 S 201 P-D 4 2CDS 281 001 R0041 591249 0.14 10 6 S 201 P-D 6 2CDS 281 001 R0061 591256 0.14 10 8 S 201 P-D 8 2CDS 281 001 R0081 591263 0.14 10 10 S 201 P-D 10 2CDS 281 001 R0101 591270 0.14 10 13 S 201 P-D 13 2CDS 281 001 R0131 591287 0.14 10 16 S 201 P-D 16 2CDS 281 001 R0161 591294 0.14 10 20 S 201 P-D 20 2CDS 281 001 R0201 591300 0.14 10 25 S 201 P-D 25 2CDS 281 001 R0251 591317 0.14 10 32 S 201 P-D 32 2CDS 281 001 R0321 591324 0.14 10

40 S 201 P-D 40

2CDS 281 001 R0401 591331 0.14 10 50 S 201 P-D 50 2CDS 281 001 R0501 591348 0.14 10 63 S 201 P-D 63 2CDS 281 001 R0631 591355 0.14 10 2 0.5 S 202 P-D 0.5 2CDS 282 001 R0981 591362 0.28 5 1 S 202 P-D 1 2CDS 282 001 R0011 591379 0.28 5 1.6 S 202 P-D 1.6 2CDS 282 001 R0971 591386 0.28 5 2 S 202 P-D 2 2CDS 282 001 R0021 591393 0.28 5 3 S 202 P-D 3 2CDS 282 001 R0031 591409 0.28 5 4 S 202 P-D 4 2CDS 282 001 R0041 591416 0.28 5 6 S 202 P-D 6 2CDS 282 001 R0061 591423 0.28 5 8 S 202 P-D 8 2CDS 282 001 R0081 591430 0.28 5 10 S 202 P-D 10 2CDS 282 001 R0101 591447 0.28 5 13 S 202 P-D 13 2CDS 282 001 R0131 591454 0.28 5 16 S 202 P-D 16 2CDS 282 001 R0161 591461 0.28 5 20 S 202 P-D 20 2CDS 282 001 R0201 591478 0.28 5 25 S 202 P-D 25 2CDS 282 001 R0251 591485 0.28 5 32 S 202 P-D 32 2CDS 282 001 R0321 591492 0.28 5 40 S 202 P-D 40 2CDS 282 001 R0401 591508 0.28 5 50 S 202 P-D 50 2CDS 282 001 R0501 591515 0.28 5 63 S 202 P-D 63 2CDS 282 001 R0631 591522 0.28 5 3 0.5 S 203 P-D 0.5 2CDS 283 001 R0981 591539 0.42 1 1 S 203 P-D 1 2CDS 283 001 R0011 591546 0.42 1 1.6 S 203 P-D 1.6 2CDS 283 001 R0971 591553 0.42 1 2 S 203 P-D 2 2CDS 283 001 R0021 591560 0.42 1 3 S 203 P-D 3 2CDS 283 001 R0031 591577 0.42 1 4 S 203 P-D 4 2CDS 283 001 R0041 591584 0.42 1 6 S 203 P-D 6 2CDS 283 001 R0061 591591 0.42 1 8 S 203 P-D 8 2CDS 283 001 R0081 591607 0.42 1 10 S 203 P-D 10 2CDS 283 001 R0101 591614 0.42 1 13 S 203 P-D 13 2CDS 283 001 R0131 591621 0.42 1 16 S 203 P-D 16 2CDS 283 001 R0161 591638 0.42 1 20 S 203 P-D 20 2CDS 283 001 R0201 591645 0.42 1 25 S 203 P-D 25 2CDS 283 001 R0251 591652 0.42 1 32 S 203 P-D 32 2CDS 283 001 R0321 591669 0.42 1 40 S 203 P-D 40 2CDS 283 001 R0401 591676 0.42 1 50 S 203 P-D50 2CDS 283 001 R0501 591683 0.42 1 63 S 203 P-D63 2CDS 283 001 R0631 591690 0.42 1 UBmax 72 V ... UBmax 125 V ... /L54709 UBmax D 2CSC400057F0201 2CSC400056F02012CSC400058F0201

pro M compact® S 200 P-D D With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-D 0.5 NA 2CDS 281 103 R0981 591874 0.28 5 + 1 S 201 P-D 1 NA 2CDS 281 103 R0011 591881 0.28 5 NA 1.6 S 201 P-D 1.6 NA 2CDS 281 103 R0971 591898 0.28 5 2 S 201 P-D 2 NA 2CDS 281 103 R0021 591904 0.28 5 3 S 201 P-D 3 NA 2CDS 281 103 R0031 591911 0.28 5 4 S 201 P-D 4 NA 2CDS 281 103 R0041 591928 0.28 5 6 S 201 P-D 6 NA 2CDS 281 103 R0061 591935 0.28 5 8 S 201 P-D 8 NA 2CDS 281 103 R0081 591942 0.28 5 10 S 201 P-D 10 NA 2CDS 281 103 R0101 591959 0.28 5 13 S 201 P-D 13 NA 2CDS 281 103 R0131 591966 0.28 5 16 S 201 P-D 16 NA 2CDS 281 103 R0161 591973 0.28 5 20 S 201 P-D 20 NA 2CDS 281 103 R0201 591980 0.28 5 25 S 201 P-D 25 NA 2CDS 281 103 R0251 591997 0.28 5 32 S 201 P-D 32 NA 2CDS 281 103 R0321 592000 0.28 5 S 201 P-D 40 NA 2CDS 281 103 R0401 592017 0.28 5 50 S 201 P-D 50 NA 2CDS 281 103 R0501 592024 0.28 5 63 S 201 P-D 63 NA 2CDS 281 103 R0631 592031 0.28 5 3 0.5 S 203 P-D 0.5 NA 2CDS 283 103 R0981 592048 0.56 1 + 1 S 203 P-D 1 NA 2CDS 283 103 R0011 592055 0.56 1 NA 1.6 S 203 P-D 1.6 NA 2CDS 283 103 R0971 592062 0.56 1 2 S 203 P-D 2 NA 2CDS 283 103 R0021 592079 0.56 1 3 S 203 P-D 3 NA 2CDS 283 103 R0031 592086 0.56 1 4 S 203 P-D 4 NA 2CDS 283 103 R0041 592093 0.56 1 6 S 203 P-D 6 NA 2CDS 283 103 R0061 592109 0.56 1 8 S 203 P-D 8 NA 2CDS 283 103 R0081 592116 0.56 1 10 S 203 P-D 10 NA 2CDS 283 103 R0101 592123 0.56 1 13 S 203 P-D 13 NA 2CDS 283 103 R0131 592130 0.56 1 16 S 203 P-D 16 NA 2CDS 283 103 R0161 592147 0.56 1 20 S 203 P-D 20 NA 2CDS 283 103 R0201 592154 0.56 1 25 S 203 P-D 25 NA 2CDS 283 103 R0251 592161 0.56 1 32 S 203 P-D 32 NA 2CDS 283 103 R0321 592178 0.56 1 40 S 203 P-D 40 NA 2CDS 283 103 R0401 592185 0.56 1 50 S 203 P-D 50 NA 2CDS 283 103 R0501 592192 0.56 1 63 S 203 P-D 63 NA 2CDS 283 103 R0631 592208 0.56 1 UBmax 72 V ... UBmax 125 V ... /L54709 4 0.5 S 204 P-D 0.5 2CDS 284 001 R0981 591706 0.56 1 1 S 204 P-D 1 2CDS 284 001 R0011 591713 0.56 1 1.6 S 204 P-D 1.6 2CDS 284 001 R0971 591720 0.56 1 2 S 204 P-D 2 2CDS 284 001 R0021 591737 0.56 1 3 S 204 P-D 3 2CDS 284 001 R0031 591744 0.56 1 4 S 204 P-D 4 2CDS 284 001 R0041 591751 0.56 1 6 S 204 P-D 6 2CDS 284 001 R0061 591768 0.56 1 8 S 204 P-D 8 2CDS 284 001 R0081 591775 0.56 1 10 S 204 P-D 10 2CDS 284 001 R0101 591782 0.56 1 13 S 204 P-D 13 2CDS 284 001 R0131 591799 0.56 1 16 S 204 P-D 16 2CDS 284 001 R0161 591805 0.56 1 20 S 204 P-D 20 2CDS 284 001 R0201 591812 0.56 1 25 S 204 P-D 25 2CDS 284 001 R0251 591829 0.56 1 32 S 204 P-D 32 2CDS 284 001 R0321 591836 0.56 1 40 S 204 P-D 40 2CDS 284 001 R0401 591843 0.56 1 50 S 204 P-D 50 2CDS 284 001 R0501 591850 0.56 1 63 S 204 P-D 63 2CDS 284 001 R0631 591867 0.56 1 /L54706 suitable for flow-type heaters 12 kW /L54708 suitable for flow-type heaters 21, 24 and 27 kW /L54707 suitable for flow-type heaters 18 kW /L54709 U Bmax 125 V ... with 2 poles connected in series Selection tables MCBs S 200 series P 25000 - 15000 2CSC400060F0201 2CSC400059F02012CSC400062F0201

pro M compact® S 200 P-K K Selection tables MCBs S 200 series P 25000 - 15000 2CSC400004F0201 2CSC400002F02012CSC400128F0201 UBmax 72 V ... UBmax S 200 P-K (power) characteristic Function: protection and control of the circuits like motors, transformers and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=25 kA for 0.5 A≤In≤25 A; Icu=15 kA for 32 A≤In≤63 A (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.2 S 201 P-K 0.2 2CDS 281 001 R0087 592215 0.14 10 0.3 S 201 P-K 0.3 2CDS 281 001 R0117 592222 0.14 10 0.5 S 201 P-K 0.5 2CDS 281 001 R0157 592239 0.14 10 0.75 S 201 P-K 0.75 2CDS 281 001 R0187 592246 0.14 10 1 S 201 P-K 1 2CDS 281 001 R0217 592253 0.14 10 1.6 S 201 P-K 1.6 2CDS 281 001 R0257 592260 0.14 10 2 S 201 P-K 2 2CDS 281 001 R0277 592277 0.14 10 3 S 201 P-K 3 2CDS 281 001 R0317 592284 0.14 10 4 S 201 P-K 4 2CDS 281 001 R0337 592291 0.14 10 6 S 201 P-K 6 2CDS 281 001 R0377 592307 0.14 10 8 S 201 P-K 8 2CDS 281 001 R0407 592314 0.14 10 10 S 201 P-K 10 2CDS 281 001 R0427 592321 0.14 10 13 S 201 P-K 13 2CDS 281 001 R0447 592338 0.14 10 16 S 201 P-K 16 2CDS 281 001 R0467 592345 0.14 10 S 201 P-K 20 2CDS 281 001 R0487 592352 0.14 10 25 S 201 P-K 25 2CDS 281 001 R0517 592369 0.14 10 32 S 201 P-K 32 2CDS 281 001 R0537 592376 0.14 10 40 S 201 P-K 40 2CDS 281 001 R0557 592383 0.14 10 50 S 201 P-K 50 2CDS 281 001 R0577 592390 0.14 10 63 S 201 P-K 63 2CDS 281 001 R0607 592406 0.14 10 2 0.2 S 202 P-K 0.2 2CDS 282 001 R0087 592413 0.28 5 0.3 S 202 P-K 0.3 2CDS 282 001 R0117 592420 0.28 5 0.5 S 202 P-K 0.5 2CDS 282 001 R0157 592437 0.28 5 0.75 S 202 P-K 0.75 2CDS 282 001 R0187 592444 0.28 5 1 S 202 P-K 1 2CDS 282 001 R0217 592451 0.28 5 1.6 S 202 P-K 1.6 2CDS 282 001 R0257 592468 0.28 5 2 S 202 P-K 2 2CDS 282 001 R0277 592475 0.28 5 3 S 202 P-K 3 2CDS 282 001 R0317 592482 0.28 5 4 S 202 P-K 4 2CDS 282 001 R0337 592499 0.28 5 6 S 202 P-K 6 2CDS 282 001 R0377 592505 0.28 5 8 S 202 P-K 8 2CDS 282 001 R0407 592512 0.28 5 10 S 202 P-K 10 2CDS 282 001 R0427 592529 0.28 5 13 S 202 P-K 13 2CDS 282 001 R0447 592536 0.28 5 16 S 202 P-K 16 2CDS 282 001 R0467 592543 0.28 5 20 S 202 P-K 20 2CDS 282 001 R0487 592550 0.28 5 25 S 202 P-K 25 2CDS 282 001 R0517 592567 0.28 5 32 S 202 P-K 32 2CDS 282 001 R0537 592574 0.28 5 40 S 202 P-K 40 2CDS 282 001 R0557 592581 0.28 5 50 S 202 P-K 50 2CDS 282 001 R0577 592598 0.28 5 63 S 202 P-K 63 2CDS 282 001 R0607 592604 0.28 5 3 0.2 S 203 P-K 0.2 2CDS 283 001 R0087 592611 0.42 1 0.3 S 203 P-K 0.3 2CDS 283 001 R0117 592628 0.42 1 0.5 S 203 P-K 0.5 2CDS 283 001 R0157 592635 0.42 1 0.75 S 203 P-K 0.75 2CDS 283 001 R0187 592642 0.42 1 1 S 203 P-K 1 2CDS 283 001 R0217 592659 0.42 1 1.6 S 203 P-K 1.6 2CDS 283 001 R0257 592666 0.42 1 2 S 203 P-K 2 2CDS 283 001 R0277 592673 0.42 1 3 S 203 P-K 3 2CDS 283 001 R0317 592680 0.42 1 4 S 203 P-K 4 2CDS 283 001 R0337 592697 0.42 1 6 S 203 P-K 6 2CDS 283 001 R0377 592703 0.42 1 8 S 203 P-K 8 2CDS 283 001 R0407 592710 0.42 1 10 S 203 P-K 10 2CDS 283 001 R0427 592727 0.42 1 13 S 203 P-K 13 2CDS 283 001 R0447 592734 0.42 1 16 S 203 P-K 16 2CDS 283 001 R0467 592741 0.42 1 20 S 203 P-K 20 2CDS 283 001 R0487 592758 0.42 1 UBmax 125 V ... /L54706

pro M compact® K With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.2 S 201 P-K 0.2 NA 2CDS 281 103 R0087 593014 0.28 5 + 0.3 S 201 P-K 0.3 NA 2CDS 281 103 R0117 593021 0.28 5 NA 0.5 S 201 P-K 0.5 NA 2CDS 281 103 R0157 593038 0.28 5 0.75 S 201 P-K 0.75 NA 2CDS 281 103 R0187 593045 0.28 5 1 S 201 P-K 1 NA 2CDS 281 103 R0217 593052 0.28 5 1.6 S 201 P-K 1.6 NA 2CDS 281 103 R0257 593069 0.28 5 2 S 201 P-K 2 NA 2CDS 281 103 R0277 593076 0.28 5 3 S 201 P-K 3 NA 2CDS 281 103 R0317 593083 0.28 5 4 S 201 P-K 4 NA 2CDS 281 103 R0337 593090 0.28 5 6 S 201 P-K 6 NA 2CDS 281 103 R0377 593106 0.28 5 8 S 201 P-K 8 NA 2CDS 281 103 R0407 593113 0.28 5 10 S 201 P-K 10 NA 2CDS 281 103 R0427 593120 0.28 5 13 S 201 P-K 13 NA 2CDS 281 103 R0447 593137 0.28 5 16 S 201 P-K 16 NA 2CDS 281 103 R0467 593144 0.28 5 S 201 P-K 20 NA 2CDS 281 103 R0487 593151 0.28 5 25 S 201 P-K 25 NA 2CDS 281 103 R0517 593168 0.28 5 32 S 201 P-K 32 NA 2CDS 281 103 R0537 593175 0.28 5 40 S 201 P-K 40 NA 2CDS 281 103 R0557 593182 0.28 5 50 S 201 P-K 50 NA 2CDS 281 103 R0577 593199 0.28 5 63 S 201 P-K 63 NA 2CDS 281 103 R0607 593205 0.28 5 3 0.2 S 203 P-K 0.2 NA 2CDS 283 103 R0087 593212 0.56 2 + 0.3 S 203 P-K 0.3 NA 2CDS 283 103 R0117 593229 0.56 2 NA 0.5 S 203 P-K 0.5 NA 2CDS 283 103 R0157 593236 0.56 2 0.75 S 203 P-K 0.75 NA 2CDS 283 103 R0187 593243 0.56 2 1 S 203 P-K 1 NA 2CDS 283 103 R0217 593250 0.56 2 1.6 S 203 P-K 1.6 NA 2CDS 283 103 R0257 593267 0.56 2 2 S 203 P-K 2 NA 2CDS 283 103 R0277 593274 0.56 2 3 S 203 P-K 3 NA 2CDS 283 103 R0317 593281 0.56 2 4 S 203 P-K 4 NA 2CDS 283 103 R0337 593298 0.56 2 6 S 203 P-K 6 NA 2CDS 283 103 R0377 593304 0.56 2 8 S 203 P-K 8 NA 2CDS 283 103 R0407 593311 0.56 2 10 S 203 P-K 10 NA 2CDS 283 103 R0427 593328 0.56 2 13 S 203 P-K 13 NA 2CDS 283 103 R0447 593335 0.56 2 16 S 203 P-K 16 NA 2CDS 283 103 R0467 593342 0.56 2 20 S 203 P-K 20 NA 2CDS 283 103 R0487 593359 0.56 2 25 S 203 P-K 25 NA 2CDS 283 103 R0517 593366 0.56 2 32 S 203 P-K 32 NA 2CDS 283 103 R0537 593373 0.56 2 40 S 203 P-K 40 NA 2CDS 283 103 R0557 593380 0.56 2 50 S 203 P-K 50 NA 2CDS 283 103 R0577 593397 0.56 2 63 S 203 P-K 63 NA 2CDS 283 103 R0607 593403 0.56 2 UBmax 60 V ... UBmax 72 V ... UBmax 25 S 203 P-K 25 2CDS 283 001 R0517 592765 0.42 1 32 S 203 P-K 32 2CDS 283 001 R0537 592772 0.42 1 40 S 203 P-K 40 2CDS 283 001 R0557 592789 0.42 1 50 S 203 P-K 50 2CDS 283 001 R0577 592796 0.42 1 63 S 203 P-K 63 2CDS 283 001 R0607 592802 0.42 1 4 0.2 S 204 P-K 0.2 2CDS 284 001 R0087 592819 0.56 1 0.3 S 204 P-K 0.3 2CDS 284 001 R0117 592826 0.56 1 0.5 S 204 P-K 0.5 2CDS 284 001 R0157 592833 0.56 1 0.75 S 204 P-K 0.75 2CDS 284 001 R0187 592840 0.56 1 1 S 204 P-K 1 2CDS 284 001 R0217 592857 0.56 1 1.6 S 204 P-K 1.6 2CDS 284 001 R0257 592864 0.56 1 2 S 204 P-K 2 2CDS 284 001 R0277 592871 0.56 1 3 S 204 P-K 3 2CDS 284 001 R0317 592888 0.56 1 4 S 204 P-K 4 2CDS 284 001 R0337 592895 0.56 1 6 S 204 P-K 6 2CDS 284 001 R0377 592901 0.56 1 8 S 204 P-K 8 2CDS 284 001 R0407 592918 0.56 1 10 S 204 P-K 10 2CDS 284 001 R0427 592925 0.56 1 13 S 204 P-K 13 2CDS 284 001 R0447 592932 0.56 1 16 S 204 P-K 16 2CDS 284 001 R0467 592949 0.56 1 20 S 204 P-K 20 2CDS 284 001 R0487 592956 0.56 1 25 S 204 P-K 25 2CDS 284 001 R0517 592963 0.56 1 32 S 204 P-K 32 2CDS 284 001 R0537 592970 0.56 1 40 S 204 P-K 40 2CDS 284 001 R0557 592987 0.56 1 50 S 204 P-K 50 2CDS 284 001 R0577 592994 0.56 1 63 S 204 P-K 63 2CDS 284 001 R0607 593007 0.56 1 /L54706 U Bmax 125 V ... with 2 poles connected in series S 200 P-KSelection tables MCBs S 200 series P 25000 - 15000 2CSC400003F0201 2CSC400132F02012CSC400132F0201

pro M compact® S 200 P-Z Z S 200 P-Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icu=25 kA for 0.5 A≤In≤25 A; Icu=15 kA for 32 A≤In≤63 A (acc. to VDE 0660 Part 101) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-Z 0.5 2CDS 281 001 R0158 593410 0.14 10 1 S 201 P-Z 1 2CDS 281 001 R0218 593427 0.14 10 1.6 S 201 P-Z 1.6 2CDS 281 001 R0258 593434 0.14 10 2 S 201 P-Z 2 2CDS 281 001 R0278 593441 0.14 10 3 S 201 P-Z 3 2CDS 281 001 R0318 593458 0.14 10 4 S 201 P-Z 4 2CDS 281 001 R0338 593465 0.14 10 6 S 201 P-Z 6 2CDS 281 001 R0378 593472 0.14 10 8 S 201 P-Z 8 2CDS 281 001 R0408 593489 0.14 10 10 S 201 P-Z 10 2CDS 281 001 R0428 593496 0.14 10 16 S 201 P-Z 16 2CDS 281 001 R0468 593502 0.14 10 20 S 201 P-Z 20 2CDS 281 001 R0488 593519 0.14 10 25 S 201 P-Z 25 2CDS 281 001 R0518 593526 0.14 10 32 S 201 P-Z 32 2CDS 281 001 R0538 593533 0.14 10 40 S 201 P-Z 40 2CDS 281 001 R0558 593540 0.14 10 S 201 P-Z 50 2CDS 281 001 R0578 593557 0.14 10 63 S 201 P-Z 63 2CDS 281 001 R0608 593564 0.14 10 2 0.5 S 202 P-Z 0.5 2CDS 282 001 R0158 593571 0.28 5 1 S 202 P-Z 1 2CDS 282 001 R0218 593588 0.28 5 1.6 S 202 P-Z 1.6 2CDS 282 001 R0258 593595 0.28 5 2 S 202 P-Z 2 2CDS 282 001 R0278 593601 0.28 5 3 S 202 P-Z 3 2CDS 282 001 R0318 593618 0.28 5 4 S 202 P-Z 4 2CDS 282 001 R0338 593625 0.28 5 6 S 202 P-Z 6 2CDS 282 001 R0378 593632 0.28 5 8 S 202 P-Z 8 2CDS 282 001 R0408 593649 0.28 5 10 S 202 P-Z 10 2CDS 282 001 R0428 593656 0.28 5 16 S 202 P-Z 16 2CDS 282 001 R0468 593663 0.28 5 20 S 202 P-Z 20 2CDS 282 001 R0488 593670 0.28 5 25 S 202 P-Z 25 2CDS 282 001 R0518 593687 0.28 5 32 S 202 P-Z 32 2CDS 282 001 R0538 593694 0.28 5 40 S 202 P-Z 40 2CDS 282 001 R0558 593700 0.28 5 50 S 202 P-Z 50 2CDS 282 001 R0578 593717 0.28 5 63 S 202 P-Z 63 2CDS 282 001 R0608 593724 0.28 5 3 0.5 S 203 P-Z 0.5 2CDS 283 001 R0158 593731 0.42 1 1 S 203 P-Z 1 2CDS 283 001 R0218 593748 0.42 1 1.6 S 203 P-Z 1.6 2CDS 283 001 R0258 593755 0.42 1 2 S 203 P-Z 2 2CDS 283 001 R0278 593762 0.42 1 3 S 203 P-Z 3 2CDS 283 001 R0318 593779 0.42 1 4 S 203 P-Z 4 2CDS 283 001 R0338 593786 0.42 1 6 S 203 P-Z 6 2CDS 283 001 R0378 593793 0.42 1 8 S 203 P-Z 8 2CDS 283 001 R0408 593809 0.42 1 10 S 203 P-Z 10 2CDS 283 001 R0428 593816 0.42 1 16 S 203 P-Z 16 2CDS 283 001 R0468 593823 0.42 1 20 S 203 P-Z 20 2CDS 283 001 R0488 593830 0.42 1 25 S 203 P-Z 25 2CDS 283 001 R0518 593847 0.42 1 32 S 203 P-Z 32 2CDS 283 001 R0538 593854 0.42 1 40 S 203 P-Z 40 2CDS 283 001 R0558 593861 0.42 1 50 S 203 P-Z 50 2CDS 283 001 R0578 593878 0.42 1 63 S 203 P-Z 63 2CDS 283 001 R0608 593885 0.42 1 UBmax 72 V ... UBmax 125 V ... /L54706 UBmax 2CSC400004F0201 2CSC400002F02012CSC400128F0201

pro M compact® S 200 P-Z Z With disconnecting neutral NA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 P-Z 0.5 NA 2CDS 281 103 R0158 594059 0.28 5 + 1 S 201 P-Z 1 NA 2CDS 281 103 R0218 594066 0.28 5 NA 1.6 S 201 P-Z 1.6 NA 2CDS 281 103 R0258 594073 0.28 5 2 S 201 P-Z 2 NA 2CDS 281 103 R0278 594080 0.28 5 3 S 201 P-Z 3 NA 2CDS 281 103 R0318 594097 0.28 5 4 S 201 P-Z 4 NA 2CDS 281 103 R0338 594103 0.28 5 6 S 201 P-Z 6 NA 2CDS 281 103 R0378 594110 0.28 5 8 S 201 P-Z 8 NA 2CDS 281 103 R0408 594127 0.28 5 10 S 201 P-Z 10 NA 2CDS 281 103 R0428 594134 0.28 5 16 S 201 P-Z 16 NA 2CDS 281 103 R0468 594141 0.28 5 20 S 201 P-Z 20 NA 2CDS 281 103 R0488 594158 0.28 5 25 S 201 P-Z 25 NA 2CDS 281 103 R0518 594165 0.28 5 32 S 201 P-Z 32 NA 2CDS 281 103 R0538 594172 0.28 5 40 S 201 P-Z 40 NA 2CDS 281 103 R0558 594189 0.28 5 S 201 P-Z 50 NA 2CDS 281 103 R0578 594196 0.28 5 63 S 201 P-Z 63 NA 2CDS 281 103 R0608 594202 0.28 5 3 0.5 S 203 P-Z 0.5 NA 2CDS 283 103 R0158 594219 0.56 1 + 1 S 203 P-Z 1 NA 2CDS 283 103 R0218 594226 0.56 1 NA 1.6 S 203 P-Z 1.6 NA 2CDS 283 103 R0258 594233 0.56 1 2 S 203 P-Z 2 NA 2CDS 283 103 R0278 594240 0.56 1 3 S 203 P-Z 3 NA 2CDS 283 103 R0318 594257 0.56 1 4 S 203 P-Z 4 NA 2CDS 283 103 R0338 594264 0.56 1 6 S 203 P-Z 6 NA 2CDS 283 103 R0378 594271 0.56 1 8 S 203 P-Z 8 NA 2CDS 283 103 R0408 594288 0.56 1 10 S 203 P-Z 10 NA 2CDS 283 103 R0428 594295 0.56 1 16 S 203 P-Z 16 NA 2CDS 283 103 R0468 594301 0.56 1 20 S 203 P-Z 20 NA 2CDS 283 103 R0488 594318 0.56 1 25 S 203 P-Z 25 NA 2CDS 283 103 R0518 594325 0.56 1 32 S 203 P-Z 32 NA 2CDS 283 103 R0538 594332 0.56 1 40 S 203 P-Z 40 NA 2CDS 283 103 R0558 594349 0.56 1 50 S 203 P-Z 50 NA 2CDS 283 103 R0578 594356 0.56 1 63 S 203 P-Z 63 NA 2CDS 283 103 R0608 594363 0.56 1 UBmax 72 V ... UBmax 4 0.5 S 204 P-Z 0.5 2CDS 284 001 R0158 593892 0.56 1 1 S 204 P-Z 1 2CDS 284 001 R0218 593908 0.56 1 1.6 S 204 P-Z 1.6 2CDS 284 001 R0258 593915 0.56 1 2 S 204 P-Z 2 2CDS 284 001 R0278 593922 0.56 1 3 S 204 P-Z 3 2CDS 284 001 R0318 593939 0.56 1 4 S 204 P-Z 4 2CDS 284 001 R0338 593946 0.56 1 6 S 204 P-Z 6 2CDS 284 001 R0378 593953 0.56 1 8 S 204 P-Z 8 2CDS 284 001 R0408 593960 0.56 1 10 S 204 P-Z 10 2CDS 284 001 R0428 593977 0.56 1 16 S 204 P-Z 16 2CDS 284 001 R0468 593984 0.56 1 20 S 204 P-Z 20 2CDS 284 001 R0488 593991 0.56 1 25 S 204 P-Z 25 2CDS 284 001 R0518 594004 0.56 1 32 S 204 P-Z 32 2CDS 284 001 R0538 594011 0.56 1 40 S 204 P-Z 40 2CDS 284 001 R0558 594028 0.56 1 50 S 204 P-Z 50 2CDS 284 001 R0578 594035 0.56 1 63 S 204 P-Z 63 2CDS 284 001 R0608 594042 0.56 1 /L54706 UBmax 125 V ... with 2 poles connected in series UBmax 125 V ... /L54706 Selection tables MCBs S 200 series P 25000 - 15000 2CSC400003F0201 2CSC400132F02012CSC400132F0201

pro M compact® S 200 U-KSelection tables MCBs S 200 series U 10000 K 2CSC400015F0201 2CSC400014F0201 S 200 U-K characteristic Function: protection and control of the circuits like motors, transformers and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL 489, CSA 22.2 No. 5 Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.2 S 201 U-K 0.2 2CDS 271 417 R0087 619226 0.14 10 0.3 S 201 U-K 0.3 2CDS 271 417 R0117 619233 0.14 10 0.5 S 201 U-K 0.5 2CDS 271 417 R0157 619240 0.14 10 0.75 S 201 U-K 0.75 2CDS 271 417 R0187 619257 0.14 10 1 S 201 U-K 1 2CDS 271 417 R0217 619264 0.14 10 1.6 S 201 U-K 1.6 2CDS 271 417 R0257 619271 0.14 10 2 S 201 U-K 2 2CDS 271 417 R0277 619288 0.14 10 3 S 201 U-K 3 2CDS 271 417 R0317 619295 0.14 10 4 S 201 U-K 4 2CDS 271 417 R0337 619301 0.14 10 5 S 201 U-K 5 2CDS 271 417 R0357 619318 0.14 10 6 S 201 U-K 6 2CDS 271 417 R0377 619325 0.14 10 8 S 201 U-K 8 2CDS 271 417 R0407 619332 0.14 10 10 S 201 U-K 10 2CDS 271 417 R0427 619349 0.14 10 13 S 201 U-K 13 2CDS 271 417 R0447 619356 0.14 10 15 S 201 U-K 15 2CDS 271 417 R0457 619363 0.14 10 16 S 201 U-K 16 2CDS 271 417 R0467 619370 0.14 10

20 S 201 U-K 20 2CDS 271 417 R0487 619387

0.14 10 25 S 201 U-K 25 2CDS 271 417 R0517 619394 0.14 10 30 S 201 U-K 30 2CDS 271 417 R0527 619400 0.14 10 32 S 201 U-K 32 2CDS 271 417 R0537 619417 0.14 10 40 S 201 U-K 40 2CDS 271 417 R0557 619424 0.14 10 50 S 201 U-K 50 2CDS 271 417 R0577 619431 0.14 10 60 S 201 U-K 60 2CDS 271 417 R0587 619448 0.14 10 63 S 201 U-K 63 2CDS 271 417 R0607 619455 0.14 10 2 0.2 S 202 U-K 0.2 2CDS 272 417 R0087 619462 0.28 5 0.3 S 202 U-K 0.3 2CDS 272 417 R0117 619479 0.28 5 0.5 S 202 U-K 0.5 2CDS 272 417 R0157 619486 0.28 5 0.75 S 202 U-K 0.75 2CDS 272 417 R0187 619493 0.28 5 1 S 202 U-K 1 2CDS 272 417 R0217 619509 0.28 5 1.6 S 202 U-K 1.6 2CDS 272 417 R0257 619516 0.28 5 2 S 202 U-K 2 2CDS 272 417 R0277 619523 0.28 5 3 S 202 U-K 3 2CDS 272 417 R0317 619530 0.28 5 4 S 202 U-K 4 2CDS 272 417 R0337 619547 0.28 5 5 S 202 U-K 5 2CDS 272 417 R0357 619554 0.28 5 6 S 202 U-K 6 2CDS 272 417 R0377 619561 0.28 5 8 S 202 U-K 8 2CDS 272 417 R0407 619578 0.28 5 10 S 202 U-K 10 2CDS 272 417 R0427 619585 0.28 5 13 S 202 U-K 13 2CDS 272 417 R0447 619592 0.28 5 15 S 202 U-K 15 2CDS 272 417 R0457 619608 0.28 5 16 S 202 U-K 16 2CDS 272 417 R0467 619615 0.28 5 20 S 202 U-K 20 2CDS 272 417 R0487 619622 0.28 5 25 S 202 U-K 25 2CDS 272 417 R0517 619639 0.28 5 30 S 202 U-K 30 2CDS 272 417 R0527 619646 0.28 5 32 S 202 U-K 32 2CDS 272 417 R0537 619653 0.28 5

K System pro M compact ®2CSC400017F0201 2CSC400016F0201 40 S 202 U-K 40 2CDS 272 417 R0557 619660 0.28 5 50 S 202 U-K 50 2CDS 272 417 R0577 619677 0.28 5 60 S 202 U-K 60 2CDS 272 417 R0587 619684 0.28 5 63 S 202 U-K 63 2CDS 272 417 R0607 619691 0.28 5 3 0.2 S 203 U-K 0.2 2CDS 273 417 R0087 619707 0.42 3 0.3 S 203 U-K 0.3 2CDS 273 417 R0117 619714 0.42 3 0.5 S 203 U-K 0.5 2CDS 273 417 R0157 619721 0.42 3 0.75 S 203 U-K 0.75 2CDS 273 417 R0187 619738 0.42 3 1 S 203 U-K 1 2CDS 273 417 R0217 619745 0.42 3 1.6 S 203 U-K 1.6 2CDS 273 417 R0257 619752 0.42 3 2 S 203 U-K 2 2CDS 273 417 R0277 619769 0.42 3 3 S 203 U-K 3 2CDS 273 417 R0317 619776 0.42 3 4 S 203 U-K 4 2CDS 273 417 R0337 619783 0.42 3 5 S 203 U-K 5 2CDS 273 417 R0357 619790 0.42 3 6 S 203 U-K 6 2CDS 273 417 R0377 619806 0.42 3 8 S 203 U-K 8 2CDS 273 417 R0407 619813 0.42 3 10 S 203 U-K 10 2CDS 273 417 R0427 619820 0.42 3 13 S 203 U-K 13 2CDS 273 417 R0447 619837 0.42 3 15 S 203 U-K 15 2CDS 273 417 R0457 619844 0.42 3 16 S 203 U-K 16 2CDS 273 417 R0467 619851 0.42 3 20 S 203 U-K 20 2CDS 273 417 R0487 619868 0.42 3 25 S 203 U-K 25 2CDS 273 417 R0517 619875 0.42 3 30 S 203 U-K 30 2CDS 273 417 R0527 619882 0.42 3 32 S 203 U-K 32 2CDS 273 417 R0537 619899 0.42 3 40 S 203 U-K 40 2CDS 273 417 R0557 619905 0.42 3 50 S 203 U-K 50 2CDS 273 417 R0577 619912 0.42 3 60 S 203 U-K 60 2CDS 273 417 R0587 619929 0.42 3 63 S 203 U-K 63 2CDS 273 417 R0607 619936 0.42 3 4 0.2 S 204 U-K 0.2 2CDS 274 417 R0087 619943 0.56 2 0.3 S 204 U-K 0.3 2CDS 274 417 R0117 619479 0.56 2 0.5 S 204 U-K 0.5 2CDS 274 417 R0157 619967 0.56 2 0.75 S 204 U-K 0.75 2CDS 274 417 R0187 619974 0.56 2 1 S 204 U-K 1 2CDS 274 417 R0217 619509 0.56 2 1.6 S 204 U-K 1.6 2CDS 274 417 R0257 619998 0.56 2 2 S 204 U-K 2 2CDS 274 417 R0277 620000 0.56 2 3 S 204 U-K 3 2CDS 274 417 R0317 620017 0.56 2 4 S 204 U-K 4 2CDS 274 417 R0337 620024 0.56 2 5 S 204 U-K 5 2CDS 274 417 R0357 620031 0.56 2 6 S 204 U-K 6 2CDS 274 417 R0377 620048 0.56 2 8 S 204 U-K 8 2CDS 274 417 R0407 620055 0.56 2 10 S 204 U-K 10 2CDS 274 417 R0427 620062 0.56 2 13 S 204 U-K 13 2CDS 274 417 R0447 620079 0.56 2 15 S 204 U-K 15 2CDS 274 417 R0457 620086 0.56 2 16 S 204 U-K 16 2CDS 274 417 R0467 620093 0.56 2 20 S 204 U-K 20 2CDS 274 417 R0487 620109 0.56 2 25 S 204 U-K 25 2CDS 274 417 R0517 620116 0.56 2 30 S 204 U-K 30 2CDS 274 417 R0527 620123 0.56 2 32 S 204 U-K 32 2CDS 274 417 R0537 620130 0.56 2 40 S 204 U-K 40 2CDS 274 417 R0557 620147 0.56 2 50 S 204 U-K 50 2CDS 274 417 R0577 620154 0.56 2 60 S 204 U-K 60 2CDS 274 417 R0587 620161 0.56 2 63 S 204 U-K 63 2CDS 274 417 R0607 620178 0.56 2

pro M compact® S 200 U-ZSelection tables MCBs S 200 series U 10000 Z 2CSC400014F02012CSC400015F0201 S 200 U-Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL 489, CSA 22.2 No. 5 Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 U-Z 0.5 2CDS 271 417 R0158 620185 0.14 10 1 S 201 U-Z 1 2CDS 271 417 R0218 620192 0.14 10 1.6 S 201 U-Z 1.6 2CDS 271 417 R0258 620208 0.14 10 2 S 201 U-Z 2 2CDS 271 417 R0278 620215 0.14 10 3 S 201 U-Z 3 2CDS 271 417 R0318 620222 0.14 10 4 S 201 U-Z 4 2CDS 271 417 R0338 620239 0.14 10 5 S 201 U-Z 5 2CDS 271 417 R0358 620246 0.14 10 6 S 201 U-Z 6 2CDS 271 417 R0378 620253 0.14 10 8 S 201 U-Z 8 2CDS 271 417 R0408 620260 0.14 10 10 S 201 U-Z 10 2CDS 271 417 R0428 620277 0.14 10 15 S 201 U-Z 15 2CDS 271 417 R0458 620291 0.14 10 16 S 201 U-Z 16 2CDS 271 417 R0468 620307 0.14 10 20 S 201 U-Z 20 2CDS 271 417 R0488 620314 0.14 10 25 S 201 U-Z 25 2CDS 271 417 R0518 620321 0.14 10 30 S 201 U-Z 30 2CDS 271 417 R0528 622851 0.14 10 32 S 201 U-Z 32 2CDS 271 417 R0538 620345 0.14 10

40 S 201 U-Z 40 2CDS 271 417 R0558 620352

0.14 10 50 S 201 U-Z 50 2CDS 271 417 R0578 620369 0.14 10 60 S 201 U-Z 60 2CDS 271 417 R0588 620376 0.14 10 63 S 201 U-Z 63 2CDS 271 417 R0608 620383 0.14 10 2 0.5 S 202 U-Z 0.5 2CDS 272 417 R0158 620390 0.28 5 1 S 202 U-Z 1 2CDS 272 417 R0218 620406 0.28 5 1.6 S 202 U-Z 1.6 2CDS 272 417 R0258 620413 0.28 5 2 S 202 U-Z 2 2CDS 272 417 R0278 620420 0.28 5 3 S 202 U-Z 3 2CDS 272 417 R0318 620437 0.28 5 4 S 202 U-Z 4 2CDS 272 417 R0338 620444 0.28 5 5 S 202 U-Z 5 2CDS 272 417 R0358 620451 0.28 5 6 S 202 U-Z 6 2CDS 272 417 R0378 620468 0.28 5 8 S 202 U-Z 8 2CDS 272 417 R0408 620475 0.28 5 10 S 202 U-Z 10 2CDS 272 417 R0428 620482 0.28 5 15 S 202 U-Z 15 2CDS 272 417 R0458 620505 0.28 5 16 S 202 U-Z 16 2CDS 272 417 R0468 620512 0.28 5 20 S 202 U-Z 20 2CDS 272 417 R0488 620529 0.28 5 25 S 202 U-Z 25 2CDS 272 417 R0518 620536 0.28 5 30 S 202 U-Z 30 2CDS 272 417 R0528 620543 0.28 5 32 S 202 U-Z 32 2CDS 272 417 R0538 620550 0.28 5 40 S 202 U-Z 40 2CDS 272 417 R0558 620567 0.28 5 50 S 202 U-Z 50 2CDS 272 417 R0578 620574 0.28 5 60 S 202 U-Z 60 2CDS 272 417 R0588 620581 0.28 5 63 S 202 U-Z 63 2CDS 272 417 R0608 620598 0.28 5

Z System pro M compact ®2CSC400017F0201 2CSC400016F0201 3 0.5 S 203 U-Z 0.5 2CDS 273 417 R0158 620604 0.42 3 1 S 203 U-Z 1 2CDS 273 417 R0218 620611 0.42 3 1.6 S 203 U-Z 1.6 2CDS 273 417 R0258 620628 0.42 3 2 S 203 U-Z 2 2CDS 273 417 R0278 620635 0.42 3 3 S 203 U-Z 3 2CDS 273 417 R0318 620624 0.42 3 4 S 203 U-Z 4 2CDS 273 417 R0338 620659 0.42 3 5 S 203 U-Z 5 2CDS 273 417 R0358 620666 0.42 3 6 S 203 U-Z 6 2CDS 273 417 R0378 620673 0.42 3 8 S 203 U-Z 8 2CDS 273 417 R0408 620680 0.42 3 10 S 203 U-Z 10 2CDS 273 417 R0428 620697 0.42 3 15 S 203 U-Z 15 2CDS 273 417 R0458 620710 0.42 3 16 S 203 U-Z 16 2CDS 273 417 R0468 620727 0.42 3 20 S 203 U-Z 20 2CDS 273 417 R0488 620734 0.42 3 25 S 203 U-Z 25 2CDS 273 417 R0518 620741 0.42 3 30 S 203 U-Z 30 2CDS 273 417 R0528 620758 0.42 3 32 S 203 U-Z 32 2CDS 273 417 R0538 620765 0.42 3 40 S 203 U-Z 40 2CDS 273 417 R0558 620772 0.42 3 50 S 203 U-Z 50 2CDS 273 417 R0578 620789 0.42 3 60 S 203 U-Z 60 2CDS 273 417 R0588 620796 0.42 3 63 S 203 U-Z 63 2CDS 273 417 R0608 620802 0.42 3 4 0.5 S 204 U-Z 0.5 2CDS 274 417 R0158 620819 0.56 2 1 S 204 U-Z 1 2CDS 274 417 R0218 620826 0.56 2 1.6 S 204 U-Z 1.6 2CDS 274 417 R0258 620833 0.56 2 2 S 204 U-Z 2 2CDS 274 417 R0278 620840 0.56 2 3 S 204 U-Z 3 2CDS 274 417 R0318 620857 0.56 2 4 S 204 U-Z 4 2CDS 274 417 R0338 620864 0.56 2 5 S 204 U-Z 5 2CDS 274 417 R0358 620871 0.56 2 6 S 204 U-Z 6 2CDS 274 417 R0378 620888 0.56 2 8 S 204 U-Z 8 2CDS 274 417 R0408 620895 0.56 2 10 S 204 U-Z 10 2CDS 274 417 R0428 620901 0.56 2 15 S 204 U-Z 15 2CDS 274 417 R0458 620925 0.56 2 16 S 204 U-Z 16 2CDS 274 417 R0468 620932 0.56 2 20 S 204 U-Z 20 2CDS 274 417 R0488 620949 0.56 2 25 S 204 U-Z 25 2CDS 274 417 R0518 620956 0.56 2 30 S 204 U-Z 30 2CDS 274 417 R0528 620963 0.56 2 32 S 204 U-Z 32 2CDS 274 417 R0538 620970 0.56 2 40 S 204 U-Z 40 2CDS 274 417 R0558 620987 0.56 2 50 S 204 U-Z 50 2CDS 274 417 R0578 620994 0.56 2 60 S 204 U-Z 60 2CDS 274 417 R0588 621007 0.56 2 63 S 204 U-Z 63 2CDS 274 417 R0608 621014 0.56 2

pro M compact® S 200 UP-KSelection tables MCBs S 200 series UP 10000 K 2CSC400019F0201 2CSC400018F0201 S 200 UP-K characteristic Function: protection and control of the circuits like motors, transformers and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL 489, CSA 22.2 No. 5 Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.2 S 201 UP-K 0.2 2CDS 271 317 R0087 615631 0.14 10 0.3 S 201 UP-K 0.3 2CDS 271 317 R0117 615648 0.14 10 0.5 S 201 UP-K 0.5 2CDS 271 317 R0157 615655 0.14 10 0.75 S 201 UP-K 0.75 2CDS 271 317 R0187 615662 0.14 10 1 S 201 UP-K 1 2CDS 271 317 R0217 615679 0.14 10 1.6 S 201 UP-K 1.6 2CDS 271 317 R0257 615686 0.14 10 2 S 201 UP-K 2 2CDS 271 317 R0277 615693 0.14 10 3 S 201 UP-K 3 2CDS 271 317 R0317 615709 0.14 10 4 S 201 UP-K 4 2CDS 271 317 R0337 615716 0.14 10 5 S 201 UP-K 5 2CDS 271 317 R0357 615723 0.14 10 6 S 201 UP-K 6 2CDS 271 317 R0377 615730 0.14 10 8 S 201 UP-K 8 2CDS 271 317 R0407 615747 0.14 10 10 S 201 UP-K 10 2CDS 271 317 R0427 615754 0.14 10 13 S 201 UP-K 13 2CDS 271 317 R0447 615761 0.14 10 15 S 201 UP-K 15 2CDS 271 317 R0457 615778 0.14 10 16 S 201 UP-K 16 2CDS 271 317 R0467 615785 0.14 10

20 S 201 UP-K 20 2CDS 271 317 R0487 615792

0.14 10 25 S 201 UP-K 25 2CDS 271 317 R0517 615808 0.14 10 2 0.2 S 202 UP-K 0.2 2CDS 272 317 R0087 615877 0.28 5 0.3 S 202 UP-K 0.3 2CDS 272 317 R0117 615884 0.28 5 0.5 S 202 UP-K 0.5 2CDS 272 317 R0157 615891 0.28 5 0.75 S 202 UP-K 0.75 2CDS 272 317 R0187 615907 0.28 5 1 S 202 UP-K 1 2CDS 272 317 R0217 615914 0.28 5 1.6 S 202 UP-K 1.6 2CDS 272 317 R0257 615921 0.28 5 2 S 202 UP-K 2 2CDS 272 317 R0277 615938 0.28 5 3 S 202 UP-K 3 2CDS 272 317 R0317 615945 0.28 5 4 S 202 UP-K 4 2CDS 272 317 R0337 615952 0.28 5 5 S 202 UP-K 5 2CDS 272 317 R0357 615969 0.28 5 6 S 202 UP-K 6 2CDS 272 317 R0377 615976 0.28 5 8 S 202 UP-K 8 2CDS 272 317 R0407 615983 0.28 5 10 S 202 UP-K 10 2CDS 272 317 R0427 615990 0.28 5 13 S 202 UP-K 13 2CDS 272 317 R0447 616003 0.28 5 15 S 202 UP-K 15 2CDS 272 317 R0457 616010 0.28 5 16 S 202 UP-K 16 2CDS 272 317 R0467 616027 0.28 5 20 S 202 UP-K 20 2CDS 272 317 R0487 616034 0.28 5 25 S 202 UP-K 25 2CDS 272 317 R0517 616041 0.28 5

S 200 UP-KSelection tables MCBs S 200 series UP 10000 K System pro M compact ®2CSC400022F0201 2CSC400021F0201 3 0.2 S 203 UP-K 0.2 2CDS 273 317 R0087 616119 0.42 3 0.3 S 203 UP-K 0.3 2CDS 273 317 R0117 616126 0.42 3 0.5 S 203 UP-K 0.5 2CDS 273 317 R0157 616133 0.42 3 0.75 S 203 UP-K 0.75 2CDS 273 317 R0187 616140 0.42 3 1 S 203 UP-K 1 2CDS 273 317 R0217 616157 0.42 3 1.6 S 203 UP-K 1.6 2CDS 273 317 R0257 616164 0.42 3 2 S 203 UP-K 2 2CDS 273 317 R0277 616171 0.42 3 3 S 203 UP-K 3 2CDS 273 317 R0317 616188 0.42 3 4 S 203 UP-K 4 2CDS 273 317 R0337 616195 0.42 3 5 S 203 UP-K 5 2CDS 273 317 R0357 616201 0.42 3 6 S 203 UP-K 6 2CDS 273 317 R0377 616218 0.42 3 8 S 203 UP-K 8 2CDS 273 317 R0407 616225 0.42 3 10 S 203 UP-K 10 2CDS 273 317 R0427 616232 0.42 3 13 S 203 UP-K 13 2CDS 273 317 R0447 616249 0.42 3 15 S 203 UP-K 15 2CDS 273 317 R0457 616256 0.42 3 16 S 203 UP-K 16 2CDS 273 317 R0467 616263 0.42 3 20 S 203 UP-K 20 2CDS 273 317 R0487 616270 0.42 3 25 S 203 UP-K 25 2CDS 273 317 R0517 616287 0.42 3 4 0.2 S 204 UP-K 0.2 2CDS 274 317 R0087 616355 0.56 2 0.3 S 204 UP-K 0.3 2CDS 274 317 R0117 616362 0.56 2 0.5 S 204 UP-K 0.5 2CDS 274 317 R0157 616379 0.56 2 0.75 S 204 UP-K 0.75 2CDS 274 317 R0187 616386 0.56 2 1 S 204 UP-K 1 2CDS 274 317 R0217 616393 0.56 2 1.6 S 204 UP-K 1.6 2CDS 274 317 R0257 616409 0.56 2 2 S 204 UP-K 2 2CDS 274 317 R0277 616416 0.56 2 3 S 204 UP-K 3 2CDS 274 317 R0317 616423 0.56 2 4 S 204 UP-K 4 2CDS 274 317 R0337 616430 0.56 2 5 S 204 UP-K 5 2CDS 274 317 R0357 616447 0.56 2 6 S 204 UP-K 6 2CDS 274 317 R0377 616454 0.56 2 8 S 204 UP-K 8 2CDS 274 317 R0407 616461 0.56 2 10 S 204 UP-K 10 2CDS 274 317 R0427 616478 0.56 2 13 S 204 UP-K 13 2CDS 274 317 R0447 616485 0.56 2 15 S 204 UP-K 15 2CDS 274 317 R0457 616492 0.56 2 16 S 204 UP-K 16 2CDS 274 317 R0467 616508 0.56 2 20 S 204 UP-K 20 2CDS 274 317 R0487 616515 0.56 2 25 S 204 UP-K 25 2CDS 274 317 R0517 616522 0.56 2

pro M compact® S 200 UP-ZSelection tables MCBs S 200 series UP 10000 Z 2CSC400018F02012CSC400019F0201 S 200 UP-Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL 489, CSA 22.2 No. 5 Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 201 UP-Z 0.5 2CDS 271 317 R0158 616591 0.14 10 1 S 201 UP-Z 1 2CDS 271 317 R0218 616607 0.14 10 1.6 S 201 UP-Z 1.6 2CDS 271 317 R0258 616614 0.14 10 2 S 201 UP-Z 2 2CDS 271 317 R0278 616621 0.14 10 3 S 201 UP-Z 3 2CDS 271 317 R0318 616638 0.14 10 4 S 201 UP-Z 4 2CDS 271 317 R0338 616645 0.14 10 5 S 201 UP-Z 5 2CDS 271 317 R0358 616652 0.14 10 6 S 201 UP-Z 6 2CDS 271 317 R0378 616669 0.14 10 8 S 201 UP-Z 8 2CDS 271 317 R0408 616676 0.14 10 10 S 201 UP-Z 10 2CDS 271 317 R0428 616683 0.14 10 13 S 201 UP-Z 13 2CDS 271 317 R0448 616690 0.14 10 15 S 201 UP-Z 15 2CDS 271 317 R0458 616706 0.14 10 16 S 201 UP-Z 16 2CDS 271 317 R0468 616713 0.14 10 20 S 201 UP-Z 20 2CDS 271 317 R0488 616720 0.14 10 25 S 201 UP-Z 25 2CDS 271 317 R0518 616737 0.14 10 2 0.5 S 202 UP-Z 0.5 2CDS 272 317 R0158 616805 0.28 5

1 S 202 UP-Z 1 2CDS 272 317 R0218

616812 0.28 5 1.6 S 202 UP-Z 1.6 2CDS 272 317 R0258 616829 0.28 5 2 S 202 UP-Z 2 2CDS 272 317 R0278 616836 0.28 5 3 S 202 UP-Z 3 2CDS 272 317 R0318 616843 0.28 5 4 S 202 UP-Z 4 2CDS 272 317 R0338 616850 0.28 5 5 S 202 UP-Z 5 2CDS 272 317 R0358 616867 0.28 5 6 S 202 UP-Z 6 2CDS 272 317 R0378 616874 0.28 5 8 S 202 UP-Z 8 2CDS 272 317 R0408 616881 0.28 5 10 S 202 UP-Z 10 2CDS 272 317 R0428 616898 0.28 5 13 S 202 UP-Z 13 2CDS 272 317 R0448 616904 0.28 5 15 S 202 UP-Z 15 2CDS 272 317 R0458 616911 0.28 5 16 S 202 UP-Z 16 2CDS 272 317 R0468 616928 0.28 5 20 S 202 UP-Z 20 2CDS 272 317 R0488 616935 0.28 5 25 S 202 UP-Z 25 2CDS 272 317 R0518 616942 0.28 5

S 200 UP-ZSelection tables MCBs S 200 series UP 10000 Z System pro M compact 2CSC400022F0201 2CSC400021F0201 3 0.5 S 203 UP-Z 0.5 2CDS 273 317 R0158 617017 0.42 3 1 S 203 UP-Z 1 2CDS 273 317 R0218 617024 0.42 3 1.6 S 203 UP-Z 1.6 2CDS 273 317 R0258 617031 0.42 3 2 S 203 UP-Z 2 2CDS 273 317 R0278 617048 0.42 3 3 S 203 UP-Z 3 2CDS 273 317 R0318 617055 0.42 3 4 S 203 UP-Z 4 2CDS 273 317 R0338 617062 0.42 3 5 S 203 UP-Z 5 2CDS 273 317 R0358 617079 0.42 3 6 S 203 UP-Z 6 2CDS 273 317 R0378 617086 0.42 3 8 S 203 UP-Z 8 2CDS 273 317 R0408 617093 0.42 3 10 S 203 UP-Z 10 2CDS 273 317 R0428 617109 0.42 3 13 S 203 UP-Z 13 2CDS 273 317 R0448 617116 0.42 3 15 S 203 UP-Z 15 2CDS 273 317 R0458 617123 0.42 3 16 S 203 UP-Z 16 2CDS 273 317 R0468 617130 0.42 3 20 S 203 UP-Z 20 2CDS 273 317 R0488 617147 0.42 3 25 S 203 UP-Z 25 2CDS 273 317 R0518 617154 0.42 3 4 0.5 S 204 UP-Z 0.5 2CDS 274 317 R0158 617222 0.56 2 1 S 204 UP-Z 1 2CDS 274 317 R0218 617239 0.56 2 1.6 S 204 UP-Z 1.6 2CDS 274 317 R0258 617246 0.56 2 2 S 204 UP-Z 2 2CDS 274 317 R0278 617253 0.56 2 3 S 204 UP-Z 3 2CDS 274 317 R0318 617260 0.56 2 4 S 204 UP-Z 4 2CDS 274 317 R0338 617277 0.56 2 5 S 204 UP-Z 5 2CDS 274 317 R0358 617284 0.56 2 6 S 204 UP-Z 6 2CDS 274 317 R0378 617291 0.56 2 8 S 204 UP-Z 8 2CDS 274 317 R0408 617307 0.56 2 10 S 204 UP-Z 10 2CDS 274 317 R0428 617314 0.56 2 13 S 204 UP-Z 13 2CDS 274 317 R0448 617321 0.56 2 15 S 204 UP-Z 15 2CDS 274 317 R0458 617338 0.56 2 16 S 204 UP-Z 16 2CDS 274 317 R0468 617345 0.56 2 20 S 204 UP-Z 20 2CDS 274 317 R0488 617352 0.56 2 25 S 204 UP-Z 25 2CDS 274 317 R0518 617369 0.56 2

S 200 UDC-K characteristic Function: protection and control of the circuits like motors, transformers and auxiliary circuits, against overloads and short-circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: UL 489 (only DC, please note polarity of device) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 1 S 201 UDC-K 1 2CDS 271 517 R0217 825924 0.150 10 1,6 S 201 UDC-K 1.6 2CDS 271 517 R0257 825948 0.150 10 2 S 201 UDC-K 2 2CDS 271 517 R0277 825955 0.150 10 3 S 201 UDC-K 3 2CDS 271 517 R0317 825962 0.150 10 4 S 201 UDC-K 4 2CDS 271 517 R0337 825979 0.150 10 5 S 201 UDC-K 5 2CDS 271 517 R0357 825986 0.150 10 6 S 201 UDC-K 6 2CDS 271 517 R0377 825993 0.150 10 8 S 201 UDC-K 8 2CDS 271 517 R0407 826006 0.150 10 10 S 201 UDC-K 10 2CDS 271 517 R0427 826013 0.150 10 13 S 201 UDC-K 13 2CDS 271 517 R0447 826020 0.150 10 15 S 201 UDC-K 15 2CDS 271 517 R0457 826037 0.150 10 16 S 201 UDC-K 16 2CDS 271 517 R0467 826044 0.150 10 20 S 201 UDC-K 20 2CDS 271 517 R0487 826051 0.150 10 25 S 201 UDC-K 25 2CDS 271 517 R0517 826068 0.150 10 30 S 201 UDC-K 30 2CDS 271 517 R0527 826075 0.150 10 32 S 201 UDC-K 32 2CDS 271 517 R0537 826082 0.150 10

40 S 201 UDC-K 40 2CDS 271 517 R0557 826099

0.150 10 50 S 201 UDC-K 50 2CDS 271 517 R0577 826105 0.150 10 60 S 201 UDC-K 60 2CDS 271 517 R0587 826112 0.150 10 63 S 201 UDC-K 63 2CDS 271 517 R0607 826129 0.150 10 2 1 S 202 UDC-K 1 2CDS 272 517 R0217 825061 0.300 5 1,6 S 202 UDC-K 1.6 2CDS 272 517 R0257 825160 0.300 5 2 S 202 UDC-K 2 2CDS 272 517 R0277 825177 0.300 5 3 S 202 UDC-K 3 2CDS 272 517 R0317 825184 0.300 5 4 S 202 UDC-K 4 2CDS 272 517 R0337 825191 0.300 5 5 S 202 UDC-K 5 2CDS 272 517 R0357 825207 0.300 5 6 S 202 UDC-K 6 2CDS 272 517 R0377 825214 0.300 5 8 S 202 UDC-K 8 2CDS 272 517 R0407 825221 0.300 5 10 S 202 UDC-K 10 2CDS 272 517 R0427 825238 0.300 5 13 S 202 UDC-K 13 2CDS 272 517 R0447 825245 0.300 5 15 S 202 UDC-K 15 2CDS 272 517 R0457 825252 0.300 5 16 S 202 UDC-K 16 2CDS 272 517 R0467 825269 0.300 5 20 S 202 UDC-K 20 2CDS 272 517 R0487 825276 0.300 5 25 S 202 UDC-K 25 2CDS 272 517 R0517 825283 0.300 5 30 S 202 UDC-K 30 2CDS 272 517 R0527 825290 0.300 5 32 S 202 UDC-K 32 2CDS 272 517 R0537 825306 0.300 5 40 S 202 UDC-K 40 2CDS 272 517 R0557 825313 0.300 5 50 S 202 UDC-K 50 2CDS 272 517 R0577 825320 0.300 5 60 S 202 UDC-K 60 2CDS 272 517 R0587 825337 0.300 5 63 S 202 UDC-K 63 2CDS 272 517 R0607 825344 0.300 5 System pro M compact® S 200 UDC-KSelection tables MCBs S 200 series UDC K 2CDC 021 126 F0010 2CDC 021 127 F0010

S 200 UDC-Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits. Applications: commercial and industrial. Standard: UL 489 (only DC, please note polarity of device) Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 1 S 201 UDC-Z 1 2CDS 271 517 R0218 826136 0.150 10 1,6 S 201 UDC-Z 1.6 2CDS 271 517 R0258 826143 0.150 10 2 S 201 UDC-Z 2 2CDS 271 517 R0278 826150 0.150 10 3 S 201 UDC-Z 3 2CDS 271 517 R0318 826167 0.150 10 4 S 201 UDC-Z 4 2CDS 271 517 R0338 826174 0.150 10 5 S 201 UDC-Z 5 2CDS 271 517 R0358 826181 0.150 10 6 S 201 UDC-Z 6 2CDS 271 517 R0378 826198 0.150 10 8 S 201 UDC-Z 8 2CDS 271 517 R0408 826204 0.150 10 10 S 201 UDC-Z 10 2CDS 271 517 R0428 826211 0.150 10 15 S 201 UDC-Z 15 2CDS 271 517 R0458 826228 0.150 10 16 S 201 UDC-Z 16 2CDS 271 517 R0468 826235 0.150 10 20 S 201 UDC-Z 20 2CDS 271 517 R0488 826242 0.150 10 25 S 201 UDC-Z 25 2CDS 271 517 R0518 826259 0.150 10 30 S 201 UDC-Z 30 2CDS 271 517 R0528 826266 0.150 10 32 S 201 UDC-Z 32 2CDS 271 517 R0538 826273 0.150 10 40 S 201 UDC-Z 40 2CDS 271 517 R0558 826280 0.150 10

50 S 201 UDC-Z 50 2CDS 271 517 R0578 826297

0.150 10 60 S 201 UDC-Z 60 2CDS 271 517 R0588 826303 0.150 10 63 S 201 UDC-Z 63 2CDS 271 517 R0608 826310 0.150 10 2 1 S 202 UDC-Z 1 2CDS 272 517 R0218 825351 0.300 5 1,6 S 202 UDC-Z 1.6 2CDS 272 517 R0258 825368 0.300 5 2 S 202 UDC-Z 2 2CDS 272 517 R0278 825375 0.300 5 3 S 202 UDC-Z 3 2CDS 272 517 R0318 825382 0.300 5 4 S 202 UDC-Z 4 2CDS 272 517 R0338 825399 0.300 5 5 S 202 UDC-Z 5 2CDS 272 517 R0358 825405 0.300 5 6 S 202 UDC-Z 6 2CDS 272 517 R0378 825412 0.300 5 8 S 202 UDC-Z 8 2CDS 272 517 R0408 825429 0.300 5 10 S 202 UDC-Z 10 2CDS 272 517 R0428 825436 0.300 5 15 S 202 UDC-Z 15 2CDS 272 517 R0458 825443 0.300 5 16 S 202 UDC-Z 16 2CDS 272 517 R0468 825450 0.300 5 20 S 202 UDC-Z 20 2CDS 272 517 R0488 825467 0.300 5 25 S 202 UDC-Z 25 2CDS 272 517 R0518 825474 0.300 5 30 S 202 UDC-Z 30 2CDS 272 517 R0528 825481 0.300 5 32 S 202 UDC-Z 32 2CDS 272 517 R0538 825498 0.300 5 40 S 202 UDC-Z 40 2CDS 272 517 R0558 825504 0.300 5 50 S 202 UDC-Z 50 2CDS 272 517 R0578 825511 0.300 5 60 S 202 UDC-Z 60 2CDS 272 517 R0588 825528 0.300 5 63 S 202 UDC-Z 63 2CDS 272 517 R0608 825535 0.300 5 S 200 UDC-ZSelection tables MCBs S 200 series UDC Z System pro M compact 2CDC 021 128 F0010 2CDC 021 129 F0010

The SN 201 range of circuit- breakers is the new ABB range of 1P+N single-module MCBs. These circuit-breakers are available with rated currents from 2 to 40 A, in the version with C characteristic, and with rated currents from 6 to

40 A, in the version with B

and D characteristics. For each current there are also three different breaking capacities available: 4.5 kA (SN 201 L series), 6 kA (SN 201 series) and 10 kA (SN 201 M series). The circuit-breakers have been designed to ensure, in the final closing section, that the closing speed of the contacts is independent of the speed at which the knob rotated. The trip mechanism (ABB international patent) ensures perfect closure every time, thereby considerably improving the performance of these devices and extending ensuring maximum safety of the operation. Due to larger size of the DIN rail fixing system, made with 2 bistable fixing devices, the same screwdriver used for tightening the terminals can also be used for assembling and disassembling the device. All versions are equipped with high capacity cage type terminals (16 mm 2). The SN 201 range circuit breakers have been designed for wiring with the ABB SACE Unifix rapid system. The SN 201 fully integrates with the range of System pro M compact ® miniature circuit-breakers, sharing the wide selection of accessories available through a dedicated interface (half module), which also can be used as auxiliary contact. their average lifetime. A redesigned red/green toggle makes the ON/OFF status immediately apparent. With the practical label carrier fitted in the new SN 201 circuit-breakers it’s possible to give maximum visibility to the information relating to the protected loads. The larger neutral hole allows the use of an insulated screwdriver to tighten the screws of both wire terminals, 2CSC400005F0201 2CSC400134F0201 2CSC400129F0201 2CSC400133F0201

Selection tables of MCBs SN 201 series Miniature circuit-breakers SN 201 series

Max. operating voltage Ub max. AC V DC 1P V DC 1P+N V Min. operating voltage Ub min. V Rated frequency Hz Rated breaking capacity acc. to IEC/EN 60898 ultimate Icn A Rated making and breaking capacity of an individual pole Icn1 kA Rated breaking capacity ultimate Icu kA acc. to IEC 947-2 1P+N - 230 V service Ics kA Rated impulse withstand voltage (1,2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Overvoltage category Thermal-magnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In D: 10 In ≤ Im ≤ 20 In Toggle Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC 68-2 constant climate conditions °C/RH variable climate conditions °C/RH Reference temperature for calibration of thermal element °C Ambient temperature (with daily average ≤+35°C) °C Storage temperature °C Terminal size upper/lower per cable mm2 Tightening torque N*m Mounting Pole dimensions (H x D x W) mm Pole weight g SN 201Technical features MCBs SN 201 series System pro M compact®

2 ≤ In ≤ 40 /L54706 1P+N 230 500 254 125 12VAC - 12VDC 50…60 4500 6000 10000 4.5 6 6 61 0 1 0 4.5 6 7.5 2.5 III ■■■ ■■■ black sealable in ON-OFF position 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+55 -40…+70 1,2 on DIN rail EN 60715 (35mm) by means of rapid fixing device 85 x 68.9 x 17.6 110 SN 201Technical features MCBs SN 201 series /L54706 SN201 and SN201M series in B and D characteristic are available for rated current In ≥ 6 A System pro M compact®

SN 201 L - B characteristic Function: overload and short-circuit protection of circuits in final distribution; protection of long cable lengths in TN and IT systems. Applications: residential. Standard: IEC/EN 60898 Icn: 4.5 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 2 SN201 L B2 2CSS245101R0025 087366 0.110 6 4 SN201 L B4 2CSS245101R0045 087465 0.110 6 6 SN201 L B6 2CSS245101R0065 087564 0.110 6 10 SN201 L B10 2CSS245101R0105 087663 0.110 6 16 SN201 L B16 2CSS245101R0165 087762 0.110 6 20 SN201 L B20 2CSS245101R0205 087861 0.110 6 25 SN201 L B25 2CSS245101R0255 087960 0.110 6 32 SN201 L B32 2CSS245101R0325 088066 0.110 6 40 SN201 L B40 2CSS245101R0405 088165 0.110 6 SN 201 L - C characteristic Function: overload and short-circuit protection of circuits in final distribution; protection of resistive and inductive loads with low inrush current. Applications: residential. Standard: IEC/EN 60898 Icn: 4.5 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 2 SN201 L C2 2CSS245101R0024 088264 0.110 6 4 SN201 L C4 2CSS245101R0044 088363 0.110 6 6 SN201 L C6 2CSS245101R0064 088462 0.110 6 10 SN201 L C10 2CSS245101R0104 088561 0.110 6 16 SN201 L C16 2CSS245101R0164 088660 0.110 6 20 SN201 L C20 2CSS245101R0204 088769 0.110 6 25 SN201 L C25 2CSS245101R0254 088868 0.110 6 32 SN201 L C32 2CSS245101R0324 088967 0.110 6 40 SN201 L C40 2CSS245101R0404 089063 0.110 6 B C System pro M compact® 2CSC400001F02022CSC400667F00012CSC400666F0001

Function: overload and short-circuits protection of circuits in final distribution; protection of long cable lengths in TN and IT systems. Applications: residential and commercial. Standard: IEC/EN 60898 Icn: 6 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 6 SN201 B6 2CSS255101R0065 090762 0.110 6 10 SN201 B10 2CSS255101R0105 090861 0.110 6 16 SN201 B16 2CSS255101R0165 090960 0.110 6 20 SN201 B20 2CSS255101R0205 091066 0.110 6 25 SN201 B25 2CSS255101R0255 091165 0.110 6 32 SN201 B32 2CSS255101R0325 091264 0.110 6 40 SN201 B40 2CSS255101R0405 091363 0.110 6 SN 201 - C characteristic Function: overload and short-circuit protection of circuits in final distribution; protection of resistive and inductive loads with low inrush current. Applications: residential and commercial. Standard: IEC/EN 60898 Icn: 6 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 2 SN201 C2 2CSS255101R0024 091462 0.110 6 4 SN201 C4 2CSS255101R0044 091561 0.110 6 6 SN201 C6 2CSS255101R0064 091660 0.110 6 10 SN201 C10 2CSS255101R0104 091769 0.110 6 13 SN201 C13 2CSS255101R0134 091868 0.110 6 16 SN201 C16 2CSS255101R0164 091967 0.110 6 20 SN201 C20 2CSS255101R0204 092063 0.110 6 25 SN201 C25 2CSS255101R0254 092162 0.110 6 32 SN201 C32 2CSS255101R0324 092261 0.110 6 40 SN201 C40 2CSS255101R0404 092360 0.110 6 B C 6000 System pro M compact® 2CSC400672F00012CSC400671F0001

Function: protection and control of the circuits against overloads and short-circuits in final distribution; protection for circuits which supply loads with high inrush current at the circuit closing. Applications: residential and commercial. Standard: IEC/EN 60898 Icn: 6 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 6 SN201 D6 2CSS255101R0061 092469 0,110 6

10 SN201 D10 2CSS255101R0101 092568 0,110 6

16 SN201 D16 2CSS255101R0161 092667 0,110 6

20 SN201 D20 2CSS255101R0201 092766 0,110 6

25 SN201 D25 2CSS255101R0251 092865 0,110 6

32 SN201 D32 2CSS255101R0321 092964 0,110 6

40 SN201 D40 2CSS255101R0401 093060 0,110 6

D System pro M compact® 2CSC400670F0001

SN 201 M - B characteristic Function: overloads and short-circuit protection of circuits in final distribution; protection of long cable lengths in TN and IT systems. Applications: residential and commercial. Standard: IEC/EN 60898 Icn: 10 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 6 SN201 M B6 2CSS275101R0065 093152 0.110 6 10 SN201 M B10 2CSS275101R0105 093251 0.110 6 16 SN201 M B16 2CSS275101R0165 093350 0.110 6 20 SN201 M B20 2CSS275101R0205 093459 0.110 6 25 SN201 M B25 2CSS275101R0255 093558 0.110 6 32 SN201 M B32 2CSS275101R0325 093657 0.110 6 40 SN201 M B40 2CSS275101R0405 093756 0.110 6 SN 201 M - C characteristic Function: overload and short-circuit protection of circuits in final distribution; protection of resistive and inductive loads with low inrush current. Applications: residential and commercial. Standard: IEC/EN 60898 Icn: 10 kA Number Rated Order details Bbn Price Price Weight Pack of poles current 8012542 1 piece group 1 piece unit In A Type Order code EAN kg pc. 1+N 2 SN201 M C2 2CSS275101R0024 093862 0.110 6 4 SN201 M C4 2CSS275101R0044 093961 0.110 6 6 SN201 M C6 2CSS275101R0064 094067 0.110 6 10 SN201 M C10 2CSS275101R0104 094166 0.110 6 16 SN201 M C16 2CSS275101R0164 094265 0.110 6 20 SN201 M C20 2CSS275101R0204 094364 0.110 6 25 SN201 M C25 2CSS275101R0254 094463 0.110 6 32 SN201 M C32 2CSS275101R0324 094562 0.110 6 40 SN201 M C40 2CSS275101R0404 094661 0.110 6 B C System pro M compact® 2CSC400665F00012CSC400664F0001

MCBs for heavy-duty industrial protection consist of three different ranges. S 280 series, which includes the 80 A and 100 A rated current versions (one pole, one module), available in B and C characteristics, 6 kA breaking capacity according to IEC/EN

60898 Standard and 35 mm

size of the terminals. The range includes also the S 280 UC series that protects direct current circuits with high voltages. In all circuit-breakers of the range there is no specific mechanical constraint between the case and the internal mechanical components which form three independent functional blocks: in this way, any distortion of the case, in the event of thermal shock, does not affect the correct functioning of the circuit-breaker. The supply lines of the protected circuit can be connected to either the upper or lower terminals of the circuit-breakers (reversibility of connections). The double terminal of these circuit-breakers enables simultaneous connection of cables and busbars. S 290 series, for the use in switchboards and consumer units for modular devices with 45 mm slotting and rated currents up to 125 A. They can be mounted alongside standard modular circuit-breakers because of their modular design and ability to be installed on 35 mm DIN EN 50022 rails. The circuit-breakers are available in 1-2-3-4 pole versions with a width equal to 1 module and a half per pole (27 mm); the characteristic curves are B, C, D and K. S700 series is a range of selective main circuit breakers (smcb) for the use as main incoming protective device for any distribiution board or meter cabinet. The main application of S700 is the selective overload and short-circuit protection and isolation of circuits in 230/400 V installations. The outstanding selectivity in combination with high isolation capability and the suitability for the use by laymen are the main characteristics of this range, including single and multipole devices, different tripping characteristics and a broad range of accessories. WT63 is a main current limiting device for the use in dedicated motor protection circuits. With WT 63 it is possible to create smart motor protection solutions for 690V applications, where WT63 can be used as a main current limitor for several motor groups - ensuring high breaking capacity by selective current limiting. The extensive S800 range offers the right high performance MCBs with high-rated breaking capacities and various tripping characteristics. The units of the S800S series, both AC and DC types, operate in a nominal current range of between 6 and 125 A covering breaking capacities of up to 50 kA. The S800N is the ideal solution for applications of up to 36 kA, the S800C for applications up to 25 kA; of course also for current ratings of between 10 and 125 A. The high-rated breaking capacities of up to 50 kA allow electrical distribution systems to be configured and operated safely in an uncomplicated manner. Compact dimensions ensure that energy distribution systems can be set up in a space-saving way. S800 MCBs satisfy all the main standards and approvals. For the photovoltaic market ABB supply the new S800PV range allowing complete protection in such innovative plants. The heavy duty circuit breakers S500 complete the range of the S800. The devices of the series S500K and S500UC-K provide the opportunity to adjust the rated current. This has the benefit to get a very precise tripping. The S500K has a short-circuit current of up to 50 kA. The S500UC-K is only for DC applications such as railway systems or DC-networks. He offers a high rated operating voltage up to 750 V DC and a breaking capacity of up to 30 kA.

Miniature circuit-breakers S 280, S 290, S700, S800 and S500 series Index Selection tables of MCBs S 280 series 80-100 A Selection tables of MCBs S 280 UC series Selection tables of MCBs S 290 series Selection tables of MCBs S700 series Selection tables of MCBs S800 series Selection tables of MCBs S500 series

MCBs S 280 series 80-100 A S 280 80 - 100 A Electrical Data Standards IEC/EN IEC/EN 60898-1, IEC/EN 60947-2 UL/CSA – Poles 1P , 2P , 3P , 4P Tripping characteristics B, C Rated current I n A 80…100 A Rated voltage Un IEC/EN 60898-1 V 1P: 230 V AC 2...4P: 400 V AC Rated voltage Un IEC/EN 60898-2 V – Rated voltage Ue IEC/EN 60947-2 V 1P: 230 - 240 V AC 2...4P: 230/400 - 240/415 V AC Rated voltage UL/CSA V – Insulation voltage U i IEC/EN 60898-1 / 60947-2 V 250 V AC (phase to ground),

500 V AC (phase to phase)

Max. operating voltage UBmax. V 1P: 253 V AC 2…4P: 440 V AC Min. operating voltage UBmin. V 12 V AC Rated frequency f Hz 50 / 60 Hz Rated short-circuit capacity I cn IEC/EN 60898-1 kA 6 kA Ultimate short-circuit capacity Icu IEC/EN 60947-2 kA 6 kA Service short-circuit capacity Ics IEC/EN 60947-2 kA 6 kA Energy limiting class IEC/EN 60898-1 – Overvoltage category IEC/EN 60898-1 / 60947-2 III Pollution degree IEC/EN 60898-1 2 IEC/EN 60947-2 3 Rated impulse withstand voltage U imp. (1.2/50 μs) IEC/EN 60898-1 / 60947-2 kV 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectric test voltage IEC/EN 60898-1 kV 2 kV (50 / 60 Hz, 1 min.) Mechanical Data Housing Insulation group I, RAL 7035 Toggle Insulation group II, black, sealable Contact position indication Marking on toggle (I ON / 0 OFF), Real CPI (red ON / green OFF) Protection degree IEC/EN 60529 IP20 / IPXXB, IP40 in enclosure with cover Electrical endurance ops. 4,000 ops. Mechanical endurance ops. 10,000 ops. Shock resistance IEC/EN 60068-2-27 30 g - 3 shocks - 11 ms Vibration resistance IEC/EN 60068-2-6 5 g - 20 cycles at 5…150…5 Hz with load 0.8 I n Tropicalization (damp heat cyclic) IEC/EN 60068-2-30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100% Ambient temperature °C -25 … +55°C Storage temperature °C -40 … +70°C Reference temperature for tripping characteristics IEC/EN 60898-1 IEC/EN 60947-2 °C B, C: 30°C Installation Terminal Cage (shock protected) Cross-section of conductors (top / bottom) IEC/EN 60898-1 / 60947-2 mm 2 35 mm2 / 35 mm2 UL/CSA AWG – Cross-section of busbars (top / bottom) IEC/EN 60898-1 / 60947-2 mm 2 16 mm2 / 16 mm2 UL/CSA AWG – Torque IEC/EN Nm 2.5 Nm UL/CSA in-Ibs. – Screwdriver No. 2 Pozidrive Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip Mounting position Any Supply Optional Dimensions and weight Mounting dimensions DIN 43880 Mounting dimension 1 Pole dimensions (H x D x W) mm 90 x 69 x 17.5 mm Pole weight g ca. 160 g Combination with aux. elements signal contact/auxiliary switch Yes shunt trip Yes undervoltage release Yes

S 280 80-100A B characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 8012542 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S281 B80 GHS2810001R0805 499503 0.140 1/6 100 S281 B100 GHS2810001R0825 499602 0.140 1/6 2 80 S282 B80 GHS2820001R0805 500100 0.275 1/3 100 S282 B100 GHS2820001R0825 500209 0.275 1/3 3 80 S283 B80 GHS2830001R0805 500704 0.400 1/2 100 S283 B100 GHS2830001R0825 500803 0.400 1/2 4 80 S284 B80 GHS2840001R0805 518006 0.525 1 100 S284 B100 GHS2840001R0825 518105 0.525 1 System pro M S 280 B and C Selection tables MCBs S 280 series 80-100 A S 280 80-100A C characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for resistive and inductive loads with low inrush current. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 8012542 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S281 C80 GHS2810001R0804 499305 0.140 1/6 100 S281 C100 GHS2810001R0824 499404 0.140 1/6 2 80 S282 C80 GHS2820001R0804 499909 0.275 1/3 100 S282 C100 GHS2820001R0824 500001 0.275 1/3 3 80 S283 C80 GHS2830001R0804 500506 0.400 1/2 100 S283 C100 GHS2830001R0824 500605 0.400 1/2 4 80 S284 C80 GHS2840001R0804 517801 0.525 1 100 S284 C100 GHS2840001R0824 517900 0.525 1 2CSC400475F02012CSC400476F0201 2CSC400474F02012CSC400477F0201 B & C 6000

S 280 UC Technical features MCBs S 280 series UC S 280 UC Electrical Data Standards IEC/EN Acc. to IEC/EN 60898-2, IEC/EN 60947-2 UL/CSA UL 1077, CSA 22.2 No. 235 Poles 1P , 2P , 3P , 4P Tripping characteristics B, K, Z Rated current I n A 0.2…63 A Rated voltage Un IEC/EN 60898-1 V – Rated voltage Un IEC/EN 60898-2 V 1P: 220 V DC, 230 V AC 2P: 400 V DC, 400 V AC Rated voltage Ue IEC/EN 60947-2 V 1P: 220 V DC 2...4P: 440 V DC Rated voltage UL/CSA V 1P: 250 V DC, 277 V AC 2...4P: 500 V DC, 480 V AC Insulation voltage Ui IEC/EN 60898-2 / 60947-2 V 250 V AC (phase to ground), Max. operating voltage UBmax. V 1P: 253 V AC, 242 V DC 2…4P: 440 V AC, 484 V DC Min. operating voltage UBmin. V 12 V AC - 12 V DC Rated frequency f Hz 50 / 60 Hz Rated short-circuit capacity I cn IEC/EN 60898-2 kA ≤ 40 A: 6 kA > 40 A: 4.5 kA Ultimate short-circuit capacity Icu IEC/EN 60947-2 kA ≤ 40 A: 6 kA > 40 A: 4.5 kA Service short-circuit capacity Ics IEC/EN 60947-2 kA ≤ 40 A: 6 kA > 40 A: 4.5 kA Rated interrupting capacity UL 1077, CSA 22.2 No. 235 kA 4.5 kA (10 kA 60 V DC 1P , 125 V DC 2P) Energy limiting class IEC/EN 60898-2 3 Overvoltage category IEC/EN 60898-2 / 60947-2 III Pollution degree IEC/EN 60898-2 2 IEC/EN 60947-2 3 Rated impulse withstand voltage U imp. (1.2/50 μs) IEC/EN 60898-2 / 60947-2 kV 4 kV (test voltage 6.2 kV at sea level, 5 kV at 2,000 m) Dielectric test voltage IEC/EN 60898-2 kV 2 kV (50 / 60 Hz, 1 min.) Mechanical Data Housing Insulation group I, RAL 7035 Toggle Insulation group II, black, sealable Contact position indication Marking on toggle (I ON / 0 OFF), Real CPI (red ON / green OFF) Protection degree IEC/EN 60529 IP20 / IPXXB, IP40 in enclosure with cover Electrical endurance ops. 10,000 ops. (AC), 1,000 ops. (DC) Mechanical endurance ops. 20,000 ops. Shock resistance IEC/EN 60068-2-27 30 g - 3 shocks - 11 ms Vibration resistance IEC/EN 60068-2-6 5g - 20 cycles at 5…150…5 Hz with load 0.8 I n Tropicalization (damp heat cyclic) IEC/EN 60068-2-30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100% Ambient temperature °C -25 … +55°C Storage temperature °C -40 … +70°C Reference temperature for tripping characteristics IEC/EN 60898-2 IEC/EN 60947-2 °C B: 30°C K, Z: 20°C Installation Terminal Cage (shock protected) Cross-section of conductors (top / bottom) IEC/EN 60898-2 / 60947-2 mm 2 25 mm2 / 25 mm2 UL/CSA AWG 18 - 4 AWG Cross-section of busbars (top / bottom) IEC/EN 60898-2 / 60947-2 mm 2 16 mm2 / 16 mm2 UL/CSA AWG – Torque IEC/EN Nm 2.5 Nm UL/CSA in-Ibs. 17.5 in-lbs. Screwdriver No. 2 Pozidrive Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip Mounting position Any Supply Please note polarity of device Dimensions and weight Mounting dimensions DIN 43880 Mounting dimension 1 Pole dimensions (H x D x W) mm 90 x 69 x 17.5 mm Pole weight g ca. 140 g Combination with aux. elements signal contact/auxiliary switch Yes shunt trip Yes undervoltage release Yes

2CSC400475F0201 2CSC400474F0201 B Selection tables MCBs S 280 series UC max voltage 220 V DC 1 pole, 440 V DC 2, 3 and 4 poles S 280 series UC B characteristic Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems; version dedicated to application in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles. Applications: industrial. Standard: Acc. to IEC/EN 60898-2 Icn=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016779 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 6 S281-UC B 6 GHS2810164R0065 162302 0.130 10/40 10 S281-UC B10 GHS2810164R0105 162401 0.130 10/40 UBmax 16 S281-UC B16 GHS2810164R0165 162500 0.130 10/40 254 V~ 20 S281-UC B20 GHS2810164R0205 162609 0.130 10/40 242 V –... 25 S281-UC B25 GHS2810164R0255 162708 0.130 10/40 2 6 S282-UC B 6 GHS2820164R0065 162807 0.260 5/20 10 S282-UC B10 GHS2820164R0105 162906 0.260 5/20 UBmax 16 S282-UC B16 GHS2820164R0165 163002 0.260 5/20 440 V~ 20 S282-UC B20 GHS2820164R0205 163101 0.260 5/20 440 V –... 25 S282-UC B25 GHS2820164R0255 163200 0.260 5/20

2CSC400474F02012CSC400475F0201 Selection tables MCBs S 280 series UC max voltage 220 V DC 1 pole, 440 V DC 2, 3 and 4 poles S 280 series UC K (power) characteristic Function: protection and control of the circuits like motors and auxiliary circuits, against overloads and short-circuits; version dedicated to application in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles. Advantages: no nuisance tripping in the case of functional peak currents up to 8xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: industrial. Standard: Acc. to IEC/EN 60947-2 Icu=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4012233 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.2 S 281 UC-K 0.2 GHS2810164R0087 634200 0.130 10/40 0.3 S 281 UC-K 0.3 GHS2810164R0117 634309 0.130 10/40 0.5 S 281 UC-K 0.5 GHS2810164R0157 634408 0.130 10/40 0.75 S 281 UC-K 0.75 GHS2810164R0187 635504 0.130 10/40 1 S 281 UC-K 1 GHS2810164R0217 634606 0.130 10/40 1.6 S 281 UC-K 1.6 GHS2810164R0257 634705 0.130 10/40 2 S 281 UC-K 2 GHS2810164R0277 634804 0.130 10/40 3 S 281 UC-K 3 GHS2810164R0317 634903 0.130 10/40 4 S 281 UC-K 4 GHS2810164R0337 635009 0.130 10/40 6 S 281 UC-K 6 GHS2810164R0377 635207 0.130 10/40 8 S 281 UC-K 8 GHS2810164R0407 635108 0.130 10/40 10 S 281 UC-K 10 GHS2810164R0427 635306 0.130 10/40 16 S 281 UC-K 16 GHS2810164R0467 635405 0.130 10/40 20 S 281 UC-K 20 GHS2810164R0487 635603 0.130 10/40 25 S 281 UC-K 25 GHS2810164R0517 635702 0.130 10/40 32 S 281 UC-K 32 GHS2810164R0537 635801 0.130 10/40 UBmax 40 S 281 UC-K 40 GHS2810164R0557 635900 0.130 10/40 254 V~ 50 S 281 UC-K 50 GHS2810164R0577 636006 0.160 10/40 242 V –... 63 S 281 UC-K 63 GHS2810164R0607 636105 0.160 10/40 2 0.2 S 282 UC-K 0.2 GHS2820164R0087 636204 0.260 5/20 0.3 S 282 UC-K 0.3 GHS2820164R0117 636303 0.260 5/20 0.5 S 282 UC-K 0.5 GHS2820164R0157 636402 0.260 5/20 0.75 S 282 UC-K 0.75 GHS2820164R0187 636501 0.260 5/20 1 S 282 UC-K 1 GHS2820164R0217 636600 0.260 5/20 1.6 S 282 UC-K 1.6 GHS2820164R0257 636709 0.260 5/20 2 S 282 UC-K 2 GHS2820164R0277 652808 0.260 5/20 3 S 282 UC-K 3 GHS2820164R0317 636808 0.260 5/20 4 S 282 UC-K 4 GHS2820164R0337 636907 0.260 5/20 6 S 282 UC-K 6 GHS2820164R0377 637003 0.260 5/20 8 S 282 UC-K 8 GHS2820164R0407 637102 0.260 5/20 10 S 282 UC-K 10 GHS2820164R0427 637201 0.260 5/20 16 S 282 UC-K 16 GHS2820164R0467 637300 0.260 5/20 20 S 282 UC-K 20 GHS2820164R0487 637409 0.260 5/20 25 S 282 UC-K 25 GHS2820164R0517 637508 0.260 5/20 32 S 282 UC-K 32 GHS2820164R0537 637607 0.260 5/20 UBmax 40 S 282 UC-K 40 GHS2820164R0557 637706 0.260 5/20 440 V~ 50 S 282 UC-K 50 GHS2820164R0577 637904 0.320 5/20 440 V –... 63 S 282 UC-K 63 GHS2820164R0607 638000 0.320 5/20 K

2CSC400479F0201 2CSC400478F0201 Selection tables MCBs S 280 series UC max voltage 220 V DC 1 pole, 440 V DC 2, 3 and 4 poles 3 0.2 S 283 UC-K 0.2 GHS2830164R0087 738106 0.390 3/12 0.3 S 283 UC-K 0.3 GHS2830164R0117 738205 0.390 3/12 0.5 S 283 UC-K 0.5 GHS2830164R0157 738304 0.390 3/12 0.75 S 283 UC-K 0.75 GHS2830164R0187 738403 0.390 3/12 1 S 283 UC-K 1 GHS2830164R0217 738502 0.390 3/12 1.6 S 283 UC-K 1.6 GHS2830164R0257 738601 0.390 3/12 2 S 283 UC-K 2 GHS2830164R0277 738700 0.390 3/12 3 S 283 UC-K 3 GHS2830164R0317 738809 0.390 3/12 4 S 283 UC-K 4 GHS2830164R0337 738908 0.390 3/12 6 S 283 UC-K 6 GHS2830164R0377 739004 0.390 3/12 8 S 283 UC-K 8 GHS2830164R0407 739103 0.390 3/12 10 S 283 UC-K 10 GHS2830164R0427 739202 0.390 3/12 16 S 283 UC-K 16 GHS2830164R0467 739301 0.390 3/12 20 S 283 UC-K 20 GHS2830164R0487 739400 0.390 3/12 25 S 283 UC-K 25 GHS2830164R0517 739509 0.390 3/12 32 S 283 UC-K 32 GHS2830164R0537 739608 0.390 3/12 UBmax 40 S 283 UC-K 40 GHS2830164R0557 739707 0.390 3/12 440 V~ 50 S 283 UC-K 50 GHS2830164R0577 739806 0.480 3/12 440 V –... 63 S 283 UC-K 63 GHS2830164R0607 739905 0.480 3/12 4 0.2 S 284 UC-K 0.2 GHS2840164R0087 741601 0.520 2 0.3 S 284 UC-K 0.3 GHS2840164R0117 741700 0.520 2 0.5 S 284 UC-K 0.5 GHS2840164R0157 741809 0.520 2 0.75 S 284 UC-K 0.75 GHS2840164R0187 741908 0.520 2 1 S 284 UC-K 1 GHS2840164R0217 742004 0.520 2 1.6 S 284 UC-K 1.6 GHS2840164R0257 742103 0.520 2 2 S 284 UC-K 2 GHS2840164R0277 742202 0.520 2 3 S 284 UC-K 3 GHS2840164R0317 742301 0.520 2 4 S 284 UC-K 4 GHS2840164R0337 742400 0.520 2 6 S 284 UC-K 6 GHS2840164R0377 742509 0.520 2 8 S 284 UC-K 8 GHS2840164R0407 742608 0.520 2 10 S 284 UC-K 10 GHS2840164R0427 742707 0.520 2 16 S 284 UC-K 16 GHS2840164R0467 742806 0.520 2 20 S 284 UC-K 20 GHS2840164R0487 743001 0.520 2

25 S 284 UC-K 25 GHS2840164R0517 743100

0.520 2 32 S 284 UC-K 32 GHS2840164R0537 743209 0.520 2 UBmax 40 S 284 UC-K 40 GHS2840164R0557 743308 0.520 2 440 V~ 50 S 284 UC-K 50 GHS2840164R0577 743407 0.640 2 440 V –... 63 S 284 UC-K 63 GHS2840164R0607 743506 0.640 2 K

2CSC400481F0201 2CSC400480F0201 Z Selection tables MCBs S 280 series UC max voltage 220 V DC 1 pole, 440 V DC 2, 3 and 4 poles S 280 series UC Z characteristic Function: protection and control of the electronic circuits against weak and long duration overloads and short-circuits; version dedicated to application in direct current circuits for voltages up to 220 V DC 1 pole and 440 V DC 2, 3 and 4 poles. Applications: industrial. Standard: Acc. to IEC/EN 60947-2 Icu=6 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4012233 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 0.5 S 281 UC-Z 0.5 GHS2810164R0158 638604 0.130 10/40 1 S 281 UC-Z 1 GHS2810164R0218 638703 0.130 10/40 1.6 S 281 UC-Z 1.6 GHS2810164R0258 638802 0.130 10/40 2 S 281 UC-Z 2 GHS2810164R0278 638901 0.130 10/40 3 S 281 UC-Z 3 GHS2810164R0318 639007 0.130 10/40 4 S 281 UC-Z 4 GHS2810164R0338 639106 0.130 10/40 6 S 281 UC-Z 6 GHS2810164R0378 639205 0.130 10/40 8 S 281 UC-Z 8 GHS2810164R0408 639403 0.130 10/40 10 S 281 UC-Z 10 GHS2810164R0428 639502 0.130 10/40 16 S 281 UC-Z 16 GHS2810164R0468 639601 0.130 10/40 20 S 281 UC-Z 20 GHS2810164R0488 639700 0.130 10/40 25 S 281 UC-Z 25 GHS2810164R0518 639809 0.130 10/40 32 S 281 UC-Z 32 GHS2810164R0538 639908 0.130 10/40 UBmax 40 S 281 UC-Z 40 GHS2810164R0558 640003 0.130 10/40

254 V~ 50 S 281 UC-Z 50

GHS2810164R0578 640102 0.160 10/40 242 V –... 63 S 281 UC-Z 63 GHS2810164R0608 640201 0.160 10/40 2 0.5 S 282 UC-Z 0.5 GHS2820164R0158 640300 0.260 5/20 1 S 282 UC-Z 1 GHS2820164R0218 640409 0.260 5/20 1.6 S 282 UC-Z 1.6 GHS2820164R0258 642304 0.260 5/20 2 S 282 UC-Z 2 GHS2820164R0278 641000 0.260 5/20 3 S 282 UC-Z 3 GHS2820164R0318 641109 0.260 5/20 4 S 282 UC-Z 4 GHS2820164R0338 641208 0.260 5/20 6 S 282 UC-Z 6 GHS2820164R0378 641307 0.260 5/20 8 S 282 UC-Z 8 GHS2820164R0408 641406 0.260 5/20 10 S 282 UC-Z 10 GHS2820164R0428 641505 0.260 5/20 16 S 282 UC-Z 16 GHS2820164R0468 641604 0.260 5/20 20 S 282 UC-Z 20 GHS2820164R0488 641703 0.260 5/20 25 S 282 UC-Z 25 GHS2820164R0518 641802 0.260 5/20 32 S 282 UC-Z 32 GHS2820164R0538 641901 0.260 5/20 UBmax 40 S 282 UC-Z 40 GHS2820164R0558 642007 0.260 5/20 440 V~ 50 S 282 UC-Z 50 GHS2820164R0578 642106 0.320 5/20 440 V –... 63 S 282 UC-Z 63 GHS2820164R0608 642205 0.320 5/20

2CSC400479F0201 2CSC400478F0201 Z Selection tables MCBs S 280 series UC max voltage 220 V DC 1 pole, 440 V DC 2, 3 and 4 poles 3 0.5 S 283 UC-Z 0.5 GHS2830164R0158 740000 0.390 3/12 1 S 283 UC-Z 1 GHS2830164R0218 740109 0.390 3/12 1.6 S 283 UC-Z 1.6 GHS2830164R0258 740208 0.390 3/12 2 S 283 UC-Z 2 GHS2830164R0278 740307 0.390 3/12 3 S 283 UC-Z 3 GHS2830164R0318 740406 0.390 3/12 4 S 283 UC-Z 4 GHS2830164R0338 740505 0.390 3/12 6 S 283 UC-Z 6 GHS2830164R0378 740604 0.390 3/12 8 S 283 UC-Z 8 GHS2830164R0408 740703 0.390 3/12 10 S 283 UC-Z 10 GHS2830164R0428 740802 0.390 3/12 16 S 283 UC-Z 16 GHS2830164R0468 740901 0.390 3/12 20 S 283 UC-Z 20 GHS2830164R0488 741007 0.390 3/12 25 S 283 UC-Z 25 GHS2830164R0518 741106 0.390 3/12 32 S 283 UC-Z 32 GHS2830164R0538 741205 0.390 3/12 UBmax 40 S 283 UC-Z 40 GHS2830164R0558 741304 0.390 3/12 440 V~ 50 S 283 UC-Z 50 GHS2830164R0578 741403 0.480 3/12 440 V –... 63 S 283 UC-Z 63 GHS2830164R0608 741502 0.480 3/12 4 0.5 S 284 UC-Z 0.5 GHS2840164R0158 743605 0.520 2 1 S 284 UC-Z 1 GHS2840164R0218 743704 0.520 2 1.6 S 284 UC-Z 1.6 GHS2840164R0258 743803 0.520 2 2 S 284 UC-Z 2 GHS2840164R0278 743902 0.520 2 3 S 284 UC-Z 3 GHS2840164R0318 744008 0.520 2 4 S 284 UC-Z 4 GHS2840164R0338 744107 0.520 2 6 S 284 UC-Z 6 GHS2840164R0378 744206 0.520 2 8 S 284 UC-Z 8 GHS2840164R0408 744305 0.520 2 10 S 284 UC-Z 10 GHS2840164R0428 744404 0.520 2 16 S 284 UC-Z 16 GHS2840164R0468 744503 0.520 2 20 S 284 UC-Z 20 GHS2840164R0488 744602 0.520 2 25 S 284 UC-Z 25 GHS2840164R0518 744701 0.520 2 32 S 284 UC-Z 32 GHS2840164R0538 744800 0.520 2 UBmax 40 S 284 UC-Z 40 GHS2840164R0558 744909 0.520 2 440 V~ 50 S 284 UC-Z 50 GHS2840164R0578 745005 0.640 2 440 V –... 63 S 284 UC-Z 63 GHS2840164R0608 745104 0.640 2

Electrical Data Standards IEC/EN IEC/EN 60898-1, IEC/EN 60947-2 UL/CSA UL 1077 Poles 1P , 2P , 3P , 4P Tripping characteristics B, C, D, K Rated current I n A 80…125 A Rated voltage Un IEC/EN 60898-1 V 1P: 230 V AC 2...4P: 400 V AC Rated voltage Un IEC/EN 60898-2 V – Rated voltage Ue IEC/EN 60947-2 V 1P: 230 V AC 2...4P: 230/400 V AC Rated voltage UL/CSA V 1P: 277 V AC 2...4P: 480/277 V AC Insulation voltage Ui IEC/EN 60898-1 / 60947-2 V 250 V AC (phase to ground), Max. operating voltage UBmax. V IEC: 253/440 V AC UL: 480/277 V AC IEC/UL 1P: 60 V DC; 2P ...4P: 125 V DC Min. operating voltage UBmin. V 24 V AC - 24 V DC Rated frequency f Hz 50 / 60 Hz Rated short-circuit capacity I cn IEC/EN 60898-1 kA 10 kA Ultimate short-circuit capacity Icu IEC/EN 60947-2 kA B, C: 20 kA D, K: 15 kA Service short-circuit capacity Ics IEC/EN 60947-2 kA B, C: 10 kA D, K: 8 kA Rated interrupting capacity UL 1077 kA 5 kA Energy limiting class IEC/EN 60898-1 – Overvoltage category IEC/EN 60898-1 / 60947-2 III Pollution degree IEC/EN 60898-1 3 IEC/EN 60947-2 – Rated impulse withstand voltage U imp. (1.2/50 μs) IEC/EN 60898-1 / 60947-2 kV 4 kV (test voltage 6.2kV at sea level, 5 kV at 2,000 m) Dielectric test voltage IEC/EN 60898-1 kV 2 kV (50 / 60 Hz, 1 min.) Mechanical Data Housing Toggle black, sealable Contact position indication Real CPI (red ON / green OFF) Protection degree IEC/EN 60529 IP20 with connected conductors / IPXXB, IP40 in enclosure with cover Electrical endurance ops. 10,000 ops. Mechanical endurance ops. 20,000 ops. Shock resistance IEC/EN 60068-2-27 15 g - 1 shock - 11 ms Vibration resistance IEC/EN 60068-2-6 5g at 25…150 Hz, 6g at 35 Hz (4s) with load 0.8 I n Tropicalization (damp heat cyclic) IEC/EN 60068-2-30 °C/RH 28 cycles with 55°C/90-96% and 25°C/95-100% Ambient temperature °C -25 … +45°C Storage temperature °C -40 … +70°C Reference temperature for tripping characteristics IEC/EN 60898-1 IEC/EN 60947-2 °C B, C, D: 30°C K: 20°C Installation Terminal Cage (shock protected) Cross-section of conductors (top / bottom) IEC/EN 60898-1 / 60947-2 mm 2 50 mm2 / 50 mm2 UL/CSA AWG 14 - 2 AWG Cross-section of busbars (top / bottom) IEC/EN 60898-1 / 60947-2 mm 2 – UL/CSA AWG – UL/CSA in-Ibs. 22 - 31 in-lbs. Screwdriver No. 2 Pozidrive Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip Mounting position Any Supply Optional Dimensions and weight Mounting dimensions DIN 43880 – Pole dimensions (H x D x W) mm 90 x 70 x 26.25 mm Pole weight g ca. 258 g Combination with aux. elements signal contact/auxiliary switch Yes shunt trip Yes undervoltage release Yes

Function: protection and control of the circuits against overloads and short-circuits; protection for people and big length cables in TN and IT systems. Applications: commercial and industrial. Standard: IEC/EN 60898-1, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016797 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S291 B 80 GHS2912001R0805 12163 0.267 1/6 100 S291 B100 GHS2912001R0825 12170 0.267 1/6 125 S291 B125 GHS2912001R0845 12187 0.267 1/6 2 80 S292 B 80 GHS2922001R0805 09583 0.534 1/3 100 S292 B100 GHS2922001R0825 09590 0.534 1/3 125 S292 B125 GHS2922001R0845 12194 0.534 1/3 3 80 S293 B 80 GHS2932001R0805 09606 0.801 1/2 100 S293 B100 GHS2932001R0825 09613 0.801 1/2 125 S293 B125 GHS2932001R0845 12200 0.801 1/2 4 80 S294 B 80 GHS2942001R0805 11968 1.068 1 100 S294 B100 GHS2942001R0825 11975 1.068 1 125 S294 B125 GHS2942001R0845 12217 1.068 1 2CSC400010F0201 2CSC400020F02012CSC400011F02012CSC400012F0201 B 10000

Function: protection and control of the circuits against overloads and short-circuits when high nominal currents are required; protection for resistive and inductive loads with low inrush current. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016799 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S291 C 80 GHS2912001R0804 570541 0.267 1/6 100 S291 C100 GHS2912001R0824 570572 0.267 1/6 125 S291 C125 GHS2912001R0844 570602 0.267 1/6 2 80 S292 C 80 GHS2922001R0804 570626 0.534 1/3 100 S292 C100 GHS2922001R0824 570657 0.534 1/3 125 S292 C125 GHS2922001R0844 570688 0.534 1/3 3 80 S293 C 80 GHS2932001R0804 570701 0.801 1/2 100 S293 C100 GHS2932001R0824 570732 0.801 1/2 125 S293 C125 GHS2932001R0844 570763 0.801 1/2 4 80 S294 C 80 GHS2942001R0804 570787 1.068 1 100 S294 C100 GHS2942001R0824 570732 1.068 1 125 S294 C125 GHS2942001R0844 570848 1.068 1 2CSC400010F0201 2CSC400020F02012CSC400011F02012CSC400012F0201 C 10000

Function: protection and control of the circuits against overloads and short-circuits when high nominal current are required; protection for circuits which supply loads with high inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps). Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016799 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S291 D 80 GHS2912001R0801 120807 0.267 1/6 100 S291 D100 GHS2912001R0821 120906 0.267 1/6 2 80 S292 D 80 GHS2922001R0801 121002 0.534 1/3 100 S292 D100 GHS2922001R0821 121507 0.534 1/3 3 80 S293 D 80 GHS2932001R0801 121705 0.801 1/2 100 S293 D100 GHS2932001R0821 121804 0.801 1/2 4 80 S294 D 80 GHS2942001R0801 121200 1.068 1 100 S294 D100 GHS2942001R0821 121309 1.068 1 System pro M S 290 DSelection tables MCBs S 290 series 2CSC400010F0201 2CSC400020F02012CSC400011F02012CSC400012F0201 D 10000

S 290 K (power) characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when high nominal current are required. Advantages: no nuisance tripping in the case of functional peak currents up to 8xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, VDE 0660 Part 101 Icn=10 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 4016799 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1 80 S291 K 80 GHS2912001R0807 570558 0.267 1/6 100 S291 K100 GHS2912001R0827 570589 0.267 1/6 2 80 S292 K 80 GHS2922001R0807 570633 0.534 1/3 100 S292 K100 GHS2922001R0827 570664 0.534 1/3 3 80 S293 K 80 GHS2932001R0807 570718 0.801 1/2 100 S293 K100 GHS2932001R0827 570749 0.801 1/2 4 80 S294 K 80 GHS2942001R0807 570794 1.068 1 100 S294 K100 GHS2942001R0827 570824 1.068 1 2CSC400010F0201 2CSC400020F02012CSC400011F02012CSC400012F0201 K 10000

Standards E DIN VDE 0645, IEC/EN 60947-2 (VDE 0660-101) Electrical features Rated current, In [A] 10 … 100 Reated voltage, Un [V] 230/400 Tripping characteristic E, K thermal tripping 1,05 … 1,2 x In short-time delayed tripping E: 5 … 6,25 x In K: 10 … 14 x In (≤ 50 A), 8 …12 x In (≥ 63 A) minimum tripping delay [ms] 10 Rated breaking capacity [kA] 25 Rated frequency [Hz] 50 Rated isolation voltage [V] 690 Rated impulse withstand capability (at 2000 m) [kV] 6 Impulse withstand test voltage (1.2/50 μs) [kV] 12.3 Isolation coordination overvoltage category IV pollution degree 3 isolation function acc. to IEC 60364-53, VDE 0100-537 Dielectric strength test voltage [V] 2000 (50 Hz, 1 min.) IP protection depending on type of terminal cover Mechanical fea- tures Mechanical switching cycles without load 1000 with rated current 1000 Shock resistance 30 g (≥ 3 shocks, 11 ms) Resistance to vibrations 2 g (20 cycles 5…150…5 Hz) Reference temperature [°C] 30 (E), 20 (K) Ambient temperature storage [°C] -40 ... +70 operating [°C] -25 ... +55 Sealing/locking sealable with 1 mm wire, lockable with 3 mm padlock,see also special accessories Installation Mounting surface mounting with 2 screws, DIN rail mounting (35 mm DIN rail acc. to EN 60715, 40 mm- busbar systems (4/5-pole, 5/10 mm x 12 mm) Terminal type saddle clamping Terminal size capable to connect solid and rigid stranded conductors incl. flexible conductors 2.5…50 mm2/70 mm2 Terminal screws tighning torque [Nm] 2.5 … 3 Max. torque for surface mounting [Nm] 2.5 … 3 (only fl at-headed screws, no circlips) Source/load side no preferencies Dimensions and weight Size see drawings Weight see order tables Accessories Factory assembled auxiliary switch (2 change-over contacts) Terminal covers Handle covers Busbar adapters DIN rail adapters Locking devices System pro M S700Technical features MCBs S700 series

pro M compact® S700 ESelection tables Selective Main Circuit Breakers S700 series S700 E characteristic Breakers of the S700 series are selective main circuit breakers for overcurrent protection in electrical installations. They have total selectivity to downstream mcb’s and outstanding selectivity to upstream protective devices due to unique current limiting selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate isolation function, they are predestinated for the use in any main distribution cabinet or meter board. The S700 product range is completed by a broad range of accessories. With dedicated adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping characteristic E and K - optional with factory assembled auxiliary switch. Number of poles Rated current Order details Bbn 4012233 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S701-E 10 GHS7015001 R0449 522507 0.55 3 16 S701-E 16 GHS7015001 R0469 522705 0.55 3 20 S701-E 20 GHS7015001 R0489 522903 0.55 3 25 S701-E 25 GHS7015001 R0519 523108 0.55 3 32 S701-E 32 GHS7015001 R0529 523207 0.55 3 35 S701-E 35 GHS7015001 R0539 523405 0.55 3 40 S701-E 40 GHS7015001 R0559 523603 0.55 3 50 S701-E 50 GHS7015001 R0579 523801 0.55 3 63 S701-E 63 GHS7015001 R0599 524006 0.55 3 80 S701-E 80 GHS7015001 R0629 524204 0.55 3 100 S701-E 100 GHS7015001 R0639 524402 0.55 3 2 16 S702-E 16 GHS7025001 R0469 1052001) 1.1 2 20 S702-E 20 GHS7025001 R0489 949007 1.1 2 25 S702-E 25 GHS7025001 R0519 1040051) 1.1 2 32 S702-E 32 GHS7025001 R0529 1054081) 1.1 2 35 S702-E 35 GHS7025001 R0539 1053091) 1.1 2 40 S702-E 40 GHS7025001 R0559 1055071) 1.1 2 50 S702-E 50 GHS7025001 R0579 1056061) 1.1 2 63 S702-E 63 GHS7025001 R0599 0520091) 1.1 2 80 S702-E 80 GHS7025001 R0629 1096041) 1.1 2 100 S702-E 100 GHS7025001 R0639 0625031) 1.1 2 3 16 S703-E 16 GHS7035001 R0469 865703 1.65 1 20 S703-E 20 GHS7035001 R0489 526307 1.65 1 25 S703-E 25 GHS7035001 R0519 526505 1.65 1 32 S703-E 32 GHS7035001 R0529 526604 1.65 1 35 S703-E 35 GHS7035001 R0539 526802 1.65 1 40 S703-E 40 GHS7035001 R0559 527007 1.65 1 50 S703-E 50 GHS7035001 R0579 527205 1.65 1 63 S703-E 63 GHS7035001 R0599 527403 1.65 1 80 S703-E 80 GHS7035001 R0629 527601 1.65 1 100 S703-E 100 GHS7035001 R0639 527809 1.65 1 4 16 S704-E 16 GHS7045001 R0469 1106001) 2.2 1 20 S704-E 20 GHS7045001 R0489 1107091) 2.2 1 25 S704-E 25 GHS7045001 R0519 1041041) 2.2 1 32 S704-E 32 GHS7045001 R0529 1108081) 2.2 1 35 S704-E 35 GHS7045001 R0539 1042031) 2.2 1 40 S704-E 40 GHS7045001 R0559 1109071) 2.2 1 50 S704-E 50 GHS7045001 R0579 1110031) 2.2 1 63 S704-E 63 GHS7045001 R0599 1111021) 2.2 1 80 S704-E 80 GHS7045001 R0629 1112011) 2.2 1 100 S704-E 100 GHS7045001 R0639 0626021) 2.2 1 1) bbn-Nr. 40 16779 E selective 25.000 A S0029b98S0011b95S0001B95S0012b95

pro M compact® S700 KSelection tables Selective Main Circuit Breakers S700 series S700 K characteristic Breakers of the S700 series are selective main circuit breakers for overcurrent protection in electrical installations. They have total selectivity to downstream mcb’s and outstanding selectivity to upstream protective devices due to unique current limiting selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate isolation function, they are predestinated for the use in any main distribution cabinet or meter board. The S700 product range is completed by a broad range of accessories. With dedicated adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping characteristic E and K - optional with factory assembled auxiliary switch. Number of poles Rated current Order details Bbn 4012233 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 16 S701-K 16 GHS7015001R0467 522606 0.55 3 20 S701-K 20 GHS7015001R0487 522804 0.55 3 25 S701-K 25 GHS7015001R0517 523009 0.55 3 35 S701-K 35 GHS7015001R0537 523306 0.55 3 40 S701-K 40 GHS7015001R0557 523504 0.55 3 50 S701-K 50 GHS7015001R0577 523702 0.55 3 63 S701-K 63 GHS7015001R0597 523900 0.55 3 80 S701-K 80 GHS7015001R0627 524105 0.55 3 100 S701-K 100 GHS7015001R0637 524303 0.55 3 2 16 S702-K 16 GHS7025001R0467 1098021) 1.1 2 20 S702-K 20 GHS7025001R0487 1097031) 1.1 2 25 S702-K 25 GHS7025001R0517 1099011) 1.1 2 35 S702-K 35 GHS7025001R0537 1100061) 1.1 2 40 S702-K 40 GHS7025001R0557 1101051) 1.1 2 50 S702-K 50 GHS7025001R0577 1102041) 1.1 2 63 S702-K 63 GHS7025001R0597 1103031) 1.1 2 80 S702-K 80 GHS7025001R0627 1104021) 1.1 2 100 S702-K 100 GHS7025001R0637 1105011) 1.1 2 3 16 S703-K 16 GHS7035001R0467 526109 1.65 1 20 S703-K 20 GHS7035001R0487 526208 1.65 1 25 S703-K 25 GHS7035001R0517 526406 1.65 1 35 S703-K 35 GHS7035001R0537 526703 1.65 1 40 S703-K 40 GHS7035001R0557 526901 1.65 1 50 S703-K 50 GHS7035001R0577 527106 1.65 1 63 S703-K 63 GHS7035001R0597 527304 1.65 1 80 S703-K 80 GHS7035001R0627 527502 1.65 1 100 S703-K 100 GHS7035001R0637 527700 1.65 1 4 16 S704-K 16 GHS7045001R0467 1113001) 2.2 1 20 S704-K 20 GHS7045001R0487 1114091) 2.2 1 25 S704-K 25 GHS7045001R0517 1115081) 2.2 1 35 S704-K 35 GHS7045001R0537 1116071) 2.2 1 40 S704-K 40 GHS7045001R0557 1117061) 2.2 1 50 S704-K 50 GHS7045001R0577 965205 2.2 1 63 S704-K 63 GHS7045001R0597 955503 2.2 1 80 S704-K 80 GHS7045001R0627 1118051) 2.2 1 100 S704-K 100 GHS7045001R0637 1119041) 2.2 1 1) bbn-Nr. 40 16779 K selective 25.000 A S0029b98S0011b95S0001B95S0012b95

pro M compact® S700 E+H2WRSelection tables Selective Main Circuit Breakers S700 series S700 E characteristic Breakers of the S700 series are selective main circuit breakers for overcurrent protection in electrical installations. They have total selectivity to downstream mcb’s and outstanding selectivity to upstream protective devices due to unique current limiting selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate isolation function, they are predestinated for the use in any main distribution cabinet or meter board. The S700 product range is completed by a broad range of accessories. With dedicated adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping characteristic E and K - optional with factory assembled auxiliary switch. With factory assembled auxiliary switch (change-over contacts) Number of poles Rated current Order details Bbn 4012233 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 16 S701-E 16+H2WR GHS7010316 R0469 456609 0.65 3 20 S701-E 20+H2WR GHS7010316 R0489 456708 0.65 3 25 S701-E 25+H2WR GHS7010316 R0519 456807 0.65 3 32 S701-E 32+H2WR GHS7010316 R0529 456906 0.65 3 35 S701-E 35+H2WR GHS7010316 R0539 457002 0.65 3 40 S701-E 40+H2WR GHS7010316 R0559 457101 0.65 3 50 S701-E 50+H2WR GHS7010316 R0579 457200 0.65 3 63 S701-E 63+H2WR GHS7010316 R0599 457309 0.65 3 80 S701-E 80+H2WR GHS7010316 R0629 457408 0.65 3 100 S701-E 100+H2WR GHS7010316 R0639 457507 0.65 3 2 16 S702-E 16+H2WR GHS7020316 R0469 458405 1.2 2 20 S702-E 20+H2WR GHS7020316 R0489 458504 1.2 2 25 S702-E 25+H2WR GHS7020316 R0519 458603 1.2 2 32 S702-E 32+H2WR GHS7020316 R0529 458702 1.2 2 35 S702-E 35+H2WR GHS7020316 R0539 458801 1.2 2 40 S702-E 40+H2WR GHS7020316 R0559 458900 1.2 2 50 S702-E 50+H2WR GHS7020316 R0579 459006 1.2 2 63 S702-E 63+H2WR GHS7020316 R0599 459105 1.2 2 80 S702-E 80+H2WR GHS7020316 R0629 459204 1.2 2 100 S702-E 100+H2WR GHS7020316 R0639 459303 1.2 2 3 16 S703-E 16+H2WR GHS7030316 R0469 460200 1.75 1 20 S703-E 20+H2WR GHS7030316 R0489 460309 1.75 1 25 S703-E 25+H2WR GHS7030316 R0519 460408 1.75 1 32 S703-E 32+H2WR GHS7030316 R0529 460507 1.75 1 35 S703-E 35+H2WR GHS7030316 R0539 460606 1.75 1 40 S703-E 40+H2WR GHS7030316 R0559 460705 1.75 1 50 S703-E 50+H2WR GHS7030316 R0579 460804 1.75 1 63 S703-E 63+H2WR GHS7030316 R0599 460903 1.75 1 80 S703-E 80+H2WR GHS7030316 R0629 461009 1.75 1 100 S703-E 100+H2WR GHS7030316 R0639 461108 1.75 1 4 16 S704-E 16+H2WR GHS7040316 R0469 462006 2.3 1 20 S704-E 20+H2WR GHS7040316 R0489 462105 2.3 1 25 S704-E 25+H2WR GHS7040316 R0519 462204 2.3 1 32 S704-E 32+H2WR GHS7040316 R0529 462303 2.3 1 35 S704-E 35+H2WR GHS7040316 R0539 462402 2.3 1 40 S704-E 40+H2WR GHS7040316 R0559 462501 2.3 1 50 S704-E 50+H2WR GHS7040316 R0579 462600 2.3 1 63 S704-E 63+H2WR GHS7040316 R0599 462709 2.3 1 80 S704-E 80+H2WR GHS7040316 R0629 462808 2.3 1 100 S704-E 100+H2WR GHS7040316 R0639 462907 2.3 1 E selective 25.000 A S0029b98S0011b95S0001B95S0012b95

pro M compact® S700 K+H2WRSelection tables Selective Main Circuit Breakers S700 series S700 K characteristic Breakers of the S700 series are selective main circuit breakers for overcurrent protection in electrical installations. They have total selectivity to downstream mcb’s and outstanding selectivity to upstream protective devices due to unique current limiting selectivity. Since S700 breakers are designed for overvoltage category IV and incorporate isolation function, they are predestinated for the use in any main distribution cabinet or meter board. The S700 product range is completed by a broad range of accessories. With dedicated adapters, S700 products can be assembled on flat surfaces, on DIN rails or 40 mm busbar systems. To adapt S700 to different installations, they are available 1- to 4-pole with tripping characteristic E and K - optional with factory assembled auxiliary switch. With factory assembled auxiliary switch (change-over contacts) Number of poles Rated current Order details Bbn 4012233 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 16 S701-K 16+H2WR GHS7010316R0467 455800 0.65 3 20 S701-K 20+H2WR GHS7010316R0487 455909 0.65 3 25 S701-K 25+H2WR GHS7010316R0517 456005 0.65 3 35 S701-K 35+H2WR GHS7010316R0537 456104 0.65 3 40 S701-K 40+H2WR GHS7010316R0557 456203 0.65 3 50 S701-K 50+H2WR GHS7010316R0577 456302 0.65 3 63 S701-K 63+H2WR GHS7010316R0597 456401 0.65 3 80 S701-K 80+H2WR GHS7010316R0627 499651 0.65 3 100 S701-K 100+H2WR GHS7010316R0637 499729 0.65 3 2 16 S702-K 16+H2WR GHS7020316R0467 457606 1.2 2 20 S702-K 20+H2WR GHS7020316R0487 457705 1.2 2 25 S702-K 25+H2WR GHS7020316R0517 457804 1.2 2 35 S702-K 35+H2WR GHS7020316R0537 457903 1.2 2 40 S702-K 40+H2WR GHS7020316R0557 458009 1.2 2 50 S702-K 50+H2WR GHS7020316R0577 458108 1.2 2 63 S702-K 63+H2WR GHS7020316R0597 458207 1.2 2 80 S702-K 80+H2WR GHS7020316R0627 499750 1.2 2 100 S702-K 100+H2WR GHS7020316R0637 499767 1.2 2 3 16 S703-K 16+H2WR GHS7030316R0467 459402 1.75 1 20 S703-K 20+H2WR GHS7030316R0487 459501 1.75 1 25 S703-K 25+H2WR GHS7030316R0517 459600 1.75 1 35 S703-K 35+H2WR GHS7030316R0537 459709 1.75 1 40 S703-K 40+H2WR GHS7030316R0557 459808 1.75 1 50 S703-K 50+H2WR GHS7030316R0577 459907 1.75 1 63 S703-K 63+H2WR GHS7030316R0597 460002 1.75 1 80 S703-K 80+H2WR GHS7030316R0627 499774 1.75 1 100 S703-K 100+H2WR GHS7030316R0637 499781 1.75 1 4 16 S704-K 16+H2WR GHS7040316R0467 461207 2.3 1 20 S704-K 20+H2WR GHS7040316R0487 461306 2.3 1 25 S704-K 25+H2WR GHS7040316R0517 461405 2.3 1 35 S704-K 35+H2WR GHS7040316R0537 461504 2.3 1 40 S704-K 40+H2WR GHS7040316R0557 461603 2.3 1 50 S704-K 50+H2WR GHS7040316R0577 461702 2.3 1 63 S704-K 63+H2WR GHS7040316R0597 461801 2.3 1 80 S704-K 80+H2WR GHS7040316R0627 499798 2.3 1 100 S704-K 100+H2WR GHS7040316R0637 499804 2.3 1 K selective 25.000 A S0029b98S0011b95S0001B95S0012b95

pro M compact® Selection tables Selective Short-Circuit Current Limiter WT63 WT63 characteristic WT63 is a short-circuit current limiter for 690 V AC applications. In combination with other ABB devices WT63 offers smart solutions for coordinated motor protection according to IEC/EN 60947-4-1. As a main limiting device, WT63 can increase the short-circuit brea- king capability for several groups of motor circuits to high values at 690 V AC. For further information according to selection and installation see the coordination table. Number of poles Rated current Order details Bbn 4016779 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 3 63 WT63-3 2CDH103012R0599 510677 1.65 1 with factory assembled auxiliary switch (change-over contacts) 3 63 WT63-3 HS 2CDH103816R0599 510684 1.75 1 terminal cover (2 per pole mandatory) S700 KA 1 GHS7001903R0001 5202031) 0.001 6 1) bbn-Nr. 40 12233 Motor starter combinations acc. to IEC/EN 60947-4-1

690 V AC, 35 kA, type 2, normal start-up

Motor short-circuit protection contactor overload protection wiring Rated output Rated current Current limiter manual motor starter tripping current Type safety clear- ance Type current setting range WT63-MMS [kW] [A] [A] [mm] [A] [mm2] 0.37 0.61 WT63-3 or WT63-3 HS MS/MO 325-1.0 11.50 A9 15 TA 25 DU 1.0 0.63-1.0 max. 16 For further combinations please contact the manufacturer. Application notes

  • WT63 may only be used for motor starter combinations confirmed by the manufacturer
  • Max. no. of motor groups to be protected by WT63: 5
  • The wiring between WT63 and MMS has to be short-circuit proof
  • WT63 has to be installed with fitted terminal covers (factory assembled)
  • The max. total operating current of WT63 has to be limited to 63 A, the max. total start-up current shall not exceed 450 A For more details see separate product brochure. S0029b98S0029b98S0029b98

pro M compact® TECHNICAL FEATURES S800S Characteristics available B, C, D K KM UCB, UCK Rated operating voltage Ue (AC) 50/60Hz [V] 400/690 400/690 400/690 - (DC)/pole [V] max. 125 max. 125 max. 125 250 Rated insulation voltage Ui [V] 690 690 690 250 /L54706 Rated impulse withstand voltage Uimp [kV] 8888 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 (AC) 50/60Hz 240/415V [kA] 50 50 50 - (AC) 50/60Hz 254/440V [kA] 30 30 30 - (AC) 50/60Hz 289/500V (up to 80A) [kA] 15 15 15 - (AC) 50/60Hz 289/500V (100...125A) [kA] 10 10 10 - (AC) 50/60Hz 400/690V (up to 80A) [kA] 6 6 6 - (DC) 125V (1-pole) [kA] 30 30 (DC) 250V (1-pole) [kA] - - - 50 (DC) 250V (2-pole) [kA] 30 30 (DC) 375V (3-pole) [kA] 30 30 30 (DC) 500V (2-pole) [kA] - - - 50 (DC) 500V (4-pole) [kA] 30 30 (DC) 750V (3-pole) [kA] - - - 50 (DC) 750V (4-pole) [kA] - - - 50 Rated short-circuit breaking capacity Icn EN 60898-1 (AC) 50/60Hz 240/415V (up to 80A) [kA] 25 - - - Service short-circuit breaking capacity Ics in accordance with IEC 60947-2 -- (AC) 50/60Hz 240/415V [kA] 40 40 40 - (AC) 50/60Hz 254/440V (up to 80A) [kA] 22.5 22.5 22.5 - (AC) 50/60Hz 254/440V (100...125A) [kA] 15 15 15 - (AC) 50/60Hz 289/500V (up to 63A) [kA] 11 11 11 - (AC) 50/60Hz 289/500V (80A) [kA] 8 8 8 - (AC) 50/60Hz 400/690V (up to 80A) [kA] 4 4 4 - (DC) 125V (1-pole) [kA] 30 30 (DC) 250V (1-pole) [kA] - - - 50 (DC) 250V (2-pole) [kA] 30 30 (DC) 375V (3-pole) [kA] 30 30 30 (DC) 500V (2-pole) [kA] - - - 50 (DC) 500V (4-pole) [kA] 30 30 (DC) 750V (3-pole) [kA] - - - 50 (DC) 750V (4-pole) [kA] - - - 50 Service short-circuit breaking capacity Ics in accordance with EN 60898-1 (AC) 50/60Hz 240/415V (up to 80A) [kA] 12.5 - - - Rated frequency [Hz] 50/60, (16 2⁄3) 50/60, (16 2⁄3) 50/60 - Mounting position any Disconnector properties according to IEC 60947-2 yes Standards IEC 60947-2 EN 60898-1 - - - Tightening torque [Nm] min. 3 / max. 4 AC/DC supply any Mounting on DIN top hat rail EN 60715 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Type of protection IP20, IP40 (only actuation side) Classification in accordance with NF-16-101, NF16-102 I3F2 Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat.1/class B /L54706 DC)/pole

pro M compact® TECHNICAL FEATURES S800N Characteristics available B, C, D Max. rated continuous current In [A] 10...125 Poles 1...4 Rated operating voltage Ue (AC) 50/60Hz [V] 400/690 (DC)/pole [V] max. 125 Rated insulation voltage Ui [V] 690 Rated impulse withstand voltage Uimp [kV] 8 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 (AC) 50/60Hz 240/415V [kA] 36 (AC) 50/60Hz 254/440V [kA] 20 (AC) 50/60Hz 289/500V [kA] 10 (AC) 50/60Hz 400/690V [kA] 4.5 (DC) 125V (1-pole) [kA] 20 (DC) 250V (2-poles) [kA] 20 (DC) 375V (3-poles) [kA] 20 (DC) 500V (4-poles) [kA] 20 Rated short-circuit breaking capacity Icn EN 60898-1 (AC) 50/60Hz 240/415V (up to 80A) [kA] 20 Service short-circuit breaking capacity Ics in accordance with IEC 60947-2 (AC) 50/60Hz 240/415V [kA] 30 (AC) 50/60Hz 400/690V [kA] 3 (DC) 125V (1-pole) [kA] 20 (DC) 250V (2-pole) [kA] 20 (DC) 375V (3-pole) [kA] 20 (DC) 500V (4-pole) [kA] 20 Service short-circuit breaking capacity Ics in accordance with EN 60898-1 (AC) 50/60Hz 240/415V (up to 80A) [kA] 10 Rated frequency [Hz] 50/60 Mounting position any Disconnector properties according to IEC 60947-2 yes Standards IEC 60947-2, EN 60898-1 1...70 cable Tightening torque [Nm] min. 3 / max. 4 Supply AC any Mounting on DIN top hat rail EN 60715 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Type of protection IP20, IP40 (only actuation side) Classification in accordance with NF-16-101, NF16-102 I3F2

Characteristics available B, C, D, K Max. rated continuous current In [A] 10...125 Poles 1...4 Rated operating voltage Ue (AC) 50/60Hz [V] 254/440 (DC)/pole [V] max. 125 Rated insulation voltage Ui [V] 500 Rated impulse withstand voltage Uimp [kV] 8 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 (AC) 50/60Hz 240/415V [kA] 25 (AC) 50/60Hz 254/440V [kA] 15 (DC) 125V (1-pole) [kA] 10 (DC) 250V (2-pole) [kA] 10 (DC) 375V (3-pole) [kA] 10 (DC) 500V (4-pole) [kA] 10 Rated short-circuit breaking capacity Icn EN 60898-1 (AC) 50/60Hz 230/400V (characteristic: B, C, D /L54706) [kA] 15 Service short-circuit breaking capacity Ics in accordance with IEC 60947-2 (AC) 50/60Hz 240/415V [kA] 18 (AC) 50/60Hz 254/440V [kA] 10 (DC) 125V (1-pole) [kA] 10 (DC) 250V (2-pole) [kA] 10 (DC) 375V (3-pole) [kA] 10 (DC) 500V (4-pole) [kA] 10 Service short-circuit breaking capacity Ics in accordance with EN 60898-1 (AC) 50/60Hz 230/400V (characteristic: B, C, D /L54706) [kA] 7.5 Rated frequency [Hz] 50/60 Mounting position any Disconnector properties according to IEC 60947-2 yes Standards IEC 60947-2 EN 60898 (B, C, D) 1...70 cable Tightening torque [Nm] min. 3 / max. 4 Supply AC any Mounting on DIN top hat rail EN 60715 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Type of protection IP20 IP40 (only actuation side) Classification in accordance with NF-16-101, NF16-102 I3F2 /L54706 (DC) ≤ 100A; S800C-D125 only IEC 60947-2 S800Technical features MCBs S800 series System pro M compact®

TECHNICAL FEATURES S800U-Z S800U-K Standards UL489, CSA 22.2 No. 5-02, IEC 60947-2 Characteristics available Z/L54706 K/L54707 Rated current In [A] 10...100 Poles 1...4 Rated operating voltage Ue (AC) 50/60Hz [V] 240 Rated interrupting in accordance with UL489 1-pole [kA] 30 2...4-pole [kA] 50 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 (AC) 50/60 Hz 240/415V 1-pole [kA] 30 (AC) 50/60 Hz 240/415V 2 ...4-pole [kA] 50 Service short-circuit capacity Ics in accordance with IEC 60947-2 (AC) 50/60 Hz 240/415V 1-pole [kA] 25 (AC) 50/60 Hz 240/415V 2 ...4-pole [kA] 40 Conductor type Single conductor copper only Wire range 10...100A 8-1AWG Tightening torque 31 in.lbs. (3.5Nm) Mounting position any Permissible ambient temperature for operations [°C] -25...+60 Type of protection IP20 IP40 (only actuation side) Contacts cadmium free Certifications UL listed circuit breaker (File 312425) Standards CSA 22.2 No. 5-02 S800Technical features MCBs S800 series System pro M compact® /L54706 Magnetic release 4xIn /L54707 Magnetic release 8xIn

TECHNICAL FEATURES S800PV-S S800PV-M Characteristics available PV-S - Max. rated continuous current In [A] 10...125 32, 63, 125 Rated operating voltage Ue (AC) 50/60Hz [V] - (DC)/pole [V] 400 /L54706 10...80 A 100, 125 A 32, 63, 125 A (DC)/2 pole [V] 800 600 800 (DC)/3 pole [V] 1200 1000 1200 (DC)/4 pole [V] 1200 1200 1200 Rated insulation voltage Ui [V] 1500 Rated impulse withstand voltage Uimp [kV] 8 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 (DC) 800V (2-pole) [kA] 5 - (DC) 1200V (3-pole) [kA] 5 - (DC) 1200V (4-pole) [kA] 5 - Service short-circuit breaking capacity Ics in accordance with IEC 60947-2 (DC) 800V (2-pole) [kA] 5 - (DC) 1200V (3-pole) [kA] 5 - (DC) 1200V (4-pole) [kA] 5 - Rated short-time withstand current Icw in accordance with IEC 60947-3 (DC) 800V (2-pole) [kA] - 1.5 (DC) 1200V (3-pole) [kA] - 1.5 (DC) 1200V (4-pole) [kA] - 1.5 Rated short-circuit making capacity Icm in accordance with IEC 60947-3 (DC) 800V (2-pole) [kA] - 0.5 (DC) 1200V (3-pole) [kA] - 0.5 (DC) 1200V (4-pole) [kA] - 0.5 Mounting position any Disconnector properties according to IEC 60947-2 yes Standards IEC 60947-2 IEC 60947-3 1...70 cable Tightening torque [Nm] min. 3 / max. 4 DC supply any Mounting on DIN top hat rail EN 60715 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Type of protection IP20 IP40 (only actuation side) Resistance to vibration IEC 60068-2-6; EN 61373 Cat. 1/Class B Utilisation category A DC-21A Pollution degree 2 Overvoltage category III S800Technical features MCBs S800 series System pro M compact® /L54706 4-pole 1200VDC

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-B6* 2CCS861001R0065 408107 0.245 1 8 S801S-B8* 2CCS861001R0085 411329 0.245 1 10 S801S-B10 2CCS861001R0105 200008 0.245 1 13 S801S-B13 2CCS861001R0135 200015 0.245 1 16 S801S-B16 2CCS861001R0165 200022 0.245 1 20 S801S-B20 2CCS861001R0205 200039 0.245 1 25 S801S-B25 2CCS861001R0255 200046 0.245 1 32 S801S-B32 2CCS861001R0325 200053 0.245 1 40 S801S-B40 2CCS861001R0405 200060 0.245 1 50 S801S-B50 2CCS861001R0505 200077 0.245 1 63 S801S-B63 2CCS861001R0635 200084 0.245 1 80 S801S-B80 2CCS861001R0805 200091 0.245 1 100 S801S-B100 2CCS861001R0825 200107 0.245 1 125 S801S-B125 2CCS861001R0845 200114 0.245 1 2 6 S802S-B6* 2CCS862001R0065 408114 0.49 1 8 S802S-B8* 2CCS862001R0085 411336 0.49 1 10 S802S-B10 2CCS862001R0105 200121 0.49 1 13 S802S-B13 2CCS862001R0135 200138 0.49 1 16 S802S-B16 2CCS862001R0165 200145 0.49 1 20 S802S-B20 2CCS862001R0205 200152 0.49 1 25 S802S-B25 2CCS862001R0255 200169 0.49 1 32 S802S-B32 2CCS862001R0325 200176 0.49 1 40 S802S-B40 2CCS862001R0405 200183 0.49 1 50 S802S-B50 2CCS862001R0505 200190 0.49 1 63 S802S-B63 2CCS862001R0635 200206 0.49 1 80 S802S-B80 2CCS862001R0805 200213 0.49 1 100 S802S-B100 2CCS862001R0825 200220 0.49 1 125 S802S-B125 2CCS862001R0845 200237 0.49 1 System pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 B

3 6 S803S-B6* 2CCS863001R0065 408121 0.735 1 8 S803S-B8* 2CCS863001R0085 411343 0.735 1 10 S803S-B10 2CCS863001R0105 200244 0.735 1 13 S803S-B13 2CCS863001R0135 200251 0.735 1 16 S803S-B16 2CCS863001R0165 200268 0.735 1 20 S803S-B20 2CCS863001R0205 200275 0.735 1 25 S803S-B25 2CCS863001R0255 200282 0.735 1 32 S803S-B32 2CCS863001R0325 200299 0.735 1 40 S803S-B40 2CCS863001R0405 200305 0.735 1 50 S803S-B50 2CCS863001R0505 200312 0.735 1 63 S803S-B63 2CCS863001R0635 200329 0.735 1 80 S803S-B80 2CCS863001R0805 200336 0.735 1 100 S803S-B100 2CCS863001R0825 200343 0.735 1 125 S803S-B125 2CCS863001R0845 200350 0.735 1 4 6 S804S-B6* 2CCS864001R0065 408138 0.98 1 8 S804S-B8* 2CCS864001R0085 411350 0.98 1 10 S804S-B10 2CCS864001R0105 200367 0.98 1 13 S804S-B13 2CCS864001R0135 200374 0.98 1 16 S804S-B16 2CCS864001R0165 200381 0.98 1 20 S804S-B20 2CCS864001R0205 200398 0.98 1 25 S804S-B25 2CCS864001R0255 200404 0.98 1 32 S804S-B32 2CCS864001R0325 200411 0.98 1 40 S804S-B40 2CCS864001R0405 200428 0.98 1 50 S804S-B50 2CCS864001R0505 200435 0.98 1 63 S804S-B63 2CCS864001R0635 200442 0.98 1 80 S804S-B80 2CCS864001R0805 200459 0.98 1 100 S804S-B100 2CCS864001R0825 200466 0.98 1 125 S804S-B125 2CCS864001R0845 200473 0.98 1 * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 S800S-BSelection tables High performance MCB with cage terminal System pro M compact B

with ring terminal connection S800S-B characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-B6-R* 2CCS861002R0065 408268 0,245 1

8 S801S-B8-R* 2CCS861002R0085 411480 0,245 1

10 S801S-B10-R 2CCS861002R0105 209636 0,245 1

13 S801S-B13-R 2CCS861002R0135 209643 0,245 1

16 S801S-B16-R 2CCS861002R0165 209650 0,245 1

20 S801S-B20-R 2CCS861002R0205 209667 0,245 1

25 S801S-B25-R 2CCS861002R0255 209674 0,245 1

32 S801S-B32-R 2CCS861002R0325 209681 0,245 1

40 S801S-B40-R 2CCS861002R0405 206826 0,245 1

50 S801S-B50-R 2CCS861002R0505 206833 0,245 1

63 S801S-B63-R 2CCS861002R0635 206840 0,245 1

80 S801S-B80-R 2CCS861002R0805 206857 0,245 1

100 S801S-B100-R 2CCS861002R0825 206864 0,245 1

125 S801S-B125-R 2CCS861002R0845 206871 0,245 1

2 6 S802S-B6-R* 2CCS862002R0065 408275 0,49 1

8 S802S-B8-R* 2CCS862002R0085 411497 0,49 1

10 S802S-B10-R 2CCS862002R0105 209698 0,49 1

13 S802S-B13-R 2CCS862002R0135 209704 0,49 1

16 S802S-B16-R 2CCS862002R0165 209711 0,49 1

20 S802S-B20-R 2CCS862002R0205 209728 0,49 1

25 S802S-B25-R 2CCS862002R0255 209735 0,49 1

32 S802S-B32-R 2CCS862002R0325 209742 0,49 1

40 S802S-B40-R 2CCS862002R0405 206888 0,49 1

50 S802S-B50-R 2CCS862002R0505 206895 0,49 1

63 S802S-B63-R 2CCS862002R0635 206901 0,49 1

80 S802S-B80-R 2CCS862002R0805 206918 0,49 1

100 S802S-B100-R 2CCS862002R0825 206925 0,49 1

125 S802S-B125-R 2CCS862002R0845 206932 0,49 1

pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 B

3 6 S803S-B6-R* 2CCS863002R0065 408282 0,735 1

8 S803S-B8-R* 2CCS863002R0085 411503 0,735 1

10 S803S-B10-R 2CCS863002R0105 209759 0,735 1

13 S803S-B13-R 2CCS863002R0135 209766 0,735 1

16 S803S-B16-R 2CCS863002R0165 209773 0,735 1

20 S803S-B20-R 2CCS863002R0205 209780 0,735 1

25 S803S-B25-R 2CCS863002R0255 209797 0,735 1

32 S803S-B32-R 2CCS863002R0325 209803 0,735 1

40 S803S-B40-R 2CCS863002R0405 206949 0,735 1

50 S803S-B50-R 2CCS863002R0505 206956 0,735 1

63 S803S-B63-R 2CCS863002R0635 206963 0,735 1

80 S803S-B80-R 2CCS863002R0805 206970 0,735 1

100 S803S-B100-R 2CCS863002R0825 206987 0,735 1

125 S803S-B125-R 2CCS863002R0845 206994 0,735 1

4 6 S804S-B6-R* 2CCS864002R0065 408299 0,98 1

8 S804S-B8-R* 2CCS864002R0085 411510 0,98 1

10 S804S-B10-R 2CCS864002R0105 209810 0,98 1

13 S804S-B13-R 2CCS864002R0135 209827 0,98 1

16 S804S-B16-R 2CCS864002R0165 209834 0,98 1

20 S804S-B20-R 2CCS864002R0205 209841 0,98 1

25 S804S-B25-R 2CCS864002R0255 209858 0,98 1

32 S804S-B32-R 2CCS864002R0325 209865 0,98 1

40 S804S-B40-R 2CCS864002R0405 207007 0,98 1

50 S804S-B50-R 2CCS864002R0505 207014 0,98 1

63 S804S-B63-R 2CCS864002R0635 207021 0,98 1

80 S804S-B80-R 2CCS864002R0805 207038 0,98 1

100 S804S-B100-R 2CCS864002R0825 207045 0,98 1

125 S804S-B125-R 2CCS864002R0845 207052 0,98 1

  • Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 S800S-BSelection tables High performance MCB with ring terminal connection System pro M compact B

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for resistive and inductive loads with low inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-C6* 2CCS861001R0064 408145 0.245 1 8 S801S-C8* 2CCS861001R0084 411367 0.245 1 10 S801S-C10 2CCS861001R0104 200480 0.245 1 13 S801S-C13 2CCS861001R0134 200497 0.245 1 16 S801S-C16 2CCS861001R0164 200503 0.245 1 20 S801S-C20 2CCS861001R0204 200510 0.245 1 25 S801S-C25 2CCS861001R0254 200527 0.245 1 32 S801S-C32 2CCS861001R0324 200534 0.245 1 40 S801S-C40 2CCS861001R0404 200541 0.245 1 50 S801S-C50 2CCS861001R0504 200558 0.245 1 63 S801S-C63 2CCS861001R0634 200565 0.245 1 80 S801S-C80 2CCS861001R0804 200572 0.245 1 100 S801S-C100 2CCS861001R0824 200589 0.245 1 125 S801S-C125 2CCS861001R0844 200596 0.245 1 2 6 S802S-C6* 2CCS862001R0064 408152 0.49 1 8 S802S-C8* 2CCS862001R0084 411374 0.49 1 10 S802S-C10 2CCS862001R0104 200602 0.49 1 13 S802S-C13 2CCS862001R0134 200619 0.49 1 16 S802S-C16 2CCS862001R0164 200626 0.49 1 20 S802S-C20 2CCS862001R0204 200633 0.49 1 25 S802S-C25 2CCS862001R0254 200640 0.49 1 32 S802S-C32 2CCS862001R0324 200657 0.49 1 40 S802S-C40 2CCS862001R0404 200664 0.49 1 50 S802S-C50 2CCS862001R0504 200671 0.49 1 63 S802S-C63 2CCS862001R0634 200688 0.49 1 80 S802S-C80 2CCS862001R0804 200695 0.49 1 100 S802S-C100 2CCS862001R0824 200701 0.49 1 125 S802S-C125 2CCS862001R0844 200718 0.49 1 System pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 C

C 3 6 S803S-C6* 2CCS863001R0064 408169 0.735 1 8 S803S-C8* 2CCS863001R0084 411381 0.735 1 10 S803S-C10 2CCS863001R0104 200725 0.735 1 13 S803S-C13 2CCS863001R0134 200732 0.735 1 16 S803S-C16 2CCS863001R0164 200749 0.735 1 20 S803S-C20 2CCS863001R0204 200756 0.735 1 25 S803S-C25 2CCS863001R0254 200763 0.735 1 32 S803S-C32 2CCS863001R0324 200770 0.735 1 40 S803S-C40 2CCS863001R0404 200787 0.735 1 50 S803S-C50 2CCS863001R0504 200794 0.735 1 63 S803S-C63 2CCS863001R0634 200800 0.735 1 80 S803S-C80 2CCS863001R0804 200817 0.735 1 100 S803S-C100 2CCS863001R0824 200824 0.735 1 125 S803S-C125 2CCS863001R0844 200831 0.735 1 4 6 S804S-C6* 2CCS864001R0064 408176 0.98 1 8 S804S-C8* 2CCS864001R0084 411398 0.98 1 10 S804S-C10 2CCS864001R0104 200848 0.98 1 13 S804S-C13 2CCS864001R0134 200855 0.98 1 16 S804S-C16 2CCS864001R0164 200862 0.98 1 20 S804S-C20 2CCS864001R0204 200879 0.98 1 25 S804S-C25 2CCS864001R0254 200886 0.98 1 32 S804S-C32 2CCS864001R0324 200893 0.98 1 40 S804S-C40 2CCS864001R0404 200909 0.98 1 50 S804S-C50 2CCS864001R0504 200916 0.98 1 63 S804S-C63 2CCS864001R0634 200923 0.98 1 80 S804S-C80 2CCS864001R0804 200930 0.98 1 100 S804S-C100 2CCS864001R0824 200947 0.98 1 125 S804S-C125 2CCS864001R0844 200954 0.98 1 * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002

with ring terminal connection S800S-C characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for resistive and inductive loads with low inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2, IEC/EN 60898 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-C6-R* 2CCS861002R0064 408305 0,245 1

8 S801S-C8-R* 2CCS861002R0084 411527 0,245 1

10 S801S-C10-R 2CCS861002R0104 209872 0,245 1

13 S801S-C13-R 2CCS861002R0134 209889 0,245 1

16 S801S-C16-R 2CCS861002R0164 209896 0,245 1

20 S801S-C20-R 2CCS861002R0204 209902 0,245 1

25 S801S-C25-R 2CCS861002R0254 209919 0,245 1

32 S801S-C32-R 2CCS861002R0324 209926 0,245 1

40 S801S-C40-R 2CCS861002R0404 207069 0,245 1

50 S801S-C50-R 2CCS861002R0504 207076 0,245 1

63 S801S-C63-R 2CCS861002R0634 207083 0,245 1

80 S801S-C80-R 2CCS861002R0804 207090 0,245 1

100 S801S-C100-R 2CCS861002R0824 207106 0,245 1

125 S801S-C125-R 2CCS861002R0844 207113 0,245 1

2 6 S802S-C6-R* 2CCS862002R0064 408312 0,49 1

8 S802S-C8-R* 2CCS862001R0084 411534 0,49 1

10 S802S-C10-R 2CCS862002R0104 209933 0,49 1

13 S802S-C13-R 2CCS862002R0134 209940 0,49 1

16 S802S-C16-R 2CCS862002R0164 209957 0,49 1

20 S802S-C20-R 2CCS862002R0204 209964 0,49 1

25 S802S-C25-R 2CCS862002R0254 209971 0,49 1

32 S802S-C32-R 2CCS862002R0324 209988 0,49 1

40 S802S-C40-R 2CCS862002R0404 207120 0,49 1

50 S802S-C50-R 2CCS862002R0504 207137 0,49 1

63 S802S-C63-R 2CCS862002R0634 207144 0,49 1

80 S802S-C80-R 2CCS862002R0804 207151 0,49 1

100 S802S-C100-R 2CCS862002R0824 207168 0,49 1

125 S802S-C125-R 2CCS862002R0844 207175 0,49 1

pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 C

  • Standard: EN/IEC 60947-2 3 6 S803S-C6-R* 2CCS863002R0064 408329 0,735 1

8 S803S-C8-R* 2CCS863002R0084 411541 0,735 1

10 S803S-C10-R 2CCS863002R0104 209995 0,735 1

13 S803S-C13-R 2CCS863002R0134 210007 0,735 1

16 S803S-C16-R 2CCS863002R0164 210014 0,735 1

20 S803S-C20-R 2CCS863002R0204 210021 0,735 1

25 S803S-C25-R 2CCS863002R0254 210038 0,735 1

32 S803S-C32-R 2CCS863002R0324 210045 0,735 1

40 S803S-C40-R 2CCS863002R0404 207182 0,735 1

50 S803S-C50-R 2CCS863002R0504 207199 0,735 1

63 S803S-C63-R 2CCS863002R0634 207205 0,735 1

80 S803S-C80-R 2CCS863002R0804 207212 0,735 1

100 S803S-C100-R 2CCS863002R0824 207229 0,735 1

125 S803S-C125-R 2CCS863002R0844 207236 0,735 1

4 6 S804S-C6-R* 2CCS864002R0064 408336 0,98 1

8 S804S-C8-R* 2CCS864002R0084 411558 0,98 1

10 S804S-C10-R 2CCS864002R0104 210052 0,98 1

13 S804S-C13-R 2CCS864002R0134 210069 0,98 1

16 S804S-C16-R 2CCS864002R0164 210076 0,98 1

20 S804S-C20-R 2CCS864002R0204 210083 0,98 1

25 S804S-C25-R 2CCS864002R0254 210090 0,98 1

32 S804S-C32-R 2CCS864002R0324 210106 0,98 1

40 S804S-C40-R 2CCS864002R0404 207243 0,98 1

50 S804S-C50-R 2CCS864002R0504 207250 0,98 1

63 S804S-C63-R 2CCS864002R0634 207267 0,98 1

80 S804S-C80-R 2CCS864002R0804 207274 0,98 1

100 S804S-C100-R 2CCS864002R0824 207281 0,98 1

125 S804S-C125-R 2CCS864002R0844 207298 0,98 1

2CCC413001F00022CCC413001F0002 S800S-CSelection tables High performance MCB with ring terminal connection System pro M compact C

D S800S-DSelection tables High performance MCB with cage terminal S800S-D characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for circuits which supply loads with high inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-D6* 2CCS861001R0061 408183 0.245 1 8 S801S-D8* 2CCS861001R0081 411404 0.245 1 10 S801S-D10 2CCS861001R0101 200961 0.245 1 13 S801S-D13 2CCS861001R0131 200978 0.245 1 16 S801S-D16 2CCS861001R0161 200985 0.245 1 20 S801S-D20 2CCS861001R0201 200992 0.245 1 25 S801S-D25 2CCS861001R0251 201005 0.245 1 32 S801S-D32 2CCS861001R0321 201012 0.245 1 40 S801S-D40 2CCS861001R0401 201029 0.245 1 50 S801S-D50 2CCS861001R0501 201036 0.245 1 63 S801S-D63 2CCS861001R0631 201043 0.245 1 80 S801S-D80 2CCS861001R0801 201050 0.245 1 100 S801S-D100 2CCS861001R0821 201067 0.245 1 125 S801S-D125 2CCS861001R0841 201074 0.245 1 2 6 S802S-D6* 2CCS862001R0061 408190 0.49 1 8 S802S-D8* 2CCS862001R0081 411411 0.49 1 10 S802S-D10 2CCS862001R0101 201081 0.49 1 13 S802S-D13 2CCS862001R0131 201098 0.49 1 16 S802S-D16 2CCS862001R0161 201104 0.49 1 20 S802S-D20 2CCS862001R0201 201111 0.49 1 25 S802S-D25 2CCS862001R0251 201128 0.49 1 32 S802S-D32 2CCS862001R0321 201135 0.49 1 40 S802S-D40 2CCS862001R0401 201142 0.49 1 50 S802S-D50 2CCS862001R0501 201159 0.49 1 63 S802S-D63 2CCS862001R0631 201166 0.49 1 80 S802S-D80 2CCS862001R0801 201173 0.49 1 100 S802S-D100 2CCS862001R0821 201180 0.49 1 125 S802S-D125 2CCS862001R0841 201197 0.49 1 System pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002

3 6 S803S-D6* 2CCS863001R0061 408206 0.735 1 8 S803S-D8* 2CCS863001R0081 411428 0.735 1 10 S803S-D10 2CCS863001R0101 201203 0.735 1 13 S803S-D13 2CCS863001R0131 201210 0.735 1 16 S803S-D16 2CCS863001R0161 201227 0.735 1 20 S803S-D20 2CCS863001R0201 201234 0.735 1 25 S803S-D25 2CCS863001R0251 201241 0.735 1 32 S803S-D32 2CCS863001R0321 201258 0.735 1 40 S803S-D40 2CCS863001R0401 201265 0.735 1 50 S803S-D50 2CCS863001R0501 201272 0.735 1 63 S803S-D63 2CCS863001R0631 201289 0.735 1 80 S803S-D80 2CCS863001R0801 201296 0.735 1 100 S803S-D100 2CCS863001R0821 201302 0.735 1 125 S803S-D125 2CCS863001R0841 201319 0.735 1 4 6 S804S-D6* 2CCS864001R0061 408213 0.98 1 8 S804S-D8* 2CCS864001R0081 411435 0.98 1 10 S804S-D10 2CCS864001R0101 201326 0.98 1 13 S804S-D13 2CCS864001R0131 201333 0.98 1 16 S804S-D16 2CCS864001R0161 201340 0.98 1 20 S804S-D20 2CCS864001R0201 201357 0.98 1 25 S804S-D25 2CCS864001R0251 201364 0.98 1 32 S804S-D32 2CCS864001R0321 201371 0.98 1 40 S804S-D40 2CCS864001R0401 201388 0.98 1 50 S804S-D50 2CCS864001R0501 201395 0.98 1 63 S804S-D63 2CCS864001R0631 201401 0.98 1 80 S804S-D80 2CCS864001R0801 201418 0.98 1 100 S804S-D100 2CCS864001R0821 201425 0.98 1 125 S804S-D125 2CCS864001R0841 201432 0.98 1 D S800S-DSelection tables High performance MCB with cage terminal System pro M compact * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002

with ring terminal connection S800S-D characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for circuits which supply loads with high inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2, IEC/EN 60898 Icn=25 kA Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-D6-R* 2CCS861002R0061 408343 0,245 1

8 S801S-D8-R* 2CCS861002R0081 411565 0,245 1

10 S801S-D10-R 2CCS861002R0101 210113 0,245 1

13 S801S-D13-R 2CCS861002R0131 210120 0,245 1

16 S801S-D16-R 2CCS861002R0161 210137 0,245 1

20 S801S-D20-R 2CCS861002R0201 210144 0,245 1

25 S801S-D25-R 2CCS861002R0251 210151 0,245 1

32 S801S-D32-R 2CCS861002R0321 210168 0,245 1

40 S801S-D40-R 2CCS861002R0401 207304 0,245 1

50 S801S-D50-R 2CCS861002R0501 207311 0,245 1

63 S801S-D63-R 2CCS861002R0631 207328 0,245 1

80 S801S-D80-R 2CCS861002R0801 207335 0,245 1

100 S801S-D100-R 2CCS861002R0821 207342 0,245 1

125 S801S-D125-R 2CCS861002R0841 207359 0,245 1

2 6 S802S-D6-R* 2CCS862002R0061 408350 0,49 1

8 S802S-D8-R* 2CCS862002R0081 411572 0,49 1

10 S802S-D10-R 2CCS862002R0101 210175 0,49 1

13 S802S-D13-R 2CCS862002R0131 210182 0,49 1

16 S802S-D16-R 2CCS862002R0161 210199 0,49 1

20 S802S-D20-R 2CCS862002R0201 210205 0,49 1

25 S802S-D25-R 2CCS862002R0251 210212 0,49 1

32 S802S-D32-R 2CCS862002R0321 210229 0,49 1

40 S802S-D40-R 2CCS862002R0401 207366 0,49 1

50 S802S-D50-R 2CCS862002R0501 207373 0,49 1

63 S802S-D63-R 2CCS862002R0631 207380 0,49 1

80 S802S-D80-R 2CCS862002R0801 207397 0,49 1

100 S802S-D100-R 2CCS862002R0821 207403 0,49 1

125 S802S-D125-R 2CCS862002R0841 207410 0,49 1

pro M compact® * Standard: EN/IEC 60947-2 2CCC413001F00022CCC413001F0002 D

  • Standard: EN/IEC 60947-2 3 6 S803S-D6-R* 2CCS863002R0061 408367 0,735 1

8 S803S-D8-R* 2CCS863002R0081 411589 0,735 1

10 S803S-D10-R 2CCS863002R0101 210236 0,735 1

13 S803S-D13-R 2CCS863002R0131 210243 0,735 1

16 S803S-D16-R 2CCS863002R0161 210250 0,735 1

20 S803S-D20-R 2CCS863002R0201 210267 0,735 1

25 S803S-D25-R 2CCS863002R0251 210274 0,735 1

32 S803S-D32-R 2CCS863002R0321 210281 0,735 1

40 S803S-D40-R 2CCS863002R0401 207427 0,735 1

50 S803S-D50-R 2CCS863002R0501 207434 0,735 1

63 S803S-D63-R 2CCS863002R0631 207441 0,735 1

80 S803S-D80-R 2CCS863002R0801 207458 0,735 1

100 S803S-D100-R 2CCS863002R0821 207465 0,735 1

125 S803S-D125-R 2CCS863002R0841 207472 0,735 1

4 6 S804S-D6-R* 2CCS864002R0061 408374 0,98 1

8 S804S-D8-R* 2CCS864002R0081 411596 0,98 1

10 S804S-D10-R 2CCS864002R0101 210298 0,98 1

13 S804S-D13-R 2CCS864002R0131 210304 0,98 1

16 S804S-D16-R 2CCS864002R0161 210311 0,98 1

20 S804S-D20-R 2CCS864002R0201 210328 0,98 1

25 S804S-D25-R 2CCS864002R0251 210335 0,98 1

32 S804S-D32-R 2CCS864002R0321 210342 0,98 1

40 S804S-D40-R 2CCS864002R0401 207489 0,98 1

50 S804S-D50-R 2CCS864002R0501 207496 0,98 1

63 S804S-D63-R 2CCS864002R0631 207502 0,98 1

80 S804S-D80-R 2CCS864002R0801 207519 0,98 1

100 S804S-D100-R 2CCS864002R0821 207526 0,98 1

125 S804S-D125-R 2CCS864002R0841 207533 0,98 1

with ring terminal connection System pro M compact D 2CCC413001F00022CCC413001F0002

2CCC413001F00022CCC413001F0002 K S800S-KSelection tables High performance MCB with cage terminal S800S-K characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when a high breaking capacity is required; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-K6 2CCS861001R0067 408220 0.245 1 8 S801S-K8 2CCS861001R0407 411442 0.245 1 10 S801S-K10 2CCS861001R0427 201449 0.245 1 13 S801S-K13 2CCS861001R0447 201456 0.245 1 16 S801S-K16 2CCS861001R0467 201463 0.245 1 20 S801S-K20 2CCS861001R0487 201470 0.245 1 25 S801S-K25 2CCS861001R0517 201487 0.245 1 32 S801S-K32 2CCS861001R0537 201494 0.245 1 40 S801S-K40 2CCS861001R0557 201500 0.245 1 50 S801S-K50 2CCS861001R0577 201517 0.245 1 63 S801S-K63 2CCS861001R0597 201524 0.245 1 80 S801S-K80 2CCS861001R0627 201531 0.245 1 100 S801S-K100 2CCS861001R0637 201548 0.245 1 125 S801S-K125 2CCS861001R0647 201555 0.245 1 2 6 S802S-K6 2CCS862001R0067 408237 0.49 1 8 S802S-K8 2CCS862001R0407 411459 0.49 1 10 S802S-K10 2CCS862001R0427 201562 0.49 1 13 S802S-K13 2CCS862001R0447 201579 0.49 1 16 S802S-K16 2CCS862001R0467 201586 0.49 1 20 S802S-K20 2CCS862001R0487 201593 0.49 1 25 S802S-K25 2CCS862001R0517 201609 0.49 1 32 S802S-K32 2CCS862001R0537 201616 0.49 1 40 S802S-K40 2CCS862001R0557 201623 0.49 1 50 S802S-K50 2CCS862001R0577 201630 0.49 1 63 S802S-K63 2CCS862001R0597 201647 0.49 1 80 S802S-K80 2CCS862001R0627 201654 0.49 1 100 S802S-K100 2CCS862001R0637 201661 0.49 1 125 S802S-K125 2CCS862001R0647 201678 0.49 1 System pro M compact®

3 6 S803S-K6 2CCS863001R0067 408244 0.735 1 8 S803S-K8 2CCS863001R0407 411466 0.735 1 10 S803S-K10 2CCS863001R0427 201685 0.735 1 13 S803S-K13 2CCS863001R0447 201692 0.735 1 16 S803S-K16 2CCS863001R0467 201708 0.735 1 20 S803S-K20 2CCS863001R0487 201715 0.735 1 25 S803S-K25 2CCS863001R0517 201722 0.735 1 32 S803S-K32 2CCS863001R0537 201739 0.735 1 40 S803S-K40 2CCS863001R0557 201746 0.735 1 50 S803S-K50 2CCS863001R0577 201753 0.735 1 63 S803S-K63 2CCS863001R0597 201760 0.735 1 80 S803S-K80 2CCS863001R0627 201777 0.735 1 100 S803S-K100 2CCS863001R0637 201784 0.735 1 125 S803S-K125 2CCS863001R0647 201791 0.735 1 4 6 S804S-K6 2CCS864001R0067 408251 0.98 1 8 S804S-K8 2CCS864001R0407 411473 0.98 1 10 S804S-K10 2CCS864001R0427 201807 0.98 1 13 S804S-K13 2CCS864001R0447 201814 0.98 1 16 S804S-K16 2CCS864001R0467 201821 0.98 1 20 S804S-K20 2CCS864001R0487 201838 0.98 1 25 S804S-K25 2CCS864001R0517 201845 0.98 1 32 S804S-K32 2CCS864001R0537 201852 0.98 1 40 S804S-K40 2CCS864001R0557 201869 0.98 1 50 S804S-K50 2CCS864001R0577 201876 0.98 1 63 S804S-K63 2CCS864001R0597 201883 0.98 1 80 S804S-K80 2CCS864001R0627 201890 0.98 1 100 S804S-K100 2CCS864001R0637 201906 0.98 1 125 S804S-K125 2CCS864001R0647 201913 0.98 1 K S800S-KSelection tables High performance MCB with cage terminal System pro M compact ®2CCC413001F00022CCC413001F0002

K S800S-KSelection tables High performance MCB with ring terminal cable connection S800S-K characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when a high breaking capacity is required; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 6 S801S-K6-R 2CCS861002R0067 408381 0,245 1

8 S801S-K8-R 2CCS861002R0407 411602 0,245 1

10 S801S-K10-R 2CCS861002R0427 209391 0,245 1

13 S801S-K13-R 2CCS861002R0447 209407 0,245 1

16 S801S-K16-R 2CCS861002R0467 209414 0,245 1

20 S801S-K20-R 2CCS861002R0487 209421 0,245 1

25 S801S-K25-R 2CCS861002R0517 209438 0,245 1

32 S801S-K32-R 2CCS861002R0537 209445 0,245 1

40 S801S-K40-R 2CCS861002R0557 207540 0,245 1

50 S801S-K50-R 2CCS861002R0577 207557 0,245 1

63 S801S-K63-R 2CCS861002R0597 207564 0,245 1

80 S801S-K80-R 2CCS861002R0627 207571 0,245 1

100 S801S-K100-R 2CCS861002R0637 207588 0,245 1

125 S801S-K125-R 2CCS861002R0647 207595 0,245 1

2 6 S802S-K6-R 2CCS862002R0067 408398 0,49 1

8 S802S-K8-R 2CCS862002R0407 411619 0,49 1

10 S802S-K10-R 2CCS862002R0427 209452 0,49 1

13 S802S-K13-R 2CCS862002R0447 209469 0,49 1

16 S802S-K16-R 2CCS862002R0467 209476 0,49 1

20 S802S-K20-R 2CCS862002R0487 209483 0,49 1

25 S802S-K25-R 2CCS862002R0517 209490 0,49 1

32 S802S-K32-R 2CCS862002R0537 209506 0,49 1

40 S802S-K40-R 2CCS862002R0557 207601 0,49 1

50 S802S-K50-R 2CCS862002R0577 207618 0,49 1

63 S802S-K63-R 2CCS862002R0597 207625 0,49 1

80 S802S-K80-R 2CCS862002R0627 207632 0,49 1

100 S802S-K100-R 2CCS862002R0637 207649 0,49 1

125 S802S-K125-R 2CCS862002R0647 207656 0,49 1

pro M compact®2CCC413001F00022CCC413001F0002

3 6 S803S-K6-R 2CCS863002R0067 408404 0,735 1

8 S803S-K8-R 2CCS863002R0407 411626 0,735 1

10 S803S-K10-R 2CCS863002R0427 209513 0,735 1

13 S803S-K13-R 2CCS863002R0447 209520 0,735 1

16 S803S-K16-R 2CCS863002R0467 209537 0,735 1

20 S803S-K20-R 2CCS863002R0487 209544 0,735 1

25 S803S-K25-R 2CCS863002R0517 209551 0,735 1

32 S803S-K32-R 2CCS863002R0537 209568 0,735 1

40 S803S-K40-R 2CCS863002R0557 207663 0,735 1

50 S803S-K50-R 2CCS863002R0577 207670 0,735 1

63 S803S-K63-R 2CCS863002R0597 207687 0,735 1

80 S803S-K80-R 2CCS863002R0627 207694 0,735 1

100 S803S-K100-R 2CCS863002R0637 207700 0,735 1

125 S803S-K125-R 2CCS863002R0647 207717 0,735 1

4 6 S804S-K6-R 2CCS864002R0067 408411 0,98 1

8 S804S-K8-R 2CCS864002R0407 411633 0,98 1

10 S804S-K10-R 2CCS864002R0427 209575 0,98 1

13 S804S-K13-R 2CCS864002R0447 209582 0,98 1

16 S804S-K16-R 2CCS864002R0467 209599 0,98 1

20 S804S-K20-R 2CCS864002R0487 209605 0,98 1

25 S804S-K25-R 2CCS864002R0517 209612 0,98 1

32 S804S-K32-R 2CCS864002R0537 209629 0,98 1

40 S804S-K40-R 2CCS864002R0557 207724 0,98 1

50 S804S-K50-R 2CCS864002R0577 207731 0,98 1

63 S804S-K63-R 2CCS864002R0597 207748 0,98 1

80 S804S-K80-R 2CCS864002R0627 207755 0,98 1

100 S804S-K100-R 2CCS864002R0637 207762 0,98 1

125 S804S-K125-R 2CCS864002R0647 207779 0,98 1

K S800S-KSelection tables High performance MCB with ring terminal cable connection System pro M compact ®2CCC413001F00022CCC413001F0002

S800S-KM-R characteristic with ring terminal connection Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; only magnetic version dedicated to protect motors; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 3 20 S803S-KM20-R 2CCS863002R0486 210830 0,735 1

25 S803S-KM25-R 2CCS863002R0516 210847 0,735 1

32 S803S-KM32-R 2CCS863002R0536 210854 0,735 1

40 S803S-KM40-R 2CCS863002R0556 207786 0,735 1

50 S803S-KM50-R 2CCS863002R0576 207793 0,735 1

63 S803S-KM63-R 2CCS863002R0596 207809 0,735 1

80 S803S-KM80-R 2CCS863002R0626 207816 0,735 1

S800S-KM characteristic with cage terminal Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; only magnetic version dedicated to protect motors; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 3 20 S803S-KM20 2CCS863001R0486 202194 0.735 1 25 S803S-KM25 2CCS863001R0516 202200 0.735 1 32 S803S-KM32 2CCS863001R0536 202217 0.735 1 40 S803S-KM40 2CCS863001R0556 202224 0.735 1 50 S803S-KM50 2CCS863001R0576 202231 0.735 1 63 S803S-KM63 2CCS863001R0596 202248 0.735 1 80 S803S-KM80 2CCS863001R0626 202255 0.735 1 System pro M compact®2CCC413001F00022CCC413001F0002

B S800S-UCBSelection tables High performance MCB with cage terminal S800S-UCB characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801S-UCB10 2CCS861001R1105 202842 0.245 1 13 S801S-UCB13 2CCS861001R1135 202859 0.245 1 16 S801S-UCB16 2CCS861001R1165 202866 0.245 1 20 S801S-UCB20 2CCS861001R1205 202873 0.245 1 25 S801S-UCB25 2CCS861001R1255 202880 0.245 1 32 S801S-UCB32 2CCS861001R1325 202897 0.245 1 40 S801S-UCB40 2CCS861001R1405 202903 0.245 1 50 S801S-UCB50 2CCS861001R1505 202910 0.245 1 63 S801S-UCB63 2CCS861001R1635 202927 0.245 1 80 S801S-UCB80 2CCS861001R1805 202934 0.245 1 100 S801S-UCB100 2CCS861001R1825 202941 0.245 1 125 S801S-UCB125 2CCS861001R1845 202958 0.245 1 2 10 S802S-UCB10 2CCS862001R1105 202965 0.49 1 13 S802S-UCB13 2CCS862001R1135 202972 0.49 1 16 S802S-UCB16 2CCS862001R1165 202989 0.49 1 20 S802S-UCB20 2CCS862001R1205 202996 0.49 1 25 S802S-UCB25 2CCS862001R1255 203009 0.49 1 32 S802S-UCB32 2CCS862001R1325 203016 0.49 1 40 S802S-UCB40 2CCS862001R1405 203023 0.49 1 50 S802S-UCB50 2CCS862001R1505 203030 0.49 1 63 S802S-UCB63 2CCS862001R1635 203047 0.49 1 80 S802S-UCB80 2CCS862001R1805 203054 0.49 1 100 S802S-UCB100 2CCS862001R1825 203061 0.49 1 125 S802S-UCB125 2CCS862001R1845 203078 0.49 1 3 10 S803S-UCB10 2CCS863001R1105 203085 0.735 1 13 S803S-UCB13 2CCS863001R1135 203092 0.735 1 16 S803S-UCB16 2CCS863001R1165 203108 0.735 1 20 S803S-UCB20 2CCS863001R1205 203115 0.735 1 25 S803S-UCB25 2CCS863001R1255 203122 0.735 1 32 S803S-UCB32 2CCS863001R1325 203139 0.735 1 40 S803S-UCB40 2CCS863001R1405 203146 0.735 1 50 S803S-UCB50 2CCS863001R1505 203153 0.735 1 63 S803S-UCB63 2CCS863001R1635 203160 0.735 1 80 S803S-UCB80 2CCS863001R1805 203177 0.735 1 100 S803S-UCB100 2CCS863001R1825 203184 0.735 1 125 S803S-UCB125 2CCS863001R1845 203191 0.735 1 4 10 S804S-UCB10 2CCS864001R1105 203207 0.98 1 13 S804S-UCB13 2CCS864001R1135 203214 0.98 1 16 S804S-UCB16 2CCS864001R1165 203221 0.98 1 20 S804S-UCB20 2CCS864001R1205 203238 0.98 1 25 S804S-UCB25 2CCS864001R1255 203245 0.98 1 32 S804S-UCB32 2CCS864001R1325 203252 0.98 1 40 S804S-UCB40 2CCS864001R1405 203269 0.98 1 50 S804S-UCB50 2CCS864001R1505 203276 0.98 1 63 S804S-UCB63 2CCS864001R1635 203283 0.98 1 80 S804S-UCB80 2CCS864001R1805 203290 0.98 1 100 S804S-UCB100 2CCS864001R1825 203306 0.98 1 125 S804S-UCB125 2CCS864001R1845 203313 0.98 1 System pro M compact®2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

B S800S-UCBSelection tables High performance MCB with ring terminal connection S800S-UCB characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801S-UCB10-R 2CCS861002R1105 210359 0,245 1

13 S801S-UCB13-R 2CCS861002R1135 210366 0,245 1

16 S801S-UCB16-R 2CCS861002R1165 210373 0,245 1

20 S801S-UCB20-R 2CCS861002R1205 210380 0,245 1

25 S801S-UCB25-R 2CCS861002R1255 210397 0,245 1

32 S801S-UCB32-R 2CCS861002R1325 210403 0,245 1

40 S801S-UCB40-R 2CCS861002R1405 208424 0,245 1

50 S801S-UCB50-R 2CCS861002R1505 208431 0,245 1

63 S801S-UCB63-R 2CCS861002R1635 208448 0,245 1

80 S801S-UCB80-R 2CCS861002R1805 208455 0,245 1

100 S801S-UCB100-R 2CCS861002R1825 208462 0,245 1

125 S801S-UCB125-R 2CCS861002R1845 208479 0,245 1

2 10 S802S-UCB10-R 2CCS862002R1105 210410 0,49 1

13 S802S-UCB13-R 2CCS862002R1135 210427 0,49 1

16 S802S-UCB16-R 2CCS862002R1165 210434 0,49 1

20 S802S-UCB20-R 2CCS862002R1205 210441 0,49 1

25 S802S-UCB25-R 2CCS862002R1255 210458 0,49 1

32 S802S-UCB32-R 2CCS862002R1325 210465 0,49 1

40 S802S-UCB40-R 2CCS862002R1405 208486 0,49 1

50 S802S-UCB50-R 2CCS862002R1505 208493 0,49 1

63 S802S-UCB63-R 2CCS862002R1635 208509 0,49 1

80 S802S-UCB80-R 2CCS862002R1805 208516 0,49 1

100 S802S-UCB100-R 2CCS862002R1825 208523 0,49 1

125 S802S-UCB125-R 2CCS862002R1845 208530 0,49 1

3 10 S803S-UCB10-R 2CCS863002R1105 210472 0,735 1

13 S803S-UCB13-R 2CCS863002R1135 210489 0,735 1

16 S803S-UCB16-R 2CCS863002R1165 210496 0,735 1

20 S803S-UCB20-R 2CCS863002R1205 210502 0,735 1

25 S803S-UCB25-R 2CCS863002R1255 210519 0,735 1

32 S803S-UCB32-R 2CCS863002R1325 210526 0,735 1

40 S803S-UCB40-R 2CCS863002R1405 208547 0,735 1

50 S803S-UCB50-R 2CCS863002R1505 208554 0,735 1

63 S803S-UCB63-R 2CCS863002R1635 208561 0,735 1

80 S803S-UCB80-R 2CCS863002R1805 208578 0,735 1

100 S803S-UCB100-R 2CCS863002R1825 208585 0,735 1

125 S803S-UCB125-R 2CCS863002R1845 208592 0,735 1

4 10 S804S-UCB10-R 2CCS864002R1105 210533 0,98 1

13 S804S-UCB13-R 2CCS864002R1135 210540 0,98 1

16 S804S-UCB16-R 2CCS864002R1165 210557 0,98 1

20 S804S-UCB20-R 2CCS864002R1205 210564 0,98 1

25 S804S-UCB25-R 2CCS864002R1255 210571 0,98 1

32 S804S-UCB32-R 2CCS864002R1325 210588 0,98 1

40 S804S-UCB40-R 2CCS864002R1405 208608 0,98 1

50 S804S-UCB50-R 2CCS864002R1505 208615 0,98 1

63 S804S-UCB63-R 2CCS864002R1635 208622 0,98 1

80 S804S-UCB80-R 2CCS864002R1805 208639 0,98 1

100 S804S-UCB100-R 2CCS864002R1825 208646 0,98 1

125 S804S-UCB125-R 2CCS864002R1845 208653 0,98 1

pro M compact®2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

K S800S-UCKSelection tables High performance MCB with cage terminal S800S-UCK characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when a high breaking capacity is required; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801S-UCK10 2CCS861001R1427 203320 0.245 1 13 S801S-UCK13 2CCS861001R1447 203337 0.245 1 16 S801S-UCK16 2CCS861001R1467 203344 0.245 1 20 S801S-UCK20 2CCS861001R1487 203351 0.245 1 25 S801S-UCK25 2CCS861001R1517 203368 0.245 1 32 S801S-UCK32 2CCS861001R1537 203375 0.245 1 40 S801S-UCK40 2CCS861001R1557 203382 0.245 1 50 S801S-UCK50 2CCS861001R1577 203399 0.245 1 63 S801S-UCK63 2CCS861001R1597 203405 0.245 1 80 S801S-UCK80 2CCS861001R1627 203412 0.245 1 100 S801S-UCK100 2CCS861001R1637 203429 0.245 1 125 S801S-UCK125 2CCS861001R1647 203436 0.245 1 2 10 S802S-UCK10 2CCS862001R1427 203443 0.49 1 13 S802S-UCK13 2CCS862001R1447 203450 0.49 1 16 S802S-UCK16 2CCS862001R1467 203467 0.49 1 20 S802S-UCK20 2CCS862001R1487 203474 0.49 1 25 S802S-UCK25 2CCS862001R1517 203481 0.49 1 32 S802S-UCK32 2CCS862001R1537 203498 0.49 1 40 S802S-UCK40 2CCS862001R1557 203504 0.49 1 50 S802S-UCK50 2CCS862001R1577 203511 0.49 1 63 S802S-UCK63 2CCS862001R1597 203528 0.49 1 80 S802S-UCK80 2CCS862001R1627 203535 0.49 1 100 S802S-UCK100 2CCS862001R1637 203542 0.49 1 125 S802S-UCK125 2CCS862001R1647 203559 0.49 1 3 10 S803S-UCK10 2CCS863001R1427 203566 0.735 1 13 S803S-UCK13 2CCS863001R1447 203573 0.735 1 16 S803S-UCK16 2CCS863001R1467 203580 0.735 1 20 S803S-UCK20 2CCS863001R1487 203597 0.735 1 25 S803S-UCK25 2CCS863001R1517 203603 0.735 1 32 S803S-UCK32 2CCS863001R1537 203610 0.735 1 40 S803S-UCK40 2CCS863001R1557 203627 0.735 1 50 S803S-UCK50 2CCS863001R1577 203634 0.735 1 63 S803S-UCK63 2CCS863001R1597 203641 0.735 1 80 S803S-UCK80 2CCS863001R1627 203658 0.735 1 100 S803S-UCK100 2CCS863001R1637 203665 0.735 1 125 S803S-UCK125 2CCS863001R1647 203672 0.735 1 4 10 S804S-UCK10 2CCS864001R1427 203689 0.98 1 13 S804S-UCK13 2CCS864001R1447 203696 0.98 1 16 S804S-UCK16 2CCS864001R1467 203702 0.98 1 20 S804S-UCK20 2CCS864001R1487 203719 0.98 1 25 S804S-UCK25 2CCS864001R1517 203726 0.98 1 32 S804S-UCK32 2CCS864001R1537 203733 0.98 1 40 S804S-UCK40 2CCS864001R1557 203740 0.98 1 50 S804S-UCK50 2CCS864001R1577 203757 0.98 1 63 S804S-UCK63 2CCS864001R1597 203764 0.98 1 80 S804S-UCK80 2CCS864001R1627 203771 0.98 1 100 S804S-UCK100 2CCS864001R1637 203788 0.98 1 125 S804S-UCK125 2CCS864001R1647 203795 0.98 1 System pro M compact®2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

K S800S-UCKSelection tables High performance MCB with ring terminal connection S800S-UCK characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when a high breaking capacity is required; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream; version dedicated to application in direct current circuits. Advantages: no nuisance tripping in the case of functional peak currents up to 10xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801S-UCK10-R 2CCS861002R1427 210595 0,245 1

13 S801S-UCK13-R 2CCS861002R1447 210601 0,245 1

16 S801S-UCK16-R 2CCS861002R1467 210618 0,245 1

20 S801S-UCK20-R 2CCS861002R1487 210625 0,245 1

25 S801S-UCK25-R 2CCS861002R1517 210632 0,245 1

32 S801S-UCK32-R 2CCS861002R1537 210649 0,245 1

40 S801S-UCK40-R 2CCS861002R1557 208660 0,245 1

50 S801S-UCK50-R 2CCS861002R1577 208677 0,245 1

63 S801S-UCK63-R 2CCS861002R1597 208684 0,245 1

80 S801S-UCK80-R 2CCS861002R1627 208691 0,245 1

100 S801S-UCK100-R 2CCS861002R1637 208707 0,245 1

125 S801S-UCK125-R 2CCS861002R1647 208714 0,245 1

2 10 S802S-UCK10-R 2CCS862002R1427 210656 0,490 1

13 S802S-UCK13-R 2CCS862002R1447 210663 0,490 1

16 S802S-UCK16-R 2CCS862002R1467 210670 0,490 1

20 S802S-UCK20-R 2CCS862002R1487 210687 0,490 1

25 S802S-UCK25-R 2CCS862002R1517 210694 0,490 1

32 S802S-UCK32-R 2CCS862002R1537 210700 0,490 1

40 S802S-UCK40-R 2CCS862002R1557 208721 0,490 1

50 S802S-UCK50-R 2CCS862002R1577 208738 0,490 1

63 S802S-UCK63-R 2CCS862002R1597 208745 0,490 1

80 S802S-UCK80-R 2CCS862002R1627 208752 0,490 1

100 S802S-UCK100-R 2CCS862002R1637 208769 0,490 1

125 S802S-UCK125-R 2CCS862002R1647 208776 0,490 1

3 10 S803S-UCK10-R 2CCS863002R1427 210717 0,735 1

13 S803S-UCK13-R 2CCS863002R1447 210724 0,735 1

16 S803S-UCK16-R 2CCS863002R1467 210731 0,735 1

20 S803S-UCK20-R 2CCS863002R1487 210748 0,735 1

25 S803S-UCK25-R 2CCS863002R1517 210755 0,735 1

32 S803S-UCK32-R 2CCS863002R1537 210762 0,735 1

40 S803S-UCK40-R 2CCS863002R1557 208783 0,735 1

50 S803S-UCK50-R 2CCS863002R1577 208790 0,735 1

63 S803S-UCK63-R 2CCS863002R1597 208806 0,735 1

80 S803S-UCK80-R 2CCS863002R1627 208813 0,735 1

100 S803S-UCK100-R 2CCS863002R1637 208820 0,735 1

125 S803S-UCK125-R 2CCS863002R1647 208837 0,735 1

4 10 S804S-UCK10-R 2CCS864002R1427 210779 0,98 1

13 S804S-UCK13-R 2CCS864002R1447 210786 0,98 1

16 S804S-UCK16-R 2CCS864002R1467 210793 0,98 1

20 S804S-UCK20-R 2CCS864002R1487 210809 0,98 1

25 S804S-UCK25-R 2CCS864002R1517 210816 0,98 1

32 S804S-UCK32-R 2CCS864002R1537 210823 0,98 1

40 S804S-UCK40-R 2CCS864002R1557 208844 0,98 1

50 S804S-UCK50-R 2CCS864002R1577 208851 0,98 1

63 S804S-UCK63-R 2CCS864002R1597 208868 0,98 1

80 S804S-UCK80-R 2CCS864002R1627 208875 0,98 1

100 S804S-UCK100-R 2CCS864002R1637 208882 0,98 1

125 S804S-UCK125-R 2CCS864002R1647 208899 0,98 1

pro M compact®2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

B S800N-BSelection tables High performance MCB with cage terminal S800N-B characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=20 kA (10 ... 80 A) Icu=36 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801N-B10 2CCS891001R0105 203801 0.24 1 13 S801N-B13 2CCS891001R0135 203818 0.24 1 16 S801N-B16 2CCS891001R0165 203825 0.24 1 20 S801N-B20 2CCS891001R0205 203832 0.24 1 25 S801N-B25 2CCS891001R0255 203849 0.24 1 32 S801N-B32 2CCS891001R0325 203856 0.24 1 40 S801N-B40 2CCS891001R0405 203863 0.24 1 50 S801N-B50 2CCS891001R0505 203870 0.24 1 63 S801N-B63 2CCS891001R0635 203887 0.24 1 80 S801N-B80 2CCS891001R0805 203894 0.24 1 100 S801N-B100 2CCS891001R0825 203900 0.24 1 125 S801N-B125 2CCS891001R0845 203917 0.24 1 2 10 S802N-B10 2CCS892001R0105 203924 0.48 1 13 S802N-B13 2CCS892001R0135 203931 0.48 1 16 S802N-B16 2CCS892001R0165 203948 0.48 1 20 S802N-B20 2CCS892001R0205 203955 0.48 1 25 S802N-B25 2CCS892001R0255 203962 0.48 1 32 S802N-B32 2CCS892001R0325 203979 0.48 1 40 S802N-B40 2CCS892001R0405 203986 0.48 1 50 S802N-B50 2CCS892001R0505 203993 0.48 1 63 S802N-B63 2CCS892001R0635 204006 0.48 1 80 S802N-B80 2CCS892001R0805 204013 0.48 1 100 S802N-B100 2CCS892001R0825 204020 0.48 1 125 S802N-B125 2CCS892001R0845 204037 0.48 1 3 10 S803N-B10 2CCS893001R0105 204044 0.72 1 13 S803N-B13 2CCS893001R0135 204051 0.72 1 16 S803N-B16 2CCS893001R0165 204068 0.72 1 20 S803N-B20 2CCS893001R0205 204075 0.72 1 25 S803N-B25 2CCS893001R0255 204082 0.72 1 32 S803N-B32 2CCS893001R0325 204099 0.72 1 40 S803N-B40 2CCS893001R0405 204105 0.72 1 50 S803N-B50 2CCS893001R0505 204112 0.72 1 63 S803N-B63 2CCS893001R0635 204129 0.72 1 80 S803N-B80 2CCS893001R0805 204136 0.72 1 100 S803N-B100 2CCS893001R0825 204143 0.72 1 125 S803N-B125 2CCS893001R0845 204150 0.72 1 4 10 S804N-B10 2CCS894001R0105 204167 0.96 1 13 S804N-B13 2CCS894001R0135 204174 0.96 1 16 S804N-B16 2CCS894001R0165 204181 0.96 1 20 S804N-B20 2CCS894001R0205 204198 0.96 1 25 S804N-B25 2CCS894001R0255 204204 0.96 1 32 S804N-B32 2CCS894001R0325 204211 0.96 1 40 S804N-B40 2CCS894001R0405 204228 0.96 1 50 S804N-B50 2CCS894001R0505 204235 0.96 1 63 S804N-B63 2CCS894001R0635 204242 0.96 1 80 S804N-B80 2CCS894001R0805 204259 0.96 1 100 S804N-B100 2CCS894001R0825 204266 0.96 1 125 S804N-B125 2CCS894001R0845 204273 0.96 1 System pro M compact® 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

C S800N-CSelection tables High performance MCB with cage terminal S800N-C characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for resistive and inductive loads with low inrush current; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=20 kA (10 ... 80 A) Icu=36 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801N-C10 2CCS891001R0104 204280 0.24 1 13 S801N-C13 2CCS891001R0134 204297 0.24 1 16 S801N-C16 2CCS891001R0164 204303 0.24 1 20 S801N-C20 2CCS891001R0204 204310 0.24 1 25 S801N-C25 2CCS891001R0254 204327 0.24 1 32 S801N-C32 2CCS891001R0324 204334 0.24 1 40 S801N-C40 2CCS891001R0404 204341 0.24 1 50 S801N-C50 2CCS891001R0504 204358 0.24 1 63 S801N-C63 2CCS891001R0634 204365 0.24 1 80 S801N-C80 2CCS891001R0804 204372 0.24 1 100 S801N-C100 2CCS891001R0824 204389 0.24 1 125 S801N-C125 2CCS891001R0844 204396 0.24 1 2 10 S802N-C10 2CCS892001R0104 204402 0.48 1 13 S802N-C13 2CCS892001R0134 204419 0.48 1 16 S802N-C16 2CCS892001R0164 204426 0.48 1 20 S802N-C20 2CCS892001R0204 204433 0.48 1 25 S802N-C25 2CCS892001R0254 204440 0.48 1 32 S802N-C32 2CCS892001R0324 204457 0.48 1 40 S802N-C40 2CCS892001R0404 204464 0.48 1 50 S802N-C50 2CCS892001R0504 204471 0.48 1 63 S802N-C63 2CCS892001R0634 204488 0.48 1 80 S802N-C80 2CCS892001R0804 204495 0.48 1 100 S802N-C100 2CCS892001R0824 204501 0.48 1 125 S802N-C125 2CCS892001R0844 204518 0.48 1 3 10 S803N-C10 2CCS893001R0104 204525 0.72 1 13 S803N-C13 2CCS893001R0134 204532 0.72 1 16 S803N-C16 2CCS893001R0164 204549 0.72 1 20 S803N-C20 2CCS893001R0204 204556 0.72 1 25 S803N-C25 2CCS893001R0254 204563 0.72 1 32 S803N-C32 2CCS893001R0324 204570 0.72 1 40 S803N-C40 2CCS893001R0404 204587 0.72 1 50 S803N-C50 2CCS893001R0504 204594 0.72 1 63 S803N-C63 2CCS893001R0634 204600 0.72 1 80 S803N-C80 2CCS893001R0804 204617 0.72 1 100 S803N-C100 2CCS893001R0824 204624 0.72 1 125 S803N-C125 2CCS893001R0844 204631 0.72 1 4 10 S804N-C10 2CCS894001R0104 204648 0.96 1 13 S804N-C13 2CCS894001R0134 204655 0.96 1 16 S804N-C16 2CCS894001R0164 204662 0.96 1 20 S804N-C20 2CCS894001R0204 204679 0.96 1 25 S804N-C25 2CCS894001R0254 204686 0.96 1 32 S804N-C32 2CCS894001R0324 204693 0.96 1 40 S804N-C40 2CCS894001R0404 204709 0.96 1 50 S804N-C50 2CCS894001R0504 204716 0.96 1 63 S804N-C63 2CCS894001R0634 204723 0.96 1 80 S804N-C80 2CCS894001R0804 204730 0.96 1 100 S804N-C100 2CCS894001R0824 204747 0.96 1 125 S804N-C125 2CCS894001R0844 204754 0.96 1 System pro M compact® 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

D S800N-DSelection tables High performance MCB with cage terminal S800N-D characteristic Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for circuits which supply loads with high inrush current at the circuit closing (motors, LV / LV transformers, breakdown lamps); very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60898, IEC/EN 60947-2 Icn=20 kA (10 ... 80 A) Icu=36 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801N-D10 2CCS891001R0101 204761 0.245 1 13 S801N-D13 2CCS891001R0131 204778 0.245 1 16 S801N-D16 2CCS891001R0161 204785 0.245 1 20 S801N-D20 2CCS891001R0201 204792 0.245 1 25 S801N-D25 2CCS891001R0251 204808 0.245 1 32 S801N-D32 2CCS891001R0321 204815 0.245 1 40 S801N-D40 2CCS891001R0401 204822 0.245 1 50 S801N-D50 2CCS891001R0501 204839 0.245 1 63 S801N-D63 2CCS891001R0631 204846 0.245 1 80 S801N-D80 2CCS891001R0801 204853 0.245 1 100 S801N-D100 2CCS891001R0821 204860 0.245 1 125 S801N-D125 2CCS891001R0841 204877 0.245 1 2 10 S802N-D10 2CCS892001R0101 204884 0.49 1 13 S802N-D13 2CCS892001R0131 204891 0.49 1 16 S802N-D16 2CCS892001R0161 204907 0.49 1 20 S802N-D20 2CCS892001R0201 204914 0.49 1 25 S802N-D25 2CCS892001R0251 204921 0.49 1 32 S802N-D32 2CCS892001R0321 204938 0.49 1 40 S802N-D40 2CCS892001R0401 204945 0.49 1 50 S802N-D50 2CCS892001R0501 204952 0.49 1 63 S802N-D63 2CCS892001R0631 204969 0.49 1 80 S802N-D80 2CCS892001R0801 204976 0.49 1 100 S802N-D100 2CCS892001R0821 204983 0.49 1 125 S802N-D125 2CCS892001R0841 204990 0.49 1 3 10 S803N-D10 2CCS893001R0101 205003 0.735 1 13 S803N-D13 2CCS893001R0131 205010 0.735 1 16 S803N-D16 2CCS893001R0161 205027 0.735 1 20 S803N-D20 2CCS893001R0201 205034 0.735 1 25 S803N-D25 2CCS893001R0251 205041 0.735 1 32 S803N-D32 2CCS893001R0321 205058 0.735 1 40 S803N-D40 2CCS893001R0401 205065 0.735 1 50 S803N-D50 2CCS893001R0501 205072 0.735 1 63 S803N-D63 2CCS893001R0631 205089 0.735 1 80 S803N-D80 2CCS893001R0801 205096 0.735 1 100 S803N-D100 2CCS893001R0821 205102 0.735 1 125 S803N-D125 2CCS893001R0841 205119 0.735 1 4 10 S804N-D10 2CCS894001R0101 205126 0.98 1 13 S804N-D13 2CCS894001R0131 205133 0.98 1 16 S804N-D16 2CCS894001R0161 205140 0.98 1 20 S804N-D20 2CCS894001R0201 205157 0.98 1 25 S804N-D25 2CCS894001R0251 205164 0.98 1 32 S804N-D32 2CCS894001R0321 205171 0.98 1 40 S804N-D40 2CCS894001R0401 205188 0.98 1 50 S804N-D50 2CCS894001R0501 205195 0.98 1 63 S804N-D63 2CCS894001R0631 205201 0.98 1 80 S804N-D80 2CCS894001R0801 205218 0.98 1 100 S804N-D100 2CCS894001R0821 205225 0.98 1 125 S804N-D125 2CCS894001R0841 205232 0.98 1 System pro M compact® 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2, IEC/EN 60898 Icn=15 kA Icu=25 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801C-B10 2CCS881001R0105 212087 0.245 1 13 S801C-B13 2CCS881001R0135 212247 0.245 1 16 S801C-B16 2CCS881001R0165 212407 0.245 1 20 S801C-B20 2CCS881001R0205 212568 0.245 1 25 S801C-B25 2CCS881001R0255 212728 0.245 1 32 S801C-B32 2CCS881001R0325 212889 0.245 1 40 S801C-B40 2CCS881001R0405 213046 0.245 1 50 S801C-B50 2CCS881001R0505 213206 0.245 1 63 S801C-B63 2CCS881001R0635 213367 0.245 1 80 S801C-B80 2CCS881001R0805 213527 0.245 1 100 S801C-B100 2CCS881001R0825 213688 0.245 1 125 S801C-B125 2CCS881001R0845 213848 0.245 1 2 10 S802C-B10 2CCS882001R0105 212094 0.49 1 13 S802C-B13 2CCS882001R0135 212254 0.49 1 16 S802C-B16 2CCS882001R0165 212414 0.49 1 20 S802C-B20 2CCS882001R0205 212575 0.49 1 25 S802C-B25 2CCS882001R0255 212735 0.49 1 32 S802C-B32 2CCS882001R0325 212896 0.49 1 40 S802C-B40 2CCS882001R0405 213053 0.49 1 50 S802C-B50 2CCS882001R0505 213213 0.49 1 63 S802C-B63 2CCS882001R0635 213374 0.49 1 80 S802C-B80 2CCS882001R0805 213534 0.49 1 100 S802C-B100 2CCS882001R0825 213695 0.49 1 125 S802C-B125 2CCS882001R0845 213855 0.49 1 3 10 S803C-B10 2CCS883001R0105 212100 0.735 1 13 S803C-B13 2CCS883001R0135 212261 0.735 1 16 S803C-B16 2CCS883001R0165 212421 0.735 1 20 S803C-B20 2CCS883001R0205 212582 0.735 1 25 S803C-B25 2CCS883001R0255 212742 0.735 1 32 S803C-B32 2CCS883001R0325 212902 0.735 1 40 S803C-B40 2CCS883001R0405 213060 0.735 1 50 S803C-B50 2CCS883001R0505 213220 0.735 1 63 S803C-B63 2CCS883001R0635 213381 0.735 1 80 S803C-B80 2CCS883001R0805 213541 0.735 1 100 S803C-B100 2CCS883001R0825 213701 0.735 1 125 S803C-B125 2CCS883001R0845 213862 0.735 1 4 10 S804C-B10 2CCS884001R0105 212117 0.98 1 13 S804C-B13 2CCS884001R0135 212278 0.98 1 16 S804C-B16 2CCS884001R0165 212438 0.98 1 20 S804C-B20 2CCS884001R0205 212599 0.98 1 25 S804C-B25 2CCS884001R0255 212759 0.98 1 32 S804C-B32 2CCS884001R0325 212919 0.98 1 40 S804C-B40 2CCS884001R0405 213077 0.98 1 50 S804C-B50 2CCS884001R0505 213237 0.98 1 63 S804C-B63 2CCS884001R0635 213398 0.98 1 80 S804C-B80 2CCS884001R0805 213558 0.98 1 100 S804C-B100 2CCS884001R0825 213718 0.98 1 125 S804C-B125 2CCS884001R0845 213879 0.98 1 System pro M compact® B 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2, IEC/EN 60898 Icn=15 kA Icu=25 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801C-C10 2CCS881001R0104 212124 0.245 1 13 S801C-C13 2CCS881001R0134 212285 0.245 1 16 S801C-C16 2CCS881001R0164 212445 0.245 1 20 S801C-C20 2CCS881001R0204 212605 0.245 1 25 S801C-C25 2CCS881001R0254 212766 0.245 1 32 S801C-C32 2CCS881001R0324 212926 0.245 1 40 S801C-C40 2CCS881001R0404 213084 0.245 1 50 S801C-C50 2CCS881001R0504 213244 0.245 1 63 S801C-C63 2CCS881001R0634 213404 0.245 1 80 S801C-C80 2CCS881001R0804 213565 0.245 1 100 S801C-C100 2CCS881001R0824 213725 0.245 1 125 S801C-C125 2CCS881001R0844 213886 0.245 1 2 10 S802C-C10 2CCS882001R0104 212131 0.49 1 13 S802C-C13 2CCS882001R0134 212292 0.49 1 16 S802C-C16 2CCS882001R0164 212452 0.49 1 20 S802C-C20 2CCS882001R0204 212612 0.49 1 25 S802C-C25 2CCS882001R0254 212773 0.49 1 32 S802C-C32 2CCS882001R0324 212933 0.49 1 40 S802C-C40 2CCS882001R0404 213091 0.49 1 50 S802C-C50 2CCS882001R0504 213251 0.49 1 63 S802C-C63 2CCS882001R0634 213411 0.49 1 80 S802C-C80 2CCS882001R0804 213572 0.49 1 100 S802C-C100 2CCS882001R0824 213732 0.49 1 125 S802C-C125 2CCS882001R0844 213893 0.49 1 3 10 S803C-C10 2CCS883001R0104 212148 0.735 1 13 S803C-C13 2CCS883001R0134 212308 0.735 1 16 S803C-C16 2CCS883001R0164 212469 0.735 1 20 S803C-C20 2CCS883001R0204 212629 0.735 1 25 S803C-C25 2CCS883001R0254 212780 0.735 1 32 S803C-C32 2CCS883001R0324 212940 0.735 1 40 S803C-C40 2CCS883001R0404 213107 0.735 1 50 S803C-C50 2CCS883001R0504 213268 0.735 1 63 S803C-C63 2CCS883001R0634 213428 0.735 1 80 S803C-C80 2CCS883001R0804 213589 0.735 1 100 S803C-C100 2CCS883001R0824 213749 0.735 1 125 S803C-C125 2CCS883001R0844 213909 0.735 1 4 10 S804C-C10 2CCS884001R0104 212155 0.98 1 13 S804C-C13 2CCS884001R0134 212315 0.98 1 16 S804C-C16 2CCS884001R0164 212476 0.98 1 20 S804C-C20 2CCS884001R0204 212636 0.98 1 25 S804C-C25 2CCS884001R0254 212797 0.98 1 32 S804C-C32 2CCS884001R0324 212957 0.98 1 40 S804C-C40 2CCS884001R0404 213114 0.98 1 50 S804C-C50 2CCS884001R0504 213275 0.98 1 63 S804C-C63 2CCS884001R0634 213435 0.98 1 80 S804C-C80 2CCS884001R0804 213596 0.98 1 100 S804C-C100 2CCS884001R0824 213756 0.98 1 125 S804C-C125 2CCS884001R0844 213916 0.98 1 System pro M compact® C 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2, IEC/EN 60898 Icn=15kA Icu=25 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801C-D10 2CCS881001R0101 212162 0.245 1 13 S801C-D13 2CCS881001R0131 212322 0.245 1 16 S801C-D16 2CCS881001R0161 212483 0.245 1 20 S801C-D20 2CCS881001R0201 212643 0.245 1 25 S801C-D25 2CCS881001R0251 212803 0.245 1 32 S801C-D32 2CCS881001R0321 212964 0.245 1 40 S801C-D40 2CCS881001R0401 213121 0.245 1 50 S801C-D50 2CCS881001R0501 213282 0.245 1 63 S801C-D63 2CCS881001R0631 213442 0.245 1 80 S801C-D80 2CCS881001R0801 213602 0.245 1 100 S801C-D100 2CCS881001R0821 213763 0.245 1 125 S801C-D125 2CCS881001R0841 213923 0.245 1 2 10 S802C-D10 2CCS882001R0101 212179 0.49 1 13 S802C-D13 2CCS882001R0131 212339 0.49 1 16 S802C-D16 2CCS882001R0161 212490 0.49 1 20 S802C-D20 2CCS882001R0201 212650 0.49 1 25 S802C-D25 2CCS882001R0251 212810 0.49 1 32 S802C-D32 2CCS882001R0321 212971 0.49 1 40 S802C-D40 2CCS882001R0401 213138 0.49 1 50 S802C-D50 2CCS882001R0501 213299 0.49 1 63 S802C-D63 2CCS882001R0631 213459 0.49 1 80 S802C-D80 2CCS882001R0801 213619 0.49 1 100 S802C-D100 2CCS882001R0821 213770 0.49 1 125 S802C-D125 2CCS882001R0841 213930 0.49 1 3 10 S803C-D10 2CCS883001R0101 212186 0.735 1 13 S803C-D13 2CCS883001R0131 212346 0.735 1 16 S803C-D16 2CCS883001R0161 212506 0.735 1 20 S803C-D20 2CCS883001R0201 212667 0.735 1 25 S803C-D25 2CCS883001R0251 212827 0.735 1 32 S803C-D32 2CCS883001R0321 212988 0.735 1 40 S803C-D40 2CCS883001R0401 213145 0.735 1 50 S803C-D50 2CCS883001R0501 213305 0.735 1 63 S803C-D63 2CCS883001R0631 213466 0.735 1 80 S803C-D80 2CCS883001R0801 213626 0.735 1 100 S803C-D100 2CCS883001R0821 213787 0.735 1 125 S803C-D125 2CCS883001R0841 213947 0.735 1 4 10 S804C-D10 2CCS884001R0101 212193 0.98 1 13 S804C-D13 2CCS884001R0131 212353 0.98 1 16 S804C-D16 2CCS884001R0161 212513 0.98 1 20 S804C-D20 2CCS884001R0201 212674 0.98 1 25 S804C-D25 2CCS884001R0251 212834 0.98 1 32 S804C-D32 2CCS884001R0321 212995 0.98 1 40 S804C-D40 2CCS884001R0401 213152 0.98 1 50 S804C-D50 2CCS884001R0501 213312 0.98 1 63 S804C-D63 2CCS884001R0631 213473 0.98 1 80 S804C-D80 2CCS884001R0801 213633 0.98 1 100 S804C-D100 2CCS884001R0821 213794 0.98 1 125 S804C-D125 2CCS884001R0841 213954 0.98 1 System pro M compact® D 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: IEC/EN 60947-2 Icu=25 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801C-K10 2CCS881001R0427 212209 0.245 1 13 S801C-K13 2CCS881001R0447 212360 0.245 1 16 S801C-K16 2CCS881001R0467 212520 0.245 1 20 S801C-K20 2CCS881001R0487 212681 0.245 1 25 S801C-K25 2CCS881001R0517 212841 0.245 1 32 S801C-K32 2CCS881001R0537 213008 0.245 1 40 S801C-K40 2CCS881001R0557 213169 0.245 1 50 S801C-K50 2CCS881001R0577 213329 0.245 1 63 S801C-K63 2CCS881001R0597 213480 0.245 1 80 S801C-K80 2CCS881001R0627 213640 0.245 1 100 S801C-K100 2CCS881001R0637 213800 0.245 1 125 S801C-K125 2CCS881001R0647 213961 0.245 1 2 10 S802C-K10 2CCS882001R0427 212216 0.49 1 13 S802C-K13 2CCS882001R0447 212377 0.49 1 16 S802C-K16 2CCS882001R0467 212537 0.49 1 20 S802C-K20 2CCS882001R0487 212698 0.49 1 25 S802C-K25 2CCS882001R0517 212858 0.49 1 32 S802C-K32 2CCS882001R0537 213015 0.49 1 40 S802C-K40 2CCS882001R0557 213176 0.49 1 50 S802C-K50 2CCS882001R0577 213336 0.49 1 63 S802C-K63 2CCS882001R0597 213497 0.49 1 80 S802C-K80 2CCS882001R0627 213657 0.49 1 100 S802C-K100 2CCS882001R0637 213817 0.49 1 125 S802C-K125 2CCS882001R0647 213978 0.49 1 3 10 S803C-K10 2CCS883001R0427 212223 0.735 1 13 S803C-K13 2CCS883001R0447 212384 0.735 1 16 S803C-K16 2CCS883001R0467 212544 0.735 1 20 S803C-K20 2CCS883001R0487 212704 0.735 1 25 S803C-K25 2CCS883001R0517 212865 0.735 1 32 S803C-K32 2CCS883001R0537 213022 0.735 1 40 S803C-K40 2CCS883001R0557 213183 0.735 1 50 S803C-K50 2CCS883001R0577 213343 0.735 1 63 S803C-K63 2CCS883001R0597 213503 0.735 1 80 S803C-K80 2CCS883001R0627 213664 0.735 1 100 S803C-K100 2CCS883001R0637 213824 0.735 1 125 S803C-K125 2CCS883001R0647 213985 0.735 1 4 10 S804C-K10 2CCS884001R0427 212230 0.98 1 13 S804C-K13 2CCS884001R0447 212391 0.98 1 16 S804C-K16 2CCS884001R0467 212551 0.98 1 20 S804C-K20 2CCS884001R0487 212711 0.98 1 25 S804C-K25 2CCS884001R0517 212872 0.98 1 32 S804C-K32 2CCS884001R0537 213039 0.98 1 40 S804C-K40 2CCS884001R0557 213190 0.98 1 50 S804C-K50 2CCS884001R0577 213350 0.98 1 63 S804C-K63 2CCS884001R0597 213510 0.98 1 80 S804C-K80 2CCS884001R0627 213671 0.98 1 100 S804C-K100 2CCS884001R0637 213831 0.98 1 125 S804C-K125 2CCS884001R0647 213992 0.98 1 System pro M compact® K 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: UL489, CSA 22.2 NO.5-02, IEC/EN 60947-2 Icu=30 kA (1 pole), 50 kA (2...4 poles) Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801U-Z10 2CCS881017R0105 214487 0.245 1 15 S801U-Z15 2CCS881017R0155 214524 0.245 1 20 S801U-Z20 2CCS881017R0205 214562 0.245 1 25 S801U-Z25 2CCS881017R0255 214609 0.245 1 30 S801U-Z30 2CCS881017R0305 214647 0.245 1 40 S801U-Z40 2CCS881017R0405 214685 0.245 1 50 S801U-Z50 2CCS881017R0505 214722 0.245 1 60 S801U-Z60 2CCS881017R0605 214760 0.245 1 70 S801U-Z70 2CCS881017R0705 214807 0.245 1 80 S801U-Z80 2CCS881017R0805 214845 0.245 1 90 S801U-Z90 2CCS881017R0905 214883 0.245 1 100 S801U-Z100 2CCS881017R0825 214920 0.245 1 2 10 S802U-Z10 2CCS862017R0105 214494 0.49 1 15 S802U-Z15 2CCS862017R0155 214531 0.49 1 20 S802U-Z20 2CCS862017R0205 214579 0.49 1 25 S802U-Z25 2CCS862017R0255 214616 0.49 1 30 S802U-Z30 2CCS862017R0305 214654 0.49 1 40 S802U-Z40 2CCS862017R0405 214692 0.49 1 50 S802U-Z50 2CCS862017R0505 214739 0.49 1 60 S802U-Z60 2CCS862017R0605 214777 0.49 1 70 S802U-Z70 2CCS862017R0705 214814 0.49 1 80 S802U-Z80 2CCS862017R0805 214852 0.49 1 90 S802U-Z90 2CCS862017R0905 214890 0.49 1 100 S802U-Z100 2CCS862017R0825 214937 0.49 1 3 10 S803U-Z10 2CCS863017R0105 214500 0.735 1 15 S803U-Z15 2CCS863017R0155 214548 0.735 1 20 S803U-Z20 2CCS863017R0205 214586 0.735 1 25 S803U-Z25 2CCS863017R0255 214623 0.735 1 30 S803U-Z30 2CCS863017R0305 214661 0.735 1 40 S803U-Z40 2CCS863017R0405 214708 0.735 1 50 S803U-Z50 2CCS863017R0505 214746 0.735 1 60 S803U-Z60 2CCS863017R0605 214784 0.735 1 70 S803U-Z70 2CCS863017R0705 214821 0.735 1 80 S803U-Z80 2CCS863017R0805 214869 0.735 1 90 S803U-Z90 2CCS863017R0905 214906 0.735 1 100 S803U-Z100 2CCS863017R0825 214944 0.735 1 4 10 S804U-Z10 2CCS864017R0105 214517 0.98 1 15 S804U-Z15 2CCS864017R0155 214555 0.98 1 20 S804U-Z20 2CCS864017R0205 214593 0.98 1 25 S804U-Z25 2CCS864017R0255 214630 0.98 1 30 S804U-Z30 2CCS864017R0305 214678 0.98 1 40 S804U-Z40 2CCS864017R0405 214715 0.98 1 50 S804U-Z50 2CCS864017R0505 214753 0.98 1 60 S804U-Z60 2CCS864017R0605 214791 0.98 1 70 S804U-Z70 2CCS864017R0705 214838 0.98 1 80 S804U-Z80 2CCS864017R0805 214876 0.98 1 90 S804U-Z90 2CCS864017R0905 214913 0.98 1 100 S804U-Z100 2CCS864017R0825 214951 0.98 1 System pro M compact® Z 2CCC413001F00022CCC413001F00022CCC413001F00022CCC413001F0002

Function: protection and control of the circuits against overloads and short-circuits when a high breaking capacity is required; protection for people and big length cables in TN and IT systems; very useful when selectivity is needed vs an MCCB or back-up vs other MCBs wired downstream. Applications: commercial and industrial. Standard: UL489, CSA 22.2 NO.5-02, IEC/EN 60947-2 Icu=30 kA (1-pole), 50 kA (2...4-pole) Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 1 10 S801U-K10 2CCS881017R0427 214005 0.245 1 15 S801U-K15 2CCS881017R0457 214043 0.245 1 20 S801U-K20 2CCS881017R0487 214081 0.245 1 25 S801U-K25 2CCS881017R0517 214128 0.245 1 30 S801U-K30 2CCS881017R0527 214166 0.245 1 40 S801U-K40 2CCS881017R0557 214203 0.245 1 50 S801U-K50 2CCS881017R0577 214241 0.245 1 60 S801U-K60 2CCS881017R0587 214289 0.245 1 70 S801U-K70 2CCS881017R0707 214326 0.245 1 80 S801U-K80 2CCS881017R0627 214364 0.245 1 90 S801U-K90 2CCS881017R0907 214401 0.245 1 100 S801U-K100 2CCS881017R0637 214449 0.245 1 2 10 S802U-K10 2CCS862017R0427 214012 0.49 1 15 S802U-K15 2CCS862017R0457 214050 0.49 1 20 S802U-K20 2CCS862017R0487 214098 0.49 1 25 S802U-K25 2CCS862017R0517 214135 0.49 1 30 S802U-K30 2CCS862017R0527 214173 0.49 1 40 S802U-K40 2CCS862017R0557 214210 0.49 1 50 S802U-K50 2CCS862017R0577 214258 0.49 1 60 S802U-K60 2CCS862017R0587 214296 0.49 1 70 S802U-K70 2CCS862017R0707 214333 0.49 1 80 S802U-K80 2CCS862017R0627 214371 0.49 1 90 S802U-K90 2CCS862017R0907 214418 0.49 1 100 S802U-K100 2CCS862017R0637 214456 0.49 1 3 10 S803U-K10 2CCS863017R0427 214029 0.735 1 15 S803U-K15 2CCS863017R0457 214067 0.735 1 20 S803U-K20 2CCS863017R0487 214104 0.735 1 25 S803U-K25 2CCS863017R0517 214142 0.735 1 30 S803U-K30 2CCS863017R0527 214180 0.735 1 40 S803U-K40 2CCS863017R0557 214227 0.735 1 50 S803U-K50 2CCS863017R0577 214265 0.735 1 60 S803U-K60 2CCS863017R0587 214302 0.735 1 70 S803U-K70 2CCS863017R0707 214340 0.735 1 80 S803U-K80 2CCS863017R0627 214388 0.735 1 90 S803U-K90 2CCS863017R0907 214425 0.735 1 100 S803U-K100 2CCS863017R0637 214463 0.735 1 4 10 S804U-K10 2CCS864017R0427 214036 0.98 1 15 S804U-K15 2CCS864017R0457 214074 0.98 1 20 S804U-K20 2CCS864017R0487 214111 0.98 1 25 S804U-K25 2CCS864017R0517 214159 0.98 1 30 S804U-K30 2CCS864017R0527 214197 0.98 1 40 S804U-K40 2CCS864017R0557 214234 0.98 1 50 S804U-K50 2CCS864017R0577 214272 0.98 1 60 S804U-K60 2CCS864017R0587 214319 0.98 1 70 S804U-K70 2CCS864017R0707 214357 0.98 1 80 S804U-K80 2CCS864017R0627 214395 0.98 1 90 S804U-K90 2CCS864017R0907 214432 0.98 1 100 S804U-K100 2CCS864017R0637 214470 0.98 1 System pro M compact® K 2CCC413001F00022CCC413001F0002 2CCC413001F00022CCC413001F0002

Function: protection and control of photovoltaic strings against overloads and short-circuits. Ideal replacement for fuses due to comfortable string failure identification and signalisation. Applications: Photovoltaic systems. Standard: IEC 60947-2 Icu=5 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 2 10 S802PV-S10 2CCP842001R1109 210939 0.49 1 13 S802PV-S13 2CCP842001R1139 210946 0.49 1 16 S802PV-S16 2CCP842001R1169 210953 0.49 1 20 S802PV-S20 2CCP842001R1209 210960 0.49 1 25 S802PV-S25 2CCP842001R1259 210977 0.49 1 32 S802PV-S32 2CCP842001R1329 210984 0.49 1 40 S802PV-S40 2CCP842001R1409 210991 0.49 1 50 S802PV-S50 2CCP842001R1509 211004 0.49 1 63 S802PV-S63 2CCP842001R1639 211011 0.49 1 80 S802PV-S80 2CCP842001R1809 211028 0.49 1 100 S802PV-S100 2CCP842001R1829 214968 0.49 1 125 S802PV-S125 2CCP842001R1849 214999 0.49 1 3 10 S803PV-S10 2CCP843001R1109 211035 0.735 1 13 S803PV-S13 2CCP843001R1139 211042 0.735 1 16 S803PV-S16 2CCP843001R1169 211059 0.735 1 20 S803PV-S20 2CCP843001R1209 211066 0.735 1 25 S803PV-S25 2CCP843001R1259 211073 0.735 1 32 S803PV-S32 2CCP843001R1329 211080 0.735 1 40 S803PV-S40 2CCP843001R1409 211097 0.735 1 50 S803PV-S50 2CCP843001R1509 211103 0.735 1 63 S803PV-S63 2CCP843001R1639 211110 0.735 1 80 S803PV-S80 2CCP843001R1809 211127 0.735 1 100 S803PV-S100 2CCP843001R1829 214975 0.740 1 125 S803PV-S125 2CCP843001R1849 215002 0.740 1 4 10 S804PV-S10 2CCP844001R1109 211134 0.98 1 13 S804PV-S13 2CCP844001R1139 211141 0.98 1 16 S804PV-S16 2CCP844001R1169 211158 0.98 1 20 S804PV-S20 2CCP844001R1209 211165 0.98 1 25 S804PV-S25 2CCP844001R1259 211172 0.98 1 32 S804PV-S32 2CCP844001R1329 211189 0.98 1 40 S804PV-S40 2CCP844001R1409 211196 0.98 1 50 S804PV-S50 2CCP844001R1509 211202 0.98 1 63 S804PV-S63 2CCP844001R1639 211219 0.98 1 80 S804PV-S80 2CCP844001R1809 211226 0.98 1 100 S804PV-S100 2CCP844001R1829 214982 0.98 1 125 S804PV-S125 2CCP844001R1849 215019 0.98 1 System pro M compact® PV-S 2CCC413001F00022CCC413001F00022CCC413001F0002

Function: DC main switch for photovoltaic applications. Safe disconnection of photovoltaic arrays. Applications: Photovoltaic systems. Standard: IEC 60947-3 Icw=1.5 kA Number of poles Rated current Order details Bbn 7612271 Price 1 piece Price group Weight 1 piece Pack unit In A Type code Order code EAN kg pc. 2 32 S802PV-M32 2CCP812001R1329 211233 0.43 1 63 S802PV-M63 2CCD842001R1590 215026 0.65 1 125 S802PV-M125 2CCP812001R1849 211240 0.43 1 3 32 S803PV-M32 2CCP813001R1329 211257 0.65 1 63 S803PV-M63 2CCD843001R1590 215033 0.65 1 125 S803PV-M125 2CCP813001R1849 211264 0.65 1 4 32 S804PV-M32 2CCP814001R1329 211271 0.86 1 63 S804PV-M63 2CCD844001R1590 215040 0.86 1 125 S804PV-M125 2CCP814001R1849 211288 0.86 1 System pro M compact® 2CCC413001F00022CCC413001F00022CCC413001F0002

Standards IEC/EN 60947-2, UL 1077 /L54706, CAN/CSA-C22.2 No. 35 Rated current In A adjustable 0.1 ≤ In ≤ 3 / 2.8 ≤ In ≤ 11 / 10 ≤ In ≤ 45 Poles 1, 2, 3+N, NA Rated voltage Ue IEC AC V 230/400; 250/440; 3x500; 400/690 UL/CSA AC V 240/415; 277/480; 346/600 Insulation voltage Ui V 690 Max. operating IEC AC V 400/690 voltage Ub max. UL/CSA AC V 600 Y/346 Rated frequency Hz 16 2/3, 50/60 Rated breaking capacity ultimate Icu kA 100 (0.1 - 3A) 50 (2.8 - 11A) 30 (10 - 45A) acc. to IEC/EN 60947-2 1P @ 230 VAC 2P , 3P , 4P@ 400 VAC service Ics kA 100 (0.1 - 3A) 30 (2.8 - 11A) 25 (10 - 45A) Rated interrupting capacity IR kA 14 acc. to UL1077, CSA22.2 No.35 1P@277 VAC 2P ,3P ,4P@480 VAC Rated impulse withstand voltage (1.2/50) Uimp kV 6 Overvoltage category Thermomagnetic release K: 8 In ≤ Im ≤ 14 In Q characteristic Toggle grey sealable in ON-OFF position Protection degree housing IP4X terminals IP2X Tropicalization humid heat °C/RH DIN 50016 acc. to IEC/EN 60068-2 Reference temperature for setting of thermal element °C 40 Ambient temperature (with daily average °C -25…+55 ≤ +35 °C) Terminal type cage (shock protected) Terminal size top/bottom for cable IEC mm 2 1 ... 25 UL/CSA AWG 17 Tightening torque Nm 2.5 Mounting on DIN rail EN 60715 Connection from top and bottom Pole dimensions (H x D x W) mm 91 x 92 x 25 Pole weight g 250 Combinable with: signal contact/auxiliary switch yes shunt trip yes undervoltage release yes (factory fitted) mechanical interlock no motor operating device no /L54706 supplementary protection

TECHNICAL FEATURES S500UC-K Standards IEC/EN 60947-2, UL 1077 /L54706, CAN/CSA-C22.2 /L54706 No. 35 Rated current In A adjustable 0.1 ≤ In ≤ 3 / 2.8 ≤ In ≤ 11 / 10 ≤ In ≤ 45 Poles 1 ... 4 Rated voltage Ue DC V 250 per pole (4P 750V) Insulation voltage Ui V 1000 VDC Max. operating voltage Ub max. DC V 250 per pole (4P 750V) Rated breaking capacity ultimate Icu kA 30 acc. to IEC/EN 60947-2 1P@ 250 VDC 2P@500 VDC 3P , 4P@ 750 VDC Rated interrupting capacity IR kA 30 acc. to UL1077, CSA22.2 No.235 1P@60 VDC 2P , 3P , 4P@125 VDC Rated impulse withstand voltage Uimp kV 6 Overvoltage category Thermomagnetic release characteristic K: 8 In ≤ Im ≤ 14 In Q Toggle grey sealable in ON-OFF position Protection degree housing IP4X terminals IP2X Tropicalization humid heat °C/RH DIN 50016 acc. to IEC/EN 60068-2 Reference temperature for setting of thermal element °C 40 Ambient temperature (with daily average ≤ +35 °C) °C -25…+55 Terminal type cage (shock protected) Terminal size top/bottom for cable IEC mm 2 1 ... 25 UL/CSA AWG 17-4 Tightening torque IEC Nm 2.5 Tool Nr. 2 Posidriv Mounting on DIN rail EN 60715 Connection from top and bottom Pole dimensions (H x D x W) mm 91 x 92 x 25 Pole weight g 250 Combinable with: signal contact/auxiliary switch yes shunt trip yes undervoltage release yes (factory fitted) mechanical interlock no motor operating device no /L54706 supplementary protection

MCBs S500 series with adjustable thermal release for motor protection S500-K (power) characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when an high breaking capacity is required; very useful when it is needed selectivity vs an MCCB or back-up vs other MCBs wired downstream; version with adjustable thermal release, dedicated to protect motors. Advantages: No nuisance tripping in the case of functional peak currents up to 8xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL 1077 Icu up to 100 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 7612270 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1-1.5 S501 K1 - 1.5 2CCF008863R0001 303076 0.250 1 2-3 S501 K2-3 2CCF008865R0001 303090 0.250 1 5.3-8 S501 K5.3 - 8 2CCF008868R0001 303120 0.250 1 7.3-11 S501 K7.3 - 11 2CCF008869R0001 303137 0.250 1 10-15 S501 K10 - 15 2CCF008870R0001 303144 0.250 1 14-20 S501 K14 - 20 2CCF008871R0001 303151 0.250 1 18-26 S501 K18 - 26 2CCF008872R0001 303168 0.250 1 23-32 S501 K23 - 32 2CCF008873R0001 303175 0.250 1 29-37 S501 K29 - 37 2CCF008874R0001 303182 0.250 1 34-41 S501 K34 - 41 2CCF008877R0001 303199 0.250 1 38-45 S501 K38 - 45 2CCF008888R0001 303205 0.250 1 1-1.5 S502 K1 - 1.5 2CCF008901R0001 303328 0.500 1 2-3 S502 K2-3 2CCF008903R0001 303342 0.500 1 5.3-8 S502 K5.3 - 8 2CCF008906R0001 303373 0.500 1 7.3-11 S502 K7.3 - 11 2CCF008907R0001 303380 0.500 1 10-15 S502 K10 - 15 2CCF008908R0001 303397 0.500 1 14-20 S502 K14 - 20 2CCF008909R0001 303403 0.500 1 18-26 S502 K18 - 26 2CCF008910R0001 303410 0.500 1 23-32 S502 K23 - 32 2CCF008911R0001 303427 0.500 1 29-37 S502 K29 - 37 2CCF008912R0001 303434 0.500 1 34-41 S502 K34 - 41 2CCF008913R0001 303441 0.500 1 38-45 S502 K38 - 45 2CCF008926R0001 303458 0.500 1 K 2CCC413001F00022CCC413001F0002

1-1.5 S503 K1 - 1.5 2CCF008939R0001 303571 0.750 1 2-3 S503 K2-3 2CCF008941R0001 303595 0.750 1 5.3-8 S503 K5.3 - 8 2CCF008944R0001 303625 0.750 1 7.3-11 S503 K7.3 - 11 2CCF008945R0001 303632 0.750 1 10-15 S503 K10 - 15 2CCF008946R0001 303649 0.750 1 14-20 S503 K14 - 20 2CCF008947R0001 303656 0.750 1 18-26 S503 K18 - 26 2CCF008948R0001 303663 0.750 1 23-32 S503 K23 - 32 2CCF008949R0001 303670 0.750 1 29-37 S503 K29 - 37 2CCF008950R0001 303687 0.750 1 34-41 S503 K34 - 41 2CCF008951R0001 303694 0.750 1 38-45 S503 K38 - 45 2CCF008964R0001 303700 0.750 1 4 0.1-0.15 S504UC-K0,15 2CCF011771R0001 302758 0,92 1 0.14-0.21 S504UC-K0,21 2CCF011772R0001 302765 0,92 1 0.2-0.3 S504UC-K0,3 2CCF011576R0001 302772 0,92 1 0.28-0.42 S504UC-K0,42 2CCF011773R0001 302789 0,92 1 0.38-0.58 S504UC-K0,58 2CCF011774R0001 302796 0,92 1 0.53-0.8 S504UC-K0,8 2CCF011775R0001 302802 0,92 1 0.73-1.1 S504UC-K1,1 2CCF011776R0001 302819 0,92 1 1-1.5 S504UC-K1,5 2CCF011777R0001 302826 0,92 1 1.4-2.1 S504UC-K2,1 2CCF011778R0001 302833 0,92 1 2-3 S504UC-K3 2CCF011779R0001 302840 0,92 1 2.8-4.2 S504UC-K4,2 2CCF011780R0001 302857 0,92 1 3.8-5.8 S504UC-K5,8 2CCF011781R0001 302864 0,92 1 5.3-8 S504UC-K8 2CCF011782R0001 302871 0,92 1 7.3-11 S504UC-K11 2CCF011509R0001 302888 0,92 1 10-15 S504UC-K15 2CCF011783R0001 302895 0,92 1 14-20 S504UC-K20 2CCF011784R0001 302901 0,92 1 18-26 S504UC-K26 2CCF011785R0001 302918 0,92 1 23-32 S504UC-K32 2CCF011786R0001 302925 0,92 1 29-37 S504UC-K37 2CCF011787R0001 302932 0,92 1 34-41 S504UC-K41 2CCF011788R0001 302949 0,92 1 38-45 S504UC-K45 2CCF011789R0001 302956 0,92 1 Note: from 5 to 6 poles available upon request System pro M S500-KSelection tables MCBs S500 series with adjustable thermal release for motor protection K 2CCC413001F0002

2CCC413001F0002 2CCC413001F0002 System pro M S500UC-KSelection tables MCBs S500UC series (especially for direct current) K S500UC series K (power) characteristic Function: protection and control of the circuits like motors, transformer and auxiliary circuits, against overloads and short-circuits when an high breaking capacity is required; very useful when it is needed selectivity vs an MCCB or back-up vs other MCBs wired downstream; version with adjustable thermal release, dedicated to protect motors; version dedicated to application in direct current circuits. Advantages: No nuisance tripping in the case of functional peak currents up to 8xIn, depending on the series; through its highly sensitive thermostatic bimetal trip, the K-type characteristic offers protection to damageable elements in the overcurrent range; it also provides the best protection to cables and lines. Applications: commercial and industrial. Standard: IEC/EN 60947-2, UL1077 Icu up to 30 kA Number Rated Order Bbn Price Price Weight Pack of poles current details 7612270 1 piece group 1 piece unit In A Type code Order code EAN kg pc. 1-1.5 S501 UC-K1 - 1.5 2CCF009009R0001 302079 0.250 1 2-3 S501 UC-K2-3 2CCF009015R0001 302093 0.250 1 5.3-8 S501 UC-K5.3 - 8 2CCF009024R0001 302123 0.250 1 7.3-11 S501 UC-K7.3 - 11 2CCF009027R0001 302130 0.250 1 10-15 S501 UC-K10 - 15 2CCF009030R0001 302147 0.250 1 14-20 S501 UC-K14 - 20 2CCF009033R0001 302154 0.250 1 18-26 S501 UC-K18 - 26 2CCF009036R0001 302161 0.250 1 23-32 S501 UC-K23 - 32 2CCF009039R0001 302178 0.250 1 29-37 S501 UC-K29 - 37 2CCF009042R0001 302185 0.250 1 34-41 S501 UC-K34 - 41 2CCF009045R0001 302192 0.250 1 38-45 S501 UC-K38 - 45 2CCF009048R0001 302208 0.250 8 1-1.5 S502 UC-K1 - 1.5 2CCF009010R0001 302321 0.500 1 2-3 S502 UC-K2-3 2CCF009016R0001 302345 0.500 1 5.3-8 S502 UC-K5.3 - 8 2CCF009025R0001 302376 0.500 1 7.3-11 S502 UC-K7.3 - 11 2CCF009028R0001 302383 0.500 1 10-15 S502 UC-K10 - 15 2CCF009031R0001 302390 0.500 1 14-20 S502 UC-K14 - 20 2CCF009034R0001 302406 0.500 1 18-26 S502 UC-K18 - 26 2CCF009037R0001 302413 0.500 1 23-32 S502 UC-K23 - 32 2CCF009040R0001 302420 0.500 1 29-37 S502 UC-K29 - 37 2CCF009043R0001 302437 0.500 1 34-41 S502 UC-K34 - 41 2CCF009046R0001 302444 0.500 1 38-45 S502 UC-K38 - 45 2CCF009049R0001 302451 0.500 1

1-1.5 S503 UC-K1 - 1.5 2CCF009011R0001 302574 0.750 1 2-3 S503 UC-K2-3 2CCF009017R0001 302598 0.750 1 5.3-8 S503 UC-K5.3 - 8 2CCF009026R0001 302628 0.750 1 7.3-11 S503 UC-K7.3 - 11 2CCF009029R0001 302635 0.750 1 10-15 S503 UC-K10 - 15 2CCF009032R0001 302642 0.750 1 14-20 S503 UC-K14 - 20 2CCF009035R0001 302659 0.750 1 18-26 S503 UC-K18 - 26 2CCF009038R0001 302666 0.750 1 23-32 S503 UC-K23 - 32 2CCF009041R0001 302673 0.750 1 29-37 S503 UC-K29 - 37 2CCF009044R0001 302680 0.750 1 34-41 S503 UC-K34 - 41 2CCF009047R0001 302697 0.750 1 38-45 S503 UC-K38 - 45 2CCF009050R0001 302703 0.750 1 4 0.1-0.15 S504UC-K0,15 2CCF011771R0001 302758 0,92 1 0.14-0.21 S504UC-K0,21 2CCF011772R0001 302765 0,92 1 0.2-0.3 S504UC-K0,3 2CCF011576R0001 302772 0,92 1 0.28-0.42 S504UC-K0,42 2CCF011773R0001 302789 0,92 1 0.38-0.58 S504UC-K0,58 2CCF011774R0001 302796 0,92 1 0.53-0.8 S504UC-K0,8 2CCF011775R0001 302802 0,92 1 0.73-1.1 S504UC-K1,1 2CCF011776R0001 302819 0,92 1 1-1.5 S504UC-K1,5 2CCF011777R0001 302826 0,92 1 1.4-2.1 S504UC-K2,1 2CCF011778R0001 302833 0,92 1 2-3 S504UC-K3 2CCF011779R0001 302840 0,92 1 2.8-4.2 S504UC-K4,2 2CCF011780R0001 302857 0,92 1 3.8-5.8 S504UC-K5,8 2CCF011781R0001 302864 0,92 1 5.3-8 S504UC-K8 2CCF011782R0001 302871 0,92 1 7.3-11 S504UC-K11 2CCF011509R0001 302888 0,92 1 10-15 S504UC-K15 2CCF011783R0001 302895 0,92 1 14-20 S504UC-K20 2CCF011784R0001 302901 0,92 1 18-26 S504UC-K26 2CCF011785R0001 302918 0,92 1 23-32 S504UC-K32 2CCF011786R0001 302925 0,92 1 29-37 S504UC-K37 2CCF011787R0001 302932 0,92 1 34-41 S504UC-K41 2CCF011788R0001 302949 0,92 1 38-45 S504UC-K45 2CCF011789R0001 302956 0,92 1 Note: from 4 to 6 poles available upon request System pro M S500UC-KSelection tables MCBs S500UC series (especially for direct current) K 2CCC413001F0002

2CSC400266F02012CSC400162F0201 2CSC400170F0201 2CSC400244F0201

to people and installations against fault current to earth. They are divided into three families: - RCCBs , which are sensitive only to earth fault current (therefore they have to be connected in series with a MCB or a fuse to protect them against overcurrents and short-circuits) - RCD-blocks , which are devices to be assembled on a MCB with lower or equal rated current to provide protection against both earth-fault currents and overload or short-circuits - RCBOs , which combines in a single device protection against both earth-fault currents and overloads or short-circuits. New RCDs System pro M compact ® range presents a wide offer for all the three families, respectively F 200, DDA 200 and DS 200 series. A large offer for standard instantaneous and selective AC and A types is completed with some confi gurations for special applications, like AP-R type against perturbations or AE type for emergency stop. All sizes up to 63 A with all the sensitivity thresholds up to 1 A are offered in all the possible pole confi gurations. The new F200 PV B is specifi cally designed for differential protect against earth-fault currents in photovoltaic installation. ABB expands the offering of its System pro M compact ® with new residual current circuitbreakers with overcurrent protection, DS201 (1 phase + neutral) and DS202C (2 phases) both available in two modules. The new residual current circuitbreakers with overcurrent protection are a technologically advanced and comprehensive range, as concerns size, tripping characteristics, breaking capacity and accessories. DS201 and DS202C combine protection against overcurrent the differential tripping and which cannot be activated in case of manual operation on the toggle. With the practical label carrier fi tted in the new circuitbreakers you can give maximum visibility to the information relating to the protected loads. ABB RCDs obtained a lot of marks and approvals and offer the same “plus” advantages of the other System pro M compact ® devices. Residual current relays together with toroidal transformers can detect leakage current. They are available in modular version (RD2 range and the new RD3 electronic residual current relay range) and in front panel versions (RD range). A common range of toroidal transformers is available for all the residual current relays. and earth fault current in a single device. DS201 and DS202C are equipped with clear indication fl ags. The internal contact position allows an exact information of the circuit-breaker status: “green”, open contacts; “red”, closed contacts, independently of the toggle position. Any earth fault can be immediately identifi ed through the blue indicator, that signals

RCBOs DS201 and DS202C series RCBOs DS 200 series Residual current devices F 200, DDA 200 and DS 200 series

pro M compact® F 200 TECHNICAL FEATURES Standards Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage Ue IEC V UL/CSA V Insulation voltage Ui V Max. operating voltage of circuit test IEC V UL/CSA V Min. operating voltage of circuit test V Rated frequency Hz Rated conditional short-circuit current Inc=IΔc SCPD - fuse gG 100 A kA kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Overvoltage category Surge current resistance (wave 8/20) A Mechanical Toggle features Contact position indicator (CPI) Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC/EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Ambient temperature (with daily average ≤ +35 °C) IEC °C UL/CSA °C Storage temperature °C Installation Terminal type Terminal size top/bottom for cable IEC mm UL/CSA AWG Terminal size top/bottom for busbar IEC mm 2 UL/CSA AWG Tightening torque IEC N*m UL/CSA in-lbs. Tool Mounting Connection Withdrawal from busbar Dimensions Dimensions (H x D x W) 2P mm and weight 4P mm Weight 2P g 4P g Combination Combinable with: auxiliary contact with auxiliary signal contact/auxiliary switch elements shunt trip undervoltage release /L54706 Ground-fault sensing and relaying equipment-component (up to 63 A) /L54707 prior to connection of aluminium conductors (≥ 4 mm2) ensure that their contact points are cleaned, brushed and coated with grease

pro M compact® F 200 F200 AC F200 A F200 AC AP-R F200 A AP-R F200 AC S F200 A S F200 A 400 Hz F200 A 16 2/3 Hz IEC/EN 61008, UL 1053 /L54706 IEC/EN 61008 IEC/EN 61008 AC A AC A AC A A A 2P , 4P (for 125 A only 4P) 4P 2P , 4P 16, 25, 40, 63, 80, 100, 125 25, 40, 63 25, 40, 63, 80, 100, 125 40, 63 40, 63, 80, 100, 125 25, 40 63 230/400 - 240/415 480Y/277 (up to 63 A) - 500 254 (440 for 125 A); 440 for F 200 left neutral 254 254 277 (up to 63 A); 480 for F 200 left neutral - 110 (185 for 125 A); 195 for F 200 left neutral 110 110 50…60 50...400 16 2/3 10 (for 125 A fuse is gG 125 A) 1 (1.25 for 125 A) 2.5 III, disconnector abilities 250 3000 5000 250 250 blue sealable in ON-OFF position yes 10000 (2000 for 125 A) 10000 10000 20000 (5000 for 125 A) 20000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -40…+70 failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) (cage for In > 63 A) /L54707 25/25 (35/35 single slot terminal for In > 63 A) 25/25 25/25 18-4 (up to 63 A) - 10/10 (not for In = 80-100 A) 10/10 10/10 18-8 (up to 63 A) - 2.8 (3 for In = 125 A) 2.8 2.8 25 (up to 63 A) - Nr. 2 Pozidriv on DIN rail EN 60715 (35 mm) by means of fast clip device from top and bottom it is possible without using any tools only from the bottom (not for 125 A) 85 x 69 x 35 85 x 69 x 70 (85 x 69.5 x 72 for 125 A) 85 x 69 x 70 85 x 69 x 70 200 - 350 (380 for In = 80 and 100 A and 460 for In = 125A) 350 350 yes (no for 125 A) yes yes yes yes yes yes (no for 125 A) yes yes yes (no for 125 A) yes yes

Function: protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 10 16 F202 AC-16/0.01 2CSF202001R0160 779902 0.225 1/6 30 25 F202 AC-25/0.03 2CSF202001R1250 780007 0.225 1/6 40 F202 AC-40/0.03 2CSF202001R1400 780106 0.225 1/6 63 F202 AC-63/0.03 2CSF202001R1630 780205 0.225 1/6 80 F202 AC-80/0.03 2CSF202001R1800 914204 0.225 1/6 100 F202 AC-100/0.03 2CSF202001R1900 914303 0.225 1/6 100 25 F202 AC-25/0.1 2CSF202001R2250 780304 0.225 1/6 40 F202 AC-40/0.1 2CSF202001R2400 780403 0.225 1/6 63 F202 AC-63/0.1 2CSF202001R2630 780502 0.225 1/6 80 F202 AC-80/0.1 2CSF202001R2800 914402 0.225 1/6 100 F202 AC-100/0.1 2CSF202001R2900 914501 0.225 1/6 300 25 F202 AC-25/0.3 2CSF202001R3250 780601 0.225 1/6 40 F202 AC-40/0.3 2CSF202001R3400 780700 0.225 1/6 63 F202 AC-63/0.3 2CSF202001R3630 780809 0.225 1/6 80 F202 AC-80/0.3 2CSF202001R3800 914600 0.225 1/6 100 F202 AC-100/0.3 2CSF202001R3900 914709 0.225 1/6 500 25 F202 AC-25/0.5 2CSF202001R4250 780908 0.225 1/6 40 F202 AC-40/0.5 2CSF202001R4400 781004 0.225 1/6 63 F202 AC-63/0.5 2CSF202001R4630 781103 0.225 1/6 80 F202 AC-80/0.5 2CSF202001R4800 914808 0.225 1/6 100 F202 AC-100/0.5 2CSF202001R4900 914907 0.225 1/6 4 30 25 F204 AC-25/0.03 2CSF204001R1250 781202 0.375 1/3 40 F204 AC-40/0.03 2CSF204001R1400 781301 0.375 1/3 63 F204 AC-63/0.03 2CSF204001R1630 781400 0.375 1/3 80 F204 AC-80/0.03 2CSF204001R1800 916604 0.405 1/3 100 F204 AC-100/0.03 2CSF204001R1900 916703 0.405 1/3 125 F204 AC-125/0.03 2CSF204001R1950 941507 0.500 1 100 25 F204 AC-25/0.1 2CSF204001R2250 781509 0.375 1/3 40 F204 AC-40/0.1 2CSF204001R2400 781608 0.375 1/3 63 F204 AC-63/0.1 2CSF204001R2630 781707 0.375 1/3 80 F204 AC-80/0.1 2CSF204001R2800 916802 0.405 1/3 100 F204 AC-100/0.1 2CSF204001R2900 916901 0.405 1/3 125 F204 AC-125/0.1 2CSF204001R2950 941606 0.500 1 300 25 F204 AC-25/0.3 2CSF204001R3250 781806 0.375 1/3 40 F204 AC-40/0.3 2CSF204001R3400 781905 0.375 1/3 63 F204 AC-63/0.3 2CSF204001R3630 782001 0.375 1/3 80 F204 AC-80/0.3 2CSF204001R3800 917007 0.405 1/3 100 F204 AC-100/0.3 2CSF204001R3900 917106 0.405 1/3 125 F204 AC-125/0.3 2CSF204001R3950 941705 0.500 1 500 25 F204 AC-25/0.5 2CSF204001R4250 782100 0.375 1/3 40 F204 AC-40/0.5 2CSF204001R4400 782209 0.375 1/3 63 F204 AC-63/0.5 2CSF204001R4630 782308 0.375 1/3 80 F204 AC-80/0.5 2CSF204001R4800 917205 0.405 1/3 100 F204 AC-100/0.5 2CSF204001R4900 917304 0.405 1/3 125 F204 AC-125/0.5 2CSF204001R4950 941804 0.500 1 AC 2CSC400565F02012CSC400569F02012CSC400197F0201

AC w type, for overseas markets System pro M compact F 200 AC for overseas markets AC 2CSC400565F02012CSC400569F0201 F 200 AC type (for overseas markets) Function: protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Marking: according to IEC 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 10 16 F202 AC-16/0.01 2CSF202005R0160 814603 0.225 1/6 30 25 F202 AC-25/0.03 2CSF202005R1250 814702 0.225 1/6 40 F202 AC-40/0.03 2CSF202005R1400 814801 0.225 1/6 63 F202 AC-63/0.03 2CSF202005R1630 814900 0.225 1/6 80 F202 AC-80/0.03 2CSF202005R1800 935902 0.225 1/6 100 F202 AC-100/0.03 2CSF202005R1900 936008 0.225 1/6 100 25 F202 AC-25/0.1 2CSF202005R2250 815006 0.225 1/6 40 F202 AC-40/0.1 2CSF202005R2400 815105 0.225 1/6 63 F202 AC-63/0.1 2CSF202005R2630 815204 0.225 1/6 80 F202 AC-80/0.1 2CSF202005R2800 936107 0.225 1/6 100 F202 AC-100/0.1 2CSF202005R2900 936206 0.225 1/6 300 25 F202 AC-25/0.3 2CSF202005R3250 815303 0.225 1/6 40 F202 AC-40/0.3 2CSF202005R3400 815402 0.225 1/6 63 F202 AC-63/0.3 2CSF202005R3630 815501 0.225 1/6 80 F202 AC-80/0.3 2CSF202005R3800 936305 0.225 1/6 100 F202 AC-100/0.3 2CSF202005R3900 936404 0.225 1/6 500 80 F202 AC-80/0.5 2CSF202005R4800 936503 0.225 1/6 100 F202 AC-100/0.5 2CSF202005R4900 936602 0.225 1/6 4 30 25 F204 AC-25/0.03 2CSF204005R1250 817109 0.375 1/3 40 F204 AC-40/0.03 2CSF204005R1400 817208 0.375 1/3 63 F204 AC-63/0.03 2CSF204005R1630 817307 0.375 1/3 80 F204 AC-80/0.03 2CSF204005R1800 936701 0.405 1/3 100 F204 AC-100/0.03 2CSF204005R1900 936800 0.405 1/3 100 25 F204 AC-25/0.1 2CSF204005R2250 817406 0.375 1/3 40 F204 AC-40/0.1 2CSF204005R2400 817505 0.375 1/3 63 F204 AC-63/0.1 2CSF204005R2630 817604 0.375 1/3 80 F204 AC-80/0.1 2CSF204005R2800 936909 0.405 1/3 100 F204 AC-100/0.1 2CSF204005R2900 937005 0.405 1/3 300 25 F204 AC-25/0.3 2CSF204005R3250 817703 0.375 1/3 40 F204 AC-40/0.3 2CSF204005R3400 817802 0.375 1/3 63 F204 AC-63/0.3 2CSF204005R3630 817901 0.375 1/3 80 F204 AC-80/0.3 2CSF204005R3800 937104 0.405 1/3 100 F204 AC-100/0.3 2CSF204005R3900 937203 0.405 1/3 500 80 F204 AC-80/0.5 2CSF204005R4800 937302 0.405 1/3 100 F204 AC-100/0.5 2CSF204005R4900 937401 0.405 1/3

A F 200 A type Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 10 16 F202 A-16/0.01 2CSF202101R0160 782407 0.225 1/6 30 25 F202 A-25/0.03 2CSF202101R1250 782506 0.225 1/6 40 F202 A-40/0.03 2CSF202101R1400 782605 0.225 1/6 63 F202 A-63/0.03 2CSF202101R1630 782704 0.225 1/6 80 F202 A-80/0.03 2CSF202101R1800 915201 0.225 1/6 100 F202 A-100/0.03 2CSF202101R1900 915300 0.225 1/6 100 25 F202 A-25/0.1 2CSF202101R2250 786900 0.225 1/6 40 F202 A-40/0.1 2CSF202101R2400 787006 0.225 1/6 63 F202 A-63/0.1 2CSF202101R2630 787105 0.225 1/6 80 F202 A-80/0.1 2CSF202101R2800 915409 0.225 1/6 100 F202 A-100/0.1 2CSF202101R2900 915508 0.225 1/6 300 25 F202 A-25/0.3 2CSF202101R3250 782803 0.225 1/6 40 F202 A-40/0.3 2CSF202101R3400 782902 0.225 1/6 63 F202 A-63/0.3 2CSF202101R3630 783008 0.225 1/6 80 F202 A-80/0.3 2CSF202101R3800 915607 0.225 1/6 100 F202 A-100/0.3 2CSF202101R3900 915706 0.225 1/6 500 25 F202 A-25/0.5 2CSF202101R4250 783107 0.225 1/6 40 F202 A-40/0.5 2CSF202101R4400 783206 0.225 1/6 63 F202 A-63/0.5 2CSF202101R4630 783305 0.225 1/6 80 F202 A-80/0.5 2CSF202101R4800 915805 0.225 1/6 100 F202 A-100/0.5 2CSF202101R4900 915904 0.225 1/6 4 30 25 F204 A-25/0.03 2CSF204101R1250 783404 0.375 1/3 40 F204 A-40/0.03 2CSF204101R1400 783503 0.375 1/3 63 F204 A-63/0.03 2CSF204101R1630 783602 0.375 1/3 80 F204 A-80/0.03 2CSF204101R1800 917809 0.405 1/3 100 F204 A-100/0.03 2CSF204101R1900 917908 0.405 1/3 125 F204 A-125/0.03 2CSF204101R1950 941903 0.500 1 100 25 F204 A-25/0.1 2CSF204101R2250 787204 0.375 1/3 40 F204 A-40/0.1 2CSF204101R2400 787303 0.375 1/3 63 F204 A-63/0.1 2CSF204101R2630 787402 0.375 1/3 80 F204 A-80/0.1 2CSF204101R2800 918004 0.405 1/3 100 F204 A-100/0.1 2CSF204101R2900 918103 0.405 1/3 125 F204 A-125/0.1 2CSF204101R2950 942009 0.500 1 300 25 F204 A-25/0.3 2CSF204101R3250 783701 0.375 1/3 40 F204 A-40/0.3 2CSF204101R3400 783800 0.375 1/3 63 F204 A-63/0.3 2CSF204101R3630 783909 0.375 1/3 80 F204 A-80/0.3 2CSF204101R3800 918202 0.405 1/3 100 F204 A-100/0.3 2CSF204101R3900 918301 0.405 1/3 125 F204 A-125/0.3 2CSF204101R3950 942108 0.500 1 500 25 F204 A-25/0.5 2CSF204101R4250 784005 0.375 1/3 40 F204 A-40/0.5 2CSF204101R4400 784104 0.375 1/3 63 F204 A-63/0.5 2CSF204101R4630 784203 0.375 1/3 80 F204 A-80/0.5 2CSF204101R4800 918400 0.405 1/3 100 F204 A-100/0.5 2CSF204101R4900 918509 0.405 1/3 125 F204 A-125/0.5 2CSF204101R4950 942207 0.500 1 2CSC400565F02012CSC400569F02012CSC400197F0201

F 200 AC type with neutral pole on the left Function: protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Product helpful where for installation habits, for wiring with busbars or cables, for special needs neutral on the left is needed. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 4 30 25 F204 AC-25/0.03 2CSF204023R1250 815907 0.375 1/3 40 F204 AC-40/0.03 2CSF204023R1400 816003 0.375 1/3 63 F204 AC-63/0.03 2CSF204023R1630 816102 0.375 1/3 80 F204 AC-80/0.03 2CSF204023R1800 917403 0.405 1/3 100 F204 AC-100/0.03 2CSF204023R1900 917502 0.405 1/3 125 F204 AC-125/0.03 2CSF204023R1950 975106 0.500 1 100 25 F204 AC-25/0.1 2CSF204023R2250 816201 0.375 1/3 40 F204 AC-40/0.1 2CSF204023R2400 816300 0.375 1/3 63 F204 AC-63/0.1 2CSF204023R2630 816409 0.375 1/3 300 25 F204 AC-25/0.3 2CSF204023R3250 816508 0.375 1/3 40 F204 AC-40/0.3 2CSF204023R3400 816607 0.375 1/3 63 F204 AC-63/0.3 2CSF204023R3630 816706 0.375 1/3 80 F204 AC-80/0.3 2CSF204023R3800 917601 0.405 1/3 100 F204 AC-100/0.3 2CSF204023R3900 917700 0.405 1/3 125 F204 AC-125/0.3 2CSF204023R3950 975304 0.500 1 500 25 F204 AC-25/0.5 2CSF204023R4250 816805 0.375 1/3 40 F204 AC-40/0.5 2CSF204023R4400 816904 0.375 1/3 63 F204 AC-63/0.5 2CSF204023R4630 817000 0.375 1/3 N1 / 2 N2 / 1 2CSC400571F02012CSC400197F0201 Selection tables RCCBs F 200 series AC w type left neutral System pro M compact F 200 left neutral

F 200 A type with neutral pole on the left Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault cur- rents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Product helpful where for installation habits, for wiring with busbars or cables, for special needs neutral on the left is needed. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 4 30 25 F204 A-25/0.03 2CSF204123R1250 820109 0.375 1/3 40 F204 A-40/0.03 2CSF204123R1400 820208 0.375 1/3 63 F204 A-63/0.03 2CSF204123R1630 820307 0.375 1/3 80 F204 A-80/0.03 2CSF204123R1800 918608 0.405 1/3 100 F204 A-100/0.03 2CSF204123R1900 918707 0.405 1/3 125 F204 A-125/0.03 2CSF204123R1950 967705 0.500 1 100 25 F204 A-25/0.1 2CSF204123R2250 820406 0.375 1/3 40 F204 A-40/0.1 2CSF204123R2400 820505 0.375 1/3 63 F204 A-63/0.1 2CSF204123R2630 820604 0.375 1/3 300 25 F204 A-25/0.3 2CSF204123R3250 820703 0.375 1/3 40 F204 A-40/0.3 2CSF204123R3400 820802 0.375 1/3 63 F204 A-63/0.3 2CSF204123R3630 820901 0.375 1/3 80 F204 A-80/0.3 2CSF204123R3800 918806 0.405 1/3 100 F204 A-100/0.3 2CSF204123R3900 918905 0.405 1/3 125 F204 A-125/0.3 2CSF204123R3950 967804 0.500 1 500 25 F204 A-25/0.5 2CSF204123R4250 821007 0.375 1/3 40 F204 A-40/0.5 2CSF204123R4400 821106 0.375 1/3 63 F204 A-63/0.5 2CSF204123R4630 821205 0.375 1/3 A N1 / 2 N2 / 1 2CSC400197F0201 2CSC400571F0201

AC w type, AP-R (high immunity) System pro M compact F 200 AC AP-R F 200 AP-R, AC type Function: protection against the effects of sinusoidal alternating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (I Δn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Surge current resistance (wave 8/20)=3000 A Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 25 F202 AC-25/0.03 AP-R 2CSF202301R1250 785705 0.225 1/6 40 F202 AC-40/0.03 AP-R 2CSF202301R1400 823704 0.225 1/6 63 F202 AC-63/0.03 AP-R 2CSF202301R1630 785804 0.225 1/6 4 30 25 F204 AC-25/0.03 AP-R 2CSF204301R1250 785903 0.375 1/3 40 F204 AC-40/0.03 AP-R 2CSF204301R1400 823803 0.375 1/3 63 F204 AC-63/0.03 AP-R 2CSF204301R1630 786009 0.375 1/3 AC 2CSC400565F02012CSC400569F0201

A Selection tables RCCBs F 200 series A y type, AP-R (high immunity) System pro M compact F 200 A AP-R F 200 AP-R, A type Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61008 Surge current resistance (wave 8/20)=3000 A Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 25 F202 A-25/0.03 AP-R 2CSF202401R1250 785101 0.225 1/6 40 F202 A-40/0.03 AP-R 2CSF202401R1400 785200 0.225 1/6 63 F202 A-63/0.03 AP-R 2CSF202401R1630 785309 0.225 1/6 80 F202 A-80/0.03 AP-R 2CSF202401R1800 916406 0.225 1/6 100 F202 A-100/0.03 AP-R 2CSF202401R1900 916505 0.225 1/6 4 30 25 F204 A-25/0.03 AP-R 2CSF204401R1250 785408 0.375 1/3 40 F204 A-40/0.03 AP-R 2CSF204401R1400 785507 0.375 1/3 63 F204 A-63/0.03 AP-R 2CSF204401R1630 785606 0.375 1/3 80 F204 A-80/0.03 AP-R 2CSF204401R1800 919407 0.405 1/3 100 F204 A-100/0.03 AP-R 2CSF204401R1900 919506 0.405 1/3 125 F204 A-125/0.03 AP-R 2CSF204401R1950 967903 0.500 1 2CSC400565F02012CSC400569F02012CSC400197F0201

AC w type, selective System pro M compact F 200 AC S AC F 200 AC selective type Function: protection against the effects of sinusoidal alternating earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide); protection against indirect contacts. Application: commercial, industrial. Standard: IEC/EN 61008 Surge current resistance (wave 8/20)=5000 A Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 100 40 F202 AC S-40/0.1 2CSF202901R2400 821304 0.225 1/6 63 F202 AC S-63/0.1 2CSF202901R2630 821403 0.225 1/6 300 40 F202 AC S-40/0.3 2CSF202901R3400 821502 0.225 1/6 63 F202 AC S-63/0.3 2CSF202901R3630 821601 0.225 1/6 500 40 F202 AC S-40/0.5 2CSF202901R4400 821700 0.225 1/6 63 F202 AC S-63/0.5 2CSF202901R4630 821809 0.225 1/6 1000 40 F202 AC S-40/1 2CSF202901R5400 821908 0.225 1/6 63 F202 AC S-63/1 2CSF202901R5630 822004 0.225 1/6 4 100 40 F204 AC S-40/0.1 2CSF204901R2400 822103 0.375 1/3 63 F204 AC S-63/0.1 2CSF204901R2630 822202 0.375 1/3 300 40 F204 AC S-40/0.3 2CSF204901R3400 822301 0.375 1/3 63 F204 AC S-63/0.3 2CSF204901R3630 822400 0.375 1/3 500 40 F204 AC S-40/0.5 2CSF204901R4400 822509 0.375 1/3 63 F204 AC S-63/0.5 2CSF204901R4630 822608 0.375 1/3 1000 40 F204 AC S-40/1 2CSF204901R5400 822707 0.375 1/3 63 F204 AC S-63/1 2CSF204901R5630 822806 0.375 1/3 2CSC400565F02012CSC400569F0201

A y type, selective System pro M compact F 200 A S A F 200 A selective type Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide); protection against indirect contacts. Application: commercial, industrial. Standard: IEC/EN 61008 Surge current resistance (wave 8/20)=5000 A Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 100 40 F202 A S-40/0.1 2CSF202201R2400 822905 0.225 1/6 63 F202 A S-63/0.1 2CSF202201R2630 823001 0.225 1/6 100 F202 A S-100/0.1 2CSF202201R2900 916000 0.225 1/6 300 40 F202 A S-40/0.3 2CSF202201R3400 784302 0.225 1/6 63 F202 A S-63/0.3 2CSF202201R3630 784401 0.225 1/6 100 F202 A S-100/0.3 2CSF202201R3900 916109 0.225 1/6 500 40 F202 A S-40/0.5 2CSF202201R4400 784500 0.225 1/6 63 F202 A S-63/0.5 2CSF202201R4630 784609 0.225 1/6 100 F202 A S-100/0.5 2CSF202201R4900 916208 0.225 1/6 1000 40 F202 A S-40/1 2CSF202201R5400 823100 0.225 1/6 63 F202 A S-63/1 2CSF202201R5630 823209 0.225 1/6 100 F202 A S-100/1 2CSF202201R5900 916307 0.225 1/6 4 100 40 F204 A S-40/0.1 2CSF204201R2400 823308 0.375 1/3 63 F204 A S-63/0.1 2CSF204201R2630 823407 0.375 1/3 100 F204 A S-100/0.1 2CSF204201R2900 919001 0.405 1/3 300 40 F204 A S-40/0.3 2CSF204201R3400 784708 0.375 1/3 63 F204 A S-63/0.3 2CSF204201R3630 784807 0.375 1/3 100 F204 A S-100/0.3 2CSF204201R3900 919100 0.405 1/3 125 F204 A S-125/0.3 2CSF204201R3950 968207 0.500 1 500 40 F204 A S-40/0.5 2CSF204201R4400 784906 0.375 1/3 63 F204 A S-63/0.5 2CSF204201R4630 785002 0.375 1/3 100 F204 A S-100/0.5 2CSF204201R4900 919209 0.405 1/3 125 F204 A S-125/0.5 2CSF204201R4950 968405 0.500 1 1000 40 F204 A S-40/1 2CSF204201R5400 823506 0.375 1/3 63 F204 A S-63/1 2CSF204201R5630 823605 0.375 1/3 100 F204 A S-100/1 2CSF204201R5900 919308 0.405 1/3 2CSC400565F02012CSC400569F02012CSC400197F0201

RCCBs F 200 series A y type for high frequency and railways applications System pro M compact® F 200 A 400 Hz F 200 A 16 2/3 Hz A F 200 A type for high frequency (400 Hz) Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with Idn=30 mA) contacts. Advantages: increasing the frequency generates an increase of the magnetic reluctance of the toroi- dal transformer of standard RCCB and what follows is the value of the increasing operating residual current at 400 Hz reaching values 3 or more times higher than those of the residual current at 50Hz. The RCCB F 200 400 Hz guarantees protection against indirect contacts and additional protection against direct (with I Δn=30 mA) contacts considering that the operating residual current doesn’t increase with the increase of the network frequency. Application: commercial, industrial. Standard: IEC/EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 4 30 25 F204 A-25/0.03 400Hz 2CSF204197R1250 968603 0.375 1/3 40 F204 A-40/0.03 400Hz 2CSF204197R1400 968702 0.375 1/3 2CSC400569F0201 A F200 A type 16 2/3 Hz Function: protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. The RCCB F200 16 2/3 Hz can work at rated frequency of 16 2/3 Hz which is common in railways

applications

Application: railways Standard: IEC/ EN 61008 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 F202 A-63/0.03 16-2/3Hz 2CSF202196R1630 734536 0.225 1/6 300 63 F202 A-63/0.3 16-2/3Hz 2CSF202196R3630 733638 0.225 1/6 500 63 F202 A-63/0.5 16-2/3Hz 2CSF202196R4630 734437 0.225 1/6 4 30 63 F204 A-63/0.03 16-2/3Hz 2CSF204196R1630 733539 0.375 1/3 300 63 F204 A-63/0.3 16-2/3Hz 2CSF204196R3630 734338 0.375 1/3 500 63 F204 A-63/0.5 16-2/3Hz 2CSF204196R4630 733430 0.375 1/3 2CSC400569F0201

type, B y type selective System pro M compact® F 200 B B F 200 B type for smooth DC earth fault current Function: protection against the effects of sinusoidal alternating, direct pulsating and pulsating DC or smooth DC earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: industrial. Standard: IEC/EN 61008, IEC 62423 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 4 30 40 F204 B-40/0.03 2CSF204501R1400 988403 0.500 1 63 F204 B-63/0.03 2CSF204501R1630 988502 0.500 1 125 /L54706 F204 B-125/0.03 2CSF204523R1950 988700 0.500 1 300 63 F204 B-63/0.3 2CSF204501R3630 989004 0.500 1 125 /L54706 F204 B-125/0.3 2CSF204523R3950 989202 0.500 1 500 125 /L54706 F204 B-125/0.5 2CSF204523R4950 730439 0.500 1 /L54706 Devices with rated current In=125 A are with neutral on the left F 200 B selective type for smooth DC earth fault current Function: protection against the effects of sinusoidal alternating, direct pulsating and pulsating DC or smooth DC earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide); protection against indirect contacts. Application: industrial. Standard: IEC/EN 61008, IEC 62423 Surge current resistance (wave 8/20)=5000 A Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 4 300 63 F204 B S-63/0.3 2CSF204801R3630 989301 0.500 1 125 /L54706 F204 B S-125/0.3 2CSF204823R3950 989509 0.500 1 500 125 /L54706 F204 B S-125/0.5 2CSF204823R4950 731238 0.500 1 /L54706 Devices with rated current In=125 A are with neutral on the left 2CSC400197F0001 2CSC400197F0001 1/2 3/4 5/6 7/8/N T Input Output2/1 4/3 6/5 8/7/N N3 57 T Input OutputN4 68 1/2 3/4 5/6 7/8/N T Input Output2/1 4/3 6/5 8/7/N N3 57 T Input OutputN4 68

RCCBs F 200 series - B y type for continuous, selective continuous type fault currents System pro M compact® F 200 B Type (wave form of the detected dispersion current) B Rated current In [A] 40 63 125 No. of poles 4 Rated voltage Un [V] 230/400 Working range of test circuit [V] 185 V AC-440 V AC Rated conditional short-circuit current Inc [kA] 10 Rated conditional residual short-circuit current IΔc [kA] 10 Rated making and breaking capacity Im [A] 500 800 1250 Rated residual making and breaking capacity IΔm [A] 500 800 1250 Surge current resistance ring wave 0,5 ms/100 kHz: 200 A, impulse 8/20 μs: 3 kA (impulse 8/20 μs: 5 kA for F200 type B S - selective) Working frequency range [Hz] 0-1000 Min. operating voltage for detecting type A/AC residual currents [V] 0 V for detecting type B residual currents [V] 30 V a.c. Own consumption [W] max. 3.5 Dissipated power Pv [W] 2.9 7.2 28 Short-circuit fuse acc. to VDE 0636/IEC 60269-1 80 A/gL 100 A/gG 125 A/gL Tripping time F200 type B [ms] 1 x IΔn ≤ 300 ms; 5 x IΔn ≤ 40 ms Tripping time F200 type B S [ms] 1 x IΔn > 130 ms ≤ 500 ms; 5 x IΔn > 50 ms ≤ 150 ms Toggle Blue sealable in ON/OFF position Impact resistance 20 g/20 ms Protection degree IP40 (after installation in distribution board) Supply terminal 1, 3, 5, 7 Ambient temperature [°C] -25…+40 Resistance to climate changes acc. to IEC 68-2-30 25 °C/55 °C; 93%/97% relative humidity, 28 cycles Cables max. size [mm2] 1x1.5-50 mm 2; 2x1.5-16 mm2 Terminal size [mm2]5 0 Tightening torque [N*m] 3 Mechanical life > 5000 Electrical life > 2000 Electromagnetic compatibility IEC 61453; DIN VDE 0664 Pt.30 Mounting on DIN rail EN 60715 (35 mm) by means of fast clip device Dimensions (H x P x L) [mm] 85 x 69,5 x 70 Weight 4P [g] 500

pro M compact® F 200 PV B B F200 PV B type for smooth DC earth fault current for photovoltaic Function: protection against the effects of sinusoidal alternating, direct pulsanting and pulsanting DC or smooth DC earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30mA) contacts. Where an electrical installation includes a PV power supply system without at least simple separation between the AC side and the DC side, an RCD installed to provide fault protection by automatic disconnection of supply should be type B according to IEC 60755, amendment 2 (according to IEC Application: particularly suitable for use in solar energy (photovoltaic) systems standard: IEC/EN 61008, IEC 62423 Marking: according to EN 61008 Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 25 F202PV B-25/0,03 2CSF202601R1250 071235 0.500 1 63 F202PV B-63/0,03 2CSF202601R1630 368632 0.500 1 300 25 F202PV B-25/0,3 2CSF202601R3250 910831 0.500 1 63 F202PV B-63/0,3 2CSF202601R3630 659037 0.500 1 T 2CSC400676F0001

pro M compact® F 200 PV B Rated current In 25A 63 A Rated sensitivity IΔn 0.03 - 0.3 A Working frequency range 0 - 1000 Hz Rated voltage Un 230 V AC Rated frequency 50 Hz Min. operating voltage for detecting type A/AC residual currents for detecting type B residual currents

0 V (mains voltage-independent)

30 V AC

Own consumption max. 1.2 W Working range of test circuit 100 V AC – 250 V AC No. of poles: 2-pole Dissipated power Pv 1.2 W 7.2 W Short-circuit fuse to VDE 0636 / IEC 60269-1 100 A/gG Tripping times F200PV B type 1xI Δn ≤ 300 ms; 5xIΔn ≤ 40 ms Rated making and breaking capacity Im 500 A 800 A Rated residual making and breaking capacity IΔm 500 A 800 A Rated short circuit current Inc 10 kA Rated conditional residual short-circuit current IΔc 10 kA Surge current resistance Ring wave 0.5 ms / 100 kHz: 200 A, impulse 8/20 μs: 3 kA Impact resistance 20 g / 20 ms duration Enclosure protection type IP40 (after installation in distribution board) Input side Terminals 5, 7 Ambient temperature -25°C to 40°C Resistance to climate changes according to IEC 68-2-30 damp / heat cyclic (25°C / 55°C; 93% / 97% rel.hum., 28 cycles) Tightening torque of fastening screws 3 Nm Mechanical life > 5000 switching cycles Electrical life > 2000 switching cycles Electromagnetic compatibility IEC 61453; DIN VDE 0664 Pt.30 (interference resistance-industrial environment) Mounting On DIN rail EN 60715 (35 mm) by means of fast clip device; any mounting position Toggle Blue sealable in ON/OFF position. Dimensions (H x D x W) 85 x 69 x 72 mm Weight 500 g

3 TECHNICAL FEATURES

Operating characteristic: type Rated current In [A] Poles Rated voltage Ue 2P [V] Insulation voltage Ui [V] Operating voltage of circuit test Ut 2P [V] Rated frequency Hz Rated breaking capacity according to IEC EN 61009 [A] Rated breaking capacity according to IEC EN 60947-2 [A] Rated residual breaking capacity IΔm [kA] Rated inpulse withstand capacity (1,2/50) Uimp [kV] Dielectric test voltage at ind. freq. for 1 min. [kV] Surge current resistance (wave 8/20) [A] Rated sensitivity IΔn [A] Toggle Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat [°C/RH] according to DIN 40046 IEC 68-2 constant climatic conditions [°C/RH] variable climatic conditions [°C/RH] Ambient temperature (with daily average ≤ +35 °C) [°C] Storage temperature [°C] Terminal type 2P 3P/4P In=25 and 40 A 3P/4P In=63 A Terminal size 2P [mm 3P/4P In=25 and 40 A [mm 2] 3P/4P In=63 A [mm 2] Tightening torque 2P [N*m] 3P/4P In=25 and 40 A [N*m] 3P/4P In=63 A [N*m] Mounting Dimensions 2P [mm] H x P x L 3P/4P In=25 and 40 A [mm] 3P/4P In=63 A [mm] Weight 2P [g] 3P/4P In=25 and 40 A [g] 3P/4P In=63 A [g] Combinable with S 200 L S 200 S 200 M S 200 P /L54706 All RCD-blocks DDA 200 with rated current 63 A are provided with two additional terminals for remote tripping. /L54707 DDA200 A AE is provided with two additional terminals for remote release in positive safety. A remote control circuit should be connected to those terminals where circuit breakers or push buttons with normally closed c ontacts should be inserted. Technical features RCD-blocks DDA 200 series System pro M compact® DDA 200

3DDA 200 AC DDA 200 A DDA 200 AC AP-R DDA 200 A AP-R DDA 200 A AE DDA 200 AC S DDA 200 A S DDA 200 B IEC EN 61009 App.G IEC EN 61009 App. G and IEC 60755 A CAA CA AA CA B 25, 40, 63 /L54706 25, 40, 63 /L54706 63 /L54707 63 /L54706 63 2P , 3P , 4P 3P , 4P 230 (400 for special execution @400 V) 230 230 400 230 230 500 110-254 (400 for special execution @400 V) 195-440 (110-254 for special execution @110 V) 195-440 (110-254 for special execution @110 V) 184-264 110-254 195-440 195-440 310-440 310-440 184-264 195-254 50…60 same of the coupled MCB same of the coupled MCB same of the coupled MCB 2,5 250 3000 250 5000 3000 (5000 for selective types) blue 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25...+55 -40…+70 bi-directional cylinder-lift cage type bi-directional cylinder-lift (rigid or fl exible) up to 25 (rigid or fl exible) up to 16 (rigid or fl exible) up to 25 2.8 1.2 2.8 on DIN rail EN 60715 (35 mm) by means of fast clip device 85 x 69 x 35 85 x 69 x 35 85 x 69 x 70 175 175 325 yes yes yes yes Technical features RCD-blocks DDA 200 series System pro M compact DDA 200

Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Ann. G Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 10 25 DDA202 AC-25/0.01 2CSB202001R0250 791003 0.180 1 30 25 DDA202 AC-25/0.03 2CSB202001R1250 791102 0.180 1 40 DDA202 AC-40/0.03 2CSB202001R1400 791201 0.180 1 63 /L54707 DDA202 AC-63/0.03 2CSB202001R1630 791300 0.180 1 100 25 DDA202 AC-25/0.1 2CSB202001R2250 791409 0.180 1 40 DDA202 AC-40/0.1 2CSB202001R2400 791508 0.180 1 63 /L54707 DDA202 AC-63/0.1 2CSB202001R2630 791607 0.180 1 300 25 DDA202 AC-25/0.3 2CSB202001R3250 791706 0.180 1 40 DDA202 AC-40/0.3 2CSB202001R3400 791805 0.180 1 63 /L54707 DDA202 AC-63/0.3 2CSB202001R3630 791904 0.180 1 500 25 DDA202 AC-25/0.5 2CSB202001R4250 792000 0.180 1 40 DDA202 AC-40/0.5 2CSB202001R4400 792109 0.180 1 63 /L54707 DDA202 AC-63/0.5 2CSB202001R4630 792208 0.180 1 1000 25 DDA202 AC-25/1 2CSB202001R5250 808305 0.180 1 40 DDA202 AC-40/1 2CSB202001R5400 808404 0.180 1 63 /L54707 DDA202 AC-63/1 2CSB202001R5630 792307 0.180 1 2000 63 DDA202 AC-63/2 2CSB202001R6630 792406 0.180 1 3 30 25 DDA203 AC-25/0.03 2CSB203001R1250 792505 0.220 1 40 DDA203 AC-40/0.03 2CSB203001R1400 792604 0.220 1 63 /L54707 DDA203 AC-63/0.03 2CSB203001R1630 792703 0.260 1 100 25 DDA203 AC-25/0.1 2CSB203001R2250 792802 0.220 1 40 DDA203 AC-40/0.1 2CSB203001R2400 792901 0.220 1 63 /L54707 DDA203 AC-63/0.1 2CSB203001R2630 793007 0.260 1 300 25 DDA203 AC-25/0.3 2CSB203001R3250 793106 0.220 1 40 DDA203 AC-40/0.3 2CSB203001R3400 793205 0.220 1 63 /L54707 DDA203 AC-63/0.3 2CSB203001R3630 793304 0.260 1 500 25 DDA203 AC-25/0.5 2CSB203001R4250 793403 0.220 1 40 DDA203 AC-40/0.5 2CSB203001R4400 793502 0.220 1 63 /L54707 DDA203 AC-63/0.5 2CSB203001R4630 793601 0.260 1 1000 25 DDA203 AC-25/1 2CSB203001R5250 808503 0.220 1 40 DDA203 AC-40/1 2CSB203001R5400 808602 0.220 1 63 /L54707 DDA203 AC-63/1 2CSB203001R5630 793700 0.260 1 2000 63 DDA203 AC-63/2 2CSB203001R6630 793809 0.260 1 4 30 25 DDA204 AC-25/0.03 2CSB204001R1250 793908 0.260 1 40 DDA204 AC-40/0.03 2CSB204001R1400 794004 0.260 1 63 /L54706 /L54707 DDA204 AC-63/0.03 2CSB204001R1630 794103 0.305 1 100 25 DDA204 AC-25/0.1 2CSB204001R2250 794202 0.260 1 40 DDA204 AC-40/0.1 2CSB204001R2400 794301 0.260 1 63 /L54707 DDA204 AC-63/0.1 2CSB204001R2630 794400 0.305 1 300 25 DDA204 AC-25/0.3 2CSB204001R3250 794509 0.260 1 40 DDA204 AC-40/0.3 2CSB204001R3400 794608 0.260 1 63 /L54707 DDA204 AC-63/0.3 2CSB204001R3630 794707 0.305 1 500 25 DDA204 AC-25/0.5 2CSB204001R4250 794806 0.260 1 40 DDA204 AC-40/0.5 2CSB204001R4400 794905 0.260 1 63 /L54707 DDA204 AC-63/0.5 2CSB204001R4630 795001 0.305 1 1000 25 DDA204 AC-25/1 2CSB204001R5250 808701 0.260 1 40 DDA204 AC-40/1 2CSB204001R5400 808800 0.260 1 63 /L54707 DDA204 AC-63/1 2CSB204001R5630 795100 0.305 1 2000 63 DDA204 AC-63/2 2CSB204001R6630 795209 0.305 1 /L54706 version with test button working at 110VAC - 254VAC is available. For selection tables refer to special version paragraph. /L54707 provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400163F02012CSC400164F02012CSC400165F0201

A DDA 200 A type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Ann. G Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 10 25 DDA202 A-25/0.01 2CSB202101R0250 795308 0.180 1 30 25 DDA202 A-25/0.03 2CSB202101R1250 795407 0.180 1 40 DDA202 A-40/0.03 2CSB202101R1400 795506 0.180 1 63 /L54707 DDA202 A-63/0.03 2CSB202101R1630 795605 0.180 1 100 25 DDA202 A-25/0.1 2CSB202101R2250 795704 0.180 1 40 DDA202 A-40/0.1 2CSB202101R2400 795803 0.180 1 63 /L54707 DDA202 A-63/0.1 2CSB202101R2630 795902 0.180 1 300 25 DDA202 A-25/0.3 2CSB202101R3250 796008 0.180 1 40 DDA202 A-40/0.3 2CSB202101R3400 796107 0.180 1 63 /L54707 DDA202 A-63/0.3 2CSB202101R3630 796206 0.180 1 500 25 DDA202 A-25/0.5 2CSB202101R4250 796305 0.180 1 40 DDA202 A-40/0.5 2CSB202101R4400 796404 0.180 1 63 /L54707 DDA202 A-63/0.5 2CSB202101R4630 796503 0.180 1 1000 25 DDA202 A-25/1 2CSB202101R5250 808909 0.180 1

40 DDA202 A-40/1 2CSB202101R5400

809005 0.180 1 63 /L54707 DDA202 A-63/1 2CSB202101R5630 796602 0.180 1 3 30 25 DDA203 A-25/0.03 2CSB203101R1250 796701 0.220 1 40 /L54706 DDA203 A-40/0.03 2CSB203101R1400 796800 0.220 1 63 /L54706 /L54707 DDA203 A-63/0.03 2CSB203101R1630 796909 0.260 1 100 25 DDA203 A-25/0.1 2CSB203101R2250 797005 0.220 1 40 DDA203 A-40/0.1 2CSB203101R2400 797104 0.220 1 63 /L54707 DDA203 A-63/0.1 2CSB203101R2630 797203 0.260 1 300 25 DDA203 A-25/0.3 2CSB203101R3250 797302 0.220 1 40 DDA203 A-40/0.3 2CSB203101R3400 797401 0.220 1 63 /L54707 DDA203 A-63/0.3 2CSB203101R3630 797500 0.260 1 500 25 DDA203 A-25/0.5 2CSB203101R4250 797609 0.220 1 40 DDA203 A-40/0.5 2CSB203101R4400 797708 0.220 1 63 /L54707 DDA203 A-63/0.5 2CSB203101R4630 797807 0.260 1 1000 25 DDA203 A-25/1 2CSB203101R5250 809104 0.220 1 40 DDA203 A-40/1 2CSB203101R5400 809203 0.220 1 63 /L54707 DDA203 A-63/1 2CSB203101R5630 797906 0.260 1 4 30 25 DDA204 A-25/0.03 2CSB204101R1250 798002 0.260 1 40 DDA204 A-40/0.03 2CSB204101R1400 798101 0.260 1 63 /L54706 /L54707 DDA204 A-63/0.03 2CSB204101R1630 798200 0.305 1 100 25 DDA204 A-25/0.1 2CSB204101R2250 798309 0.260 1 40 DDA204 A-40/0.1 2CSB204101R2400 798408 0.260 1 63 /L54707 DDA204 A-63/0.1 2CSB204101R2630 798507 0.305 1 300 25 DDA204 A-25/0.3 2CSB204101R3250 798606 0.260 1 40 DDA204 A-40/0.3 2CSB204101R3400 798705 0.260 1 63 /L54707 DDA204 A-63/0.3 2CSB204101R3630 798804 0.305 1 500 25 DDA204 A-25/0.5 2CSB204101R4250 798903 0.260 1 40 DDA204 A-40/0.5 2CSB204101R4400 799009 0.260 1 63 /L54707 DDA204 A-63/0.5 2CSB204101R4630 799108 0.305 1 1000 25 DDA204 A-25/1 2CSB204101R5250 809302 0.260 1 40 DDA204 A-40/1 2CSB204101R5400 809401 0.260 1 63 /L54707 DDA204 A-63/1 2CSB204101R5630 799207 0.305 1 /L54706 version with test button working at 110VAC - 254VAC is available. For selection tables refer to special version paragraph. /L54707 provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400163F02012CSC400164F02012CSC400165F0201

pro M compact® Selection tables RCD-blocks DDA 200 series special version DDA 200 @ 110 V DDA 200 @ 400 V DDA 200 special version 110 V and 400 V Function: special version of RCD-blocks to assembly on site with MCBs S 200 series. Special version are available with protection against the effects of sinusoidal alternating and/or direct pulsating earth fault currents, protection against indirect contacts and additional protection against direct contacts (with IΔn=30 mA). DDA200 110 V is a particular RCD-block with voltage range for test button Ut = 110-245 V. RCD- blocks work for naval applications where the IT system is typically used and the voltage between the phase and the neutral conductor is 115 - 125 V. DDA200 110 V (Ut = 110-245 V) are suitable for naval applications. Special version is also available for 400 V in the two poles version working in two-phase industrial systems where voltage between phases is 400 V. Applications: naval, industrial. Standards: IEC EN 61009 Ann. G

110 V version

Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. AC type 4 AC 63 /L54706 DDA 204 AC-63/0.03 110V 2CSB204099R1630 929901 0.350 1 A type 3 A 40 DDA 203 A-40/0.03 110V 2CSB203199R1400 811701 0.350 1 3 A 63 /L54706 DDA 203 A-63/0.03 110V 2CSB203199R1630 811800 0.350 1 4 A 63 /L54706 DDA 204 A-63/0.03 110V 2CSB204199R1630 812104 0.350 1

400 V version

Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. A type 2 A 63 /L54706 DDA 202 A-63/0.03 400V 2CSB202192R1630 954934 0.200 1 /L54706 provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400115F00012CSC400116F0001 In=40 A 2CSC400562F0001

A DDA 200 AP-R, A type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Ann. G Surge current resistance (wave 8/20)=3000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 25 DDA202 A-25/0.03 AP-R 2CSB202401R1250 801108 0.180 1 40 DDA202 A-40/0.03 AP-R 2CSB202401R1400 801207 0.180 1 63 /L54706 DDA202 A-63/0.03 AP-R 2CSB202401R1630 801306 0.180 1 3 30 25 DDA203 A-25/0.03 AP-R 2CSB203401R1250 811008 0.220 1 40 DDA203 A-40/0.03 AP-R 2CSB203401R1400 811107 0.220 1 63 /L54706 DDA203 A-63/0.03 AP-R 2CSB203401R1630 811206 0.260 1 4 30 25 DDA204 A-25/0.03 AP-R 2CSB204401R1250 801405 0.260 1 40 DDA204 A-40/0.03 AP-R 2CSB204401R1400 801504 0.260 1 63 /L54706 DDA204 A-63/0.03 AP-R 2CSB204401R1630 801603 0.305 1 /L54706 provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400163F0201 AC DDA 200 AP-R, AC type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Ann. G Surge current resistance (wave 8/20)=3000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 25 DDA202 AC-25/0.03 AP-R 2CSB202301R1250 800507 0.180 1 40 DDA202 AC-40/0.03 AP-R 2CSB202301R1400 800606 0.180 1 63 /L54706 DDA202 AC-63/0.03 AP-R 2CSB202301R1630 800705 0.180 1 3 30 25 DDA203 AC-25/0.03 AP-R 2CSB203301R1250 810704 0.220 1 40 DDA203 AC-40/0.03 AP-R 2CSB203301R1400 810803 0.220 1 63 /L54706 DDA203 AC-63/0.03 AP-R 2CSB203301R1630 810902 0.260 1 4 30 25 DDA204 AC-25/0.03 AP-R 2CSB204301R1250 800804 0.260 1 40 DDA204 AC-40/0.03 AP-R 2CSB204301R1400 800903 0.260 1 63 /L54706 DDA204 AC-63/0.03 AP-R 2CSB204301R1630 801009 0.305 1 2/1 4/3 246 In=63 A Y1 Y2 System pro M compact® Selection tables RCD-blocks DDA 200 series AC w type and A y type, AP-R (high immunity) DDA 200 AP-R 2CSC400163F0201

A y type, AE (for emergency stop) System pro M compact DDA 200 AE A DDA 200 AE, A type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. The RCD-block is provided with two additional terminals to be used in emergency circuits for remote opening in positive safety. A remote control circuit should be connected to those terminals where NC push buttons should be inserted in series. ATTENTION! It’s allowed to use multiple NC buttons to control one DDA200 AE but it’s not permitted to use one button in a control circuit for more RCD-blocks DDA200 AE. DDA200 AE must be supplied by the top side. Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 DDA202 A-63/0.03 AE 2CSB202701R1630 801702 0.180 1 300 63 DDA202 A-63/0.3 AE 2CSB202701R3630 801801 0.180 1 500 63 DDA202 A-63/0.5 AE 2CSB202701R4630 801900 0.180 1 1000 63 DDA202 A-63/1 AE 2CSB202701R5630 802006 0.180 1 3 30 63 DDA203 A-63/0.03 AE 2CSB203701R1630 802105 0.260 1 300 63 DDA203 A-63/0.3 AE 2CSB203701R3630 802204 0.260 1 500 63 DDA203 A-63/0.5 AE 2CSB203701R4630 802303 0.260 1 1000 63 DDA203 A-63/1 AE 2CSB203701R5630 802402 0.260 1 4 30 63 DDA204 A-63/0.03 AE 2CSB204701R1630 802501 0.305 1 300 63 DDA204 A-63/0.3 AE 2CSB204701R3630 802600 0.305 1 500 63 DDA204 A-63/0.5 AE 2CSB204701R4630 802709 0.305 1 1000 63 DDA204 A-63/1 AE 2CSB204701R5630 802808 0.305 1 2CSC400163F02012CSC400563F02012CSC400562F0201 Y1 Y2 2 4 6 2 4 6 1 3 5 INPUT OUTPUT Y1 Y2 2 4 6 N 2 4 6 N 1 3 5 N INPUT OUTPUT Y1 Y2 2 4 2 4 1 3 Y1 Y2 INPUT OUTPUT

pro M compact® AC Selection tables RCD-blocks DDA 200 series AC w type, selective DDA 200 AC S DDA 200 AC selective type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide). Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G Surge current resistance (wave 8/20)=5000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 100 63 DDA202 AC S-63/0.1 2CSB202901R2630 809500 0.180 1 300 63 DDA202 AC S-63/0.3 2CSB202901R3630 809609 0.180 1 500 63 DDA202 AC S-63/0.5 2CSB202901R4630 809708 0.180 1 1000 63 DDA202 AC S-63/1 2CSB202901R5630 809807 0.180 1 3 100 63 DDA203 AC S-63/0.1 2CSB203901R2630 809906 0.260 1 300 63 DDA203 AC S-63/0.3 2CSB203901R3630 810001 0.260 1 500 63 DDA203 AC S-63/0.5 2CSB203901R4630 810100 0.260 1 1000 63 DDA203 AC S-63/1 2CSB203901R5630 810209 0.260 1 4 100 63 DDA204 AC S-63/0.1 2CSB204901R2630 810308 0.305 1 300 63 DDA204 AC S-63/0.3 2CSB204901R3630 810407 0.305 1 500 63 DDA204 AC S-63/0.5 2CSB204901R4630 810506 0.305 1 1000 63 DDA204 AC S-63/1 2CSB204901R5630 810605 0.305 1 Attention: All DDA 200 AC S are provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400163F02012CSC400563F02012CSC400562F0201

pro M compact® A Selection tables RCD-blocks DDA 200 series A y type, selective DDA 200 A S DDA 200 A selective type Function: RCD-block for assembly on site with MCBs S 200 series. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide). Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G Surge current resistance (wave 8/20)=5000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 100 63 DDA202 A S-63/0.1 2CSB202201R2630 799306 0.180 1 300 63 DDA202 A S-63/0.3 2CSB202201R3630 799405 0.180 1 500 63 DDA202 A S-63/0.5 2CSB202201R4630 799504 0.180 1 1000 63 DDA202 A S-63/1 2CSB202201R5630 799603 0.180 1 3 100 63 DDA203 A S-63/0.1 2CSB203201R2630 799702 0.260 1 300 63 DDA203 A S-63/0.3 2CSB203201R3630 799801 0.260 1 500 63 DDA203 A S-63/0.5 2CSB203201R4630 799900 0.260 1 1000 63 DDA203 A S-63/1 2CSB203201R5630 800002 0.260 1 4 100 63 DDA204 A S-63/0.1 2CSB204201R2630 800101 0.305 1 300 63 DDA204 A S-63/0.3 2CSB204201R3630 800200 0.305 1 500 63 DDA204 A S-63/0.5 2CSB204201R4630 800309 0.305 1 1000 63 DDA204 A S-63/1 2CSB204201R5630 800408 0.305 1 Attention: All DDA 200 A S are provided with additional terminals for remote tripping 2/1 4/3 246 In=63 A Y1 Y2 2CSC400163F02012CSC400563F02012CSC400562F0201

pro M compact® DDA 200 B B DDA 200 type B for continuous type fault currents RCD-blocks type B are also sensitive to continuous or mainly continuous (continuous with weak ondulation) current pulsating earth fault currents. They are also sensitive to alternate sinusoidal and direct pulsating earth fault currents as with type A circuit breakers. They satisfy the requirements of type A devices and thus the requirements for type AC devices which can be considered an extension. For this reason the differential blocks type B are sometimes referred as “universal type”, as sensitive to “all” kind of residual current shape. DDA 200 type B can be coupled with all the S 200 series MCBs. They are used for protection in installations with electronic equipments according to EN 50178. Applications: tertiary and industrial. Standards: IEC EN 61009 Ann. G, IEC 60755 Surge current resistance (8/20 wave): 3000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 DDA202 B-63/0.03 2CSB202501R1630 987802 0.260 1 300 63 DDA202 B-63/0.3 2CSB202501R3630 987703 0.260 1 3 30 63 DDA203 B-63/0.03 2CSB203501R1630 154754 0.325 1 300 63 DDA203 B-63/0.3 2CSB203501R3630 154853 0.325 1 4 30 63 DDA204 B-63/0.03 2CSB204501R1630 987505 0.325 1 300 63 DDA204 B-63/0.3 2CSB204501R3630 987604 0.325 1 DDA 200 type B for selective continuous type fault currents Function: protection against the effects of alternate sinusoidal, direct pulsating, continuous current and continuous current pulsating earth fault currents with an intentional trip delay that permits se- lectivity with instantaneous type devices placed downstream (for further information on selectivity, see chapter 10). DDA 200 type B can be coupled with all the S 200 series MCBs. They are used for protection in installations with electronic equipments according to EN 50178. Applications: tertiary and industrial. Standards: IEC EN 61009 Ann. G, IEC 60755 Surge current resistance (8/20 wave): 5000 A Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 3 300 63 DDA203 B S-63/0.3 2CSB203801R3630 987901 0.325 1 4 300 63 DDA204 B S-63/0.3 2CSB204801R3630 154952 0.325 1 B 2CSC400125F0001 6/52/1 4/3 N 51 3 N 246 N 6/52/1 4/3 51 3 24 6 2CSC400563F0001

pro M compact® TECHNICAL CHARACTERISTICS Standards Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage Ue V Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn A Rated breaking capacity acc. to IEC/EN 60947-2 ultimate Icu kA 1P+N @230 VAC service Ics kA Rated residual breaking capacity IΔm kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Thermomagnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In K: 10 In ≤ Im ≤ 14 In Surge current resistance (wave 8/20) A Mechanical Toggle features Flag indicators Electrical life Mechanical life Protection degree housing terminals Tropicalization constant climatic conditions °C/RH acc. to IEC /EN 60068-2 variable climatic conditions °C/RH Reference temperature for setting of thermal element °C Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Installation Terminal type top bottom Terminal size top/bottom for cables mm Terminal size top/bottom for busbar mm2 Tightening torque top/bottom N*m Mounting Connection Dimensions Dimensions (H x D x W) mm and weight Weight g Combination Combinable with: auxiliary contact with auxiliary signal contact elements shunt trip undervoltage release

pro M compact® DS201 L DS201 DS201 M IEC / EN 61009 AC A APR AC A APR AC A APR 1P+N 6 ≤ In ≤ 32 1 ≤ In ≤ 40 4 ≤ In ≤ 40 230-240 500 254 110 50…60 4500 6000 10000 61 0 1 0 4.5 6 7.5 4.5 6 6 2.5 QQ QQ QQQQQQQQQ Q 250 (3000 for APR versions) black sealable in ON-OFF position differential trip indicator (blue) contact position indicator (green/red) 10000 20000 IP4X IP2X 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+55 -40…+70 failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) 2.8 on DIN rail EN 60715 (35 mm) by means of fast clip device from top and bottom 85 x 69 x 35 239 yes yes yes yes

DS201 L A type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=4.5 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 6 DS201 L C6 A10 2CSR245140R0064 163404 0.240 5 10 DS201 L C10 A10 2CSR245140R0104 171003 0.240 5 16 DS201 L C16 A10 2CSR245140R0164 171102 0.240 5 30 6 DS201 L C6 A30 2CSR245140R1064 172406 0.240 5 10 DS201 L C10 A30 2CSR245140R1104 172505 0.240 5 16 DS201 L C16 A30 2CSR245140R1164 172604 0.240 5 20 DS201 L C20 A30 2CSR245140R1204 172703 0.240 5 25 DS201 L C25 A30 2CSR245140R1254 173809 0.240 5 32 DS201 L C32 A30 2CSR245140R1324 173908 0.240 5 300 6 DS201 L C6 A300 2CSR245140R3064 174004 0.240 5 10 DS201 L C10 A300 2CSR245140R3104 174103 0.240 5 16 DS201 L C16 A300 2CSR245140R3164 174202 0.240 5 20 DS201 L C20 A300 2CSR245140R3204 174301 0.240 5 25 DS201 L C25 A300 2CSR245140R3254 174707 0.240 5 32 DS201 L C32 A300 2CSR245140R3324 174806 0.240 5 C DS201 L AC type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=4.5 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 L C6 AC30 2CSR245040R1064 171201 0.240 5 10 DS201 L C10 AC30 2CSR245040R1104 171300 0.240 5 16 DS201 L C16 AC30 2CSR245040R1164 171409 0.240 5 20 DS201 L C20 AC30 2CSR245040R1204 171508 0.240 5 25 DS201 L C25 AC30 2CSR245040R1254 171607 0.240 5 32 DS201 L C32 AC30 2CSR245040R1324 171706 0.240 5 300 6 DS201 L C6 AC300 2CSR245040R3064 171805 0.240 5 10 DS201 L C10 AC300 2CSR245040R3104 171904 0.240 5 16 DS201 L C16 AC300 2CSR245040R3164 172000 0.240 5 20 DS201 L C20 AC300 2CSR245040R3204 172109 0.240 5 25 DS201 L C25 AC300 2CSR245040R3254 172208 0.240 5 32 DS201 L C32 AC300 2CSR245040R3324 172307 0.240 5 C Selection tables RCBOs DS201 series 4500 AC w type, A y type DS201 LSystem pro M compact® 1 7 1 7 2CSC400005F02022CSC400005F0202

DS201 L APR type, C characteristic Function: protection against the effects of sinusoidal alternating earth fault currents, providing an optimal trade-off between safety and continuity of service, thanks to the resistance to unwanted tripping; protection against indirect contact and additional protection against direct (I Δn=30mA) contact; protection and isolation of resistive and inductive loads. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=4.5 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 L C6 APR30 2CSR245440R1064 174905 0.240 5 10 DS201 L C10 APR30 2CSR245440R1104 175001 0.240 5 16 DS201 L C16 APR30 2CSR245440R1164 175100 0.240 5 20 DS201 L C20 APR30 2CSR245440R1204 175209 0.240 5 25 DS201 L C25 APR30 2CSR245440R1254 175605 0.240 5 32 DS201 L C32 APR30 2CSR245440R1324 175704 0.240 5 C Selection tables RCBOs DS201 series 4500 A y APR type DS201 LSystem pro M compact® 1 7 2CSC400005F0202

DS201 AC type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 C6 AC30 2CSR255040R1064 294504 0.240 5 10 DS201 C10 AC30 2CSR255040R1104 294603 0.240 5 13 DS201 C13 AC30 2CSR255040R1134 294702 0.240 5 16 DS201 C16 AC30 2CSR255040R1164 294801 0.240 5 20 DS201 C20 AC30 2CSR255040R1204 294900 0.240 5 25 DS201 C25 AC30 2CSR255040R1254 295006 0.240 5 32 DS201 C32 AC30 2CSR255040R1324 296003 0.240 5 40 DS201 C40 AC30 2CSR255040R1404 296102 0.240 5 C DS201 AC type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 B6 AC30 2CSR255040R1065 279709 0.240 5 10 DS201 B10 AC30 2CSR255040R1105 280309 0.240 5 13 DS201 B13 AC30 2CSR255040R1135 285205 0.240 5 16 DS201 B16 AC30 2CSR255040R1165 285304 0.240 5 20 DS201 B20 AC30 2CSR255040R1205 285403 0.240 5 25 DS201 B25 AC30 2CSR255040R1255 285502 0.240 5 32 DS201 B32 AC30 2CSR255040R1325 285601 0.240 5 40 DS201 B40 AC30 2CSR255040R1405 285700 0.240 5 100 6 DS201 B6 AC100 2CSR255040R2065 285809 0.240 5 10 DS201 B10 AC100 2CSR255040R2105 285908 0.240 5 13 DS201 B13 AC100 2CSR255040R2135 286004 0.240 5 16 DS201 B16 AC100 2CSR255040R2165 286103 0.240 5 20 DS201 B20 AC100 2CSR255040R2205 286202 0.240 5 25 DS201 B25 AC100 2CSR255040R2255 286301 0.240 5 32 DS201 B32 AC100 2CSR255040R2325 286400 0.240 5 40 DS201 B40 AC100 2CSR255040R2405 286509 0.240 5 300 6 DS201 B6 AC300 2CSR255040R3065 286608 0.240 5 10 DS201 B10 AC300 2CSR255040R3105 286707 0.240 5 13 DS201 B13 AC300 2CSR255040R3135 293903 0.240 5 16 DS201 B16 AC300 2CSR255040R3165 294009 0.240 5 20 DS201 B20 AC300 2CSR255040R3205 294108 0.240 5 25 DS201 B25 AC300 2CSR255040R3255 294207 0.240 5 32 DS201 B32 AC300 2CSR255040R3325 294306 0.240 5 40 DS201 B40 AC300 2CSR255040R3405 294405 0.240 5 B Selection tables RCBOs DS201 series 6000 AC w type, APR type DS201System pro M compact® 1 7 1 7 2CSC400005F02022CSC400005F0202

100 6 DS201 C6 AC100 2CSR255040R2064 296201 0.240 5 10 DS201 C10 AC100 2CSR255040R2104 296409 0.240 5 13 DS201 C13 AC100 2CSR255040R2134 370802 0.240 5 16 DS201 C16 AC100 2CSR255040R2164 370901 0.240 5 20 DS201 C20 AC100 2CSR255040R2204 371601 0.240 5 25 DS201 C25 AC100 2CSR255040R2254 371700 0.240 5 32 DS201 C32 AC100 2CSR255040R2324 371809 0.240 5 40 DS201 C40 AC100 2CSR255040R2404 498100 0.240 5 300 6 DS201 C6 AC300 2CSR255040R3064 498209 0.240 5 10 DS201 C10 AC300 2CSR255040R3104 498308 0.240 5 13 DS201 C13 AC300 2CSR255040R3134 505907 0.240 5 16 DS201 C16 AC300 2CSR255040R3164 506003 0.240 5 20 DS201 C20 AC300 2CSR255040R3204 506102 0.240 5 25 DS201 C25 AC300 2CSR255040R3254 506201 0.240 5 32 DS201 C32 AC300 2CSR255040R3324 618300 0.240 5 40 DS201 C40 AC300 2CSR255040R3404 638407 0.240 5 1000 6 DS201 C6 AC1000 2CSR255040R5064 996606 0.240 5 10 DS201 C10 AC1000 2CSR255040R5104 996705 0.240 5 16 DS201 C16 AC1000 2CSR255040R5164 996804 0.240 5 20 DS201 C20 AC1000 2CSR255040R5204 996903 0.240 5 25 DS201 C25 AC1000 2CSR255040R5254 997009 0.240 5 32 DS201 C32 AC1000 2CSR255040R5324 997108 0.240 5 40 DS201 C40 AC1000 2CSR255040R5404 997207 0.240 5 DS201 APR type, C characteristic Function: protection against the effects of sinusoidal alternating earth fault currents, providing an optimal trade-off between safety and continuity of service thanks to the resistance to unwanted tripping; protection against indirect contact and additional protection against direct (I Δn=30 mA) contact; protection and isolation of resistive and inductive loads. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 C6 APR30 2CSR255440R1064 997306 0.240 5 10 DS201 C10 APR30 2CSR255440R1104 997405 0.240 5 13 DS201 C13 APR30 2CSR255440R1134 997504 0.240 5 16 DS201 C16 APR30 2CSR255440R1164 997603 0.240 5 20 DS201 C20 APR30 2CSR255440R1204 997702 0.240 5 25 DS201 C25 APR30 2CSR255440R1254 997801 0.240 5 32 DS201 C32 APR30 2CSR255440R1324 997900 0.240 5 40 DS201 C40 APR30 2CSR255440R1404 998006 0.240 5 100 6 DS201 C6 APR100 2CSR255440R2064 126454 0.240 5 10 DS201 C10 APR100 2CSR255440R2104 126553 0.240 5 13 DS201 C13 APR100 2CSR255440R2134 126652 0.240 5 16 DS201 C16 APR100 2CSR255440R2164 126751 0.240 5 20 DS201 C20 APR100 2CSR255440R2204 126850 0.240 5 25 DS201 C25 APR100 2CSR255440R2254 126959 0.240 5 32 DS201 C32 APR100 2CSR255440R2324 127055 0.240 5 40 DS201 C40 APR100 2CSR255440R2404 127154 0.240 5 300 6 DS201 C6 APR300 2CSR255440R3064 998105 0.240 5 10 DS201 C10 APR300 2CSR255440R3104 998204 0.240 5 13 DS201 C13 APR300 2CSR255440R3134 998303 0.240 5 16 DS201 C16 APR300 2CSR255440R3164 998402 0.240 5 20 DS201 C20 APR300 2CSR255440R3204 998501 0.240 5 25 DS201 C25 APR300 2CSR255440R3254 998600 0.240 5 32 DS201 C32 APR300 2CSR255440R3324 998709 0.240 5 40 DS201 C40 APR300 2CSR255440R3404 998808 0.240 5 C Selection tables RCBOs DS201 series 6000 AC w type, APR type DS201System pro M compact® 1 7 2CSC400005F0202

C DS201 A type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS201 B10 A10 2CSR255140R0105 995708 0.240 5 13 DS201 B13 A10 2CSR255140R0135 995807 0.240 5 16 DS201 B16 A10 2CSR255140R0165 995906 0.240 5 30 6 DS201 B6 A30 2CSR255140R1065 638506 0.240 5 10 DS201 B10 A30 2CSR255140R1105 647805 0.240 5 13 DS201 B13 A30 2CSR255140R1135 655503 0.240 5 16 DS201 B16 A30 2CSR255140R1165 655602 0.240 5 20 DS201 B20 A30 2CSR255140R1205 655701 0.240 5 25 DS201 B25 A30 2CSR255140R1255 766902 0.240 5 32 DS201 B32 A30 2CSR255140R1325 814504 0.240 5 40 DS201 B40 A30 2CSR255140R1405 910602 0.240 5 100 6 DS201 B6 A100 2CSR255140R2065 990307 0.240 5 10 DS201 B10 A100 2CSR255140R2105 990406 0.240 5 13 DS201 B13 A100 2CSR255140R2135 990505 0.240 5 16 DS201 B16 A100 2CSR255140R2165 990604 0.240 5 20 DS201 B20 A100 2CSR255140R2205 990703 0.240 5

25 DS201 B25 A100

2CSR255140R2255 990802 0.240 5 32 DS201 B32 A100 2CSR255140R2325 990901 0.240 5 40 DS201 B40 A100 2CSR255140R2405 991007 0.240 5 300 6 DS201 B6 A300 2CSR255140R3065 991908 0.240 5 10 DS201 B10 A300 2CSR255140R3105 992004 0.240 5 13 DS201 B13 A300 2CSR255140R3135 992103 0.240 5 16 DS201 B16 A300 2CSR255140R3165 992202 0.240 5 20 DS201 B20 A300 2CSR255140R3205 992301 0.240 5 25 DS201 B25 A300 2CSR255140R3255 992400 0.240 5 32 DS201 B32 A300 2CSR255140R3325 992509 0.240 5 40 DS201 B40 A300 2CSR255140R3405 992608 0.240 5 B Selection tables RCBOs DS201 series 6000 A y type DS201 DS201 A type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS201 C10 A10 2CSR255140R0104 996002 0.240 5 13 DS201 C13 A10 2CSR255140R0134 996101 0.240 5 16 DS201 C16 A10 2CSR255140R0164 996200 0.240 5 30 2 DS201 C2 A30 2CSR255140R1024 123958 0.240 5 4 DS201 C4 A30 2CSR255140R1044 942306 0.240 5 6 DS201 C6 A30 2CSR255140R1064 942405 0.240 5 8 DS201 C8 A30 2CSR255140R1084 124054 0.240 5 10 DS201 C10 A30 2CSR255140R1104 952503 0.240 5 13 DS201 C13 A30 2CSR255140R1134 976004 0.240 5 16 DS201 C16 A30 2CSR255140R1164 976103 0.240 5 System pro M compact® 1 7 1 7 2CSC400005F02022CSC400005F0202

20 DS201 C20 A30 2CSR255140R1204 976202 0.240 5 25 DS201 C25 A30 2CSR255140R1254 976301 0.240 5 32 DS201 C32 A30 2CSR255140R1324 990109 0.240 5 40 DS201 C40 A30 2CSR255140R1404 990208 0.240 5 100 6 DS201 C6 A100 2CSR255140R2064 991106 0.240 5 10 DS201 C10 A100 2CSR255140R2104 991205 0.240 5 13 DS201 C13 A100 2CSR255140R2134 991304 0.240 5 16 DS201 C16 A100 2CSR255140R2164 991403 0.240 5 20 DS201 C20 A100 2CSR255140R2204 991502 0.240 5 25 DS201 C25 A100 2CSR255140R2254 991601 0.240 5 32 DS201 C32 A100 2CSR255140R2324 991700 0.240 5 40 DS201 C40 A100 2CSR255140R2404 991809 0.240 5 300 2 DS201 C2 A300 2CSR255140R3024 124153 0.240 5 4 DS201 C4 A300 2CSR255140R3044 124252 0.240 5 6 DS201 C6 A300 2CSR255140R3064 992707 0.240 5 8 DS201 C8 A300 2CSR255140R3084 124351 0.240 5 10 DS201 C10 A300 2CSR255140R3104 992806 0.240 5 13 DS201 C13 A300 2CSR255140R3134 992905 0.240 5 16 DS201 C16 A300 2CSR255140R3164 993001 0.240 5 20 DS201 C20 A300 2CSR255140R3204 993100 0.240 5 25 DS201 C25 A300 2CSR255140R3254 993209 0.240 5 32 DS201 C32 A300 2CSR255140R3324 993308 0.240 5 40 DS201 C40 A300 2CSR255140R3404 993407 0.240 5 DS201 A type, K characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 60947-2 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS201 K10 A10 2CSR255140R0107 996309 0.240 5 13 DS201 K13 A10 2CSR255140R0137 996408 0.240 5 16 DS201 K16 A10 2CSR255140R0167 996507 0.240 5 30 1 DS201 K1 A30 2CSR255140R1017 993506 0.240 5 2 DS201 K2 A30 2CSR255140R1027 993605 0.240 5 4 DS201 K4 A30 2CSR255140R1047 993704 0.240 5 6 DS201 K6 A30 2CSR255140R1067 993803 0.240 5 8 DS201 K8 A30 2CSR255140R1087 123750 0.240 5 10 DS201 K10 A30 2CSR255140R1107 993902 0.240 5 13 DS201 K13 A30 2CSR255140R1137 994008 0.240 5 16 DS201 K16 A30 2CSR255140R1167 994107 0.240 5 20 DS201 K20 A30 2CSR255140R1207 994206 0.240 5 25 DS201 K25 A30 2CSR255140R1257 994305 0.240 5 32 DS201 K32 A30 2CSR255140R1327 994404 0.240 5 40 DS201 K40 A30 2CSR255140R1407 994503 0.240 5 300 1 DS201 K1 A300 2CSR255140R3017 994602 0.240 5

2 DS201 K2 A300

2CSR255140R3027 994701 0.240 5 4 DS201 K4 A300 2CSR255140R3047 994800 0.240 5 6 DS201 K6 A300 2CSR255140R3067 994909 0.240 5 8 DS201 K8 A300 2CSR255140R3087 123859 0.240 5 10 DS201 K10 A300 2CSR255140R3107 995005 0.240 5 13 DS201 K13 A300 2CSR255140R3137 995104 0.240 5 16 DS201 K16 A300 2CSR255140R3167 995203 0.240 5 20 DS201 K20 A300 2CSR255140R3207 995302 0.240 5 25 DS201 K25 A300 2CSR255140R3257 995401 0.240 5 32 DS201 K32 A300 2CSR255140R3327 995500 0.240 5 40 DS201 K40 A300 2CSR255140R3407 995609 0.240 5 C Selection tables RCBOs DS201 series 6000 A y type DS201System pro M compact® 1 7 2CSC400005F0202

C DS201 M AC type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 M B6 AC30 2CSR275040R1065 998907 0.240 5 10 DS201 M B10 AC30 2CSR275040R1105 999003 0.240 5 13 DS201 M B13 AC30 2CSR275040R1135 999102 0.240 5 16 DS201 M B16 AC30 2CSR275040R1165 999201 0.240 5 20 DS201 M B20 AC30 2CSR275040R1205 999300 0.240 5 25 DS201 M B25 AC30 2CSR275040R1255 999409 0.240 5 32 DS201 M B32 AC30 2CSR275040R1325 999508 0.240 5 40 DS201 M B40 AC30 2CSR275040R1405 999607 0.240 5 100 6 DS201 M B6 AC100 2CSR275040R2065 106159 0.240 5 10 DS201 M B10 AC100 2CSR275040R2105 106258 0.240 5 13 DS201 M B13 AC100 2CSR275040R2135 106357 0.240 5 16 DS201 M B16 AC100 2CSR275040R2165 106456 0.240 5 20 DS201 M B20 AC100 2CSR275040R2205 106555 0.240 5 25 DS201 M B25 AC100 2CSR275040R2255 106654 0.240 5 32 DS201 M B32 AC100 2CSR275040R2325 106753 0.240 5 40 DS201 M B40 AC100 2CSR275040R2405 106852 0.240 5 300 6 DS201 M B6 AC300 2CSR275040R3065 107750 0.240 5 10 DS201 M B10 AC300 2CSR275040R3105 107859 0.240 5 13 DS201 M B13 AC300 2CSR275040R3135 107958 0.240 5 16 DS201 M B16 AC300 2CSR275040R3165 108054 0.240 5 20 DS201 M B20 AC300 2CSR275040R3205 108153 0.240 5 25 DS201 M B25 AC300 2CSR275040R3255 108252 0.240 5 32 DS201 M B32 AC300 2CSR275040R3325 108351 0.240 5 40 DS201 M B40 AC300 2CSR275040R3405 108450 0.240 5 B Selection tables RCBOs DS201 series 10000 AC w type, A y APR type DS201 M DS201 M AC type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 M C6 AC30 2CSR275040R1064 999706 0.240 5 10 DS201 M C10 AC30 2CSR275040R1104 999805 0.240 5 13 DS201 M C13 AC30 2CSR275040R1134 999904 0.240 5 16 DS201 M C16 AC30 2CSR275040R1164 105657 0.240 5 20 DS201 M C20 AC30 2CSR275040R1204 105756 0.240 5 25 DS201 M C25 AC30 2CSR275040R1254 105855 0.240 5 32 DS201 M C32 AC30 2CSR275040R1324 105954 0.240 5 40 DS201 M C40 AC30 2CSR275040R1404 106050 0.240 5 System pro M compact® 1 7 1 7 2CSC400005F02022CSC400005F0202

100 6 DS201 M C6 AC100 2CSR275040R2064 106951 0.240 5 10 DS201 M C10 AC100 2CSR275040R2104 107057 0.240 5 13 DS201 M C13 AC100 2CSR275040R2134 107156 0.240 5 16 DS201 M C16 AC100 2CSR275040R2164 107255 0.240 5 20 DS201 M C20 AC100 2CSR275040R2204 107354 0.240 5 25 DS201 M C25 AC100 2CSR275040R2254 107453 0.240 5 32 DS201 M C32 AC100 2CSR275040R2324 107552 0.240 5 40 DS201 M C40 AC100 2CSR275040R2404 107651 0.240 5 300 6 DS201 M C6 AC300 2CSR275040R3064 108559 0.240 5 10 DS201 M C10 AC300 2CSR275040R3104 108658 0.240 5 13 DS201 M C13 AC300 2CSR275040R3134 108757 0.240 5 16 DS201 M C16 AC300 2CSR275040R3164 108856 0.240 5 20 DS201 M C20 AC300 2CSR275040R3204 108955 0.240 5 25 DS201 M C25 AC300 2CSR275040R3254 109051 0.240 5 32 DS201 M C32 AC300 2CSR275040R3324 109150 0.240 5 40 DS201 M C40 AC300 2CSR275040R3404 109259 0.240 5 DS201 M APR type, C characteristic Function: protection against the effects of sinusoidal alternating earth fault currents, providing an optimal compromise between safety and continuity of service, thanks to the resistance to unwanted tripping; protection against indirect contact and additional protection against direct (I Δn=30 mA) contact; protection and isolation of resistive and inductive loads. Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 30 6 DS201 M C6 APR30 2CSR275440R1064 114154 0.240 5 10 DS201 M C10 APR30 2CSR275440R1104 114253 0.240 5 13 DS201 M C13 APR30 2CSR275440R1134 114352 0.240 5 16 DS201 M C16 APR30 2CSR275440R1164 114451 0.240 5 20 DS201 M C20 APR30 2CSR275440R1204 114550 0.240 5 25 DS201 M C25 APR30 2CSR275440R1254 114659 0.240 5 32 DS201 M C32 APR30 2CSR275440R1324 114758 0.240 5 40 DS201 M C40 APR30 2CSR275440R1404 114857 0.240 5 100 6 DS201 M C6 APR100 2CSR275440R2064 127253 0.240 5 10 DS201 M C10 APR100 2CSR275440R2104 127352 0.240 5 13 DS201 M C13 APR100 2CSR275440R2134 127451 0.240 5 16 DS201 M C16 APR100 2CSR275440R2164 127550 0.240 5 20 DS201 M C20 APR100 2CSR275440R2204 127659 0.240 5 25 DS201 M C25 APR100 2CSR275440R2254 127758 0.240 5 32 DS201 M C32 APR100 2CSR275440R2324 127857 0.240 5 40 DS201 M C40 APR100 2CSR275440R2404 127956 0.240 5 300 6 DS201 M C6 APR300 2CSR275440R3064 114956 0.240 5 10 DS201 M C10 APR300 2CSR275440R3104 115052 0.240 5 13 DS201 M C13 APR300 2CSR275440R3134 115151 0.240 5 16 DS201 M C16 APR300 2CSR275440R3164 115250 0.240 5 20 DS201 M C20 APR300 2CSR275440R3204 115359 0.240 5 25 DS201 M C25 APR300 2CSR275440R3254 115458 0.240 5 32 DS201 M C32 APR300 2CSR275440R3324 115557 0.240 5 40 DS201 M C40 APR300 2CSR275440R3404 115656 0.240 5 C Selection tables RCBOs DS201 series 10000 AC w type, A y APR type DS201 MSystem pro M compact® 1 7 2CSC400005F0202

DS201 M A type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS201 M B10 A10 2CSR275140R0105 124450 0.240 5 16 DS201 M B16 A10 2CSR275140R0165 124559 0.240 5 30 6 DS201 M B6 A30 2CSR275140R1065 109358 0.240 5 10 DS201 M B10 A30 2CSR275140R1105 109457 0.240 5 13 DS201 M B13 A30 2CSR275140R1135 109556 0.240 5 16 DS201 M B16 A30 2CSR275140R1165 109655 0.240 5 20 DS201 M B20 A30 2CSR275140R1205 109754 0.240 5 25 DS201 M B25 A30 2CSR275140R1255 109853 0.240 5 32 DS201 M B32 A30 2CSR275140R1325 109952 0.240 5 40 DS201 M B40 A30 2CSR275140R1405 110057 0.240 5 100 6 DS201 M B6 A100 2CSR275140R2065 111054 0.240 5 10 DS201 M B10 A100 2CSR275140R2105 111153 0.240 5 13 DS201 M B13 A100 2CSR275140R2135 111252 0.240 5 16 DS201 M B16 A100 2CSR275140R2165 111351 0.240 5 20 DS201 M B20 A100 2CSR275140R2205 111450 0.240 5 25 DS201 M B25 A100 2CSR275140R2255 111559 0.240 5

32 DS201 M B32 A100

2CSR275140R2325 111658 0.240 5 40 DS201 M B40 A100 2CSR275140R2405 111757 0.240 5 300 6 DS201 M B6 A300 2CSR275140R3065 112556 0.240 5 10 DS201 M B10 A300 2CSR275140R3105 112655 0.240 5 13 DS201 M B13 A300 2CSR275140R3135 112754 0.240 5 16 DS201 M B16 A300 2CSR275140R3165 112853 0.240 5 20 DS201 M B20 A300 2CSR275140R3205 112952 0.240 5 25 DS201 M B25 A300 2CSR275140R3255 113058 0.240 5 32 DS201 M B32 A300 2CSR275140R3325 113157 0.240 5 40 DS201 M B40 A300 2CSR275140R3405 113256 0.240 5 B Selection tables RCBOs DS201 series 10000 A y type DS201 MSystem pro M compact® 1 7 2CSC400005F0202

DS201 M A type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS201 M C10 A10 2CSR275140R0104 124658 0.240 5 16 DS201 M C16 A10 2CSR275140R0164 124757 0.240 5 30 4 DS201 M C4 A30 2CSR275140R1044 110156 0.240 5 6 DS201 M C6 A30 2CSR275140R1064 110255 0.240 5 10 DS201 M C10 A30 2CSR275140R1104 110354 0.240 5 13 DS201 M C13 A30 2CSR275140R1134 110453 0.240 5 16 DS201 M C16 A30 2CSR275140R1164 110552 0.240 5 20 DS201 M C20 A30 2CSR275140R1204 110651 0.240 5 25 DS201 M C25 A30 2CSR275140R1254 110750 0.240 5 32 DS201 M C32 A30 2CSR275140R1324 110859 0.240 5 40 DS201 M C40 A30 2CSR275140R1404 110958 0.240 5 100 6 DS201 M C6 A100 2CSR275140R2064 111856 0.240 5 10 DS201 M C10 A100 2CSR275140R2104 111955 0.240 5 16 DS201 M C16 A100 2CSR275140R2164 112051 0.240 5 20 DS201 M C20 A100 2CSR275140R2204 112150 0.240 5 25 DS201 M C25 A100 2CSR275140R2254 112259 0.240 5

32 DS201 M C32 A100

2CSR275140R2324 112358 0.240 5 40 DS201 M C40 A100 2CSR275140R2404 112457 0.240 5 300 6 DS201 M C6 A300 2CSR275140R3064 113355 0.240 5 10 DS201 M C10 A300 2CSR275140R3104 113454 0.240 5 13 DS201 M C13 A300 2CSR275140R3134 113553 0.240 5 16 DS201 M C16 A300 2CSR275140R3164 113652 0.240 5 20 DS201 M C20 A300 2CSR275140R3204 113751 0.240 5 25 DS201 M C25 A300 2CSR275140R3254 113850 0.240 5 32 DS201 M C32 A300 2CSR275140R3324 113959 0.240 5 40 DS201 M C40 A300 2CSR275140R3404 114055 0.240 5 C Selection tables RCBOs DS201 series 10000 A y type DS201 MSystem pro M compact® 1 7 2CSC400005F0202

Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage Ue V Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn A Rated breaking capacity acc. to IEC/EN 60947-2 ultimate Icu kA 2P @230 VAC service Ics kA Rated residual breaking capacity I Δm kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Thermomagnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In K: 10 In ≤ Im ≤ 14 In Surge current resistance (wave 8/20) A Mechanical Toggle features Flag indicators Electrical life Mechanical life Protection degree housing terminals Tropicalization constant climatic conditions °C/RH acc. to IEC /EN 60068-2 variable climatic conditions °C/RH Reference temperature for setting of thermal element °C Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Installation Terminal type top bottom Terminal size top/bottom for cables mm Terminal size top/bottom for busabar mm2 Tightening torque top/bottom N*m Mounting Connection Dimensions Dimensions (H x D x W) mm and weight Weight g Combination Combinable with: auxiliary contact with auxiliary signal contact elements shunt trip undervoltage release System pro M compact®

6 ≤ In ≤ 32 230-240 500 254 110 50…60 6000 10000 10 10 6 7.5 2.5 QQ Q QQ Q 250 (3000 for APR versions) black sealable in ON-OFF position differential trip indicator (blue) contact position indicator (green/red) 10000 20000 IP4X IP2X 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+55 -40…+70 failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) failsafe bi-directional cylinder-lift terminal at top and bottom (shock protected) 2.8 on DIN rail EN 60715 (35 mm) by means of fast clip device from top and bottom 85 x 69 x 35 239 yes yes yes yes System pro M compact®

DS202C A type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 6 DS202C B6 A30 2CSR252140R1065 132257 0.240 5 10 DS202C B10 A30 2CSR252140R1105 132356 0.240 5 13 DS202C B13 A30 2CSR252140R1135 132455 0.240 5 16 DS202C B16 A30 2CSR252140R1165 132554 0.240 5 20 DS202C B20 A30 2CSR252140R1205 132653 0.240 5 25 DS202C B25 A30 2CSR252140R1255 132752 0.240 5 32 DS202C B32 A30 2CSR252140R1325 132851 0.240 5 300 6 DS202C B6 A300 2CSR252140R3065 132950 0.240 5 10 DS202C B10 A300 2CSR252140R3105 133056 0.240 5 13 DS202C B13 A300 2CSR252140R3135 133155 0.240 5 16 DS202C B16 A300 2CSR252140R3165 133254 0.240 5 20 DS202C B20 A300 2CSR252140R3205 133353 0.240 5 25 DS202C B25 A300 2CSR252140R3255 133452 0.240 5 32 DS202C B32 A300 2CSR252140R3325 133551 0.240 5 B Selection tables RCBOs DS202C series 6000 A y type DS202C ASystem pro M compact® 2CSC400006F0202

DS202C A type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=6 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 6 DS202C C6 A30 2CSR252140R1064 122357 0.240 5 10 DS202C C10 A30 2CSR252140R1104 122456 0.240 5 13 DS202C C13 A30 2CSR252140R1134 122555 0.240 5 16 DS202C C16 A30 2CSR252140R1164 122654 0.240 5 20 DS202C C20 A30 2CSR252140R1204 122753 0.240 5 25 DS202C C25 A30 2CSR252140R1254 122852 0.240 5 32 DS202C C32 A30 2CSR252140R1324 122951 0.240 5 300 6 DS202C C6 A300 2CSR252140R3064 123057 0.240 5 10 DS202C C10 A300 2CSR252140R3104 123156 0.240 5 13 DS202C C13 A300 2CSR252140R3134 123255 0.240 5 16 DS202C C16 A300 2CSR252140R3164 123354 0.240 5 20 DS202C C20 A300 2CSR252140R3204 123453 0.240 5 25 DS202C C25 A300 2CSR252140R3254 123552 0.240 5 32 DS202C C32 A300 2CSR252140R3324 123651 0.240 5 C Selection tables RCBOs DS202C series 6000 A y type DS202C ASystem pro M compact® 2CSC400005F0202

DS202C M A type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 13 DS202C M C13 A10 2CSR272140R0134 117957 0.240 5 16 DS202C M C16 A10 2CSR272140R0164 118053 0.240 5 30 6 DS202C M C6 A30 2CSR272140R1064 118855 0.240 5 10 DS202C M C10 A30 2CSR272140R1104 118954 0.240 5 13 DS202C M C13 A30 2CSR272140R1134 119050 0.240 5 16 DS202C M C16 A30 2CSR272140R1164 119159 0.240 5 20 DS202C M C20 A30 2CSR272140R1204 119258 0.240 5 25 DS202C M C25 A30 2CSR272140R1254 119357 0.240 5 32 DS202C M C32 A30 2CSR272140R1324 119456 0.240 5 300 6 DS202C M C6 A300 2CSR272140R3064 120254 0.240 5 10 DS202C M C10 A300 2CSR272140R3104 120353 0.240 5 13 DS202C M C13 A300 2CSR272140R3134 120452 0.240 5 16 DS202C M C16 A300 2CSR272140R3164 120551 0.240 5 20 DS202C M C20 A300 2CSR272140R3204 120650 0.240 5 25 DS202C M C25 A300 2CSR272140R3254 120759 0.240 5 32 DS202C M C32 A300 2CSR272140R3324 120858 0.240 5 C DS202C M A type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 1+N 10 10 DS202C M B10 A10 2CSR272140R0105 124856 0.240 5 13 DS202C M B13 A10 2CSR272140R0135 117759 0.240 5 16 DS202C M B16 A10 2CSR272140R0165 117858 0.240 5 30 6 DS202C M B6 A30 2CSR272140R1065 118152 0.240 5 10 DS202C M B10 A30 2CSR272140R1105 118251 0.240 5 13 DS202C M B13 A30 2CSR272140R1135 118350 0.240 5 16 DS202C M B16 A30 2CSR272140R1165 118459 0.240 5 20 DS202C M B20 A30 2CSR272140R1205 118558 0.240 5 25 DS202C M B25 A30 2CSR272140R1255 118657 0.240 5 32 DS202C M B32 A30 2CSR272140R1325 118756 0.240 5 300 6 DS202C M B6 A300 2CSR272140R3065 119555 0.240 5 10 DS202C M B10 A300 2CSR272140R3105 119654 0.240 5 13 DS202C M B13 A300 2CSR272140R3135 119753 0.240 5 16 DS202C M B16 A300 2CSR272140R3165 119852 0.240 5 20 DS202C M B20 A300 2CSR272140R3205 119951 0.240 5 25 DS202C M B25 A300 2CSR272140R3255 120056 0.240 5

32 DS202C M B32 A300

2CSR272140R3325 120155 0.240 5 B Selection tables RCBOs DS202C series 10000 A y type DS202C M ASystem pro M compact® 2CSC400005F02022CSC400005F0202

DS202C M APR type, B characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 6 DS202C M B6 APR30 2CSR272440R1065 120957 0.240 5 10 DS202C M B10 APR30 2CSR272440R1105 121053 0.240 5 13 DS202C M B13 APR30 2CSR272440R1135 121152 0.240 5 16 DS202C M B16 APR30 2CSR272440R1165 121251 0.240 5 20 DS202C M B20 APR30 2CSR272440R1205 121350 0.240 5 25 DS202C M B25 APR30 2CSR272440R1255 121459 0.240 5 32 DS202C M B32 APR30 2CSR272440R1325 121558 0.240 5 300 6 DS202C M B6 APR300 2CSR272440R3065 124955 0.240 5 DS202C M B10 APR300 2CSR272440R3105 125051 0.240 5 13 DS202C M B13 APR300 2CSR272440R3135 125150 0.240 5 16 DS202C M B16 APR300 2CSR272440R3165 125259 0.240 5 20 DS202C M B20 APR300 2CSR272440R3205 125358 0.240 5 25 DS202C M B25 APR300 2CSR272440R3255 125457 0.240 5 32 DS202C M B32 APR300 2CSR272440R3325 125556 0.240 5 DS202C M APR type, C characteristic Function: protection of end user single-phase circuits against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; pro- tection against indirect contact and additional protection against direct contact (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 6 DS202C M C6 APR30 2CSR272440R1064 121657 0.240 5 10 DS202C M C10 APR30 2CSR272440R1104 121756 0.240 5 13 DS202C M C13 APR30 2CSR272440R1134 121855 0.240 5 16 DS202C M C16 APR30 2CSR272440R1164 121954 0.240 5 20 DS202C M C20 APR30 2CSR272440R1204 122050 0.240 5 25 DS202C M C25 APR30 2CSR272440R1254 122159 0.240 5 32 DS202C M C32 APR30 2CSR272440R1324 122258 0.240 5 Selection tables RCBOs DS202C series 10000 A y APR type DS202C M APR C B System pro M compact® 2CSC400005F02022CSC400005F0202

Electrical Operating characteristic: type (wave form of the earth leakage sensed) features Poles Rated sensitivity IΔn A Rated current In A Rated voltage Ue 2P , 3P , 4P V Rated residual operating current A Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn A Rated breaking capacity ultimate Icu kA acc. to IEC/EN 60947-2 1P+N @230 VAC, 2P , 3P , 4P @400 VAC service Ics kA Rated residual breaking capacity IΔm kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Overvoltage category Thermomagnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In K: 10 In ≤ Im ≤ 14 In Surge current resistance (wave 8/20) A Mechanical Toggle 2P , 3P , 4P features Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC /EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Reference temperature for setting of thermal element °C Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Installation Terminal type top bottom 2P 3P/4P In ≤ 40 A 3P/4P 50 A ≤ In ≤ 63 A Terminal size top/bottom per cable 2P mm 3P/4P In ≤ 40 A mm 2 3P/4P 50 A ≤ In ≤ 63 A mm 2 Tightening torque top/bottom 2P N*m 3P/4P In ≤ 40 A N*m 3P/4P 50 A ≤ In ≤ 63 A N*m Mounting Connection Dimensions Dimensions (H x D x W) 2P mm and weight 3P In ≤ 40 A mm 4P In ≤ 40 A mm 3P 50 A ≤ In ≤ 63 A mm 4P 50 A ≤ In ≤ 63 A mm Weight 2P g 3P In ≤ 40 A g 4P In ≤ 40 A g 3P 50 A ≤ In ≤ 63 A g 4P 50 A ≤ In ≤ 63 A g Combination Combinable with: auxiliary contact with auxiliary signal contact/auxiliary switch elements shunt trip undervoltage release /L54706 Available depending on type and characteristic curve. For 2P RCBOs A type B-C curves up to 32 A, refer to DS202C 2 protected poles RCBOs in only two modules /L54707 Prior to connection of aluminium conductors (≥ 4 mm2) ensure that their contact points are cleaned, brushed and coated with grease Technical features RCBOs DS 200 series System pro M compact® DS 200

pro M compact® DS 200 DS 200 AC DS 200 A DS 200 M AC DS 200 M A IEC/EN 61009, IEC/EN 60947-2 A CAA CA 2P , 3P , 4P 0.03 6 ≤In ≤ 63 /L54706 230-240 230/400 - 240/415 0.03 500 254 (440 for 3P and 4P) 110 (195 for 3P and 4P) 50…60 6000 6000 10000 10000 10 10 15 15 7.5 7.5 11.2 11.2 6 6 10 10 2.5 III, disconnector abilities Q Q Q 250 black (MCB) sealable in ON-OFF position + blue (RCD) 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+55 -25…+55 failsafe bidirectional cylinder-lift terminal (shock protected) /L54707 failsafe bidirectional cylinder-lift terminal (shock protected) /L54707 cage (shock protected) failsafe bidirectional cylinder-lift terminal (shock protected) /L54707 (rigid and flexible) up to 25/25 (rigid and flexible) up to 25/16 (rigid and flexible) up to 25/25 2.8/2.8 2.8/1.2 2.8/2.8 on DIN rail EN 60715 (35 mm) by means of fast clip device 715 (35 mm) by means of fast clip devicefrom top and bottom 85 x 69 x 70 85 x 69 x 87.5 85 x 69 x 105 85 x 69 x 122.5 85 x 69 x 140 475 625 775 775 925 yes yes yes yes

pro M compact® B Selection tables RCBOs DS 200 series 6000 - AC w type DS 200 AC B DS 200 AC type, B characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional pro- tection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 and IEC/EN 60947-2 Icn=6 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 AC 30 6 DS202 AC-B6/0.03 2CSR252001R1065 863502 0.440 1 DS202 AC-B10/0.03 2CSR252001R1105 863601 0.440 1 13 DS202 AC-B13/0.03 2CSR252001R1135 863700 0.440 1 16 DS202 AC-B16/0.03 2CSR252001R1165 863809 0.440 1 20 DS202 AC-B20/0.03 2CSR252001R1205 863908 0.440 1 25 DS202 AC-B25/0.03 2CSR252001R1255 864004 0.440 1 32 DS202 AC-B32/0.03 2CSR252001R1325 864103 0.440 1 40 DS202 AC-B40/0.03 2CSR252001R1405 864202 0.440 1 50 /L54706 DS202 AC-B50/0.03 2CSR252001R1505 864301 0.440 1 63 /L54706 DS202 AC-B63/0.03 2CSR252001R1635 864400 0.440 1 3 AC 30 6 DS203 AC-B6/0.03 2CSR253001R1065 865506 0.610 1 DS203 AC-B10/0.03 2CSR253001R1105 865605 0.610 1 13 DS203 AC-B13/0.03 2CSR253001R1135 865704 0.610 1 16 DS203 AC-B16/0.03 2CSR253001R1165 865803 0.610 1 20 DS203 AC-B20/0.03 2CSR253001R1205 865902 0.610 1 25 DS203 AC-B25/0.03 2CSR253001R1255 866008 0.610 1 32 DS203 AC-B32/0.03 2CSR253001R1325 866107 0.610 1 40 DS203 AC-B40/0.03 2CSR253001R1405 866206 0.610 1 50 /L54706 DS203 AC-B50/0.03 2CSR253001R1505 866305 0.650 1 63 /L54706 DS203 AC-B63/0.03 2CSR253001R1635 866404 0.650 1 4 AC 30 6 DS204 AC-B6/0.03 2CSR254001R1065 867500 0.780 1 DS204 AC-B10/0.03 2CSR254001R1105 867609 0.780 1 13 DS204 AC-B13/0.03 2CSR254001R1135 867708 0.780 1 16 DS204 AC-B16/0.03 2CSR254001R1165 867807 0.780 1 20 DS204 AC-B20/0.03 2CSR254001R1205 867906 0.780 1 25 DS204 AC-B25/0.03 2CSR254001R1255 868002 0.780 1 32 DS204 AC-B32/0.03 2CSR254001R1325 868101 0.780 1 40 DS204 AC-B40/0.03 2CSR254001R1405 868200 0.780 1 50 /L54706 DS204 AC-B50/0.03 2CSR254001R1505 868309 0.825 1 63 /L54706 DS204 AC-B63/0.03 2CSR254001R1635 868408 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 5/6 7/8 In up to 40 A 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® C Selection tables RCBOs DS 200 series 6000 - AC w type DS 200 AC C DS 200 AC type, C characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional pro- tection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 and IEC/EN 60947-2 Icn=6 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 AC 30 6 DS202 AC-C6/0.03 2CSR252001R1064 869504 0.440 1 DS202 AC-C10/0.03 2CSR252001R1104 869603 0.440 1 13 DS202 AC-C13/0.03 2CSR252001R1134 869702 0.440 1 16 DS202 AC-C16/0.03 2CSR252001R1164 869801 0.440 1 20 DS202 AC-C20/0.03 2CSR252001R1204 869900 0.440 1 25 DS202 AC-C25/0.03 2CSR252001R1254 870005 0.440 1 32 DS202 AC-C32/0.03 2CSR252001R1324 870104 0.440 1 40 DS202 AC-C40/0.03 2CSR252001R1404 870203 0.440 1 50 /L54706 DS202 AC-C50/0.03 2CSR252001R1504 870302 0.440 1 63 /L54706 DS202 AC-C63/0.03 2CSR252001R1634 870401 0.440 1 3 AC 30 6 DS203 AC-C6/0.03 2CSR253001R1064 871507 0.610 1 DS203 AC-C10/0.03 2CSR253001R1104 871606 0.610 1 13 DS203 AC-C13/0.03 2CSR253001R1134 871705 0.610 1 16 DS203 AC-C16/0.03 2CSR253001R1164 871804 0.610 1 20 DS203 AC-C20/0.03 2CSR253001R1204 871903 0.610 1 25 DS203 AC-C25/0.03 2CSR253001R1254 872009 0.610 1 32 DS203 AC-C32/0.03 2CSR253001R1324 872108 0.610 1 40 DS203 AC-C40/0.03 2CSR253001R1404 872207 0.610 1 50 /L54706 DS203 AC-C50/0.03 2CSR253001R1504 872306 0.650 1 63 /L54706 DS203 AC-C63/0.03 2CSR253001R1634 872405 0.650 1 4 AC 30 6 DS204 AC-C6/0.03 2CSR254001R1064 873501 0.780 1 DS204 AC-C10/0.03 2CSR254001R1104 873600 0.780 1 13 DS204 AC-C13/0.03 2CSR254001R1134 873709 0.780 1 16 DS204 AC-C16/0.03 2CSR254001R1164 873808 0.780 1 20 DS204 AC-C20/0.03 2CSR254001R1204 873907 0.780 1 25 DS204 AC-C25/0.03 2CSR254001R1254 874003 0.780 1 32 DS204 AC-C32/0.03 2CSR254001R1324 874102 0.780 1 40 DS204 AC-C40/0.03 2CSR254001R1404 874201 0.780 1 50 /L54706 DS204 AC-C50/0.03 2CSR254001R1504 874300 0.825 1 63 /L54706 DS204 AC-C63/0.03 2CSR254001R1634 874409 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 5/6 7/8 In up to 40 A 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® B Selection tables RCBOs DS 200 series 6000 - A y type DS 200 A B DS 200 A type, B characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 and IEC/EN 60947-2 Icn=6 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 A 30 40 DS202 A-B40/0.03 2CSR252101R1405 858201 0.440 1 50 /L54706 DS202 A-B50/0.03 2CSR252101R1505 858300 0.440 1 63 /L54706 DS202 A-B63/0.03 2CSR252101R1635 858409 0.440 1 3 A 30 6 DS203 A-B6/0.03 2CSR253101R1065 858508 0.610 1 10 DS203 A-B10/0.03 2CSR253101R1105 858607 0.610 1 13 DS203 A-B13/0.03 2CSR253101R1135 858706 0.610 1 16 DS203 A-B16/0.03 2CSR253101R1165 858805 0.610 1 20 DS203 A-B20/0.03 2CSR253101R1205 858904 0.610 1 25 DS203 A-B25/0.03 2CSR253101R1255 859000 0.610 1 32 DS203 A-B32/0.03 2CSR253101R1325 859109 0.610 1 40 DS203 A-B40/0.03 2CSR253101R1405 859208 0.610 1 50 /L54706 DS203 A-B50/0.03 2CSR253101R1505 859307 0.650 1 63 /L54706 DS203 A-B63/0.03 2CSR253101R1635 859406 0.650 1 4 A 30 6 DS204 A-B6/0.03 2CSR254101R1065 859505 0.780 1 10 DS204 A-B10/0.03 2CSR254101R1105 859604 0.780 1 13 DS204 A-B13/0.03 2CSR254101R1135 859703 0.780 1 16 DS204 A-B16/0.03 2CSR254101R1165 859802 0.780 1 20 DS204 A-B20/0.03 2CSR254101R1205 859901 0.780 1 25 DS204 A-B25/0.03 2CSR254101R1255 860006 0.780 1 32 DS204 A-B32/0.03 2CSR254101R1325 860105 0.780 1 40 DS204 A-B40/0.03 2CSR254101R1405 860204 0.780 1 50 /L54706 DS204 A-B50/0.03 2CSR254101R1505 860303 0.825 1 63 /L54706 DS204 A-B63/0.03 2CSR254101R1635 860402 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® C Selection tables RCBOs DS 200 series 6000 - A y type DS 200 A C DS 200 A type, C characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 and IEC/EN 60947-2 Icn=6 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 A 30 40 DS202 A-C40/0.03 2CSR252101R1404 861201 0.440 1 50 /L54706 DS202 A-C50/0.03 2CSR252101R1504 861300 0.440 1 63 /L54706 DS202 A-C63/0.03 2CSR252101R1634 861409 0.440 1 3 A 30 6 DS203 A-C6/0.03 2CSR253101R1064 861508 0.610 1 10 DS203 A-C10/0.03 2CSR253101R1104 861607 0.610 1 13 DS203 A-C13/0.03 2CSR253101R1134 861706 0.610 1 16 DS203 A-C16/0.03 2CSR253101R1164 861805 0.610 1 20 DS203 A-C20/0.03 2CSR253101R1204 861904 0.610 1 25 DS203 A-C25/0.03 2CSR253101R1254 862000 0.610 1 32 DS203 A-C32/0.03 2CSR253101R1324 862109 0.610 1 40 DS203 A-C40/0.03 2CSR253101R1404 862208 0.610 1 50 /L54706 DS203 A-C50/0.03 2CSR253101R1504 862307 0.650 1 63 /L54706 DS203 A-C63/0.03 2CSR253101R1634 862406 0.650 1 4 A 30 6 DS204 A-C6/0.03 2CSR254101R1064 862505 0.780 1 10 DS204 A-C10/0.03 2CSR254101R1104 862604 0.780 1 13 DS204 A-C13/0.03 2CSR254101R1134 862703 0.780 1 16 DS204 A-C16/0.03 2CSR254101R1164 862802 0.780 1 20 DS204 A-C20/0.03 2CSR254101R1204 862901 0.780 1 25 DS204 A-C25/0.03 2CSR254101R1254 863007 0.780 1 32 DS204 A-C32/0.03 2CSR254101R1324 863106 0.780 1 40 DS204 A-C40/0.03 2CSR254101R1404 863205 0.780 1 50 /L54706 DS204 A-C50/0.03 2CSR254101R1504 863304 0.825 1 63 /L54706 DS204 A-C63/0.03 2CSR254101R1634 863403 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® C Selection tables RCBOs DS 200 series 6000 - A y type DS 200 A K DS 200 A type, K characteristic Function: protection and control against overloads and short-circuit in systems where motors, tran- sformers and auxiliary circuits are present. Advantages: no unwanted release in case of currents peak up to 8 x In, according to the series; thanks to the high sensibility bimetal, the K curve switches offer protection of the sensible elements from overcurrents; they also allow the best protection of cables and lines. Application: commercial, industrial. Standard: IEC/EN 60947-2 Icn=6 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 A 30 6 DS202 A-K6/0.03 2CSR252101R1067 930303 0.475 1 10 DS202 A-K10/0.03 2CSR252101R1107 900702 0.475 1 13 DS202 A-K13/0.03 2CSR252101R1137 930402 0.475 1 16 DS202 A-K16/0.03 2CSR252101R1167 930501 0.475 1 20 DS202 A-K20/0.03 2CSR252101R1207 930600 0.475 1 25 DS202 A-K25/0.03 2CSR252101R1257 930709 0.475 1 32 DS202 A-K32/0.03 2CSR252101R1327 930808 0.475 1 40 DS202 A-K40/0.03 2CSR252101R1407 930907 0.475 1 50 DS202 A-K50/0.03 2CSR252101R1507 931003 0.475 1 63 DS202 A-K63/0.03 2CSR252101R1637 931102 0.475 1 4 A 30 6 DS204 A-K6/0.03 2CSR254101R1067 931201 0.775 1 10 DS204 A-K10/0.03 2CSR254101R1107 931300 0.775 1 13 DS204 A-K13/0.03 2CSR254101R1137 931409 0.775 1 16 DS204 A-K16/0.03 2CSR254101R1167 931508 0.775 1 20 DS204 A-K20/0.03 2CSR254101R1207 931607 0.775 1 25 DS204 A-K25/0.03 2CSR254101R1257 931706 0.775 1 32 DS204 A-K32/0.03 2CSR254101R1327 931805 0.775 1 40 DS204 A-K40/0.03 2CSR254101R1407 931904 0.775 1 50 DS204 A-K50/0.03 2CSR254101R1507 932000 0.775 1 63 DS204 A-K63/0.03 2CSR254101R1637 932109 0.775 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400194F0201

pro M compact® B Selection tables RCBOs DS 200 series M 10000 - AC w type DS 200 M AC B DS 200 M AC type, B characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional pro- tection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc.

2 AC 30 6

DS202 M AC-B6/0.03 2CSR272001R1065 932208 0.440 1 10 DS202 M AC-B10/0.03 2CSR272001R1105 932307 0.440 1 13 DS202 M AC-B13/0.03 2CSR272001R1135 932406 0.440 1 16 DS202 M AC-B16/0.03 2CSR272001R1165 932505 0.440 1 20 DS202 M AC-B20/0.03 2CSR272001R1205 932604 0.440 1 25 DS202 M AC-B25/0.03 2CSR272001R1255 932703 0.440 1 32 DS202 M AC-B32/0.03 2CSR272001R1325 932802 0.440 1 40 DS202 M AC-B40/0.03 2CSR272001R1405 932901 0.440 1 50 /L54706 DS202 M AC-B50/0.03 2CSR272001R1505 933007 0.440 1 63 /L54706 DS202 M AC-B63/0.03 2CSR272001R1635 933106 0.440 1

3 AC 30 6

DS203 M AC-B6/0.03 2CSR273001R1065 933205 0.610 1 10 DS203 M AC-B10/0.03 2CSR273001R1105 933304 0.610 1 13 DS203 M AC-B13/0.03 2CSR273001R1135 933403 0.610 1 16 DS203 M AC-B16/0.03 2CSR273001R1165 933502 0.610 1 20 DS203 M AC-B20/0.03 2CSR273001R1205 933601 0.610 1 25 DS203 M AC-B25/0.03 2CSR273001R1255 933700 0.610 1 32 DS203 M AC-B32/0.03 2CSR273001R1325 933809 0.610 1 40 DS203 M AC-B40/0.03 2CSR273001R1405 933908 0.610 1 50 /L54706 DS203 M AC-B50/0.03 2CSR273001R1505 934004 0.650 1 63 /L54706 DS203 M AC-B63/0.03 2CSR273001R1635 934103 0.650 1

4 AC 30 6

DS204 M AC-B6/0.03 2CSR274001R1065 934202 0.780 1 10 DS204 M AC-B10/0.03 2CSR274001R1105 934301 0.780 1 13 DS204 M AC-B13/0.03 2CSR274001R1135 934400 0.780 1 16 DS204 M AC-B16/0.03 2CSR274001R1165 934509 0.780 1 20 DS204 M AC-B20/0.03 2CSR274001R1205 934608 0.780 1 25 DS204 M AC-B25/0.03 2CSR274001R1255 934707 0.780 1 32 DS204 M AC-B32/0.03 2CSR274001R1325 934806 0.780 1 40 DS204 M AC-B40/0.03 2CSR274001R1405 934905 0.780 1 50 /L54706 DS204 M AC-B50/0.03 2CSR274001R1505 935001 0.825 1 63 /L54706 DS204 M AC-B63/0.03 2CSR274001R1635 935100 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® C Selection tables RCBOs DS 200 series M 10000 - AC w type DS 200 M AC C DS 200 M AC type, C characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional pro- tection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. DS202 M AC-C6/0.03 2CSR272001R1064 851509 0.440 1 10 DS202 M AC-C10/0.03 2CSR272001R1104 851608 0.440 1 13 DS202 M AC-C13/0.03 2CSR272001R1134 851707 0.440 1 16 DS202 M AC-C16/0.03 2CSR272001R1164 851806 0.440 1 20 DS202 M AC-C20/0.03 2CSR272001R1204 851905 0.440 1 25 DS202 M AC-C25/0.03 2CSR272001R1254 852001 0.440 1 32 DS202 M AC-C32/0.03 2CSR272001R1324 852100 0.440 1 40 DS202 M AC-C40/0.03 2CSR272001R1404 852209 0.440 1 50 /L54706 DS202 M AC-C50/0.03 2CSR272001R1504 852308 0.440 1 63 /L54706 DS202 M AC-C63/0.03 2CSR272001R1634 852407 0.440 1 DS203 M AC-C6/0.03 2CSR273001R1064 852506 0.610 1 10 DS203 M AC-C10/0.03 2CSR273001R1104 852605 0.610 1 13 DS203 M AC-C13/0.03 2CSR273001R1134 852704 0.610 1 16 DS203 M AC-C16/0.03 2CSR273001R1164 852803 0.610 1 20 DS203 M AC-C20/0.03 2CSR273001R1204 852902 0.610 1 25 DS203 M AC-C25/0.03 2CSR273001R1254 853008 0.610 1 32 DS203 M AC-C32/0.03 2CSR273001R1324 853107 0.610 1 40 DS203 M AC-C40/0.03 2CSR273001R1404 853206 0.610 1 50 /L54706 DS203 M AC-C50/0.03 2CSR273001R1504 853305 0.650 1 63 /L54706 DS203 M AC-C63/0.03 2CSR273001R1634 853404 0.650 1 DS204 M AC-C6/0.03 2CSR274001R1064 853503 0.780 1 10 DS204 M AC-C10/0.03 2CSR274001R1104 853602 0.780 1 13 DS204 M AC-C13/0.03 2CSR274001R1134 853701 0.780 1 16 DS204 M AC-C16/0.03 2CSR274001R1164 853800 0.780 1 20 DS204 M AC-C20/0.03 2CSR274001R1204 853909 0.780 1 25 DS204 M AC-C25/0.03 2CSR274001R1254 854005 0.780 1 32 DS204 M AC-C32/0.03 2CSR274001R1324 854104 0.780 1 40 DS204 M AC-C40/0.03 2CSR274001R1404 854203 0.780 1 50 /L54706 DS204 M AC-C50/0.03 2CSR274001R1504 854302 0.825 1 63 /L54706 DS204 M AC-C63/0.03 2CSR274001R1634 854401 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® B Selection tables RCBOs DS 200 series M 10000 - A y type DS 200 M A B DS 200 M A type, B characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc.

2 A 30 40

DS202 M A-B40/0.03 2CSR272101R1405 846208 0.440 1 50 /L54706 DS202 M A-B50/0.03 2CSR272101R1505 846307 0.440 1 63 /L54706 DS202 M A-B63/0.03 2CSR272101R1635 846406 0.440 1

3 A 30 6

DS203 M A-B6/0.03 2CSR273101R1065 846505 0.610 1 10 DS203 M A-B10/0.03 2CSR273101R1105 846604 0.610 1 13 DS203 M A-B13/0.03 2CSR273101R1135 846703 0.610 1 16 DS203 M A-B16/0.03 2CSR273101R1165 846802 0.610 1 20 DS203 M A-B20/0.03 2CSR273101R1205 846901 0.610 1 25 DS203 M A-B25/0.03 2CSR273101R1255 847007 0.610 1 32 DS203 M A-B32/0.03 2CSR273101R1325 847106 0.610 1 40 DS203 M A-B40/0.03 2CSR273101R1405 847205 0.610 1 50 /L54706 DS203 M A-B50/0.03 2CSR273101R1505 847304 0.650 1 63 /L54706 DS203 M A-B63/0.03 2CSR273101R1635 847403 0.650 1

4 A 30 6

DS204 M A-B6/0.03 2CSR274101R1065 847502 0.780 1 10 DS204 M A-B10/0.03 2CSR274101R1105 847601 0.780 1 13 DS204 M A-B13/0.03 2CSR274101R1135 847700 0.780 1 16 DS204 M A-B16/0.03 2CSR274101R1165 847809 0.780 1 20 DS204 M A-B20/0.03 2CSR274101R1205 847908 0.780 1 25 DS204 M A-B25/0.03 2CSR274101R1255 848004 0.780 1 32 DS204 M A-B32/0.03 2CSR274101R1325 848103 0.780 1 40 DS204 M A-B40/0.03 2CSR274101R1405 848202 0.780 1 50 /L54706 DS204 M A-B50/0.03 2CSR274101R1505 848301 0.825 1 63 /L54706 DS204 M A-B63/0.03 2CSR274101R1635 848400 0.825 1 /L54706 provided with additional terminals for remote tripping 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400191F02012CSC400193F02012CSC400194F0201

pro M compact® C Selection tables RCBOs DS 200 series M 10000 - A y type DS 200 M A C DS 200 M A type, C characteristic Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts. Application: commercial, industrial. Standard: IEC/EN 61009 Icn=10 kA Number Type/ Rated Rated Order Bbn Price Price Weight Pack of poles class residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. DS202 M A-C40/0.03 2CSR272101R1404 849209 0.440 1 50 /L54706 DS202 M A-C50/0.03 2CSR272101R1504 849308 0.440 1 63 /L54706 DS202 M A-C63/0.03 2CSR272101R1634 849407 0.440 1 DS203 M A-C6/0.03 2CSR273101R1064 849506 0.610 1 10 DS203 M A-C10/0.03 2CSR273101R1104 849605 0.610 1 13 DS203 M A-C13/0.03 2CSR273101R1134 849704 0.610 1 16 DS203 M A-C16/0.03 2CSR273101R1164 849803 0.610 1 20 DS203 M A-C20/0.03 2CSR273101R1204 849902 0.610 1 25 DS203 M A-C25/0.03 2CSR273101R1254 850007 0.610 1 32 DS203 M A-C32/0.03 2CSR273101R1324 850106 0.610 1 40 DS203 M A-C40/0.03 2CSR273101R1404 850205 0.610 1 50 /L54706 DS203 M A-C50/0.03 2CSR273101R1504 850304 0.650 1 63 /L54706 DS203 M A-C63/0.03 2CSR273101R1634 850403 0.650 1 1/2 3/4 1/2 3/4 1/2 3/4 5/6 1/2 3/4 2/1 4/3 In=50-63 A Y1 Y2 2CSC400191F02012CSC400193F0201

In=50-63 A Y1 Y2 1/2 3/4 5/6 7/8 In up to 40 A 2CSC400194F0201 4 A 30 6 DS204 M A-C6/0.03 2CSR274101R1064 850502 0.780 1 10 DS204 M A-C10/0.03 2CSR274101R1104 850601 0.780 1 13 DS204 M A-C13/0.03 2CSR274101R1134 850700 0.780 1 16 DS204 M A-C16/0.03 2CSR274101R1164 850809 0.780 1 20 DS204 M A-C20/0.03 2CSR274101R1204 850908 0.780 1 25 DS204 M A-C25/0.03 2CSR274101R1254 851004 0.780 1 32 DS204 M A-C32/0.03 2CSR274101R1324 851103 0.780 1 40 DS204 M A-C40/0.03 2CSR274101R1404 851202 0.780 1 50 /L54706 DS204 M A-C50/0.03 2CSR274101R1504 851301 0.825 1 63 /L54706 DS204 M A-C63/0.03 2CSR274101R1634 851400 0.825 1 /L54706 provided with additional terminals for remote tripping System pro M compact® Selection tables RCBOs DS 200 series M 10000 - A y type DS 200 M A C

The range of DDA 60, 70 and selective 90 RCD blocks for the S 290 series includes 100A devices suitable for assembly with MCBs in the S 290 series of type C only. The DDA 800 RCD blocks for protecting people and electrical installations are useful when a higher breaking capacity is required. Assembling a DDA

800 RCD block with an S 800 N

RCBO with a breaking capacity of 36 kA and 50 kA respectively. The RCD-blocks must be mounted on the right side of the MCB, so that the available accessories can be mounted on the left side. DDA 800 RCD blocks are available in AC and A, A AP-R (high immunity) and A selective types. DS 800 RCBOs are available, only in the size of 125 A, in A, AP-R (high immunity) and A selective types. In compliance with IEC EN 61009, which establishes that the RCD blocks can be assembled with an MCB only once, the S 290 series DDA blocks have a mechanical pin which prevents disassembly once inserted. In contrast, RCD blocks for the S 800 series which conform to IEC EN 60947-2 app. B do not have unlosable coupling elements. DDA RCD blocks for the S 290 and S 800 series are not sensitive to impulsive atmospheric and operational discharges, therefore, they are not subject to unwanted tripping in accordance with IEC EN 61008, and IEC EN 61009, even with 8/20 μs wave up to 250 A. 2CSC400170F02012CSC400274F0201 2CSC400273F0201

DDA for S 290 and S800 series, RCBOs DS800 and 1P+N RCBOs DS271, RD2, RD3, RD residual current relays and TR toroidal transformers Index Selection tables of RCDs-blocks for MCBs S 290 series Selection tables of RCD-blocks for MCBs S800 series Selection tables of DS800 RCBOs series Selection tables of 1P+N RCBOs DS271 series Selection tables of residual current relays RD2, RD3, RD and toroidal transformers TR

Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage UN V Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Rated breaking capacity (Icn) acc. to IEC /EN 61009 A Rated breaking capacity (Icn) acc. to IEC/EN 60947-2 A Rated residual breaking capacity IΔm kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Surge current resistance (wave 8/20) A Mechanical Toggle features Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC /EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Installation Terminal size for cables mm Tightening torque N*m Mounting Dimensions Dimensions (H x D x W) 2P mm and weight 3P/4P mm Weight 2P g 3P/4P g Combination with auxiliary elements Combinable with: S 290 C characteristic S 290 D and K characteristics Technical features RCD-blocks for MCBs S 290 series DDA 60 DDA 70 DDA 90 System pro M compact

RCD-blocks for MCBs S 290 series DDA 60 DDA 70 DDA 90 DDA 60 DDA 70 DDA 90 IEC/EN 61009 Ann. G AC A A - A selective 2P , 4P 100 500 240(2P), 415(4P) 100(2P), 175(4P) 50…60 according to the breaking capacity of the associated MCB according to the breaking capacity of the associated MCB 7.5 2.5 250 1000 3000 black operating from ON-OFF position 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+45 -40…+60 3.5 on DIN rail EN 60715 (35 mm) by means of rapid fixing device 94 x 68 x 61 94 x 68 x 90 325 600 yes no System pro M compact®

DDA 60 AC type for MCBs S 290 Function: RCD-block for assembly on site with MCBs S 290 series only in C characteristic. Protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Additional terminals for remote tripping are available. Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 4016779 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 0.03 100 DDA62 100 30MA 36229002 183307 0.325 1 0.3 100 DDA62 100 300MA 36229010 183505 0.325 1 4 0.03 100 DDA 64 100 30MA 36229044 183901 0.600 1 0.3 100 DDA 64 100 300MA 36229051 184106 0.600 1 Y1 Y2 2 4/N 4/3(N) Y1 Y2 2 4 6 8/N 8/7(N) System pro M compact®2CSC400167F02012CSC400169F0201

DDA 70 A type for MCBs S 290 Function: RCD-block for assembly on site with MCBs S 290 series only in C characteristic. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Additional terminals for remote tripping are available. Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 4016779 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 0.03 100 DDA 72 100 30MA 36229069 184304 0.325 1 0.3 100 DDA 72 100 300MA 36229077 184403 0.325 1 4 0.03 100 DDA 74 100 30MA 36229101 184700 0.600 1 0.3 100 DDA 74 100 300MA 36229119 184809 0.600 1 DDA 90 A selective type for MCBs S 290 Function: RCD-block for assembly on site with MCBs S 290 series (only in C characteristic). Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents with an intentional tripping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide). Additional terminals for remote tripping are available. Application: commercial, industrial. Standard: IEC/EN 61009 Ann. G 2 0.3 100 DDA 92 100 300MA S 36229127 185103 0.325 1 1 100 DDA 92 100 1A S 36229135 185509 0.325 1 4 0.3 100 DDA 94 100 300MA S 36229168 185905 0.600 1 1 100 DDA 94 100 1A S 36229176 186001 0.600 1 A Selection tables RCD-blocks DDA 70 and DDA 90 for MCBs S 290 series DDA 70 DDA 90 Y1 Y2 2 4/N 4/3(N) Y1 Y2 2 4 6 8/N 8/7(N) Y1 Y2 2 4/N 4/3(N) Y1 Y2 2 4 6 8/N 8/7(N) System pro M compact®2CSC400169F0201 2CSC400167F02012CSC400169F02012CSC400167F0201

RCD-blocks for MCBs S800 series DDA 800 TECHNICAL FEATURES Standards Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage Ue V Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Rated breaking capacity (Icn) acc. to IEC /EN 60947-2 A Rated residual breaking capacity IΔm with S 800 N kA with S 800 S kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Surge current resistance (wave 8/20) A Mechanical Toggle features Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC /EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Terminal size for cables flexible mm rigid mm 2 Tightening torque N*m Mounting Dimensions Dimensions (H x D x W) 2P mm and weight 3P mm 4P mm Weight 2P g 3P g 4P g Combination Combinable with: S 800 N with MCBs S 800 S System pro M compact®

RCDs-blocks for MCBs S800 series DDA 800System pro M compact® DDA 800 AC DDA 800 A DDA 800 A AP-R DDA 800 A S IEC/EN 60947-2 Ann. B A C AAA 2P , 3P , 4P 63 63 100 63-100 63 100 230/400 - 240/415 - 400/690 690 690 195 50...60 according to the breaking capacity of the associated MCB according to the Icu of the associated MCB according to the Icu of the associated MCB 2.5 250 3000 5000 blue operating just from OFF position 10000 20000 IP4X IP2X 28 cycles with 55/95...100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25...+60 -40...+70 6...50 6...70 min. 3 / max. 4 on DIN rail EN 60715 (35 mm) by means of rapid fixing device 108.2 x 82.3 x 81 108.2 x 82.3 x 117 108.2 x 82.3 x 117 300 for 63 A - 415 for 100 A 400 for 63 A - 640 for 100 A 460 for 63 A - 765 for 100 A yes yes * only on 3P and 4P versions

DDA 800 AC type for MCBs S800 Function: RCD-block for assembly on site with MCBs S800 series up to 63 A. Protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: commercial, industrial. Standard: IEC/EN 60947-2 Ann. B Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 DDA802AC-63/0.03 2CSB802001R1630 919704 0.300 1 300 63 DDA802AC-63/0.3 2CSB802001R3630 919902 0.300 1 3 30 63 DDA803AC-63/0.03 2CSB803001R1630 922001 0.400 1 300 63 DDA803AC-63/0.3 2CSB803001R3630 922209 0.400 1 4 30 63 DDA804AC-63/0.03 2CSB804001R1630 924401 0.460 1 300 63 DDA804AC-63/0.3 2CSB804001R3630 924609 0.460 1 4/32/1 6/54/3 642 8/76/5 8642 System pro M compact® 2CSC400177F02012CSC400178F02012CSC400179F0201

A Selection tables RCD-blocks DDA 800 A y type DDA 800 A DDA 800 A type for MCBs S800 Function: RCD-block for assembly on site with MCBs S800 up to 100 A. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: commercial, industrial. Standard: IEC/EN 60947-2 Ann. B Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 DDA802 A-63/0.03 2CSB802101R1630 920007 0.300 1 300 63 DDA802 A-63/0.3 2CSB802101R3630 920205 0.300 1 100 DDA802 A-100/0.3 2CSB802101R3000 545033 0.415 1 500 63 DDA802 A-63/0.5 2CSB802101R4630 920403 0.300 1 100 DDA802 A-100/0.5 2CSB802101R4000 542636 0.415 1 3 30 63 DDA803 A-63/0.03 2CSB803101R1630 922308 0.400 1 300 63 DDA803 A-63/0.3 2CSB803101R3630 922506 0.400 1 100 DDA803 A-100/0.3 2CSB803101R3000 544135 0.640 1 500 63 DDA803 A-63/0.5 2CSB803101R4630 922704 0.400 1 100 DDA803 A-100/0.5 2CSB803101R4000 541738 0.640 1 4 30 63 DDA804 A-63/0.03 2CSB804101R1630 924807 0.460 1 300 63 DDA804 A-63/0.3 2CSB804101R3630 925002 0.460 1 100 DDA804 A-100/0.3 2CSB804101R3000 547532 0.765 1 500 63 DDA804 A-63/0.5 2CSB804101R4630 925200 0.460 1 100 DDA804 A-100/0.5 2CSB804101R4000 544937 0.765 1 4/32/1 6/54/3 642 8/76/5 8642 System pro M compact® 2CSC400177F02012CSC400178F02012CSC400179F0201

A Selection tables RCD-blocks DDA 800 A y type AP-R (high immunity) DDA 800 A AP-R DDA 800 A AP-R type for MCBs S800 Function: RCD-block for assembly on site with MCBs S800 up to 100 A. Protection against the ef- fects of sinusoidal alternating and direct pulsating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (with IΔn=30 mA) contacts. Application: commercial, industrial. Standard: IEC/EN 60947-2 Ann. B Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 30 63 DDA802 A-63/0.03 AP-R 2CSB802401R1630 921400 0.300 1 100 DDA802 A-100/0.03 AP-R 2CSB802401R1000 544630 0.415 1 3 30 63 DDA803 A-63/0.03 AP-R 2CSB803401R1630 923800 0.400 1 100 DDA803 A-100/0.03 AP-R 2CSB803401R1000 542230 0.640 1 4 30 63 DDA804 A-63/0.03 AP-R 2CSB804401R1630 927709 0.460 1 100 DDA804 A-100/0.03 AP-R 2CSB804401R1000 547136 0.765 1 4/32/1 6/54/3 642 8/76/5 8642 System pro M compact® 2CSC400177F02012CSC400178F02012CSC400179F0201

DDA 800 A selective type for MCBs S800 Function: RCD-block for assembly on site with MCBs S800 series up to 100 A. Protection against the effects of sinusoidal alternating and direct pulsating earth fault currents with an intentional trip- ping delay, which permits to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide). Application: commercial, industrial. Standard: IEC/EN 60947-2 Ann. B Number Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 8012542 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 300 63 DDA802 A S-63/0.3 2CSB802201R3630 920601 0.300 1 100 DDA802 A S-100/0.3 2CSB802201R3000 542537 0.415 1000 63 DDA802 A S-63/1 2CSB802201R5630 920809 0.300 1 100 DDA802 A S-100/1 2CSB802201R5000 547433 0.415 1 3 300 63 DDA803 A S-63/0.3 2CSB803201R3630 922902 0.400 1 100 DDA803 A S-100/0.3 2CSB803201R3000 544838 0.640 1 500 100 DDA803 A S-100/0.5 2CSB803201R4000 542438 0.640 1 1000 63 DDA803 A S-63/1 2CSB803201R5630 923206 0.400 1 100 DDA803 A S-100/1 2CSB803201R5000 547334 0.640 1 3 300 63 DDA804 A S-63/0.3 2CSB804201R3630 926207 0.460 1 100 DDA804 A S-100/0.3 2CSB804201R3000 544739 0.765 1 500 100 DDA804 A S-100/0.5 2CSB804201R4000 542339 0.765 1 1000 63 DDA804 A S-63/1 2CSB804201R5630 926504 0.460 1 100 DDA804 A S-100/1 2CSB804201R5000 547235 0.765 1 Selection tables RCD-blocks DDA 800 A y type selective DDA 800 A S A 4/32/1 6/54/3 642 8/76/5 8642 System pro M compact® 2CSC400177F02012CSC400178F02012CSC400179F0201

Electrical Operating characteristic: type (wave form of the earth leakage sensed) features Poles Rated sensitivity IΔn A Rated current In A Rated voltage Ue V Insulation voltage Ui V Max. operating voltage of circuit test V Min. operating voltage of circuit test V Rated frequency Hz Short-circuit breaking capacity 240/415 V kA ultimate Icu 254/440 V kA acc. to IEC/EN 60947-2 289/500 V kA (AC) 50/60 Hz 400/690 V kA Short-circuit breaking capacity 240/415 V kA service Ics 254/440 V kA acc. to IEC/EN 60947-2 289/500 V kA (AC) 50/60 Hz 400/690 V kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Thermomagnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In D: 10 In ≤ Im ≤ 20 In K: 8 In ≤ Im ≤ 14 In Surge current resistance acc. to VDE 0432 Part 2 (wave 8/20) A Mechanical Toggle features Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC /EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Ambient temperature (with daily average ≤ + 35 °C) °C Storage temperature °C Installation Terminal size for cables flexible mm2 rigid mm2 Tightening torque N*m Mounting Dimensions Dimensions (H x D x W) 2P mm and weight 3P mm 4P mm Weight 2P g 3P g 4P g Combination Combinable with: auxiliary contact with auxiliary signal contact/auxiliary switch elements shunt trip undervoltage release (*) 1A on 2P and 4P versions, while 0.3A only on 4P ones. Technical features RCBOs DS800 series DS800System pro M compact®

pro M compact® DS800S A DS800N A DS800S A S DS800N A S DS800S A AP-R DS800N A AP-R IEC/EN 60947-2 AAA 2P , 3P , 4P 2P ,4P 2P , 3P , 4P 0.3 0.3-1(*) 0.03 125 230/400-240/415-400/690 690 690 195 50…60 50 36 50 36 50 36 30 20 30 20 30 20 10 10 10 10 10 10 40 30 40 30 40 30 15 10 15 10 15 10 555555 333333 2.5 QQQQQQ Q QQQQQ QQQQQQ QQQ 250 250 5000 5000 3000 3000 black (MCB) sealable in ON-OFF position + blue (RCD) operating just from OFF position 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+60 -40…+70 6…50 6…70 min. 3 / max. 4 on DIN rail EN 60715 (35 mm) by means of rapid fi xing device 108,2 x 82,3 x 133.5 108,2 x 82,3 x 196 108,2 x 82,3 x 223 790 1140 1440 yes yes yes yes

2CCC413257F00012CCC413258F00012CCC413259F0001 Selection tables RCBOs DS800 series A y type DS800S A DS800S, A type Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts; command and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 300 125 DS802S-B125/0.3A 2CCA862005R0845 211721 0.790 1 C 300 125 DS802S-C125/0.3A 2CCA862005R0844 211738 0.790 1 D 300 125 DS802S-D125/0.3A 2CCA862005R0841 211745 0.790 1 K 300 125 DS802S-K125/0.3A 2CCA862005R0647 211752 0.790 1 3 B 300 125 DS803S-B125/0.3A 2CCA863005R0845 211769 1.14 1 C 300 125 DS803S-C125/0.3A 2CCA863005R0844 211776 1.14 1 D 300 125 DS803S-D125/0.3A 2CCA863005R0841 211783 1.14 1 K 300 125 DS803S-K125/0.3A 2CCA863005R0647 211790 1.14 1 4 B 300 125 DS804S-B125/0.3A 2CCA864005R0845 211806 1.44 1 C 300 125 DS804S-C125/0.3A 2CCA864005R0844 211813 1.44 1 D 300 125 DS804S-D125/0.3A 2CCA864005R0841 211820 1.44 1 K 300 125 DS804S-K125/0.3A 2CCA864005R0647 211837 1.44 1 System pro M compact® 5/63/4 6/54/3 3/41/2 4/32/1 7/85/6 8/76/5

DS800N, A type Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents; protection against indirect contacts; command and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=36 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 300 125 DS802N-B125/0.3A 2CCA892005R0845 211844 0.790 1 C 300 125 DS802N-C125/0.3A 2CCA892005R0844 211851 0.790 1 D 300 125 DS802N-D125/0.3A 2CCA892005R0841 211868 0.790 1 3 B 300 125 DS803N-B125/0.3A 2CCA893005R0845 211875 1.14 1 C 300 125 DS803N-C125/0.3A 2CCA893005R0844 211882 1.14 1 D 300 125 DS803N-D125/0.3A 2CCA893005R0841 211899 1.14 1 4 B 300 125 DS804N-B125/0.3A 2CCA894005R0845 211905 1.44 1 C 300 125 DS804N-C125/0.3A 2CCA894005R0844 211912 1.44 1 D 300 125 DS804N-D125/0.3A 2CCA894005R0841 211929 1.44 1 Selection tables RCBOs DS800 series A y type DS800N A System pro M compact® 2CCC413257F00012CCC413258F00012CCC413259F0001 7/85/6 8/76/5 5/63/4 6/54/3 3/41/2 4/32/1

A y type, selective DS800S A S DS800S, A selective type Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents with an intentional tripping delay, which allows to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide); protection against indirect contacts; command and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 1000 125 DS802S-B125/1AS 2CCC862006R0845 211516 0.790 1 C 1000 125 DS802S-C125/1AS 2CCC862006R0844 211523 0.790 1 D 1000 125 DS802S-D125/1AS 2CCC862006R0841 211530 0.790 1 K 1000 125 DS802S-K125/1AS 2CCC862006R0647 211547 0.790 1 4 B 300 125 DS804S-B125/0.3AS 2CCC864005R0845 211554 1.44 1 1000 125 DS804S-B125/1AS 2CCC864006R0845 211592 1.44 1 C 300 125 DS804S-C125/0.3AS 2CCC864005R0844 211561 1.44 1 1000 125 DS804S-C125/1AS 2CCC864006R0844 211608 1.44 1 D 300 125 DS804S-D125/0.3AS 2CCC864005R0841 211578 1.44 1 1000 125 DS804S-D125/1AS 2CCC864006R0841 211615 1.44 1 K 300 125 DS804S-K125/0.3AS 2CCC864005R0647 211685 1.44 1 1000 125 DS804S-K125/1AS 2CCC864006R0647 211622 1:44 1 System pro M compact® 2CCC413257F00012CCC413259F0001 3/41/2 4/32/1 7/85/6 8/76/5

DS800N, A selective type Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating earth fault currents with an intentional tripping delay, which allows to realize the selectivity with downstream instantaneous devices (for more information about selectivity see the technical guide); protection against indirect contacts; command and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=36 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 1000 125 DS802N-B125/1AS 2CCC892006R0845 211639 0.790 1 C 1000 125 DS802N-C125/1AS 2CCC892006R0844 211646 0.790 1 D 1000 125 DS802N-D125/1AS 2CCC892006R0841 211653 0.790 1 4 B 300 125 DS804N-B125/0.3AS 2CCC894005R0845 211660 1.44 1 1000 125 DS804N-B125/1AS 2CCC894006R0845 211691 1.44 1 C 300 125 DS804N-C125/0.3AS 2CCC894005R0844 211677 1.44 1 1000 125 DS804N-C125/1AS 2CCC894006R0844 211707 1.44 1 D 300 125 DS804N-D125/0.3AS 2CCC894005R0841 211684 1.44 1 1000 125 DS804N-D125/1AS 2CCC894006R0841 211714 1.44 1 Selection tables RCBOs DS800 series A y type DS800N A S System pro M compact® 2CCC413257F00012CCC413259F0001 7/85/6 8/76/5 3/41/2 4/32/1

A y type, AP-R (high immunity) DS800S A AP-R DS800S AP-R, A type Function: protection against the effects of sinusoidal alternating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (I Δn=30 mA) contacts; protection and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=50 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 30 125 DS802SB125/.03AP-R 2CCB862004R0845 211301 0.790 1 C 30 125 DS802SC125/.03AP-R 2CCB862004R0844 211318 0.790 1 D 30 125 DS802SD125/.03AP-R 2CCB862004R0841 211325 0.790 1 K 30 125 DS802SK125/.03AP-R 2CCB862004R0647 211332 0.790 1 3 B 30 125 DS803SB125/.03AP-R 2CCB863004R0845 211349 1.14 1 C 30 125 DS803SC125/.03AP-R 2CCB863004R0844 211356 1.14 1 D 30 125 DS803SD125/.03AP-R 2CCB863004R0841 211363 1.14 1 K 30 125 DS803SK125/.03AP-R 2CCB863004R0647 211370 1.14 1 4 B 30 125 DS804SB125/.03AP-R 2CCB864004R0845 211387 1.44 1 C 30 125 DS804SC125/.03AP-R 2CCB864004R0844 211394 1.44 1 D 30 125 DS804SD125/.03AP-R 2CCB864004R0841 211400 1.44 1 K 30 125 DS804SK125/.03AP-R 2CCB864004R0647 211417 1,44 1 System pro M compact® 2CCC413257F00012CCC413258F00012CCC413259F0001 5/63/4 6/54/3 3/41/2 4/32/1 7/85/6 8/76/5

DS800N AP-R, A type Function: protection against the effects of sinusoidal alternating earth fault currents, providing the best compromise between safety and continuity in the service thanks to the resistance to unwanted trippings; protection against indirect contacts and additional protection against direct (I Δn=30 mA) contacts; protection and isolation of resistive and inductive loads. Application: industrial. Standard: IEC/EN 60947-2 Icu=36 kA Number Curve Rated Rated Order Bbn Price Price Weight Pack of poles residual current details 7612271 1 piece group 1 piece unit current I Δn mA In A Type code Order code EAN kg pc. 2 B 30 125 DS802NB125/.03AP-R 2CCB892004R0845 211424 0.790 1 C 30 125 DS802NC125/.03AP-R 2CCB892004R0844 211431 0.790 1 D 30 125 DS802ND125/.03AP-R 2CCB892004R0841 211448 0.790 1 3 B 30 125 DS803NB125/.03AP-R 2CCB893004R0845 211455 1.14 1 C 30 125 DS803NC125/.03AP-R 2CCB893004R0844 211462 1.14 1 D 30 125 DS803ND125/.03AP-R 2CCB893004R0841 211479 1.14 1 4 B 30 125 DS804NB125/.03AP-R 2CCB894004R0845 211486 1.44 1 C 30 125 DS804NC125/.03AP-R 2CCB894004R0844 211493 1.44 1 D 30 125 DS804ND125/.03AP-R 2CCB894004R0841 211509 1.44 1 Selection tables RCBOs DS800 series A y type, AP-R (high immunity) DS800N A AP-R System pro M compact® 2CCC413257F00012CCC413258F00012CCC413259F0001 7/85/6 8/76/5 5/63/4 6/54/3 3/41/2 4/32/1

Electrical Type (wave form of the earth leakage sensed) features Poles Rated current In A Rated sensitivity IΔn A Rated voltage Ue V Insulation voltage Ui Max. operating voltage V Min. operating voltage V Rated frequency Hz Rated breaking capacity acc. to IEC/EN 61009 ultimate Icn A Rated breaking capacity ultimate Icu kA acc. to IEC/EN 60947-2 1P+N @230 VAC, 2P , 3P , 4P @400 VAC service Ics kA Rated residual breaking capacity IΔm kA Rated impulse withstand voltage (1.2/50) Uimp kV Dielectric test voltage at ind. freq. for 1 min. kV Thermomagnetic release B: 3 In ≤ Im ≤ 5 In characteristic C: 5 In ≤ Im ≤ 10 In Surge current resistance (wave 8/20) A Mechanical Toggle features Electrical life Mechanical life Protection degree housing terminals Tropicalization humid heat °C/RH acc. to IEC /EN 60068-2 constant climatic conditions °C/RH variable climatic conditions °C/RH Reference temperature for setting of thermal element °C Ambient temperature (with daily average ≤ +35 °C) °C Storage temperature °C Installation Terminal type top bottom Terminal size top/bottom for cables 1P+N mm line side mm 2 load side mm 2 Tightening torque top/bottom 1P+N N*m Mounting Dimensions Dimensions (H x D x W) 1P+N mm and weight Weight 1P+N g Combination Combinable with: auxiliary contact with auxiliary signal contact elements shunt trip undervoltage release Technical features RCBOs DS 271 series DS 271System pro M compact®

IEC 61009, BSEN 61009-2-2 AC A 1P+N 6 ≤ In ≤ 40 230-240 500 254 50…60 10000 7.5 2.5 Q Q 250 black sealable in on-off position 10000 20000 IP4X IP2X 28 cycles with 55/95…100 23/83 - 40/93 - 55/20 25/95 - 40/95 -25…+55 -25…+70 cage (shock protected) cage (shock protected) L1: 1up to 25; N: flexible 4; FE: flexible 0.5 L1 and N: 1 up to 10 2 top; 1.2 bottom on DIN rail EN 60715 (35 mm) by means of fast clip device 120 x 67.6 x 17.5 205 no no no no System pro M compact®

DS 271 AC type, B and C characteristics Function: protection against overload and short-circuit currents; protection against the effects of si- nusoidal alternating earth fault currents; protection against indirect contacts and additional protection against direct contacts (IΔn=30 mA). Application: residential, commercial, industrial. Standard: IEC 61009, BSEN61009-2-2 Icn=10 kA Character Rated Rated Order Bbn Price Price Weight Pack istics/ residual current details 8012542 1 piece group 1 piece unit Curve current I Δn mA In A Type code Order code EAN kg pc. B 10 6 DS271 AC-B6/0.01 ELN 2CSR175092R0065 036753 0.205 1 10 DS271 AC-B10/0.01 ELN 2CSR175092R0105 036852 0.205 1 16 DS271 AC-B16/0.01 ELN 2CSR175092R0165 036951 0.205 1 20 DS271 AC-B20/0.01 ELN 2CSR175092R0205 037057 0.205 1 25 DS271 AC-B25/0.01 ELN 2CSR175092R0255 037156 0.205 1 32 DS271 AC-B32/0.01 ELN 2CSR175092R0325 037255 0.205 1 30 6 DS271 AC-B6/0.03 ELN 2CSR175092R1065 037354 0.205 1 10 DS271 AC-B10/0.03 ELN 2CSR175092R1105 037453 0.205 1 16 DS271 AC-B16/0.03 ELN 2CSR175092R1165 037552 0.205 1 20 DS271 AC-B20/0.03 ELN 2CSR175092R1205 037651 0.205 1 25 DS271 AC-B25/0.03 ELN 2CSR175092R1255 037750 0.205 1 32 DS271 AC-B32/0.03 ELN 2CSR175092R1325 037859 0.205 1/20 C 10 6 DS271 AC-C6/0.01 ELN 2CSR175092R0064 038559 0.205 1 10 DS271 AC-C10/0.01 ELN 2CSR175092R0104 038658 0.205 1 16 DS271 AC-C16/0.01 ELN 2CSR175092R0164 038757 0.205 1/20 20 DS271 AC-C20/0.01 ELN 2CSR175092R0204 038856 0.205 1 25 DS271 AC-C25/0.01 ELN 2CSR175092R0254 038955 0.205 1 32 DS271 AC-C32/0.01 ELN 2CSR175092R0324 039051 0.205 1/20 30 6 DS271 AC-C6/0.03 ELN 2CSR175092R1064 039150 0.205 1 10 DS271 AC-C10/0.03 ELN 2CSR175092R1104 039259 0.205 1 16 DS271 AC-C16/0.03 ELN 2CSR175092R1164 039358 0.205 1 20 DS271 AC-C20/0.03 ELN 2CSR175092R1204 039457 0.205 1 25 DS271 AC-C25/0.03 ELN 2CSR175092R1254 039556 0.205 1 32 DS271 AC-C32/0.03 ELN 2CSR175092R1324 039655 0.205 1 40 DS271 AC-C40/0.03 ELN 2CSR175092R1404 128755 0.205 1 100 6 DS271 AC-C6/0.1 ELN 2CSR175092R2064 039754 0.205 1 10 DS271 AC-C10/0.1 ELN 2CSR175092R2104 039853 0.205 1/20 16 DS271 AC-C16/0.1 ELN 2CSR175092R2164 039952 0.205 1/20 20 DS271 AC-C20/0.1 ELN 2CSR175092R2204 040057 0.205 1/20 25 DS271 AC-C25/0.1 ELN 2CSR175092R2254 040156 0.205 1 32 DS271 AC-C32/0.1 ELN 2CSR175092R2324 040255 0.205 1 300 6 DS271 AC-C6/0.3 ELN 2CSR175092R3064 040354 0.205 1 10 DS271 AC-C10/0.3 ELN 2CSR175092R3104 040453 0.205 1 16 DS271 AC-C16/0.3 ELN 2CSR175092R3164 040552 0.205 1 20 DS271 AC-C20/0.3 ELN 2CSR175092R3204 040651 0.205 1 25 DS271 AC-C25/0.3 ELN 2CSR175092R3254 040750 0.205 1 32 DS271 AC-C32/0.3 ELN 2CSR175092R3324 040859 0.205 1 40 DS271 AC-C40/0.3 ELN 2CSR175092R3404 128854 0.205 1 B Selection tables RCBOs DS 271 series

10000 AC w type

C 2CSC400407F02012CSC400407F0201 System pro M compact®

DS 271 A type, B and C characteristics Function: protection against overload and short-circuit currents; protection against the effects of sinusoidal alternating and direct pulsating earth fault currents; protection against indirect contacts and additional protection against direct contacts (IΔn=30 mA). Application: commercial, industrial. Standard: IEC 61009, BSEN61009-2-2 Icn=10 kA Character Rated Rated Order Bbn Price Price Weight Pack istics/ residual current details 8012542 1 piece group 1 piece unit Curve current I Δn mA In A Type code Order code EAN kg pc. B 10 6 DS271 A-B6/0.01 ELN 2CSR175192R0065 032557 0.205 1 10 DS271 A-B10/0.01 ELN 2CSR175192R0105 032656 0.205 1 16 DS271 A-B16/0.01 ELN 2CSR175192R0165 032755 0.205 1 20 DS271 A-B20/0.01 ELN 2CSR175192R0205 032854 0.205 1 25 DS271 A-B25/0.01 ELN 2CSR175192R0255 032953 0.205 1 32 DS271 A-B32/0.01 ELN 2CSR175192R0325 033059 0.205 1 30 6 DS271 A-B6/0.03 ELN 2CSR175192R1065 033158 0.205 1 10 DS271 A-B10/0.03 ELN 2CSR175192R1105 033257 0.205 1 16 DS271 A-B16/0.03 ELN 2CSR175192R1165 033356 0.205 1 20 DS271 A-B20/0.03 ELN 2CSR175192R1205 033455 0.205 1 25 DS271 A-B25/0.03 ELN 2CSR175192R1255 033554 0.205 1 32 DS271 A-B32/0.03 ELN 2CSR175192R1325 033653 0.205 1 C 10 6 DS271 A-C6/0.01 ELN 2CSR175192R0064 034353 0.205 1 10 DS271 A-C10/0.01 ELN 2CSR175192R0104 034452 0.205 1 16 DS271 A-C16/0.01 ELN 2CSR175192R0164 034551 0.205 1 20 DS271 A-C20/0.01 ELN 2CSR175192R0204 034650 0.205 1 25 DS271 A-C25/0.01 ELN 2CSR175192R0254 034759 0.205 1 32 DS271 A-C32/0.01 ELN 2CSR175192R0324 034858 0.205 1 30 6 DS271 A-C6/0.03 ELN 2CSR175192R1064 034957 0.205 1 10 DS271 A-C10/0.03 ELN 2CSR175192R1104 035053 0.205 1/20 16 DS271 A-C16/0.03 ELN 2CSR175192R1164 035152 0.205 1/20 20 DS271 A-C20/0.03 ELN 2CSR175192R1204 035251 0.205 1/20 25 DS271 A-C25/0.03 ELN 2CSR175192R1254 035350 0.205 1 32 DS271 A-C32/0.03 ELN 2CSR175192R1324 035459 0.205 1 40 DS271 A-C40/0.03 ELN 2CSR175192R1404 128557 0.205 1 100 6 DS271 A-C6/0.1 ELN 2CSR175192R2064 035558 0.205 1 10 DS271 A-C10/0.1 ELN 2CSR175192R2104 035657 0.205 1 16 DS271 A-C16/0.1 ELN 2CSR175192R2164 035756 0.205 1 20 DS271 A-C20/0.1 ELN 2CSR175192R2204 035855 0.205 1 25 DS271 A-C25/0.1 ELN 2CSR175192R2254 035954 0.205 1 32 DS271 A-C32/0.1 ELN 2CSR175192R2324 036050 0.205 1 300 6 DS271 A-C6/0.3 ELN 2CSR175192R3064 036159 0.205 1 10 DS271 A-C10/0.3 ELN 2CSR175192R3104 036258 0.205 1 16 DS271 A-C16/0.3 ELN 2CSR175192R3164 036357 0.205 1 20 DS271 A-C20/0.3 ELN 2CSR175192R3204 036456 0.205 1 25 DS271 A-C25/0.3 ELN 2CSR175192R3254 036555 0.205 1 32 DS271 A-C32/0.3 ELN 2CSR175192R3324 036654 0.205 1 40 DS271 A-C40/0.3 ELN 2CSR175192R3404 128656 0.205 1 Selection tables RCBOs DS 271 series

10000 A y type

B C 2CSC400407F02012CSC400407F0201 System pro M compact®

Residual current relays with external toroidal transformer can detect leakage currents. Through minidip you can set sensitivity and intervention time. RD2 residual current relays Operating Order Bbn Price Price Weight Pack voltage details 8012542 1 piece group 1 piece unit V Type code Order code EAN kg pc. 230…400 a.c. RD2 2CSM142120R1201 058007 0.125 1 Technical features Operating voltage [V] 230÷400 a.c. (RD2) and Type A Frequency [Hz] 50÷60 Sensitivity settings IΔn [A] 0.03; 0.1; 0.3; 0.5; 1; 2 Intervention time [s] Fast (instantaneous); 0.3; 0.5; 1; 2; 5 settings Contact capacity [A] 10 at 250 V a.c. (ohmic) Contact type NC-C-NO Operating temperature [°C] -5…+40 Modules [No.] 2 Standards IEC/EN 62020 Indications Green LED: supply voltage present Red LED: alarm status More functions The connection between the toroidal transformer and the residual current relay is continually che- cked by the relay; if the connection interrupts, the residual current relay enters the “alarm” status. The ”test” pushbutton simulates - internally to the RD2 - the residual current conditions for the RD2 to operate. If pushed, the RD2 must enter the alarm status. The “reset” pushbutton allows the residual current relay to return to the starting condition. If the configuration is not appropriate, the de- vice will automatically consider as valid the first configuration (according to the diagram) and enter the maximum safety. OEPM0295 0.03 0.1 0.3 0.5 1 2 Fast 0.3 0.5 1 2 5 0.03 IΔn(A) 0.1 0.3 0.5 Fast Time (sec.) 0.3 0.5 Selection of calibration 2CSC400320F0201 Selection tables RD2 residual current relays RD2 System pro M compact®

RD3 residual current relays The RD3 family of electronic residual current relays provides residual current protection and monito- ring functions according to IEC/EN 60947-2:2006 annex M and can be used in conjunction with all S 200 automatic devices and Tmax range moulded case devices up to T5, for industrial installations. The RD3 residual current relays can provide status indications through two output contacts. Operating Order Bbn Price Price Weight Pack voltage details 8012542 1 piece group 1 piece unit V Type code Order code EAN kg pc. 230-400 a.c. RD3 2CSJ201001R0002 734833 0.25 1 230-400 a.c. RD3M 2CSJ202001R0002 747031 0.25 1 230-400 a.c. RD3P 2CSJ203001R0002 733836 0.25 1 Technical features RD3/RD3-48 RD3M/RD3M-48 RD3P/RD3P-48 Operating voltage RD3: 230-400 Vac +10% / -15% RD3M: 230-400 Vac +10% / -15% RD3P: 230-400 Vac +10% / -15% RD3-48: 12-48 Vac/Vdc +10% / -15% RD3M-48: 12-48 Vac/Vdc +10% / -15% RD3P-48: 12-48 Vac/Vdc +10% / -15% Auxiliary supply frequency 50-60 Hz 50-60 Hz 50-60 Hz Network monitored frequency 50 Hz -150 Hz * 50 Hz -150 Hz * 50 Hz -150 Hz * Frequency filter - 150 Hz fT = 400 Hz 150 Hz fT = 400 Hz Type A (up to I Δn=5 A), A (up to I Δn=5 A) A (up to I Δn=5 A) AC (for higher current) AC (for higher current) AC (for higher current) Operating temperature -25….+70 °C -25….+70 °C -25….+70 °C Maximum power consumption <3.6 W (RD3), <3.6W (RD3M), <3.6 W (RD3P), <600 mW (RD3-48) <600mW (RD3M-48) <600 mW (RD3P-48) Pre-alarm threshold - 60% 60% Max. resistance connection between toroidal transformer and relay 3 W 3 W 3 W Max. length connection of remote reset button 15 m 15 m 15 m Output Contact capacity Led bar indicator - - Yes Max. cable terminals section 2.5 mm² 2.5 mm² 2.5 mm² Modules 3 3 3 Protection degree IP20 IP20 IP20 Standards IEC/EN 60947-2 annex. M IEC/EN 60947-2 annex. M IEC/EN 60947-2 annex. M *RD3 can detect, as a monitor, sinusoidal earth fault currents in networks with frequencies between 50 Hz and 150 Hz. 2CSC400691F02012CSC400690F02012CSC400689F0201 Selection tables RD3 residual current relays RD3 System pro M compact®

RD front panel residual current relays RD front panel residual current relays achieve their protective function in combination with an external toroidal transformer. You can set the sensitivity between 0.025 A and 25 A, the tripping time can vary from 0.02 to 5 seconds. Residual current relays are available in 48 mm x 48 mm, 72 mm x 72 mm and 96 mm x 96 mm versions. The RD296 version is provided of dip switch to select the fail safe function (the output contacts will switch both for differential current over the threshold that for the lack of input current). The RD296-S is provided of fail safe function and memory led. The RD296-DIG version is provided of fail safe function (as the precedent). The digital display allows the visualization of differential current I Δn. Operating Order Bbn Price Price Weight Pack voltage details 8012542 1 piece group 1 piece unit V Type code Order code EAN kg pc. 115 V a.c./V d.c RD272-115 2CSG352424R1201 742401 0.322 1 115, 230, 400 V a.c. RD272-230 2CSG152424R1201 742500 0.322 1 115, 230, 400 V a.c. RD296-DIG-230 2CSG152436R1201 743309 0.383 1 Technical features RD148 RD172 RD272 RD196 RD296 RD296-S RD296-DIG Type AAAAAA Operating voltage [V] 24, 48, 115, 230 a.c./ 24, 48, 115 d.c. 24, 48, 115, 230 a.c./ 24, 48, 115 d.c. 24, 48, 115 230, 400 a.c./ 24, 48, 115 d.c. 24, 48, 115, 230, 400 a.c./ 24, 48, 115 d.c. 24, 48, 115, 230, 400 a.c./ 24, 48, 115 d.c. 24, 48, 115, 230, 400 a.c./ 24, 48, 115 d.c. Operating frequency [Hz] 50 – 60 50 – 60 50 – 60 50 – 60 50 – 60 50 – 60 from 0.03 to 30 (DIG) Number of contacts [No.] 212122 Contact type change over change over change over change over change over change over Working temperature [°C] -10…+60 -10…+60 -10…+60 -10…+60 -10…+60 -10…+60 Storage temperature [°C] -10…+70 -10…+70 -10…+70 -10…+70 -10…+70 -10…+70 Dimensions W x H [mm] 48 x 48 72 x 72 72 x 72 96 x 96 96 x 96 96 x 96 Display ----- y e s Applicable standards EN 62020 IEC 62020 EN 62020 IEC 62020 EN 62020 IEC 62020 EN 62020 IEC 62020 EN 62020 IEC 62020 EN 62020 IEC 62020 2CSC405060F00012CSC405160F00012CSC405061F00012CSC400692F0201 Selection tables Front panel residual current relays RD System pro M compact®

Dimension Ø Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm Type code Order code EAN kg pc. 29 (modular version) TRM 2CSM029000R1211 020707 0.170 1 35 TR1 2CSG035100R1211 020301 0.212 1 60 TR2 2CSG060100R1211 020400 0.274 1 80 TR3 2CSG080100R1211 020509 0.454 1 110 TR4 2CSG110100R1211 020608 0.530 1 110 (openable version) TR4/A 2CSG110200R1211 743408 0.600 1 160 TR160 2CSG160100R1211 743507 1.350 1 160 (openable version) TR160A 2CSG160200R1211 743606 1.600 1 210 TR5 2CSG210100R1211 024804 1.534 1 210 (openable version) TR5/A 2CSG210200R1211 065708 1.856 1 2CSC400494F0201 Selection tables Toroidal transformers TRSystem pro M compact®

Auxiliary elements and accessories for Auxiliary elements and accessories for MCBs S 280, S 290, S 700, Auxiliary elements and accessories

range of auxiliary elements and accessories is universal: in fact it is suitable for MCBs S 200 and SN 201 range, for RCDs F 200 range and also for RCBOs DS 200 range and it is useful in terms of stock management. The auxiliary elements range (composed by auxiliary and signal contacts, shunt trips, undervoltage releases and automatic reclosing units) is quite wide and there are different possible schemes for assemblage with devi- ces. Thus MCBs and RCDs performances are improved, even because innovative and integrated solutions can be used in every installation. The connection accessories range (busbars, connection terminals, feeder terminals) allows any kind of wiring. The range of standard accessories (labels, covers) permits to customize the installation. 2CSC400258F02012CSC400263F0201

MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series Index Schemes for combination of auxiliary elements and S 200, SN 201, F 200, DS201, DS202C and DS 200 series and accessories Technical features of auxiliary elements and accessories Technical features - Busbars Selection tables of auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series /22

pro M compact® Schemes for combination Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series ST -L H-L or NT H-BF S 200 DDA 200 HHH ST or UR or OR HHH S/H HH S/H (H) S/H (H) HH S/HBP S/H (H) S/H (H) H-R H-R H Auxiliary contact S2C-H6R H-R Auxiliary contact S2C-H6-...R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R ST Shunt trip for S 200 MCB S2C-A... UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP ST-L Shunt trip for S 200 MCBs to be mounted on the left S2C-A...L H-L Auxiliary contact for S 200 MCBs to be mounted on the left S2C-H...L H-BF Auxiliary contact for MCBs bottom fitting (1 for each pole of MCB) S2C-H01/S2C-H10 BP Mechanical tripping device S2C-BP NT Switched neutral S2C-Nt Combination of auxiliary elements with S 200, DDA 200 + S 200 or DS 200 Combination of auxiliary elements with SN 201 Combination of S 200 with motor operating device S 200 ST MOD-S MOD-S SN 201 HHS ST-F/UR S/H S/H (H) IH S/H S/H (H) HH IH Coupling interface/ auxiliary contact SN201-IH S Signal contact SN201-S H Auxiliary contact S2C-H6R S/H Signal/auxiliary contact S2C-S/H6R S/H (H) Signal/auxiliary contact used as auxiliary contact S2C-S/H6R ST-F Shunt trip of F200 RCD F2C-A UR Undervoltage release S2C-UA ST Shunt trip for S 200 MCB S S2C-A... MOD-S* Motor operating device S2C-CM... * in case of using S 200 coupled with DDA 200, MOD-S doesn’t operate in case of earth-leakage fault 2CSC400010F02022CSC400011F0202 2CSC400011F0202

pro M compact® Schemes for combination Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series F 204 125 A F 204 B type F 204 PV B F2 125 A S/H F 200 H or S/H H S/H (H) AR/MOD-F ST -F or UR or OR H or S/H S/H (H) H H Auxiliary contact S2C-H6R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP AR Auto reclosing unit F2C-ARI MOD-F Motor operating device F2C-CM ST-F Shunt trip for F 200 RCCB F2C-A F2 125 A S/H Signal/Auxiliary contact Combination of auxiliary elements with F 204 125 A, B type, PV B Combination of auxiliary elements with F 200 Combination of home automatic resetting unit with F 200 F 200 * ARH ARH Home automatic resetting unit F2C-ARH * F 202 30 mA, max 63 A Combination of auxiliary elements with DS201, DS202C DS201 DS202C + ST-F + H + H + MOD-DS + UR + H + H + OR + H + H + S/H + H + S/H + S/H (H) + H + H + ST-F + S/H + S/H (H) + UR + S/H + S/H (H) + OR + S/H + S/H (H) H Auxiliary contact S2C-H6R S/H Signal/Auxiliary contact S2C-S/H6R S/H (H) Signal/Auxiliary contact used as auxiliary contact S2C-S/H6R ST-F Shunt trip for F 200 RCCB F2C-A UR Undervoltage release S2C-UA OR Overvoltage release S2C-OVP MOD-DS Motor operating device DS2C-CM 2CSC400010F0202 2CSC400011F0202 2CSC400010F02022CSC400012F0202

pro M compact® Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series Auxiliary contact and signal/auxiliary contact S2C-H6R, S2C-H11L, S2C-H20, S2C-H02 and S2C-S/H6R Rated current A 10 Min. rated voltage UBmin AC V 24 DC V 24 Min. rated operational current/voltage 10 mA at 12 V; 5 mA at 24 V Short-circuit withstand capacity V 230 a.c. 100A with S201 K4 Overvoltage category III Surge voltage (1.2/50 ms) kV 4 Connection cross section mm 2 0.75…2.5 (up to 2 x 1.5 mm2 for S2C-H11L, S2C-H20L and S2C-H02L) Tightening torque Nm 1.2 (max. 0.8 for S2C-H11L, S2C-H20L and S2C-H02L) Contact stability in vibration test according to DIN IEC 68-2-6 5g, 20 sweep cycles 5…150…5 Hz at 24 V AC/DC, 5 mA automatic reclosing < 10 ms Mechanical service life 10000 operations Dimensions (H x D x W) mm 85 x 69 x 8.8 Auxiliary contact and signal/auxiliary contact S2C-H6-11R, S2C-H6-20R, S2C-H6-02R Rated current A 10 Min. rated voltage UBmin AC V 24 DC V 24 Min. rated operational current/voltage 10 mA at 12 V; 5 mA at 24 V Overvoltage category III Surge voltage (1.2/50 ms) kV 4 Connection cross section mm 2 0.75…2.5 Tightening torque Nm 1.2 Mechanical service life 10000 operations Dimensions (H x D x W) mm 85 x 69 x 8.8 Bottom-fitting auxiliary contact S2C-H10 and S2C-H01 Contact complement 1NO (1 make contact), 1NC (1 normally closed contact), leading make contact, late closing Contact load AC14 2 A/230 V - DC 12 identical DC13/DC13 1 A /50 V, 2 A/30 V Min. rated voltage V 12 AC/DC at 0.1 VA Short-circuit withstand capacity 230 VAC 1000 A, fault protection with S 201-K2 or Z2 Electrical serviceable life > 4000 switchover cycles Standard VDE 0106 Part 101 Connection cross-section mm 2 0.75 to 2.5 Tightening torque N*m 0.5 Signal auxiliary contact for F 200 125A and F 200 B F2 125A-S/H Rated current AC A 6 DC A 1 Min. rated voltage Ub min AC V 230 DC V 110 Connection cross section mm 2 1...1.5 Tightening torque Nm 0.8 Dimensions (H x D x W) mm 85 x 69 x 8.8 Shunt trip for S 200 MCBs S2C-A1 S2C-A2 Rated voltage AC V 12…60 110…415 DC V 12…60 110…250 Max release duration ms <10 <10 Min. release voltage AC V 7 55 DC V 10 80 Consumption on release Ub V 12 DC 12 AC 24 DC 24 AC 60 DC 60 AC 110 DC 110 AC 220 DC 230 AC 415 AC Coil resistance Ω 3.7 225 Terminals mm 2 16 16 Tightening torque Nm 2.5 2.5 Dimensions (H x D x W) mm 85 x 69 x 17.5 85 x 69 x 17.5 Shunt trip for F 200 RCCBs F2C-A1 F2C-A2 Max release duration ms 10 10 Min. release voltage AC V 6 75 DC V 4.5 55 Consumption on release Ub V 12 DC 12 AC 24 DC 60 DC 60 AC 110 DC 110 AC 250 DC 415 AC Coil resistance Ω 5.5 1355 Terminals mm 2 2x1.5 2x1.5 Tightening torque Nm 0.2 0.2 Dimensions (H x D x W) mm 85 x 69 x 17.5 85 x 69 x 17.5

pro M compact® Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series Undervoltage release S2C-UA 12 DC S2C-UA 24 AC S2C-UA 24 DC S2C-UA 48 AC S2C-UA 48 DC S2C-UA 110 AC S2C-UA 110 DC S2C-UA 230 AC S2C-UA 230 DC S2C-UA 400 AC Standards IEC/EN 60947-1 Rated voltage AC V 24 48 110 230 400 DC V 12 24 48 110 230 Frequency Hz 50…60 Release trip V 0.35 Un /L50871 V /L50871 0.7 Un Terminals mm 2 2x1.5 Resistance to corrosion °C/RH constant atmosphere: 23/83 - 40/93 - 55/20; variable atmosphere: 25/95 - 40/93 Protection degree IPXXB/IP2X Tightening torque Nm 0.4 Dimensions (H x D x W) mm 85 x 69 x 17.5 Overvoltage release S2C - OVP2 S2C - OVP1 Rated voltage VAC 230 Rated frequency Hz 50 Max non-tripping voltage AC V 253 Max tripping voltage AC V 290 275 Tripping time @ 290V AC s t<1 @ 380V AC s t<0.1 Peak current @ 315V AC A 1 @ 440V AC A 1.8 Max duration of impulse command ms 7 Operating temperature °C -5….+40 Hand operated neutral left side mounted S2C-Nt Rated current A max. 40 Terminal mm 2 10; box terminal Tightening torque Nm 1.2 Dimensions (H x D x W) mm 85 x 69 x 8.8Signal and auxiliary contacts SN201-S SN201-IH Terminals mm 2 2x1,5 Tightening torque N 1.2 Dimensions mm H: 85 x D: 68 x W: 8.9 H: 85 x D: 68,7 x W: 8.9 Rated voltage V 230 Rated current A 2 Utilization category and contact capacity SN201-S, SN201-IH AC14 Ue V 400 230 Ie A 1 2 DC12 Ue V 220 110 Ie A 1 1,5 DC13 Ue V 60 24 Ie A 2 4

Materials Busbar: E – Cu 58 F25 insulation: PS PC / ABS PS...SP PC / ABS PS...BP PA 66 Heat deflection temp. PS VST B 120 – ISO 306 = 113 °C – UL94-V0/1,5 PS...SP VST B 120 – ISO 306 = 113 °C – UL94-V0/1,5 PS...BP HDT B – ISO179 = 200 °C – UL94-V0/0,4 mm Climate stability according to DIN EN 60068 Insulation coordination Overvoltage category III / Pollution degree 2 Comparative tracking index 600 V Standards PS DIN EN 60947-1 VDE 0660 part 100 = IEC 60947-1:2004 PS...SP DIN EN 60947-1 VDE 0660 part 100 = IEC 60947-1:2004; UL1077 PS...BP DIN EN 60947-1 VDE 0660 part 100 = IEC 60947-1:2004; UL489 Dielectric strength PS 32 kV/mm PS...SP 32 kV/mm PS...BP 30 kV/mm Impulse voltage strength PS 4.5 kV PS...SP 9.5 kV PS...BP 9.5 kV Operation voltage PS 690 VAC PS...SP 480 VAC PS...BP 480 VAC Busbar cross section 10/16/30 mm Max. current Is phase see chart below Short circuit withstand capacity PS 25 kA with back up fuse NH3 355 A gG/gL500V PS...SP 10 kA with back up fuse NH3 355 A gG/gL500V PS...BP 10 kA with back up fuse NH3 355 A gG/gL500V Currrent carrying capacity at 35 °C (depending on feeding) End feeding busbar blocks PS cross section/mm2 10 16 30 max. supply current IS/phase A6 3 8 0 1) 120* Non-end feeding (center or elsewhere on the rail) busbar blocks PS cross section/mm2 10 16 30 max. current in branch IE/phase A 100 130 1) 2) 160* max. supply current IE/phase A depends on cross section * If fed via the terminals, always ensure that 130 A (110 A for terminals 16 mm2) are not exceeded, irrespective of the current carrying capacity (IS) of the busbar 1) PS...BP 115 A if cubicle size /L50871 30” x 30” x 10” 2) PS...SP 100 A System pro M compact® Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series

pro M compact® Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series Undervoltage release S2C-UA 12 DC S2C-UA 24 AC S2C-UA 24 DC S2C-UA 48 AC S2C-UA 48 DC S2C-UA 110 AC S2C-UA 110 DC S2C-UA 230 AC S2C-UA 230 DC S2C-UA 400 AC Standards IEC/EN 60947-1 Rated voltage AC V 24 48 110 230 400 DC V 12 24 48 110 230 Frequency Hz 50…60 Release trip V 0.35 Un ≥ V ≥ 0.7 Un Terminals mm 2 2x1.5 Resistance to corrosion °C/RH constant atmosphere: 23/83 - 40/93 - 55/20; variable atmosphere: 25/95 - 40/93 Protection degree IPXXB/IP2X Tightening torque Nm 0.4 Dimensions (H x D x W) mm 85 x 69 x 17.5 Overvoltage release S2C - OVP2 S2C - OVP1 Rated voltage VAC 230 Rated frequency Hz 50 Max non-tripping voltage AC V 253 Max tripping voltage AC V 290 275 Tripping time @ 290V AC s t<1 @ 380V AC s t<0.1 Peak current @ 315V AC A 1 @ 440V AC A 1.8 Max duration of impulse command ms 7 Operating temperature °C -5….+40 Hand operated neutral left side mounted S2C-Nt Rated current A max. 40 Terminal mm 2 10; box terminal Tightening torque Nm 1.2 Dimensions (H x D x W) mm 85 x 69 x 8.8

pro M compact® Motor operating devices S2C-CM F2C-CM Power consumption during 12 V a.c. VA < 15 the operation 24 V a.c. VA < 22 30 V a.c. VA < 25 Power consumption at rest VA < 1.5 Make-time at ambient temperature sec < 1 Opening time at ambient temperature sec < 0.5 Number of operations < 20.000 Operating temperature °C - 25 ... + 55 Cables length of control circuit m < 1500 Cables cross-section mm 2 < 2.5 Signal contact (terminals 3 – 4 – 5) Current carrying capacity 1NA + 1NC (change-over contact) 5 A (250 V AC) (inductive-ohmic l oad) Auxiliary contact (terminals 6 – 7 – 8) Current carrying capacity 1NA + 1NC (change-over contact) 3 A (250 V AC) (inductive-ohmic load) Remote control* By means of dry contacts Remote control terminals Terminal 9 = make contact; Terminal 10 = opening contact Terminal 11 = common reference for control contacts, +5V d.c. (supplied by the motor operating device) * Note: 1- After having powered the device, wait 5 seconds before activating the control functions. 2- In case of the device opening due to a fault, please wait 8 seconds before attempting to reclose the motor operator. Motor operating devices DS2C-CM Insulation voltage V 2500 for 1 minute Power consumption during 12 V a.c. VA < 15 the operation 24 V a.c. VA < 22 30 V a.c. VA < 25 Power consumption at rest VA < 1.5 Remote control * by means of dry contacts Make-time at ambient temperature sec < 1 Opening time at ambient temperature sec < 0.5 Time before attempting to reclose the motor operator sec 8 Number of operations < 20.000 Operating temperature °C - 25 ... + 55 Storage temperature °C - 40 ... + 70 Mounting on DIN rail EN 60715 by means of fast clip device Protection degree (EN 60529 terminals: IP2X enclosure: IP4X Cables length of control circuit m < 1500 Cables cross-section mm 2 < 2.5 Signal contact (terminals 3 – 4 – 5) 1NO + 1NC (change-over contact) Current carrying capacity 5 A (250 V AC) (resistive load) Auxiliary contact (terminals 6 – 7 – 8) 1NO + 1NC (change-over contact) Current carrying capacity 3 A (250 V AC) (resistive load) Remote control terminals Terminal 9 = make contact; Terminal 10 = opening contact Terminal 11 = common reference for control contacts, +5 V d.c. (supplied by the motor operating device) * Note: 1- After having powered the device, wait 5 seconds before activating the control functions. 2- In case of the device opening due to a fault, please wait 8 seconds before attempting to reclose the motor operator. Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series

Auto-reclosing unit F2C-ARI F2C-ARI30 Number of automatic reset attempts 3 Time of reset of the auto-reset meter sec 16 45 Power consumption during 12Va.c. VA < 15 the operation 24Va.c. VA < 22 30Va.c. VA < 25 Power consumption at rest VA < 1.5 Waiting time between auto-reset attempts sec 3 30 Closing time at ambient temperature sec < 1 Opening time at ambient temperature sec < 0.5 Number of operations < 20.000 Operating temperature °C - 25 ... + 55 Cables length of control circuit m < 1500 Cables cross-section mm 2 < 2.5 Signaling contact to signal a locked state following three auto-reset attempts (terminals 3 – 4 – 5) 1NA + 1NC (change-over contact) Current carrying capacity 5 A (250 V AC) (ohmic load) Auxiliary contact (terminals 6 – 7 – 8) 1NA + 1NC (change-over contact) Current carrying capacity 3 A (250 V AC) (ohmic load) Remote control By means of dry contacts Remote control terminals Terminal 9 = closing and remote reset contact for locked state; Terminal 10 = opening contact Terminal 11 = common reference for control contacts, +5V d.c. (supplied by the motor operating device) * After having powered the device, wait 5 seconds before activating the control functions. Home automatic resetting unit F2C-ARH /F2C-ARH-T Power supply VAC 230 Number of automatic reclosing attempts 1 Reset time for counter of automatic reclosing attempts sec 12 Power absorbed during the operation VA (t<0.5s) 20 max Power consumption in stand-by W 0.4 max Number of operations ≤ 10.000 Operating temperature °C -25 ... + 55 Signal contact cable section mm² ≤ 2.5 Signal contact for the locked state (terminals 1-2) 1NA (change-over contact) Signal contact rated current A 3 (250V AC) Accessories for range S 200 U and S 200 UP acc. to UL 489/CSA-22.2 No.5 Auxiliary contact and signal contact S2C-H6R U, S2C-S/6R U Rated current A 10 Min. rated voltage UBmin AC V 24 DC V 24 Min. rated operational current/voltage 10 mA at 12 V; 5 mA at 24 V Short-circuit withstand capacity V 230 a.c. 100A with S201 K4 Overvoltage category III Surge voltage (1.2/50 ms) kV 4 Connection cross section mm 2 0.75…2.5 Tightening torque Nm 1.2 Contact stability in vibration test 5g, 20 sweep cycles 5…150…5 Hz according to DIN IEC 68-2-6 at 24 V AC/DC, 5 mA automatic reclosing < 10 ms Mechanical service life 10000 operations Dimensions (H x D x W) mm 100 x 69 x 8.8 Shunt trip S2C-A1 U S2C-A2 U Rated voltage AC V 12…60 110…415 DC V 12…60 110…250 Max release duration ms <10 <10 Min. release voltage AC V 7 55 DC V 10 80 Consumption on release Ub V

12 DC 12 AC 24 DC 24 AC 60 DC 60 AC 110 DC 110 AC 220 DC 230 AC 415 AC

Coil resistance Ω 3.7 225 Terminals mm 2 16 16 Tightening torque Nm 2 2 Dimensions (H x D x W) mm 100 x 69 x 17.5 100 x 69 x 17.5 System pro M compact® Technical features Auxiliary elements and accessories for MCBs S 200 and SN 201, RCDs F 200, DS201, DS202C and DS 200 series

Function S2C-S/H6R: choice through a selector between indication of the position of the device’s contacts and signalling of the fault (overcurrent/short-circuit for MCBs and RCBOs; earth fault for RCCBs and RCBOs). Suitable for MCBs S 200 series, RCCBs F 200 series, RCBOs DS201, DS202C, DS 200 series. Function S2C-H6R: indication of the position of the device’s contacts. Suitable for MCBs S200 series. To be mounted on the left side of the MCBs thanks to the special pin. They are not suitable to be mounted together with RCD-block DDA200. Function S2C-H6-xxR: indication of the position of the MCB contact. Mounted on the right side. They are not suitabel to be mounted together with RCD-block DDA200 and/or other auxiliary contacts. Description Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. Signal contact/ auxiliary switch 1CO S2C-S/H6R 2CDS200922R0001 563819 0.04 1 Auxiliary contact 1CO S2C-H6R 2CDS200912R0001 563826 0.04 1 Auxiliary contact 1NO/1NC S2C-H6-11R 2CDS200946R0001 697941 0.04 1 Auxiliary contact 2NO S2C-H6-20R 2CDS200946R0002 697958 0.04 1 Auxiliary contact 2NC S2C-H6-02R 2CDS200946R0003 697965 0.04 1 Auxiliary contacts mounting on the left side Description Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. Auxiliary contact 1 NO/1NC S2C-H11L 2CDS200936R0001 648820 0.04 1 Auxiliary contact 2 NO S2C-H20L 2CDS200936R0002 648837 0.04 1 Auxiliary contact 2 NC S2C-H02L 2CDS200936R0003 648844 0.04 1 Bottom-fitting auxiliary contacts for S 200, S 200 M, S 200 P 1 NC S 2C-H01 2CDS 200 970 R0001 64551 5 0.01 1 1 NO S 2C-H10 2CDS 200 970 R0002 64552 2 0.01 1 packing unit 15 parts 1 NC S 2C-H01 15x 2CDS 200 970 R0011 64677 2 0.01 15 1 NO S 2C-H10 15x 2CDS 200 970 R0012 64681 9 0.01 15 Auxiliary contact bridge for bottom-fitting auxiliary contacts Wire jumper for integrated auxiliary contact (MCB S 200 H or auxiliary contacts S2C-H01/S2C-H10 for series connections (HKB) or parallel connections (HKB1). 1/2 mod. HKB GH V036 0504 R0100 523134 0.001 1000 1 mod. HKB 1 GH V036 0504 R0101 524209 0.001 1000 Signal contact for SN201 MCBs Function: indication of the device contact positions only after the automatic release of the MCBs due to overcurrent. Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Signal contact 1NO + 1 NC SN201-S 2CSS200924R0001 104957 0.040 1 Auxiliary contact / interface module for SN201 MCBs Function: indication of the device contact positions. The auxiliary contact can be used as an interface module between SN201 and other compact auxiliary elements. Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Interface module/Aux. Contact 1NO+1NC SN201-IH 2CSS200923R0001 104858 0.050 1 System pro M compact® Selection tables Auxiliary elements for MCBs S 200, SN 201, RCDs F 200 and DS 200 series !UTOMATIC OPENING -ANUAL OPENING 5SEDAS SIGNALCONTACT $XWRPDWLF RSHQLQJ 0DQXDO RSHQLQJ 8VHGDV DX[LOLDU\\FRQWDFW SJ SJ\\ 1311 12 14 13 11 11 12 14 2 12 14 2 11 13 SJ SJ\\ 2313 14 24 23 11 3 1 14 24 2 14 24 2 13 23 SJ SJ\\ 2111 12 22 21 11 11 12 22 2 12 22 2 11 21 2CSC400465F0201 2CSC400324F02012CSC400155F0201 !UTOMATIC OPENING -ANUAL OPENING 5SEDAS AUXILIARYCONTACT !UTOMATIC OPENING :*:/ -ANUAL OPENING 5SEDAS SIGNALCONTACT S2C-H6-11R S2C-S/H6R S2C-H6R S2C-H6-20R S2C-H6-02R S2C-S/H6R S2C-H6-... 2CSC400682F00012CSC400681F0001

pro M compact® Selection tables Auxiliary elements for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Auxiliary elements S 200, SN 201, F 200, DS 200 and other series Signal/auxiliary contact for F 200 125A and F 200 B Function: choice through a selector between indication of the position of the device’s contacts and signalling of the earth fault. Suitable for RCCBs F 200 125A and F 200 B series Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Signal/auxiliary contact F2 125A-S/H 2CSS200922R0001 941408 0.04 1 Clamping cover for F200 125A-F200 B type Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. CPV B 2CSF200988R0001 999638 1 Shunt trips Function: remote opening of the device when a voltage is applied. Suitable for MCBs S 200 series and RCBOs DS 200 series. Rated voltage Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. AC/DC 12…60 V S2C-A1 2CDS200909R0001 570992 0.15 1 AC 110…415 V/ DC110…250 V S2C-A2 2CDS200909R0002 571005 0.15 1 Function: remote opening of the device when a voltage is applied. Suitable for RCCBs F 200 series and RCBOs DS201 and DS202C. It can be used with MCBs SN201 series by means of SN201-IH interface module. Rated voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. AC/DC 12...60V F2C-A1 2CSS200933R0011 974901 0.15 1 2CSC400471F0201 2CSC400013F0202

Function: protection of the load in the event of a voltage drop (between 70% and 35% of its rated value); positive safety (device’s tripping when the voltage is disconnected) emergency stop by means of a button. Suitable for MCBs S 200 series, RCCBs F200 series and RCBOs DS201, DS202C, DS 200 series It can be used with MCBs SN201 series by means of SN201-IH interface module. Rated voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 12VDC S2C-UA 12 DC 2CSS200911R0001 839705 0.09 1 24VAC S2C-UA 24 AC 2CSS200911R0002 839804 0.09 1 24VDC S2C-UA 24 DC 2CSS200911R0007 896401 0.09 1 48VAC S2C-UA 48 AC 2CSS200911R0003 839903 0.09 1 48VDC S2C-UA 48 DC 2CSS200911R0008 896500 0.09 1 110VAC S2C-UA 110 AC 2CSS200911R0004 840008 0.09 1 110VDC S2C-UA 110 DC 2CSS200911R0009 896609 0.09 1 230VAC S2C-UA 230 AC 2CSS200911R0005 840107 0.09 1 230VDC S2C-UA 230 DC 2CSS200911R0010 896708 0.09 1 400VAC S2C-UA 400 AC 2CSS200911R0006 840206 0.09 1 Overvoltage releases Function: monitoring voltage between the neutral and phase; when an overvoltage reaches the threshold value, the OVP device causes the tripping of the associated MCB or RCCB. Suitable for MCBs of the S200 series up to 63 A, and RCCBs of the F200 series up to 100 A and RCBOs DS201 and DS202C series. Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Overvoltage release (max tripping voltage AC: 275V) S2C-OVP1 2CSS200910R0005 748137 0.100 1/5 Overvoltage release (max tripping voltage AC: 290V) S2C-OVP2 2CSS200993R0005 952039 0.100 1/5 Hand operated neutral The hand operated neutral has to be mounted to the left side of the MCB and be snaped on the DIN rail. It is used for measuring duties where the neutral conductor must be in the open position. Due to the special design of the handle - when switching ON the MCB – the neutral will make before the MCB is closed. The S2C - Nt is not to switch with a tool (screw driver). Description Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. Max 40A S2C-Nt 2CDS200918R0001 647625 0.06 1 System pro M compact® Selection tables Auxiliary elements for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Auxiliary elements S 200, SN 201, F 200, DS 200 and other series 2CSC400055F0201 2CSC400677F0001

Accessories for S 200 U and S 200 UP acc. UL 489 and CSA-22.2 No. 5 Auxiliary contact (switch) only for range U and UP S 2C-H6R U 2CDS 200 914 R0001 61561 7 0.035 1 Signal contact (bell alarm) only for range U and UP S 2C-S6R U 2CDS 200 924 R0001 64677 2 0.035 1 Shunt trip only for range U and UP 12 - 60 V AC/DC S 2C-A1 U 2CDS 200 908 R0001 64472 3 0.15 1 110-415 V AC,110-250V DC S 2C-A2 U 2CDS 200 908 R0002 64473 0 0.15 1 System pro M compact® Selection tables Auxiliary elements for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Auxiliary elements S 200, SN 201, F 200, DS 200 and other series S 2C-S6R U S 2C-H6R U S 2C-A1 U 2CSC400023F02012CSC400024F02012CSC400013F0201

Mechanical tripping device Function: it causes the automatic tripping of the circuit-breakers which it is associated to, when the panel or the door of the electrical switchboard are opened or removed. Suitable for MCBs S 200 series (on both sides of the devices) and for DS 200 (only on the right side, because on the left side there’s RCD-block DDA 200). Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Mechanical tripping device S2C-BP 2CSS200998R0001 941309 0.048 1 Plug-in base Function: it is possible to transform a standard circuit-breaker of the S 200 and F 200 range in a plug-in device which can be pulled out of the circuit where it is installed in one operation. Suitable for MCBs S 200 series and for RCCBs F 200 series up to 63 A and RCBOs DS201 and DS202C. Plug-in base S2C-EST 2CSS200999R0001 940708 0.115 1 System pro M compact® Selection tables Auxiliary elements for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Auxiliary elements S 200, SN 201, F 200, DS 200 and other series 2CSC400568F0201 2CSC400573F0201

2CSC400247F0201 2CSC400248F0201 Motor operating devices Function: S2C-CM, F2C-CM and DS2C-CM allow the remote control (opening or closing) of the coupled device. Suitable for S200 MCBs up to 63 A, F 200 RCCBs up to 100 A and RCBOs DS201 and DS202C. Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Motor operating device for 1P S200 MCBs S2C-CM1 2CSS201997R0013 026259 0,166 1 Motor operating device for 2P and 3P S200 MCBs S2C-CM2/3 2CSS203997R0013 026358 0,166 1 Motor operating device for 4P S200 MCBs S2C-CM4 2CSS204997R0013 026457 0,166 1 Motor operating device for 2P and 4P F200 RCCBs F2C-CM 2CSF200997R0013 026556 0,166 1 Motor operating device for 1P+N and 2P DS201, DS202C RCBOs DS2C-CM 2CSR201997R0013 135951 0,166 1 Auto-reclosing units Function: F2C-ARI and F2C-ARI30 allow the auto-reclosing of the coupled device in case of unwanted tripping. Suitable for F 200 RCCBs up to 100 A. Auto-reclosing unit for 2P and 4P F200 RCCBs F2C-ARI 2CSF200996R0013 026655 0,166 1 Auto-reclosing unit for 2P and 4P F200 RCCBs (30”) F2C-ARI30 2CSF200995R0013 064350 0,166 1 Home automatic resetting unit (for domestic and similar applica- tions) Function: recloses the associated residual current device (2-pole RCCBs up to 63 A - 30 mA), only after having checked that there are no effective faults in the the system protected by the RCCB. Suitable for 2-pole RCCB series with 30 mA sensitivity Home automatic resetting unit F2C-ARH 2CSF200992R0005 732433 0,200 1 Home automatic resetting unit with autotest (for domestic and similar applications) Function: recloses the associated residual current device (2-pole RCCBs up to 63 A - 30 mA ), only after having checked that there are no effective faults in the system protected by RCCB. Suitable for 2-pole RCCB series with 30 mA sensitivity. F2C-ARH-T allows the RCCBs automatic test every six months. Home automatic resetting unit with RCCBs autotest F2C-ARH-T 2CSF200991R0005 733232 0,200 1 System pro M compact® Selection tables Motor operating and autoreclosing devices for RCDs and MCBs Auxiliary elements S 200, SN 201, F 200, DS 200 and other series 2CSC400678F0001 2CSC400014F0202

0 OFF0 OFF0 OFF0 OFF

Use at 230 V AC via a TM15/12 bell transformer TM15/2 5678 1234 FAULT NL closed open OFF ON MAX 1500m

230 V AC

1 2 n ... 12-30 V a.c. 230 V AC 6789 1 0 1 1 AUX 12 345 SIGN n ... 12-48 V DC Use of several motor operating devices at 230 V AC via a single safety transformer System pro M compact® Selection tables Motor operating and autoreclosing devices for RCDs and MCBs Auxiliary elements S 200, SN 201, F 200, DS 200 and other series Wiring diagrams for S2C-CM motor operating devices 2CSC400015F0202 Modular transformer Secondary voltage N° max S2C-CM 4 usable TM15/12 12 V 1 TM15/24 24 V 1 TS16/12 12 V 1 TM30/24 12 V 2 TM30/24 24 V 3 TS 25/12-24 C 12, 24 V 5 TS 40/12-24 C 12, 24 V 6 TS 63/12-24 C 12, 24 V 7

pro M compact® Selection tables Motor operating and autoreclosing devices for RCDs and MCBs Auxiliary elements S 200, SN 201, F 200, DS 200 and other series MAX 1500 m 6 789 1 0 1 1 1 2 3 4 5 LOCKED / BLOCCATO AUX LOCKED NL closed open OFF ON 12-30 V AC 12-48 V DC Use at 230 V AC via a TN15/12 transformer 6 789 1 0 1 1 1 2 3 4 5 LOCKED / BLOCCATO AUX TM15/2 5 6 7 8 1 2 3 4 LOCKED NL closed open OFF ON MAX 1500 m 230 V AC. Wiring diagrams for DS2C-CM motor operating devices 2CSC400633F0002

Wiring diagrams for motor operating device F2C-CM and F2C-ARI auto-reclosing unit MAX 1500m 6789 1 0 1 1 12 345 LOCKED AUX LOCKED STATE NL closed / reset open OFF ON 12-30 V AC 12-48 V DC Use at 230 V AC via a TM15/12 bell transformer 67 89 1 0 1 1 12 345 LOCKED AUX TM15/2 5678 1234 LOCKED STATE NL closed / reset open OFF ON MAX 1500m Low voltage use of several motor operating devices or auto-reclosing units: 12-30 V AC, 12-48 V DC 6789 1 0 1 1 AUX 12 345 LOCKED 67 89 1 0 1 1 AUX 12 345 LOCKED 6 7 8 9 10 11 AUX 12 345 LOCKED closed / reset open 1 2 n ... 12-30 V AC 230 V AC closed / reset open closed / reset open Use of several motor operating devices or auto-reclosing units at 230 V AC via a single transformer 6789 1 0 1 1 AUX 12 345 LOCKED 67 89 1 0 1 1 AUX 12 345 LOCKED 6789 1 0 1 1 AUX 12 345 LOCKED closed / reset open 1 2 n ... 12-48 V DC closed / reset open closed / reset open System pro M compact® Selection tables Motor operating and autoreclosing devices for RCDs and MCBs Auxiliary elements S 200, SN 201, F 200, DS 200 and other series 2CSC400016F0202 Modular transformer Secondary voltage N° max F2C-CM or F2C-ARI usable TM15/12 12 V 1 TM15/24 24 V 1 TS16/12 12 V 1 TM30/24 12 V 5 TM30/24 24 V 8 TS 25/12-24 C 12, 24 V 10 TS 40/12-24 C 12 V 10 TS 63/12-24 C 12, 24 V 10

pro M compact® Selection tables Motor operating and autoreclosing devices for RCDs and MCBs Auxiliary elements S 200, SN 201, F 200, DS 200 and other series Wiring diagram for F2C-ARH and F2C-ARH-T L N LOAD 1 2 ON 2CSC400017F0202

USB Modular DIN rail device Function: Modular DIN rail device to store electronic information, files and applications. All the data required will be available in the switchboard. No supply is required. ATTENTION! MeMo2 is available with built in USB cable. MeMo4 is available with USB port (USB cable not included). Description Storage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Modular data memory 2 GB MeMo2 2CSS200960R0001 128052 0.200 1 Modular data memory 4 GB MeMo4 2CSS200960R0002 144656 0.200 1 System pro M compact® Selection tables USB Modular DIN rail device Accessories S 200, SN 201, F 200, DS 200 and other series 2CSC400018F02022CSC400019F0202

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. Pre-assembled busbars (not to be cut) 1-phase busbars, pin distance 17.6 mm, end caps PS-END 0 2 1 10 PS1/2 2CDL 210 001 R1002 463003 0.01 0.01 180 3 1 10 PS1/3 2CDL 210 001 R1003 514651 0.03 0.03 120 4 1 10 PS1/4 2CDL 210 001 R1004 648233 0.03 0.03 100 6 1 10 PS1/6 2CDL 210 001 R1006 463102 0.03 0.03 60 9 1 10 PS1/9 2CDL 210 001 R1009 463201 0.04 0.04 30 12 1 10 PS1/12 2CDL 210 001 R1012 463300 0.05 0.05 30 12 1 10 PS1/12A ➁ 2CDL 210 010 R1012 682985 0.05 0.05 30 3-phase busbars, pin distance 17.6 mm 6 3 10 PS3/6 2CDL 231 001 R1006 463409 0.04 0.04 60 9 3 10 PS3/9 2CDL 231 001 R1009 463508 0.07 0.07 30 12 3 10 PS3/12 2CDL 231 001 R1012 463607 0.10 0.10 30 12 3 10 PS3/12FI * 2CDL 231 002 R1012 463706 0.10 0.09 50 * phase sequence: L1, L2, L3, free, L2, L3, L1, ... Busbars suitable for cutting 1-phase busbars, pin distance 17.6 mm, end caps PS-END 0 60 1 10 PS1/60 2CDL 210 001 R1060 514668 0.26 0.26 20 60 1 10 PS1/60A ➁ 2CDL 210 010 R1060 682992 0.26 0.28 50 60 1 16 PS1/60/16 2CDL 210 001 R1660 516655 0.41 0.41 20 60 1 16 PS1/60/16A ➁ 2CDL 210 010 R1660 683005 0.41 0.39 50 5 1 30 PS1/5/30 ➀ 2CDL 210 001 R3005 653244 0.04 0.04 100 7 1 30 PS1/7/30 ➀ 2CDL 210 001 R3007 653251 0.06 0.06 100 10 1 30 PS1/10/30 ➀ 2CDL 210 001 R3010 653268 0.09 0.09 100 11 1 30 PS1/11/30 ➀ 2CDL 210 001 R3011 653275 0.09 0.10 100 14 1 30 PS1/14/30 ➀ 2CDL 210 001 R3014 653282 0.120 0.120 50 15 1 30 PS1/15/30 ➀ 2CDL 210 001 R3015 653299 0.130 0.130 50 18 1 30 PS1/18/30 ➀ 2CDL 210 001 R3018 653305 0.150 0.150 50 19 1 30 PS1/19/30 ➀ 2CDL 210 001 R3019 653312 0.160 0.160 50 60 1 30 PS1/60/30 2CDL 210 001 R3060 653596 0.520 0.520 20 1-phase busbars, connection of 1-pole devices with auxiliary, end caps PS-END 0 38 1 10 PS1/38H 2CDL 210 001 R1038 586139 0.27 0.27 30 38 1 16 PS1/38/16H 2CDL 210 001 R1638 586146 0.45 0.45 30 1-phase busbars, connection of neutral (blue insulation), end caps END 1.1 28 1 10 PS1/28N 2CDL 210 001 R1028 629546 0.24 0.14 50 28 1 16 PS1/28/16N 2CDL 210 001 R1628 629560 0.32 0.20 50 57 1 10 PS1/57NA ➁ 2CDL 210 011 R1057 579728 0.24 0.14 50 57 1 10 PS1/57N 2CDL 210 001 R1057 629539 0.24 0.14 50 57 1 16 PS1/57/16NA ➁ 2CDL 210 011 R1657 579735 0.32 0.20 50 57 1 16 PS1/57/16N 2CDL 210 001 R1657 629553 0.32 0.20 50 1-phase busbars, connection of auxiliaries, end caps END 1.1 except PS 1/57/6 23 1 6 PS1/23/6 2CDL 210 005 R0623 584739 0.16 0.09 50 29 1 6 PS1/29/6 2CDL 210 005 R0629 580823 0.14 0.10 50 38 1 6 PS1/38/6 2CDL 210 005 R0638 580816 0.14 0.09 50 57 1 6 PS1/57/6 2CDL 210 005 R0657 585309 0.11 0.08 50 PS 1/2 - PS 1/12 SK 0028 B 99 SK 0027 B 99 PS 3/6 - PS 3/12 ➀ inclusive of end caps ➁ pre-cutted pins ➂ use end cap PS-END 3 ➃ use end cap PS-END 3.1 ➄ removal of installed MCB not possible PS…A break-out of pins 2CDC062415F0004

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series ➀ inclusive of end caps ➁ pre-cutted pins ➂ use end cap PS-END 3 ➃ use end cap PS-END 3.1 ➄ removal of installed MCB not possible No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. 1-phase busbars, connection of hand operated neutral S2C-Nt (blue insulation), end caps END 1.1 38 1 10 PS1/38 NT 2CDL 210 002 R1038 655361 0.410 10 2-phase busbars, pin distance 17.6 mm, end caps PS-END 12 2 10 PS2/12 ➀ 2CDL 220 001 R1012 556521 0.07 0.08 50 12 2 10 PS2/12A ➀➁ 2CDL 220 010 R1012 584616 0.07 0.08 50 12 2 16 PS2/12/16 2CDL 220 001 R1612 646918 0.11 0.09 50 58 2 10 PS2/58 2CDL 220 001 R1058 556552 0.32 0.36 10 58 2 16 PS2/58/16 2CDL 220 001 R1658 556569 0.55 0.49 10 58 2 16 PS2/58/16A ➁ 2CDL 220 010 R1658 584746 0.55 0.49 10 58 2 30 PS2/58/30 ➂➄ 2CDL 220 010 R3058 654272 1.81 1.81 10 Note: PS...A is a busbar with removable pin 2-phase busbars, connection of 2-pole devices with auxiliary, end caps PS-END 48 2 10 PS2/48H 2CDL 220 001 R1048 556538 0.47 0.35 10 48 2 16 PS2/48/16H 2CDL 220 001 R1648 556545 0.68 0.48 10 48 2 16 PS2/48/16HA ➁ 2CDL 220 012 R1648 584630 0.68 0.48 10 3-phase busbars, pin distance 17.6 mm, end caps PS-END 11 3 10 PS3/11 ➀ 2CDL 230 001 R1011 649926 0.10 0.08 50 12 3 10 PS3/12 ➀ 2CDL 230 001 R1012 576116 0.09 0.09 50 12 3 10 PS3/12A ➀➁ 2CDL 230 010 R1012 584647 0.09 0.09 50 12 3 16 PS3/12/16 ➀ 2CDL 230 001 R1612 562805 0.16 0.12 50 60 3 10 PS3/60 2CDL 230 001 R1060 514699 0.51 0.47 10 60 3 10 PS3/60A ➁ 2CDL 230 010 R1060 563758 0.51 0.47 10 60 3 16 PS3/60/16 2CDL 230 001 R1660 514705 0.76 0.65 10 60 3 16 PS3/60/16A ➁ 2CDL 230 010 R1660 563765 0.76 0.65 10 60 3 30 PS3/60/30 ➂➄ 2CDL 230 001 R3060 654289 2.65 2.65 10 3-phase busbars, connection of 1-pole devices with auxiliary, end caps PS-END 39 3 10 PS3/39H 2CDL 230 001 R1039 556590 0.51 0.43 10 39 3 16 PS3/39/16H 2CDL 230 001 R1639 556606 0.76 0.60 10 3-phase busbars, connection of 2-pole devices (Phase+N) with auxiliary, end caps PS-END 24 3 10 PS3/24H 2CDL 230 001 R1024 556576 0.80 0.41 10 3-phase busbars, connection of 2-pole devices (Phase+Phase) with auxiliary, end caps PS-END 46 3 16 PS3/46/16H-IT 2CDL 230 001 R1646 662109 0.98 0.98 10 3-phase busbars, connection of 3-pole devices with auxiliary, end caps PS-END 48 3 10 PS3/48H 2CDL 230 001 R1048 556613 0.51 0.43 10 48 3 16 PS3/48/16H 2CDL 230 001 R1648 556644 0.76 0.60 10 48 3 16 PS3/48/16HA ➁ 2CDL 230 012 R1648 584654 0.76 0.60 10 3-phase busbars, connection of 1+N or RCBOs, end caps PS-END 30 3 10 PS3/30 2CDL 230 001 R1030 556583 0.50 0.42 10

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series 3-phase busbars, N of the RCD omitted, end caps PS-END 9 3 10 PS3/9FI ➀ 2CDL 230 002 R1009 517515 0.10 0.06 50 10 3 10 PS3/10FI ➀ 2CDL 230 002 R1010 517522 0.10 0.07 50 12 3 10 PS3/12FI ➀ 2CDL 230 002 R1012 571074 0.11 0.09 50 57 3 10 PS3/57FI 2CDL 230 002 R1057 556651 0.55 0.46 10 3-phase busbars, N of the RCD omitted, with auxilary at RCD end caps PS-END 12 3 10 PS3/12FIH ➀ 2CDL 230 003 R1012 571081 0.11 0.09 50 4-phase busbars, pin distance 17.6 mm, end caps PS-END 1 12 4 10 PS4/12 ➀ 2CDL 240 101 R1012 656054 0.12 0.11 30 12 4 10 PS4/12A ➀➁ 2CDL 240 110 R1012 656061 0.12 0.11 30 12 4 16 PS4/12/16 ➀ 2CDL 240 101 R1612 656078 0.24 0.16 30 60 4 10 PS4/60 2CDL 240 101 R1060 656085 0.80 0.64 10 60 4 16 PS4/60/16 2CDL 240 101 R1660 656092 1.21 0.89 10 60 4 16 PS4/60/16A ➁ 2CDL 240 110 R1660 656108 1.21 0.89 10 60 4 30 PS4/60/30 ➃➄ 2CDL 240 001 R3060 654296 3.37 3.37 10 Note: PS...A is a busbar with removable pin 4-phase busbars, connection of 4-pole devices with auxiliary, end caps PS-END 1 52 4 16 PS4/52/16H 2CDL 240 101 R1652 656115 1.30 0.78 10 52 4 16 PS4/52/16HA ➁ 2CDL 240 212 R1652 656122 1.30 0.78 10 4-phase busbars, connection of 1+N or RCBOs, end caps PS-END 1 12 4 10 PS4/12NA ➀➁ 2CDL 240 213 R1012 656139 0.14 0.10 30 58 4 10 PS4/58N 2CDL 240 101 R1058 656146 0.80 0.59 10 58 4 16 PS4/58/16N 2CDL 240 101 R1658 656153 1.21 0.77 10 58 4 16 PS4/58/16NA ➁ 2CDL 240 213 R1658 656221 1.21 0.77 10 4-phase busbars, connection of 1+N or RCBOs with auxiliary, end caps PS-END 1 48 4 16 PS4/48/16NHA ➁ 2CDL 240 114 R1648 656160 1.48 0.76 10 4-phase busbars, connection of 4-pole RCD with 1+N , end caps PS-END 1 58 4 10 PS4/58NNA ➁ 2CDL 240 110 R1058 656177 0.80 0.58 10 58 4 16 PS4/58/16NNA ➁ 2CDL 240 110 R1658 656184 1.21 0.80 10 No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. ➀ inclusive of end caps ➁ pre-cutted pins ➂ use end cap PS-END 3 ➃ use end cap PS-END 3.1 ➄ removal of installed MCB not possible

pro M compact® PS2/6/16 BP 2CDC061007S0010 No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. Pre-assembled busbars (not to be cut) UL 489 1-phase busbars, pin distance 17.6 mm, UL 489 6 1 16 PS 1/6/16 BP 2CDL 210 489 R1606 644969 0.04 0.05 1 12 1 16 PS 1/12/16 BP 2CDL 210 489 R1612 644976 0.07 0.11 1 18 1 16 PS 1/18/16 BP 2CDL 210 489 R1618 644983 0.11 0.16 1 2-phase busbars, pin distance 17.6 mm, UL489 6 2 16 PS 2/6/16 BP 2CDL 220 489 R1606 644990 0.07 0.06 1 12 2 16 PS 2/12/16 BP 2CDL 220 489 R1612 645003 0.14 0.13 1 18 2 16 PS 2/18/16 BP 2CDL 220 489 R1618 645010 0.21 0.20 1 3-phase busbars. pin distance 17.6 mm. UL 489 6 3 16 PS 3/6/16 BP 2CDL 230 489 R1606 645027 0.11 0.07 1 12 3 16 PS 3/12/16 BP 2CDL 230 489 R1612 645034 0.22 0.15 1 18 3 16 PS 3/18/16 BP 2CDL 230 489 R1618 645041 0.33 0.24 1 Shock-protection caps for PS...BP (UL 489) 3 parts BSK BP 2CDL 200 489 R0001 656368 0.001 10 Conn. Order Bbn Price Price Cu-No. Weight Pack capacity details 4016779 1 piece group 1 piece unit mm2 Type code Order code EAN kg kg pc. Feeder Terminals for PS...BP (UL 489) Terminal, insulated with pin contact 35 AST 35/15 BP 2CDL 201 489 R3515 710350 0.035 0.035 25 Feeder Terminal single-pole terminal, can be mounted side by side, feed on the pin of the busbar 50 SZ-ESK BP 2CDL 201 489 R5001 710367 0.038 50 ➀ inclusive of end caps ➁ pre-cutted pins ➂ use end cap PS-END 3 ➃ use end cap PS-END 3.1 ➄ removal of installed MCB not possible BSK BP AST35/15BP 2CDC061002S0010 SZ-ESK BP 2CDC061003S0010 Technical features Feeder terminals SZ-ESK BP / AST 35/15 BP Max. operating voltage 480 VAC Max. current 115 A 1) Protection degree IP 20 Wire range SZ-ESK PB 35 mm 2 finely stranded with ferrule 50 mm2 solid/stranded AST 35/15 BP 25 mm 2 finely stranded with ferrule 35 mm2 solid/stranded 1) regardless of the rated current of the feeder terminal the maximum current rating of the device terminal may not be exceeded Selection tables Busbars and accessories for MCBs S 200 U and S200 UP – UL 489 (Branch Protection) 2CDC 061 095 F0007

pro M compact® No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. Busbars (suitable for cutting) UL 1077 1-phase busbars, pin distance 17.6 mm, end caps PS-END 0 60 1 10 PS 1/60 SP 2CDL 210 111 R1060 830409 0.26 0.26 20 60 1 16 PS 1/60/16 SP 2CDL 210 111 R1660 830423 0.41 0.41 20 1-phase busbars, connection of 1-pole devices with auxiliary, PS-END 0 38 1 10 PS 1/38H SP 2CDL 210 111 R1038 830430 0.27 0.27 30 38 1 16 PS 1/38/16H SP 2CDL 210 111 R1638 830447 0.45 0.45 30 2-phase busbars, pin distance 17.6 mm, end caps PS-END SP 58 2 10 PS 2/58 SP 2CDL 220 111 R1058 646413 0.42 10 58 2 16 PS 2/58/16 SP 2CDL 220 111 R1658 646420 0.69 10 2-phase busbars, connection of 2-pole devices with auxiliary, end caps PS-END SP 48 2 16 PS 2/48/16 SP 2CDL 220 112 R1648 646437 0.68 10 3-phase busbars, pin distance 17.6 mm, end caps PS-END SP 60 3 10 PS 3/60 SP 2CDL 230 111 R1060 646444 0.68 10 60 3 16 PS 3/60/16 SP 2CDL 230 111 R1660 646451 1.02 10 3-phase busbars, connection of 3-pole devices with auxiliary, end caps PS-END SP 48 3 16 PS 3/48/16 SP 2CDL 230 112 R1648 646468 1.16 10 4-phase busbars, pin distance 17.6 mm, PS-END 1 SP 60 4 16 PS 4/60/16 SP 2CDL 240 311 R1660 656191 1.97 10 4-phase busbars, connection of 4-pole devices with auxiliary, end caps PS-END 1 SP 52 4 16 PS 4/52/16H SP 2CDL 240 312 R1652 656207 1.90 10 4-phase busbars, connection of 1+N and RCBO, end caps PS-END 1 SP 58 4 16 PS4/58/16N SP 2CDL 240 313 R1658 656214 1.86 10 Shock-protection caps for PS...SP (UL 1077) 5 parts BSK SP 2CDL 200 111 R0001 710398 0.001 100 Conn. Order Bbn Price Price Cu-No. Weight Pack capacity details 4016779 1 piece group 1 piece unit mm2 Type code Order code EAN kg kg pc. Feeder Terminals for PS...SP (UL 1077) Terminal, insulated with pin contact 35 AST 35/15 SP 2CDL 200 111 R0001 710398 0.038 0.025 25 Feeder Terminal single-pole terminal, can be mounted side by side, feed on the pin of the busbar 50 SZ-ESK SP 2CDL 200 489 R5001 710381 0.038 0.032 50 Technical features Feeder terminals SZ-ESK SP / AST 35/15 SP Max. operating voltage 480 VAC Max. current 115 A 1) Protection degree IP 20 Wire range SZ-ESK SP 35 mm 2 finely stranded with ferrule 50 mm2 solid/stranded AST 35/15 SP 25 mm 2 finely stranded with ferrule 35 mm2 solid/stranded 1) regardless of the rated current of the feeder terminal the maximum current rating of the device terminal may not be exceeded AST 35/15 SP 2CDC061004S0010 SZ-ESK SP 2CDC061005S0010 BSK SP 2CDC061006S0010 Selection tables Busbars and accessories for MCBs S 200 and S200 P – UL 1077 (Supplementary Protection)

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series Busbars (suitable for cutting) for DDA 200 and DS 200 – bottom mounting (RCD) 3-phase busbars, connection of DDA 202 and DS 202, end caps PSB-END 3 30 3 10 PS 3/30-DDA 202 2CDL 230 202 R1030 647472 0.97 0.41 10 30 3 16 PS 3/30/16-DDA 202 2CDL 230 202 R1630 647502 1.46 0.55 10 3-phase busbars, connection of DDA 202 and DS 202 with auxiliary, end caps PSB-END 3 26 3 16 PS 3/26/16H-DDA 202 2CDL 230 202 R1626 648912 4-phase busbars, connection of DDA 204 63 A and DS 204 50 A and 63 A, end caps PSB-END 4 32 4 10 PS 4/32-DDA 204 2CDL 240 204 R1032 647458 1.41 0.56 10 32 4 16 PS 4/32/16-DDA 204 2CDL 240 204 R1632 647465 2.12 0.77 10 No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc.

Busbars (suitable for cutting) for DDA 200 and DS 200 – top side mounting (MCB) 2-phase busbars, connection of DDA 202 and DS 202, end caps PSB-END 3 30 2 16 PS 2/30/16N-DDA 202T 2CDL 020 202 R1630 697675 0.512 10 3-phase busbars, connection of DDA 202 and DS 202, end caps PSB-END 3 30 3 16 PS 3/30/16-DDA 202T 2CDL 033 202 R1630 652629 1.25 10 3-phase busbars, connection of DDA 202 and DS 202 with auxiliary, end caps PSB-END 3 28 3 16 PS 3/28/16H-DDA 202T 2CDL 034 202 R1628 652636 1.31 10 4-phase busbars, connection of DDA 202 and DS 202, end caps PSB-END 4 (phase sequence L1-N-free-free-L2-N...) 30 4 16 PS 4/30/16N-DDA 202T 2CDL 040 202 R1630 652852 1.67 10 4-phase busbars, connection of DDA 202 and DS 202 with auxiliary, end caps PSB-END 4 30 4 16 PS 4/30/16NH-DDA 202T 2CDL 041 202 R1630 652599 1.72 10 4-phase busbars, connection of DDA 204 25 A and 40 A and DS 204 up to 40 A, end caps PSB-END 4 40 4 16 PS 4/40/16-DDA 204T 2CDL 040 204 R1640 652605 1.79 10 4-phase busbars, connection of DDA 204 25 A and 40 A and DS 204 up to 40 A with auxiliary, end caps PSB-END 4 (phase sequence L1-L2-L3-N-aux.(free)-free-free-free-free-L1) 36 4 16 PS 4/36/16H-DDA 204T 2CDL 041 204 R1636 652612 1.73 10 No. of Phases mm 2 Order Bbn Price Price Cu-No. Weight Pack pins details 4016779 1 piece group 1 piece unit Type code Order code EAN kg kg pc. System pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series

END 1.1 PS-END 0 PS-END Conn. Module Phases Order Bbn Price Price Weight Pack capacity details 4016779 1 piece group 1 piece unit mm2 Type code Order code EAN kg pc. End caps END 1.1 2CDL 200 011 R0011 638913 0.001 50 PS-END 0 2CDL 200 001 R0004 652261 0.001 50 PS-END 2CDL 200 001 R0001 514729 0.001 50 PS-END 1 2CDL 200 001 R0002 570114 0.001 50 PS-END SP 2CDL 200 110 R0001 646505 0.001 50 PS-END 1 SP 2CDL 200 110 R0002 646512 0.001 50 PS-END 3 2CDL 200 001 R3001 654302 0.001 50 PS-END 3.1 2CDL 200 001 R3002 654319 0.001 50 PSB-END 3 GHV0 361 325 R0001 556304 ➀ 0.001 50 PSB-END 4 GHV0 361 325 R0002 556403 ➀ 0.001 50 ➀ bbn-No. 4012233 System pro M compact® Accessories S 200, SN 201, F 200, DS 200 and other series Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series 2CSC400098F0201 2CSC400101F0201 2CSC400099F0201

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series PS 1/… PS 1/.../16 PS 1/.../30 PS 3/… (2CDL 231 …) PS 1/38 H PS 1/38/16 H PS 1/23/6 PS 1/29/6 PS 1/38/6 PS 1/57/6 H (integrierter Hilfskontakt) PS 2/12 PS 2/58 PS 2/58/16 PS 2/12 A PS 2/58/16 A PS 2/58 SP PS 2/58/16 SP PS 2/48 H PS 2/48/16 H PS 2/48/16 HA PS 2/48/16 SP PS 3/46/16 H-IT PS 3/39 H PS 3/39/16 H PS 1/38 NT 2CDC062166F0003 2CDC062389F0003 2CDC062021F0004 2CDC062390F0003 s0061z02 2CDC062527F0003 2CDC062526F0003 2CSC400010F0202 2CDC062148F0008 s0059z02 2CDC062019F0004 2CDC062092F0007

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series PS 3/12 PS 3/12 A PS 3/12/16 PS 3/60 PS 3/60/16 PS 3/60/30 PS 3/60 A PS 3/60/16 A PS 3/60 SP PS 3/60/16 SP PS 3/48 H PS 3/48/16 H PS 3/48/16 HA PS 3/48/16 SP PS 3/12 E 463 PS 4/12 PS 4/12/16 PS 4/60 PS 4/60/16 PS 4/12 A PS 4/60/16 A PS 4/60/16 SP PS 4/52/16 H PS 4/52/16 HA PS 4/52/16 SP PS 4/12 NA PS 4/58 N PS 4/58/16 N PS 4/58/16 NA PS 4/58/16 N SP PS 4/58/ NN A PS 4/58/16 NN A PS 4/48/16 NH A Example for overlap s0060z02 2CDC062530F0003 s0062z02s0023z01 s0250z02 s0063z02s0056z02SK0065Z02

PS 3/30/16-DDA 202 DS 202 + DS 202 + (DDA 202 + S 202) + (DDA 202 + S 202) ... DS 202 + S2C-S/H6R + (DDA 202 + S 202) + S2C-S/H6R ... PS 3/26/16H-DDA 202 PS 4/32-DDA 204 PS 4/32/16-DDA 204 DS 202 + DS 202 + DA 202 + S 202 + DDA 202 + S 202 ... PS 3/30/16-DDA 202 T DS 202 + S2C-S/H6R + DS 202 + S2C-S/H6R + DDA 202 + S 202 + S2C-S/H6R + DDA 202 + S 202 + S2C-S/H6R ... PS 3/28/16 H-DDA 202 T DS 202 + DS 202 + (DDA 202 + S 202) ... PS 4/30/16N-DDA 202 T DS 202 + S2C-S/H6R + DS 202 + S2C-S/H6R + (DDA 202 + S 202) + S2C-S/H6R + (DDA 202 + S 202) + S2C-S/H6R ... PS 4/30/16NH-DDA 202 T PS 4/40/16-DDA 204 T DS 204 (/L50872 40 A) + DS 204 (/L50872 40 A) + DDA 204 (/L50872 40 A) + S 204 + DDA 204 (/L50872 40 A) + S 204 ... PS 4/36/16 H-DDA 204 T DS 204 (/L50872 40 A) + S2C-S/H6R + DS 204 (/L50872 40 A) + S2C-S/H6R + DDA 204 (/L50872 40 A) + S 204 + S2C-S/H6R + DDA 204 (/L50872 40 A) + S 204 + S2C-S/H6R System pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series PS 2/30/16N-DDA 202T DS 202 + DS 202 + (DDA 202 + S 202) ...

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series PS 4/12 NA PS 4/58 N PS 4/58/16 N PS 4/58/16 NA PS 2/12 PS 2/12/16 PS 2/58 PS 2/58/16 PS 2/12 A PS 2758/16 A F 202 + F 202 + … PS 4748/16 NH A F 202 + S2C-S/H6R + F 202 + S PS 2/48 H PS 2/48/16 H PS 2/48/16 HA F 202 + S2C-S/H6R + F 202 + … PS 3/12 FI (2CDL 230 …) PS 3/9 FI PS 3/10 FI PS 3/57 FI F 204 + S 200 + S 200 + … PS 4/12 PS 4/12/16 PS 4/60 PS 4/60/16 PS 4/12 A PS 4/60/16 A F 204 + F 204 + … PS 3/12 FI H F 204 + S2C-S/H6R + S 200 + S 200 … PS 4/52/16 H PS 4/52/16 HA F 204 + S2C-S/H6R + … PS 4/58 NN A PS 4/58/16 NN A F 204 + F 202 + F 202 + … PS 3/11 PS 3/12 PS 3/12 A PS 3/12/16 PS 3/60 PS 3/60/16 PS 3/60 A PS 3/60/16 A F 204 (N links) + S 200 + S 200 … Beispiel für Überlappungen 1 x F 204 + 20 x S 201PS 1/3 PS 1/6 PS 1/9 PS 1/60 PS 1/60/16 F 202 + S 201 + S 201 + … 2CDC062443F0004 2CDC062437F0004 2CDC062440F0004 2CDC062438F0004 s0058z02 s0064z02 s0139z02 2CDC062441F0004 2CDC062442F0004 2CDC062439F0004 2CDC062141F0008 s0251z02

pro M compact® Selection tables Busbars and accessories for MCBs S 200, SN 201, RCDs F 200 and DS 200 series Accessories S 200, SN 201, F 200, DS 200 and other series DS 201 + S2C-S/H6R + DS 201… DS 202 + S2C-S/H6R + DS 202 C… PS 2/48 H PS 2/48/16 H PS 2/48/16 HA PS 4/48 NHA PS 4/48/16 NHA DS 201 + S2C-S/H6R + DS 201 … DS 202 + S2C-S/H6R + DS 202 … PS 3/12 A PS 3/60 A PS 3/60/16 A S 201 S 201 S 201 DS 201 DS 201 DS 202 C DS 202 C PS 2/12 PS 2/12 A PS 2/58 PS 2/58/16 PS 2/58/16 A DS 201 DS 201 … DS 202 C DC 202 C …PS 4/12 NA PS 4/58 N PS 4/58/16 N PS 4/58/16 NA DS 201 DS 201 … DS 202 C DC 202 C … PS 1/12 A PS 1/60 A PS 1/60/16 A S 201 S 201 S 201 DS 201 … DS 202 C … DS201 + S2C-S/H6R + DS201 ... DS202C + S2C-S/H6R + DS202C ... PS 2/48 H PS 2/48/16 H PS 2/48/16 HA 2CDC062054F0009 2CDC062053F0009 2CDC062056F0009 2CDC062052F0009 2CDC062052F0009 2CDC062057F00092CDC062055F0009

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series Sk 0103 Z99 BS 1/10 Rail connectors For wiring of component rails in the consumer unit, rail-to-rail clearance 125 mm. In the case of the 4-pole connector, the color of the N conductor is blue. 10 3-pole RV 3 GH V036 0504 R0023 512381 0.080 25 10 4-pole RV 4 GH V036 0504 R0024 512244 0.114 25 Auxiliary contact bridge for bottom-fitting auxiliary contacts Wire jumper for integrated auxiliary contact (MCB S200 H or auxiliary contacts S2C-H01/S2C-H10) for series connections (HKB) or parallel connections (HKB1). 1/2 mod. HKB GH V036 0504 R0100 523134 0.001 1000 1 mod. HKB 1 GH V036 0504 R0101 524209 0.001 1000 Shock-protection caps for PS... 5 parts SZ-BSK 2CDL 200 001 R0011 420006 0.003 10 5 parts BSK* 2CDL 200 001 R0012 649834 0.003 10 * closed version Shock-protection caps for busbars PS...BP - see page 4/26 PS...SP - see page 4/27 Labelling system Package comes with 40 labels, marked or blank. Blank labels can be labeled by hand with an inde- lible, waterproof pen or using a computerised labelling system (plotter). identification labels blank BS GH S200 1946 R0001 478106 0.004 30 identification labels BS Pikto GH S200 1946 R0002 478205 0.004 30 with pictograms identification labels BS 1/10 GH S200 1946 R0003 478304 0.004 30 marked 4 x 1 – 10 identification labels BS 1/20 GH S200 1946 R0004 478403 0.004 30 marked 2 x 1 – 20 identification labels BS 1/40 GH S200 1946 R0005 478502 0.004 30 marked 1 – 40 identification labels BS 41 – 80 GH S200 1946 R0006 585910 0.004 30 marked 41 – 80 identification labels BS 81 – 120 GH S200 1946 R0007 585927 0.004 30 marked 81 – 120 identification labels BS 121/160 GH S200 1946 R0008 585934 0.004 30 marked 121 – 160 Identification system ILS The ILS individual identification sytem for labels is a DIN A5 polyester film for ink jet and laser printers with high temperature resistance. (If laser printers are used, please check whether self-adhesive film with thickness of 250 μm can be fed.) Adhesive coating 3MTM9471 LE has obtained UL approval (file No. MH 11410). There are two types of sheet: uncut for making individual labels or precut with 23 stripes (6 x 191 mm each) for labelling 11 devices (1-module width) per stripe. Word template can be downloaded from www.abb.de/stotz-kontakt. Can also be used as write-on labels (ink, ballpoint pen, pencil, marker). 1 sheet DIN A5 uncut for laser printer ILS-L 2CDL 200 002 R0003 663076 0.011 1 1 sheet DIN A5 precut in 23 stripes (6 x 191 mm) for laser printer ILS-LS 2CDL 200 002 R0004 663083 0.011 1 1 sheet DIN A5 uncut for inkjet printer ILS-I 2CDL 200 002 R0005 663090 0.011 1 1 sheet DIN A5 precut in 23 stripes (6 x 191 mm) for inkjet printer IILS-IS 2CDL 200 002 R0006 663106 0.011 SZ-BSK SK 0121 Z 01 RV 4 SK 0120 Z 01 RV 3 BSK 2CSC400096F0201 identification label /L50518 2CSC400427F0201 2CSC400450F0201

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series SZ-DB 121 SZ-DB 232 N SZ-DB 125 N example 1 wiring of devices consisting of modules with different lengths with SZ-DB 125 N or 312 Conn. Terminal Type of Order Bbn Cu No. Price Price Weight Pack capacity Iug connection details 4016779 1 piece group 1 piece unit mm2 LxW mm Type code Order code EAN kg pc. Terminals, insulated with pin contact 6-25 15/4 90° Ast 25/15 QS 2CDL200010R2515 656535 0.012 50 6-25 15/4 straight Ast 25/15 S 2CDL200011R2515 656542 0.012 50 6-25 15/6 90° Ast 25/15 Q 2CDL200000R2515 656474 0.012 50 6-25 22/4 90° Ast 25/22 QS 2CDL200010R2522 669436 0.012 50 6-25 30/4 90° Ast 25/30 QS 2CDL200010R2530 656481 0.012 50 6-25 30/6 90° Ast 25/30 Q 2CDL200000R2530 656498 0.014 50 6-50 15/4 90° Ast 50/15 QS 2CDL200000R5015 656504 0.014 50 6-50 15/4 straight Ast 50/15 S 2CDL200011R5015 656566 0.014 50 6-50 15/7 90° Ast 50/15 Q 2CDL200010R5015 656559 0.014 50 6-50 15/7 straight Ast 50/15 2CDL200001R5015 656511 0.014 50 5-50 17.5/7 90° Ast 50/18 Q 2CDL200100R5018 656580 0.019 50 6-50 17.5/7 straight Ast 50/18 2CDL200101R5018 656573 0.019 50 6-50 32/6 90° Ast 50/32 Q 2CDL200000R5032 656528 0.017 50 25-95 21/6.5 straight SZ-Ast 95 gk* GHV0360501R0012 522618 0.06 0.067 50 25-95 21/6.5 straight SZ-Ast 95* GHV0360501R0013 522625 0.06 0.067 50 Abbreviations: Q terminal 90° * not for pro M compact S narrow connection pin Technical features Connection capacity 6-25 mm 2 6-50 mm 2 25-95 mm 2 Max. electrical load 63 A 100 A 225 A Max. operating voltage 600 V AC 600 V AC 690 V AC Max. tightening torque 2 Nm 3 Nm 19 Nm Feeder terminals Single-pole terminals can be mounted side by side with multipole terminals. 6-35 SZ-ESK 2 2CDL200001R3501 646765 0.024 10 6-50 SZ-ESK 3 2CDL200003R5001 652575 0.025 10 6-50 SZ-ESK 3 S 2CDL200003R5003 652889 0.024 10 Flexible connecting wires with fork-type cable lug (black) Conn. Length Order Bbn Cu No. Price Price Weight Pack capacity details 4012233 1 piece group 1 piece unit mm2 Type code Order code EAN kg pc. 6 125 SZ-DB 121 GH V036 1425 R0001 55650 2 0.006 0.025 1000/50 10 135 SZ-DB 122 N GH V036 1425 R0031 55670 0 0.010 0.02 500/25 6 260 SZ-DB 231 N GH V036 1425 R0032 55680 9 0.014 0.02 500/25 10 SZ-DB 232 N GH V036 1425 R0033 55690 8 0.022 0.04 250/25 10 330 SZ-DB 311 GH V036 1425 R0034 55700 4 0.029 0.05 100/25 with fork-type cable lug and ultrasonic compacted cable ends (black) 6 125 SZ-DB 123 GH V036 1425 R0006 55660 1 0.007 0.01 1000/50 10 135 SZ-DB 124 N GH V036 1425 R0035 55710 3 0.012 0.02 500/25 6 260 SZ-DB 235 GH V036 1425 R0036 55720 2 0.014 0.02 500/25 10 SZ-DB 236 GH V036 1425 R0037 55730 1 0.024 0.04 250/25 Advantages: - smaller dimensions for the same cross-section (more space in terminal) - nearly no transition resistances - more reliability; conductor sleeves could be loosen under specific conditions 2CSC400038F0201 Ast 25/15 QS Ast 25/15 Q Ast 25/30 QS Ast 25/30 Q Ast 50/15 QS Ast 50/15 Q Ast 50/18 Q Ast 50/32 Q SZ-Ast 95 gk Ast 25/15 S Ast 50/15 S Ast 50/15 Ast 50/18 SZ-Ast 95 Ast 50/32 Q SZ-ESK 2 SZ-ESK 3 SZ-ESK 3 S S0068Z94 S0118Z012CDC062220F0005 s0187z02 S0133b99 2CDC062244F0005 2CDC062245F0005

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series SZ-N6/3 SZ-KLB 8, 12, 16, 24 SZ-Ktr SZ-Ktr with KLB SZ-N11/3 SZ-6/3 with ultrasonic compacted cable ends (black) 6 125 SZ-DB 125 N GH V036 1425 R0038 55740 0 0.007 0.01 1000/50 6 260 SZ-DB 233 N GH V036 1425 R0039 55750 9 0.015 0.02 500/25 10 135 SZ-DB 126 N GH V036 1425 R0040 55760 8 0.013 0.02 500/25 10 260 SZ-DB 234 N GH V036 1425 R0041 55770 7 0.025 0.04 250/25 10 330 SZ-DB 312 GH V036 1425 R0042 55780 6 0.032 0.05 100/25 with ultrasonic compacted cable ends (blue) 10 135 SZ-DB 10/135 N 2CDL 200 301 R0135 66352 6 0.013 0.02 25 10 260 SZ-DB 10/260 N 2CDL 200 301 R0260 66353 3 0.025 0.04 25 10 330 SZ-DB 10/330 N 2CDL 200 301 R0330 66354 0 0.032 0.05 25 Advantages: - smaller dimensions for the same cross-section (more space in terminal) - nearly no transition resistances - more reliability; conductor sleeves could be loosen under specific conditions Input Output Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit mm2 mm 2 Type code Order code EAN kg pc. Neutral or protective-conductor terminals without insulation holder 1 x 16 6 x to 16 SZ-6/3 GH V036 0876 R0003 50592 5/L54706 0.022 10 1 x 16 2 x to 16 SZ-KLB 8 GJ I232 0131 R0001 59660 7 0.025 30 6 x to 10 1 x 16 2 x to 16 SZ-KLB 12 GJ I232 0071 R0013 59530 3 0.035 30 10 x to 10 1 x 35 4 x to 16 SZ-KLB 16 GJ I232 0072 R0017 59540 2 0.077 30 12 x to 10 1 x 35 4 x to 16 SZ-KLB 24 GJ I232 0073 R0016 59550 1 0.100 30 20 x to 10 Holders for SZ-KLB terminals Screw-fixing SZ-KLB 8 and 12 each 1 piece required SZ-KLB 16 and 24 each 2 pieces required SZ-Ktr GJ I202 4027 R0001 59450 4 0.003 100 Neutral and protective-conductor terminals with insulation holder for quick fastening onto DIN rails EN 50 022 Neutral with blue insulation holder; type C finger safe, conductor opening closed on one side 1 x 16 6 x 16 SZ-N 6/3 GH V036 0876 R0001 55570 3 0.027 20 1 x 16 11 x 16 SZ-N 11/3 GH V036 0876 R0002 55580 2 0.043 20 1 x 16 6 x 16 SZ-N 6/3 C GH V036 0876 R0011 57095 4 ➀ 0.028 20 1 x 16 6 x 16 SZ-N 11/3 C GH V036 0876 R0012 57096 1 ➀ 0.046 20 Protective conductor with green/yellow insulation holder; type C finger safe, conductor opening closed on one side 1 x 16 6 x 16 SZ-PE 6/3 GH V036 0876 R0004 55600 7 0.027 20 1 x 16 11 x 16 SZ-PE 11/3 GH V036 0876 R0005 55610 6 0.043 20 1 x 16 6 x 16 SZ-PE 6/3 C GH V036 0876 R0014 57097 8 ➀ 0.028 20 1 x 16 11 x 16 SZ-PE 11/3 C GH V036 0876 R0015 57098 5 ➀ 0.046 20 ➀ bbn-No. 40 16779 2CSC400335F0201 2CSC400438F0201 2CSC400451F02012CSC400440F0201 2CSC400444F0201 2CSC400452F0201

Example of application with SN 201 breakers Feed-in 25-15 BS9 1/12 NA BS9 1/12 Feed-in 25-15 Busbars for SN 201 range No. pins Phases Cross Order Bbn Price Price Weight Pack section details 8012542 1 piece group 1 piece unit mm 2 Type code Order code EAN kg pc. 12 1 10 BS9 1/12 2CSL910001R1012 047650 0.050 10 12 1 10 BS9 1/12 NA 2CSL910011R1012 047759 0.050 10 56 1 10 BS9 1/56 2CSL910001R1056 047353 0.140 10 56 1 10 BS9 1/56 NA 2CSL910011R1056 047452 0.140 10 12 3 10 BS9 3/12 2CSL930001R1012 047551 0.090 5 57 3 10 BS9 3/57 2CSL930001R1057 047858 0.470 5 Busbars for F200/S200 and SN 201 range 2 + 10 x 1+N 2 10 BF2-S9 UP 1N/12 2CSL920009R1012 046950 0,110 5 4 + 8 x 1+N 4 10 BF2-S9 UP 3N/12 2CSL940009R1012 047056 0,110 5 2 + 10 x 1+N 2 10 BF2-S9 DOWN 1N/12 2CSL920002R1012 047155 0,110 5 4 + 8 x 1+N 4 10 BF2-S9 DOWN 3N/12 2CSL940002R1012 047254 0,110 5 Terminals, insulated Conn. Type of Terminal Order Bbn Price Price Weight Pack capacity connect. lug L details 8012542 1 piece group 1 piece unit mm2 mm Type code Order code EAN kg pc. 25 pin 15 FEED-IN 25/15 1P 2CSL980001R2515 047957 0.010 5 25 pin 30 FEED-IN 25/30 3P 2CSL980001R2530 048053 0.010 5 End caps Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. BS9-END 3P /L54706 2CSL980001R0001 064251 0.001 20 /L54706 In combination with BS9 3/57 BF2-S9 DOWN 3N/12 L1 L2 L3 N L1 N BF2-S9 UP 1N/12 2CSC400148F0201 2CSC400146F0201 System pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series Feed-in 25-30 3P (x3) BS9 1/12 NA BS9 3/12 Feed-in 25-15 1P Phase 3 Phase 2 Phase 1 1+N systems 3+N systems 2CSC400020F0202

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series DSW 6 DSW 4 DSW 3 DSW 2 DSW 1 SZ-FB 45.53-1 SZ-FB 45.53-3 Length Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit mm Type code Order code EAN kg pc. DIN rails DIN rails (DIN EN 60 715 – 35 x 7.5) for individual installation with 2 screws on an even surface (1 module = 17.5 mm) for 1 module DSW 1 GH S210 1926 R0001 13580 6 0.060 10 for 2 modules DSW 2 GH S210 1926 R0002 13590 5 0.012 10 for 3 modules DSW 3 GH S210 1926 R0003 13600 1 0.018 10 for 4 modules DSW 4 GH S210 1926 R0004 13610 0 0.024 10 for 6 modules DSW 6 GH S210 1926 R0006 13620 9 0.036 10 DIN rail DIN EN 60 715, 35 x 7.5, material thickness 1 mm, surface protected, galvanised. 241 SKV-GTS 1 GH L110 1915 R0001 04090 2 0.09 40 DIN rails DIN EN 60 715, 35 x 7.5, material thickness 1 mm, surface galvanised. 1000 SZ-SI 45.460 GJ I232 2218 R0001 59730 7 0.35 10 2000 SZ-TS 7.5 L2 GJ I232 2218 R0007 59760 4 0.70 20 DIN rails DIN EN 60 715, 35 x 15, material thickness 1.5 mm, surface galvanised 2000 SZ-SI 45.472 GJ I232 2218 R0010 59780 2 1.30 10 2000 SZ-TS 15 L2 GJ I232 2218 R0009 59770 3 0.78 10 Spring catch for mounting devices onto DIN rails (DIN EN 60 715, 35 x 7.5) for screw type M4 SZ-FB 45.53-3 GJ I184 2013 P0003 64560 2 0.03 50 for screw type M5 SZ-FB 45.53-1 GJ I184 2013 P0004 64580 0 0.03 50 False poles Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. False pole - 1 module FP1 16021765 061304 0.01 100 False pole - 2 modules FP2 16021773 061403 0.014 50 False pole - 4 modules FP4 16021781 061502 0.022 30 False pole - 6 modules FP6 16021799 061601 0.031 20 Support for false pole SFP 16021831 061700 0.012 100 SKV-GTS 1 SZ-SI 45.460 SZ-TS 7.5 L2 SZ-SI 45.472 SZ-TS 15 L2 2CSC400048F0201 2CSC400045F0201 2CSC400449F02012CSC400047F02012CSC400049F0201 2CSC400046F02012CSC400448F0201 2CSC400107F02012CSC400529F0201 2CSC400108F0201

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series Height of Width Order Bbn Price Price Weight Pack cutout/color details 4012233 1 piece group 1 piece unit mm mm Type code Order code EAN kg pc. Blanking plates For device covers with materials of a thickness of 1 to 3 mm, width: 1 module = 17.5 mm; color: grey RAL 7035, white RAL 9001 46/grey 213 SZ-BP 1 GH L530 1904 R0001 06050 4 0.028 100 46/white 17.5 SZ-BP GH S270 1913 R0001 12857 4 /L54706 0.005 46/grey 17.5 SZ-BP 2 GH S270 1913 R0002 12861 1 /L54706 0.005 46/grey 220 SZ-BP 12 G 2CDL 000 001 R1220 65227 8 /L54706 0.022 50 46/white 220 SZ-BP 12 W 2CDL 000 001 R2220 66355 7 /L54707 0.020 50 Description Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. Locking devices for SZ-BP 12 G SZ-BP R 2CDL 000 001 R1001 652285 /L54706 0.001 30 Sealing plate Seal-proof locking of stamped-out device covers. Detachable only from the inside of the device cover. Can be used for device covers with 1.5 to 3 mm material thickness. Height of Width Order Bbn Price Price Weight Pack cutout/color details 4012233 1 piece group 1 piece unit mm mm Type code Order code EAN kg pc. 46/grey 1500 SZ-VP 1500 GJ I995 9038 R0001 60290 2 0.366 10 Rotary operating mechanism For the actuation of 2-, 3- or 4pole miniature circuit-breakers in closed distribution boards for drive- axles of 5 or 6 mm2 (square) S2C-DH GH S200 1901 R0003 57960 5 /L54706 0.01 25 End bracket Prevents lateral shifting of built-in devices mounted on DIN rails according to DIN EN 60 715, 35 x 7.5 mm. END GJ I100 1814 R0001 59090 2 0.02 50 Filling piece e.g. for heat dissipation of closely mounted devices that generate much heat. Width 8.75 mm, as spacer, two different heights, breakable, for DIN rails according to DIN EN 60 715, 35 x 7.5 mm. 8.75 SZ-FST 2 GH L530 1908 R0002 06070 2 0.01 25 Spring piece Holder for device covers, various heights available (in connection with FST 2 filling piece) SZ-FDT 2 GH L530 1908 R0005 06080 1 0.002 25 Filling piece Two different heights, breakable, for DIN rails according to DIN EN 60 715, 35 x 7.5 mm for MCBs S 220 (3 different heights) 8.75 SZ-FST GH I148 0003 R0001 59410 8 0.01 25 /L54706 bbn-Nr. 4016779 SZ-FDT 2 END S2C-DH SZ-BP 1 SZ-VP 1500 SZ-B SZ-BP 2 SZ-FST 2 + SZ-FDT 2 SZ-FST SZ-BP 12 G SZ-BP R 2CSC400064F0201 2CSC400041F0201 2CSC400050F02012CSC400054F0201 2CSC400042F0201 2CSC400446F02012CSC400043F0201 2CSC400102F0201

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series SZ-ES 68/83 SA 1 SA 2 KA 27 H + KA 27 S PCD 2 N PCD 4 N PCD 8 N Description Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. Elevation piece Compensates for different size of built-in devices with a mounting height of 68 mm and power MCBs of series S500 (83 mm) SZ-ES 68/83 GH V021 1425 R0001 53390 9 0.003 100 Locking device for MCBs and switches Prevents unauthorised or dangerous operation of the operating lever. An adaptor makes it possible to block the operating lever whether switched ON or OFF. The lever is blocked with a padlock having a cross bar section of 3 or, as the case may be, 6 mm max. For multipole devices, one lock may be fitted per pole. The lock adaptor can be used for all MCBs of the S 220, S 280 series as well as for switches E 200. The lock adaptor SA 1/S 290 can be used for all MCBs of the S 290 series. locking devices 3 mm SA 1 GJ F110 1903 R0001 58760 5 ➁ 0.004 10 for padlock bar 6 mm SA 1E GJ F110 1903 R0004 58790 2 ➁ 0.004 10 locking devices 3 mm SA 1/S 290 GJ F110 1903 R0007 58261 2 ➀ 0.004 10 for S 290, padlock bar padlock with 2 keys SA 2 GJ F110 1903 R0002 58770 4 ➁ 0.02 10 padlock, identical locking with 2 keys SA 2 i GJ F110 9999 R0001 96940 1 ➁ 0.02 10 lock adaptor incl. padlock with 3 keys in transparent box SA 3 GJ F110 1903 R0003 58780 3 ➁ 0.05 10 Terminal cover KA 27 Provides overall touch protection of live parts. Suitable for installations acc. to DIN EN 50274 (DIN VDE 0660 Part 514) and BGV A2. End parts can be snapped onto mounting rails EN 60 715, 35 mm. Covers are 486 mm = 27 modules (18 mm each) long. Knockouts for each half module for individualised use. cover, 1 piece KA 27 H GH S210 1933 R0001 13630 8 0.104 10 end part, 1 piece KA 27 S GH S210 1934 R0001 13640 7 0.027 10 Terminal covers with base plate, protection IP 40 Material: high-impact and flame-retardant (UL 94 V-0), color: white (RAL 9001), glow-wire test 960 °C according to IEC 695-2-1 The base plate has an integrated top-hat rail for snap-on fixing of MCBs, RCDs, modular built-in devices, etc. for 2 modules PCD 2 N GH S270 1921 R0002 12402 6 ➀ 0.09 1 for 4 modules PCD 4 N GH S270 1921 R0004 12404 0 ➀ 0.15 1 for 6 modules PCD 6 N GH S270 1921 R0006 12406 4 ➀ 0.2 1 for 8 modules PCD 8 N GH S270 1921 R0008 12408 8 ➀ 0.7 1 Common terminals for terminal covers PCD for PCD 4 N and 6 N KL-PCD 4/6 GH S270 1912 R0004 12502 3 ➀ 0.017 for PCD 8 N KL-PCD 8 GH S270 1912 R0008 12592 7 ➀ 0.079 ➀ bbn-No. 80 00126 ➁ bbn-No. 40 16779 2CSC400454F0201 2CSC400453F0201 2CDC051130F00082CSC400437F0201 2CSC400435F0201 2CSC400053F0201

pro M compact® Selection tables Accessories for S 200, SN 201, F 200, DS 200 and other series Accessories S 200, SN 201, F 200, DS 200 and other series Insulated housings IP 55 come with DIN rail according to DIN EN 60 715 and cable entry grommet without N + PE common terminals (see SMO) Material: high-impact and flame-retardant (UL 94 V-0), color grey (RAL 7035), glow-wire test 960 °C according to IEC 695-2-1 Type with Enclosed Order Bbn Price Price Weight Pack knock-outs cable details 8000126 1 piece group 1 piece unit grommets ø in mm Type code Order code EAN kg pc. housings for 4 modules 2 x Ø 27 2 QES 4/3 N GH L111 2304 R0013 12644 0 0.370 18 housings for 6 modules 2 x Ø 27 2 QES 6/3 N GH L111 2306 R0013 12646 4 0.440 12 housings for 10 modules 6 x Ø 32 3 QES 10/3 N GH L111 2310 R0013 12650 1 0.690 10 N + PE common terminals for QES (IP 55) Neutral and protective-conductor terminals with insulation holder for screw-fixing Description Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. for QES 4/3 N SMO 4 GH L430 1910 R0004 12880 2 0.093 10 for QES 6/3 N SMO 6 GH L430 1910 R0006 12882 6 0.125 10 for QES 10/3 N SMO 10 GH L430 1910 R0010 12884 0 0.105 10 Flanges Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Flange for rear board fixing 1 module - IP40 ME 1 16219300 304401 0.040 1 Flange for rear board fixing 2 modules - IP40 ME 2 16219318 304500 0.045 1 Flange for rear board fixing 3 modules - IP40 ME 3 16219326 304609 0.055 1 Flange for rear board fixing 4 modules - IP40 ME 4 16219334 304708 0.060 1 Flange for rear board fixing 6 modules - IP40 ME 6 16219342 304807 0.070 1 Flange for rear board fixing 8 modules - IP40 ME 8 16219359 304906 0.080 1 QES 4/3 N SMO... 2CSC400410F02012CSC400533F0201 2CSC400351F0201

series of MCBs are supported by a whole group of auxiliary elements with many functions and configurations. Undervoltage releases, shunt trips, auxiliary contacts, signal contacts, mechanical interlocks are available. A wide range of auxiliary elements considerably improves the performance of the MCBs and enables inno-va- tive and integrated solutions to be used in every installation. The S 290 circuit-breakers are supplied with special shunt tri- ps, undervoltage releases and contacts (auxiliary and signal). All the accessories are instal- led to the right of the circuit- breaker. The left part is used for installing RCD blocks. Also S800 MCBs series is completed with a wide range of accessories which includes auxiliary and signal contacts, separating neutral, rotary han- dles and interchangeable adap- ter kits. All the auxiliary elements are installed to the left side of the circuit breakers. The right part is used for instal- ling DDA 800 RCD blocks. 2CSC400188F0201

S 280, S 290 and S800 series and for RCD-blocks DDA 800 Index Selection tables of auxiliary elements for MCBs S 280 series Schemes for combination of auxiliary elements and Technical features of auxiliary elements and accessories for MCBs S 290 series ... 4 /51 Selection tables of auxiliary elements for MCBs S 290 series Schemes for combination of auxiliary elements and Selection tables of auxiliary elements and accessories for MCBs S800 series

Schemes for combination and technical features Auxiliary elements for MCBs S 280 series ST UR UR ST S/H H S S 280 H S S/H S H Auxiliary contact S Signal contact UR Undervoltare release ST Shunt trip Combination between auxiliary elements and S 280 Technical characteristics of auxiliary and signal contacts Type S2-H11 I S2-H20 I S2-H02 I S2-H21 S2-H12 S2-H30 S2-H03 S2-H11 X S2-H20 X S2-H02 X Description 1NO+1NC 2NO 2NC 2NO+1NC 1NO+2NC 3NO 3NC Min.operating voltage [V] 12 a.c.-12 d.c. Min. operating current [mA] 12 Terminals [mm 2] up to 2x1.5 Dielectric strength [kV] 3 Resistance to short-circuit at 240 V a.c. [A] 1000 (protected with S 2 breaker characteristic K - 6 A) Impulse voltage withstand capacity [kV] 4 Tightening torque [Nm] 0.7 Dimensions (WxDxH) [mm] 8.75x68x90 NB: the auxiliary contacts S2-H11 X, S2-H20 X, S2-H02 X differ from the contacts S2-H11, S2-H20, S2-H02 in that they do not have a terminal to tighten the cable which is replaced by a bayonet for the Faston connection. 2CSC400021F0202

Technical characteristics of undervoltage releases Type S2-UA 12 S2-UA 24 S2-UA 48 S2-UA 110 S2-UA 220 S2-UA 380 Standards VDE0660 part I - IEC EN 60947.1 Rated [V] a.c. - 24 48 110 220-240 380 voltage [V] d.c. 12 24 - 110 220-240 380 Frequency [Hz] 50...60 Release trip [V] 0.35 Un ≤V≤0.7 Un Terminals [mm 2] 2 x 1.5 Consumption [mA] 10 Resistance to corrosion [°C/RH] const. climatic cond.: 23/83-40/93-55/20; var. climatic cond.: 25/95-40/93 Protection degree IP20 Tightening torque [Nm] 0.4 Dimensions (WxDxH) [mm] 17.5x68x90 Technical characteristics of shunt trips Type S2-A1 S2-A2 Rated voltage [V] a.c. 12 - 60 110 - 415 d.c. 12 - 60 110 - 250 Max. release duration [ms] <10 <10 Min. release [V] voltage a.c. 7 55 d.c. 10 80 Consumption on release [VA] 12 V a.c. 35 12 V d.c. 30 24 V a.c. 140 24 V d.c. 100 48 V a.c. 600 48 V d.c. 330 110 V a.c. 40 110 V d.c. 40 220 V a.c. 180 220 V d.c. 170 Coil resistance [ Ω] 3.7 225 Terminals [mm 2] 25 25 Tightening torque [Nm] 2 2 Dimens.(WxDxH) [mm] 17.5x68x90 17.5x68x90 S2-S S2-SH 1 change over 2 change over 240 415 6 2 250 110 60 24 0.5 1 1 4 12 a.c.-12 d.c. up to 2x1.5 1000 (protected with S 2 breaker characteristic K - 6 A) 0.7 8.75x68x90 System pro M Technical features Auxiliary elements for MCBs S 280 series

Description Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. Shunt trips Function: remote opening of the device when a voltage is applied Suitable for MCBs S 280 and S 280 UC series 12-60 VAC/VDC shunt trip S2-A1 GH S280 1909 R0001 42930 1 0.145 1 110-415 VAC and 110-250 VDC shunt trip S2-A2 GH S280 1909 R0002 42940 0 0.145 1 Auxiliary contacts Function: indication of the position of the device’s contacts Suitable for MCBs S 280 and S 280 UC series Signal contacts Function: indication of the position of the device’s contacts only after the automatic release of the MCBs and RCBOs due to an overload or a short-circuit Suitable for MCBs S 280 and S 280 UC series Auxiliary contact 1 NO + 1 NC (1/2 module) S2-H11 GH S270 1916 R0001 61500 1 0.04 1 Auxiliary contact 2 NO (1/2 module) S2-H20 GH S270 1916 R0002 61510 0 0.04 1 Auxiliary contact 2 NC (1/2 module) S2-H02 GH S270 1916 R0003 61520 9 0.04 1 Auxiliary contact 1 NO +

1 NC (1/2 module) with

Faston connections S2-H11X GH S270 1917 R0001 61530 8 0.04 1 Auxiliary contact 2 NO (1/2 module) with Faston connections S2-H20X GH S270 1917 R0002 61540 7 0.04 1 Auxiliary contact 2 NC (1/2 module) with Faston connections S2-H02X GH S270 1917 R0003 61550 6 0.04 1 Auxiliary contact 2 NO + 1 NC (1/2 module) S2-H21 GH S270 1936 R0001 01370 3* 0.05 1 Auxiliary contact 1 NO + 2 NC (1/2 module) S2-H12 GH S270 1936 R0002 01380 2 * 0.05 1 Auxiliary contact 3 NO (1/2 module) S2-H30 GH S270 1936 R0003 01390 1* 0.05 1 Auxiliary contact 3 NC (1/2 module) S2-H03 GH S270 1936 R0004 01400 7* 0.05 1 Signal contact (1/2 module) S2-S GH S280 1902 R0008 12770 7* 0.07 1 Signal contact + Auxiliary contact (1/2 module) S2-S/H GH S280 1901 R0008 42900 4 0.05 1 * Bbn 4016779 System pro M Selection tables Auxiliary elements for MCBs S 280 and S 280 UC series Auxiliary elements for S 280 and S 280 UC series 11 21 31 12 22 32 13 23 33 14 24 34 11 21 33 12 22 34 11 23 33 12 24 34 11 21 12 22 13 23 14 24 13 21 14 22 96 98 96 98 96 98 Automatic opening Manual opening 12 14 96 98 12 14 96 98 12 14 96 98 Automatic opening Manual opening S2-A1 I, S2-A2 I S2-H11 S2-H20 S2-H02 S2-H21 S2-H12 S2-H30 S2-H03 S2-h11 X S2-H20 X S2-H02 X S2-S S2-S/H 2CSC400498F0201 2CSC400497F0201 2CSC400495F02012CSC400499F0201

Auxiliary elements for MCBs S 280 and S 280 UC series Auxiliary elements for S 280 and S 280 UC series Undervoltage releases Function: protection of the load in the event of a voltage drop (between 70% and 35% of its rated value); positive safety (device’s tripping when the voltage is disconnected) emergency stop by means of a button. Suitable for MCBs S 280 and S 280 UC series Description Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. Undervoltage release 12V DC (1 module) S2-UA 12 GH S280 1911 R0001 42970 7 0.09 1 Undervoltage release 24V AC/DC (1 module) S2-UA 24 GH S280 1911 R0002 42980 6 0.09 1 Undervoltage release 48V AC/DC (1 module) S2-UA 48 GH S280 1911 R0003 79360 0 0.09 1 Undervoltage release 110V AC/DC (1 module) S2-UA 110 GH S280 1911 R0004 43000 0 0.09 1 Undervoltage release 220V AC/DC (1 module) S2-UA 220 GH S280 1911 R0005 43010 9 0.09 1 Undervoltage release 380V AC (1 module) S2-UA 380 GH S280 1911 R0006 79370 9 0.09 1 Hand operated neutral The hand operated neutral has to be mounted to the left side of the MCB and be snaped on the DIN rail. It is used for measuring duties where the neutral conductor must be in the open position. Due to the special design of the handle - when switching ON the MCB – the neutral will make before the MCB is closed. The S2C - Nt is not to switch with a tool (screw driver). Hand operated neutral S2-NT GH S270 1908 R0001 36610 1 0.06 1 2CSC400503F0201

Auxiliary elements and accessories for MCBs S 290 series ST H or S h or S DDA for S 290 S 290 H or S UR HS H or S 122,5 H Auxiliary contact S Signal contact ST Shunt trip UR Undervoltare release Combination between auxiliary elements and S 290 2CSC400022F0202

Auxiliary elements and accessories for MCBs S 290 series Technical characteristics of shunt trips Type S 290 A1 S 290 A2 Rated voltage [V] Max. release duration [ms] <10 <10 Peak-up power [W] 110 V AC/ DC: 8 24 V AC/ DC: 23

415 V AC: 153 48 V AC/ DC: 108

Terminals solid conductor [mm 2] 2 x 1.5 max strandet conductor 2 x 1 max flexible conductor 2 x 1 max Tightening torque [Nm] 2 2 Dimensions (WxDxH) [mm] 17.5x68x90 17.5x68x90 Technical characteristics of undervoltage releases Type S290-UA 24 S290-UA 110 S 290-UA 230 Standards VDE0660 part I - IEC EN 60947.1 Rated [V] a.c. 230 voltage [V] d.c. - Frequency [Hz] 50...60 Release trip threshold [V] 0.35 Un≤V≤0.7 Un Terminals [mm 2] 2x1.5 Consumption [W] 2,3 1,74 1,44 Resistance to corrosion [°C/RH] constant atmosphere: 23/83-40/93-55/20; variable atmosphere: 25/95-40/93 Protection degree IPXXB/IP2X Tightening torque [Nm] 0.4 Dimensions (WxDxH) [mm] 17.5x68x90 Technical characteristics of auxiliary and signal contacts Type S 290 H11 S 290 S Description 1NO+1NC Alternating Ue [V] 230/400 current (AC 13) Ie [A] 6/2 Direct Ue [V] 24/60/110/220 current (DC 13) Ie [A] 6/3/1/1 Min. operating current [mA] 5 Terminals solid conductor [mm 2] 1 x 0.5 ...1 x 4 Dielectric strength [kV] 3 Resistance to short- [A] 1000 (protected with circuit at 240 V a.c. breaker char. K 6 A) Impulse voltage withstand capacity [kV] 4 Tightening torque [Nm] 0.5 Dimensions (WxDxH) [mm] 8.75x68x90

Description Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. Shunt trips Function: remote opening of the device when a voltage is applied Suitable for MCBs S 290 series 110-415V AC/110 DC shunt trip S 290 A1 GH S290 1909 R0011 57033 6 0,09 1 24-48V AC/DC S 290 A2 GH S290 1909 R0012 57034 3 0,09 1 Auxiliary contact Function: indication of the position of the device’s contacts Suitable for MCBs S 290 series Signal contact Function: indication of the position of the device’s contacts only after the automatic release of the MCBs and RCBOs due to an overload or a short-circuit Suitable for MCBs S 290 series Auxiliary contact 1 NO +

1 NC (1/2 module) S 290 H11 GH S290 1916 R0011 57031 2 0,05 1

Signal contact (1/2 module) S 290-S11 GH S290 1902 R0018 57032 9 0,05 1 Undervoltage releases Function: protection of the load in the event of a voltage drop (between 70% and 35% of its rated value); positive safety (device’s tripping when the voltage is disconnected) emergency stop by means of a button. Suitable for MCBs S 290 series Undervolage release DC

24 V S 290-UA 24 GH S290 1911 R0012 57035 0 0,09 1

110 V S 290-UA 110 GH S290 1911 R0014 57036 7 0,09 1

230 V S 290-UA 230 GH S290 1911 R0015 57037 4 0,09 1

2CSC400496F02012CSC400500F02012CSC400397F0201

Auxiliary switch S700 + H2WR

2 Switch-over contacts

Conv. thermal current Ith 10 A Min. operating voltage 24 V AC/DC Min. switching power 5 VA ➀ Short-circuit withstand capability 1000 A @ 230 V AC with S 200 K6 back-up Isolation coordination – overvoltage category III – pollution degree 2 – surge withstand capability 4 kV (1.2/50 μs) Wiring up to 2 x 1.5 mm Contact reliability under 5 g, 20 cycles 5…150…5 Hz @ 24 V AC/DC, 5 mA –> contact ➀ the min. operating current under operating conditions acc. to EN 60204-1 and EN 60439-1 (indoor installation): 24 V AC/DC, 5 mA (AC 12, DC 12) S700 + H2WR AC 14 Ue 400 V 230 V Ie 2 A 6 A DC 12 Ue 220 V 110 V Ie 1 A 1.5 A DC 13 Ue 60 V 24 V Ie 2 A 4 A

Application Order Bbn Price Price Weight Pack details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. DIN rail adapter for mounting S 700 onto 1 or 2 DIN rails 35 mm acc. to EN 50022 (distance of DIN rails 125 mm when using 2 DIN rails) no. to be used: S701: 1 pc. S 700 BT 3 GHS7 001 902 R0003 28440 0 ➀ 10 S 702, S703, S704: 2 pc Busbar adapter for mounting onto 40 mm busbar systems, 4 or 5 pole, with busbars 5 x 12 mm or 10 x 12 mm single phase: L1 or L2 or L3 (adjustable) S 700 SA 1 GHS7 001 917 R0001 25430 4 ➀ 0.105 1 3-phase S 700 QA GHS7 001 106 R0001 52793 4 ➀ 0.35 1 Terminal covers, 2 per pole within the shape of S 700 S 700 KA 1 GHS7 001 903 R0001 52050 3 0.001 6 for cutouts of 160 mm S 700 KA 2 GHS7 001 907 R0001 52090 9 0.01 6 for cutouts of 175 mm S 700 KA 3 GHS7 001 908 R0001 52100 5 0.01 6 with cable entry S 700 KA 4 GHS7 001 913 R0001 52140 1 0.015 6 for IP20 protection (front) S 700 KA 5 GHS7 001 903 R0005 24300 1 ➀ 0.003 6 Handle covers, 1 per pole to prevent manual switch-off S 700 SPA GHS7 001 905 R0001 52060 2 0.001 10 to prevent manual switch-off/-on transparent S 700 SPB 1 GHS7 001 906 R0001 52070 1 0.002 10 grey S 700 SPB 2 GHS7 001 906 R0002 52080 0 0.002 10 Locking for 3 mm padlock locking plate 3 pole S 700 SPE GHS7 001 909 R0001 52110 4 0.002 10 ➀ bbn-No. 4016779 System pro M Selection tables Accessories for S 700 S 700 BT 3 SK 0142 B 00 SK 0166 B 91 S 700 KA 2/3 S 700 KA 4 SK 0167 B 91 SK 0174 B 91 S 700 KA 5 SK 0072 B 96 S 700 SPA S 700 SPB 1 S 700 SPB 2 SK 0169 B 91 SK 0170 B 91 S 700 KA 1 S 700 QA S 700 SA 1 SK 0145 B 00 S 700-SPE SK 0079 Z 94 SK 119 B 02 Accessories for S 700 series

Auxiliary elements and accessories for MCBs S800 series System pro M compact ST or UR S800S/H H or S/H H DDA 800 S/H H or S/H H H Auxiliary contact S/H Signal/Auxiliary contact ST Shunt trip UR Undervoltare release Combination between auxiliary elements and S800 2CSC400023F0202

Short circuit limiter S803S-SCL Max. rated continuous current In [A] 32, 63, 125 Poles 3 Rated operating voltage Ue (AC) 50/60Hz [V] 400/690 Rated insulation voltage Ui [V] 690 Rated impulse withstand voltage Uimp [kW] 8 Ultimate short-circuit breaking capacity Icu in accordance with IEC 60947-2 400VAC [kA] 100 440VAC [kA] 100 690VAC [kA] 50 Valid combination see: http://www.abb.com/product Low Voltage Products and Systems/Modular DIN Rail Products/High Performance Circuit Breakers HPCBs/Software Service short-circuit breaking capacity Ics in accordance with IEC 60947-2 100% Icu Rated frequency [Hz] 50/60 Mounting position any Disconnector proporties according to IEC 60947-2 yes Standard IEC 60947-2 Connection Cu [mm 2] 1...25 strand 1...35 cable Connection Cu > 32 A [mm2] 6...50 strand 6...70 cable Tightening torque [Nm] min. 3/max. 4 Supply any Mounting on DIN top hat rail EN 60715 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Type of protection IP20 IP40 (only actuation side) Classification in accordance with NF-16-101, NF16-102 I3F2 Resistance to vibration IEC 60068-2-27; IEC 60068-2; EN 61373 Cat.1/ class B Rated current In Internal resistance Ri Power loss Pv [A] [m ] [W] 32 1.7 1.7 63 1.0 4.0 125 0.6 9.4 Auxiliary contact S800-AUX Utilisation category AC15 400/2A AC15 240/6A DC13 250/0.55A DC13 125V/1.1A DC13 60V/2A DC13 24V/4A Continuous thermal current In [A] 6 Rated insulation voltage Ui [V] 690 Number of contacts 2 Rated impulse withstand voltage Uimp [kV] 6 Pollution degree 3 Function of contact Changeover contacts Connection Cu [mm 2] 1 x 2.5 2 x 1.5 Tightening torque [Nm] 1 AC/DC supply any Mounting on DIN top hat rail EN 60715 Type of protection IP20 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Mech. device service life 6000 switching cycles Icu with S450E [A] 1000 Resistance to vibration IEC 60068-2-6; EN 61373 Cat.1/class B 5g, 20 frequency cycle at 24V AC/DC, 5mA brief interrupt <10ms Combined auxiliary and signal contact S800 AUX/ALT Utilisation category AC15 400/2A AC15 240/6A DC13 250/0.55A DC13 125V/1.1A DC13 60V/2A DC13 24V/4A Continuous thermal current In [A] 6 Rated insulation voltage Ui [[A]] 690 Number of contacts 2 (1x AUX, 1 x AUX/ALT) Rated impulse withstand voltage Uimp [kV] 6 Pollution degree 3 Function of contact Changeover contacts Connection Cu [mm 2] 1 x 2.5 2 x 1.5 Tightening torque [Nm] 1 AC/DC supply any Mounting on DIN top hat rail EN 60715 Type of protection IP20 Permissible ambient temperature for operations [°C] -25...+60 Storage temperature [°C] -40...+70 Mech. device service life 6000 switching cycles Icu with S450E [A] 1000 Resistance to vibration IEC 60068-2; EN 61373 Cat.1/class B 5g, 20 frequency cycle at 24V AC/DC, 5mA brief interrupt <10ms Remote switch unit S800-RSU-H Operating voltage [V] 24 DC Current consumption Irms [A] 2.5 Stand-by current [mA] < 50 Switching time OFF-ON [ms] < 500 Switching time ON-OFF [ms] < 250 Ambient operation temperature [°C] -25…+70 Switching cycles over lifetime 10000 Standard IEC 60947-2 Annex N Protection IP20 Weight [g] 300 Connection 10 pole Micro Fit 3.0

Shunt Operation Release S800-SOR S800-SOR24 S800-SOR130 S800-SOR250 S800-SOR400 Operating range [%] Ue 70...110 Rated insulation voltage Ui [V] 690 42...310 /L54706 23...119 20...105 /L54706 45...148.1 Rated frequency [Hz] DC; 50/60 Pollution degree 3 Connection Cu [mm2] 1...25 strand 1...35 cable Tightening torque [Nm] min.3/ max.4 AC/DC supply any DIN top hat rail EN 60715 Type of protection IP20 IP40 (only actuation side) Permissible ambient temperature of operations [°C] -25...+60 Storage temperature [°C] -40...+70 Resistance to vibration IEC 60068-2-6; EN61373 Cat.1/class B Undervoltage Release S800-UVR S800-UVR36 S800-UVR60 S800-UVR130 S800-UVR250 Operating range Operating opening [%] Ue 35...70 Operating closing [%] Ue 85 Rated insulation voltage Ui [V] 690 Rated frequency [Hz] DC; 50/60 Pollution degree 3 Standard IEC 60947-5-1, UL 489 Connection Cu [mm2] 1...25 strand 1...35 cable Tightening torque [Nm] min.3/ max.4 AC/DC supply any DIN top hat rail EN 60715 Type of protection IP20 IP40 (only actuation side) Permissible ambient temperature of operations [°C] -25...+60 Storage temperature [°C] -40...+70 Resistance to vibration IEC 60068-2-6; EN61373 Cat.1/class B /L54706 according to UL 489 Busbar S803-BB250 Max. rated continuous current In Side supply [A] 125 Central supply [A] 250 Conditional short circuit current Ip [kA eff] 100 protected by Tmax Poles 3 Rated operating voltage Ue (AC) 50/60Hz [V] 400/690 Rated insulation voltage Ui [V] 690 Rated impulse withstand voltage Uimp [kV] 8 Rated frequency [Hz] 50 Standards EN 60439-2:2000 Material of the bars E-Cu 58 half-hard rolled F25 Material of the insulation profile Cycoloy C 3600; UL94 V-0 at 1.5mm Material of the end caps Polyamide PA66+PA6; UL94 V-0 at 0.4mm Free of halogen and phosphorus Busbar cross-sections [mm 2]6 0 Overvoltage category III Polution degree 2 Busbar Power Connector S803-BBPC120 Max. rated continuous current In [A] 250 Poles 3 Rated operating voltage Ue [V] 400/690 Rated frequency [Hz] 50 Standards EN 60439-2:2000 Material of the terminals CuZn39Pb2; material no.:2.0380 Casing material Polyamide PA66+PA6; UL94 V-0 at 0.4mm Free of halogen and phos- phorus Tightening torque At supply end [Nm] 19 At busbar end [Nm] 3 Connection cross-section [mm 2] 1.6...120 Polution degree 2

Description Order Bbn Price Price Weight Pack details 7612271 1 piece group 1 piece unit Type code Order code EAN kg pc. Remote switching unit Remote switching unit S800-RSU-H 2CCS800900R0501 411244 0.300 1 Description Order Bbn Price Price Weight Pack details 7612271 1 piece group 1 piece unit [A] Type code Order code EAN kg pc. Short-circuit current limiters with cage terminal 32 S803S-SCL32 2CCS800900R0291 208912 0.735 1 63 S803S-SCL63 2CCS800900R0301 208929 0.735 1 125 S803S-SCL125 2CCS800900R0281 208905 0.735 1 Short-circuit current limiters with ring terminal cable connection 32 S803S-SCL32-R 2CCS800900R0332 408916 0.735 1 63 S803S-SCL63-R 2CCS800900R0331 208950 0.735 1 125 S803S-SCL125-R 2CCS800900R0311 208936 0.735 1 Description Order Bbn Price Price Weight Pack details 7612271 1 piece group 1 piece unit Type code Order code EAN kg pc. Auxiliary contact Auxiliary contact S800-AUX 2CCS800900R0011 206802 0.049 1 Combined auxiliary and signal contact Auxiliary/signal contact S800-AUX/ALT 2CCS800900R0021 206819 0.050 1 Separating neutral Separating neutral 63A S800-NT 2CCS800900R0061 208196 0.115 1 System pro M compact® breaker is not included 2CSC400025F02022CCC413019F00022CCC413020F00012CCC413069F00012CCC413070F00012CCC413067F0001

Description Order Bbn Price Price Weight Pack details 7612271 1 piece group 1 piece unit Type code Order code EAN kg pc. Shunt operation releases 12VAC/DC S800-SOR12 2CCS800900R0191 212070 0.15 1 24VAC/DC S800-SOR24 2CCS800900R0191 208318 0.15 1 48...130VAC/DC S800-SOR130 2CCS800900R0221 208349 0.15 1 110...250VAC/DC S800-SOR250 2CCS800900R0211 208332 0.15 1 220...400VAC/DC S800-SOR400 2CCS800900R0231 208356 0.15 1 Under voltage releases 24...36VAC/DC S800-UVR36 2CCS800900R0241 208363 0.15 1 48...60VAC/DC S800-UVR60 2CCS800900R0251 208370 0.15 1 110...130VAC/DC S800-UVR130 2CCS800900R0261 208387 0.15 1 220...250VAC/DC S800-UVR250 2CCS800900R0271 208394 0.15 1 Rotary drive adapter for 3-4-pole High Performance MCB Rotary Drive S800-RD 2CCS800900R0041 208172 0.080 1 Order Bbn Price Price Weight Pack details 8015644 1 piece group 1 piece unit Type code Order code EAN kg pc. Anthracite/Standard rotary handle for door assembly Anthracite rotary handle S800-RHE-H 1SDA060150R1 625771 0.21 1 Red/Emergency rotary handle for door assembly Red rotary handle S800-RHE-EM 1SDA060151R1 625764 0.21 1 Axial extension of rotary drive – rotary handle 500mm Axial extension 500mm for RHE S800-RHE-S 1SDA060179R1 626242 0.19 1 Selection tables Accessories for MCBs S800 series Accessories for S800 series System pro M compact 2CCC413239F2CCC413240F2CCC413061F00012CCC413062F00012CCC413064F0001

and RCD-blocks DDA 800 series Accessories for S800 and RCD-blocks DDA 800 series System pro M compact UL locking device UL locking device S800U-PLL 2CCS800017R0001 215057 0.03 2 Interchangeable adapter kit Cage Terminal S800N-CT2125 2CCS800900R0471 212049 0.03 2 Cage Terminal S800N-CT4125 2CCS800900R0461 212032 0.06 4 Interchangeable adapter kit Ring Terminal cable connection S800-RT2125 2CCS800900R0161 208240 0.03 2 Ring Terminal cable connection S800-RT4125 2CCS800900R0131 208219 0.06 4 IP54 protection for rotary handle IP54 kit S800-RHE-IP54 1SDA060180R1 626259 0.075 1 Description Order Bbn Price Price Weight Pack details 7612271 1 piece group 1 piece unit Type code Order code EAN kg pc. Intermediate piece Intermediate Piece 9mm S800-IP9 2CCS800900R0031 20820 2 0.011 1 Padlock device Padlock Lever Lock with 4mm hasp S800-PLL 2CCS800900R0051 208189 0.0015 1 2CCC413068F00012CCC413066F00012CCC413308F00012CCC413045F00012CCC413046F0004

and RCD-blocks DDA 800 series Accessories for S800, S500 and DDA 800 series System pro M compact Busbar Busbar 250A S803-BB250 2CCS800900R0071 208288 1.5 1 Supply block Busbar Power Connector 120mm2 S803-BBPC120 2CCS800900R0101 208301 0.46 1 Contact protection cap Busbar Isolation Cap S800-BBIC 2CCS800900R0081 208967 0.02 12 End cap End cap S800-END 2CCS800900R0091 208295 0.04 10 S 800-ILS Identification Labeling System 168x6x11.5mm S800-ILS 2CCS800900R0121 208271 0.011 1 Auxiliary elements and accessories for S500 Description Order Bbn Price Price Weight Pack details 761227 1 piece group 1 piece unit Type code Order code EAN kg pc. Auxiliary contact 1 NO and 1 NC contact S500-H11 2CCF008681R0001 0305506 0.06 1 2 NO contacts S500-H20 2CCF008682R0001 0305513 0.06 1 Signal contact 1 NO and 1 NC contact S500-S11 2CCF008684R0001 0305537 0.06 1 2 NO contacts S500-S20 2CCF008685R0001 0305544 0.06 1 Remote switch unit Remote switch unit S500-RSU-H 2CCF017987R0001 1407780 0.3 1 Auxiliary elements and accessories for DDA 800 RCD-blocks Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Ring tongue terminal kit DDA 800-RT 2CSB100913R0001 987406 0.01 1/12 breaker is not included 2CCC413057F0001 2CCC413058F0001500868150086842CSC400025F02022CSC400680F0001

The following chapter shows other protection devices in addition to the MCBs and RCDs ones.: Surge protective devices OVR: they are aimed at protecting electrical and electronic equipment against overvoltages and impulse currents (such as switching and lighting surges). SPDs feature the following two functions: - they limit overvoltage to a level acceptable by the equipment to be protected - they divert surge currents Fuse holders can protect against short circuits and overloads. They are available in the following versions: - E 90 fuse switch disconnectors that can disconnect circuits under load - E 90 and E 930 fuse holders ranges suitable for use with gG and aM cylindrical fuse - E 90 PV fuse disconnectors, designed for operating voltages of 1000 V d.c. with utilization category DC-20 Cylindrical fuses gG and aM cylindrical fuse series to protect against short circuits and overloads. The range can cover a wide range of sizes, up to 690 V AC, and in PV version up to 1000 V DC. The E 9F series is the ideal completion for the ABB range of E 90 fuse switch disconnectors, E 9F fuseholders and E 930 fuse disconnectors. Insulation monitoring devices Moreover ABB offers a wide range of insulation monitoring devices: For medical location - ISOLTESTER/ SELVTESTER insulation monitoring devices for medical locations - QSD remote signalling panel For industrial environments - ISL insulation monitoring devices TI insulating transformers for medical use: permanently connected to an IT power supply system they provide galvanic separation between the distribution network and the loads. QSO Complete electrical switchboard for medical locations : they are the ideal solution for distribution within group II medical locations, allowing monitoring of all network parameters.

OVR Surge Protective Devices Type 1 & Type 1+2 System pro M compact SPDs TECHNICAL FEATURES Type 1 OVR T1 25 TS Technology Triggered spark-gap Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class 1 / I Poles 1P - 1P - , 2P 2L 3P 3L 4P 4L 1P+N 1N 3P+N 3N Types of networks IT - TNS TNS-TNC TNC TNS TT - TNS TT - TNS Type of current A.C. Nominal voltage Un (L-N/L-L) V 400 230 230/400 230/400 230/400 Max. cont. operating voltage Uc V 440 255 -- Max. cont. operating voltage Uc (L-N / N- ) V- - 255 / 255 255 / 255 Impulse current Iimp (10/350) per pole kA 25 25 - - Impulse current Iimp (10/350) (L-N / N- ) kA - - 25 / 50 25 / 100 Imax discharge current (8/20) per pole (Imax) k A --- - Imax discharge current (8/20) (L-N/N-terre) (Imax) k A --- - Nominal discharge current In (8/20) per pole kA 25 25 - - Nominal discharge current In (8/20 (L-N / N- ) kA - 25 / 50 25 / 100 Voltage protection level Up kV 2 2.5 - - Voltage protection level Up (L-N / N- ) kV - - 2.5 / 2 2.5 / 2 Follow current interrupting rating Ifi kArms 50 50 - - Follow current interrupting rating Ifi (L-N / N- ) kArms - - 50 / 0.1 50 / 0.1 TOV (Temporary overvoltage) withstand UT (5s.) V 690 400 - - TOV (Temporary overvoltage) withstand UT (L-N: 5s. / N- : 200ms.) V - - 400 / 1200 400 / 1200 Continuous operating current Ic mA None Short-circuit withstand capability kArms 50 Load current Iload (for V-wiring) A 125 Maximum back-up fuse gG/gL - Parallel Connection A ≤125 Serial Connection (V-wiring) A ≤125 Mechanical features Stocking and operating temperature °C -40 to +80 Degree of protection IP 20 Fire resistance according to UL 94 V0 Colour of Housing Polyarylamide grey RAL 7035 State indicator Option (with TS) TS remote indicator Option (TS) Installation Wire range (L, N, ) solid wire mm 2 2.5 ... 50 stranded wire mm 2 2.5 ... 35 Stripping length (L, N, ) mm 15 Tightening torque (L, N, ) Nm 3.5 TECHNICAL FEATURES OF THE INTEGRATED AUXILIARY CONTACT (TS) Electrical features Contact complement 1NO (1 normally open contact), +1NC (1 normally closed contact) Min. load 6 V D.C. - 10 mA Max. load 250 V A.C. - 5 A Continuous operating current mA 10 Installation Connection cross-section mm2 1.5

OVR Surge Protective Devices Type 1 & Type 1+2 System pro M compact SPDs Type 1 Type1+2 Type 1+2 Type 1+2 OVR T1 25 255-7 OVR T1+2 25 255 TS OVR T1+2 15 255-7 OVR T1+2 7 275 s P Triggered spark-gap Triggered spark-gap/varistor Triggered spark-gap Varistor IEC 61643-1 / EN 61643-11 IEC 61643-1 / EN 61643-11 IEC 61643-1 / EN 61643-11 IEC 61643-1 / EN 61643-11 1 / I 1/ I 1 / I 1 / I 1P - 3P+N 3N 1P - 3P+N 3N 1P - 3P 3L 4P 4L 1P+N 1N 3P+N 3N TNS-TNC TT - TNS TNS - TNC TNS-TNC TT - TNS TNS-TNC TNC TNS TT - TNS TT - TNS 230 230/400 230 230 230/400 230 230/400 230/400 230/400 255 - 255 255 - 275 275 275 / 255 - 255 / 255 - - 255 / 255 25 - 25 15 - 7 - - - 25 / 100 - - 15 / 50 - 7 / 12 7 / 12 - - 40 60 - 70 - - 25 - 25 15 - 6 - - - 25 / 100 - - 15 / 50 - 6 6 7- 1 5 7- N A - - 650 - 334 650 - 334 - - - 650 / 1200 - - 650 / 1200 - 334 / 1200 < 2 (LED) < 1 (Varistor leakage) < 2 (LED) < 1 50 50 50 50 - 125 - - ≤125 ≤125 ≤125 ≤50 NA 125 NA NA -40 to +80 -40 to +80 -40 to +80 -40 to +80 IP 20 IP 20 IP 20 IP 20 V0 V0 V0 V0 Polyarylamide grey RAL 7035 Polyarylamide grey RAL 7035 Polyarylamide grey RAL 7035 PC grey RAL 7035 Yes Yes Yes Yes No Yes No No 15 15 15 12.5 3.5 3.5 3.5 2.8 - 1NO (1 normally open contact), - - - +1NC (1 normally closed contact) - None - - - 1.5 - -

OVR Surge Protective Devices Type 2 System pro M compact SPDs TECHNICAL FEATURES Type 2 (pluggable) OVR T2 (s) P (TS) Technology Varistor Electrical features Standard IEC 61643-1 / EN 61643-11 Type / test class 2 / II Poles 1P - 3P 3L 4P 4L 3P+N 3N 1P - 3P3L 4P4L 1P+N 1N 3P+N 3N Types of networks IT - TNS IT* IT TT - TNS TNS-TNC TNC TNS TT-TNS TT-TNS Nominal voltage Un (L-N/L-L) V 400 230/400 230/400 230 230 400 230 230/400 Max. cont. operating voltage Uc V 440 440 - 275 - Max. cont. operating voltage Uc (L-N / N-PE) V -- 440 / 255 - 275 / 255 Max. cont. operating voltage Ucpv V Maximum discharge current Imax (8/20) per pole kA 15 40 70 40 70 - - - 15 40 70 - - - Maximum discharge current Imax (8/20) (L-N / N-PE) kA - - - - - 15 /70 40 /70 70 /70 - - - 15 /70 40 /70 70 /70 Nominal discharge current In (8/20) per pole kA 5 20 30 20 30 - - - 5 20 30 - - - Nominal discharge current In (8/20) (L-N / N-PE) kA - - - - - 5/30 20/30 30/30 - - - 5/30 20/30 30/30 Follow current interrupting rating Ifi kArms NA NA - NA - Follow current interrupting rating Ifi (L-N / N-PE) kArms - - NA / 0.1 - NA / 0.1 TOV (Temporary overvoltage) withstand Ut (5s.) V 440 440 440 440 - 334 - TOV (Temporary overvoltage) withstand Ut (L-N: 5s./N-PE: 200ms) V - - 440 / 1200 - 334 / 1200 Continuous operating current Ic mA < 1 < 1 < 1 < 1 < 1 Short-circuit withstand capability kArms 50 50 50 50 50 Short-circuit D.C. current withstand capability Iscwpv A Disconnector gG -gL fuse A ≤50 ≤50 ≤50 ≤50 ≤50 curve C circuit breaker A ≤50 ≤50 ≤50 ≤50 ≤50 Mechanical features Stocking and operating temperature °C -40 to +80 Degree of protection IP 20 Fire resistance according to UL 94 V0 Material of Housing PC grey RAL 7035 Pluggable cartridge Yes Integrated thermal disconnector Yes State indicator Yes Safety reserve Option (s) TS remote indicator Option (TS) Installation Wire range (L, N, ) solid wire mm2 2.5 ... 25 stranded wire mm2 2.5 ... 16 Stripping length (L, N, ) mm 12.5 Tightening torque (L, N, ) Nm 2.8 TECHNICAL FEATURES OF THE INTEGRATED AUXILIARY CONTACT (TS) Electrical features Contact complement 1NO (1 make contact), +1NC (1 normally closed contact) Min. load 12V D.C. - 10 mA Max. load 250V A.C. - 1 A Continuous operating current mA None Installation Connection cross-section mm2 1.5

OVR Surge Protective Devices Type 2 System pro M compact SPDs Type 2 (non pluggable) Type 2 (non pluggable) OVR Plus N1 40 OVR Plus N3 15 OVR Plus N3 40 OVR T2 275 Varistor IEC 61643-1 / EN 61643-11 EN 61643-11, IEC 61643-1 EN 61643-11, IEC 61643-1 IEC 61643-1 / EN 61643-11 2 / II T2/II T2/II 2 / II 1P+N N1 44 1P - 4P 4L TT - TNS TT-TNS TT-TNS TT* - TNS - TNC TNS 230/400 230/400 230/400 230 230/400 320 320 320 275 --- - - -- 15 40 20 / 40 15/60 40/60 - - --- 5 2 0 20 5/40 20/40 - - --- 1 1 . 4 --- 1 0 . 9 NA - - NA --- - --- 3 3 4 - 334/1200 334/1200 - < 1 <0.1 <0.1 < 1 15 10 15 50 Integrated MCB Integrated MCB Integrated MCB - ≤50 - ≤50 -40 to +80 -40 to +80 IP 20 IP 20 V0 V0 PC grey RAL 7035 PC grey RAL 7035 No No No No Yes Yes Yes Yes Yes (MCB) Yes (MCB) Yes (MCB) Yes No No No No Optional (S2C-H6R) ABB (2CDS200912R0001) Optional (S2C-H6R) ABB (2CDS200912R0001) Optional (S2C-H6R) ABB (2CDS200912R0001) No 11 11 11 12.5 2.8 2,8 2,8 2,8 --- - - --- - - --- - - --- - - --- - - --- - - NEW NEW

OVR Surge Protective Devices Type 2 System pro M compact SPDs TECHNICAL FEATURES Type 2 Photovoltaic Telecom / Dataline OVR PV P (TS) OVR TC VP Technology Varistor Electrical features Standard IEC 61643-1 / EN 61643-11 / UTE C 61-740-51 IEC 61643-21 Type / test class 2 / II TC Poles 3 1 pair Types of networks Photovoltaic D.C: Type of current D.C. D.C. Low current Nominal voltage Un (L-N/L-L) V 600 1000 6 12 24 48 200 200FR Max. cont. operating voltage Uc V - - 7 14 27 53 220 220 Max. cont. operating voltage Ucpv V 670 1000 - Maximum discharge current Imax (8/20) per pole kA 40 40 10 Nominal discharge current In (8/20) per pole kA 20 20 5 Nominal discharge current In (8/20) (L-N / N-PE) kA -- - Voltage protection level Up kV 1.4 3.8 15 20 35 70 700 400 Residual voltage Ures at 3 kA per pole kV Residual voltage Ures at 3kA (L-N / N-PE) kV Follow current interrupting rating Ifi kArms -- - Follow current interrupting rating Ifi (L-N / N-PE) kArms -- - TOV (Temporary overvoltage) withstand Ut (5s.) V -- - TOV (Temporary overvoltage) withstand Ut (L-N: 5s./N-PE: 200ms) V -- - Continuous operating current Ic mA < 0.05 < 0.05 140 Short-circuit withstand capability kArms -- - Short-circuit D.C. current withstand capability Iscwpv A 100 100 Disconnector If DC current >100 A If DC current >100 A gG -gL fuse A E90PV E90PV - Circuit breaker A S802PV-S10 S804PV-S10 - Mechanical features Stocking and operating temperature °C -40 to +80 -40 to +80 Degree of protection IP 20 IP 20 Fire resistance according to UL 94 V0 V0 Material of Housing PC grey RAL 7035 PC grey RAL 7035 Pluggable cartridge Yes Yes Integrated thermal disconnector Yes (specific PV) Yes Yes Yes Yes No Yes State indicator Yes No Safety reserve No No TS remote indicator Yes (TS option) No Installation Wire range (L, N, ) Stripping length (L, N, ) mm 12.5 - Tightening torque (L, N, ) Nm 2.8 - TECHNICAL FEATURES OF THE INTEGRATED AUXILIARY CONTACT (TS) Electrical features Contact complement -- Min. load -- Max. load -- Continuous operating current mA -- Installation Connection cross-section mm2 --

OVR Surge Protective Devices SPDsSystem pro M compact® 2CSC400316F02012CSC400313F02012CSC400313F0201 2CSC400306F02012CSC400315F02012CSC400315F0201 Surge Protective Devices, Type 1 / Type 1+2 Function: Type 1 and Type 1+2 SPDs are Lightning Current Arresters. They can handle and divert high energy from lightning. They are necessary when the installation is exposed to direct lightning (for example when the building is equipped with external lightning protection system or powered by aerial lines). They shall be installed at the line entrance of the installation (meter board or main distribution board). ABB Type 1 and Type 1+2 SPDs are tested with wave-shape 10/350. Additionnaly, Type 1+2 SPDs are also tested with wave-shape 8/20 to guarantee protection against overvoltage of low energy from remote lightning stroke or from switching operations. ABB Type 1+2 SPDs feature a better voltage protection level (Up) than Type 1 SPDs which make them suitable for protection of most of electrical and electronic equipment. Type 1 Neutral SPDs are for TT networks when used in combination with phase SPDs Type 1 or Type 1+2. Application: residential, commercial, industrial Standard: IEC 61643-1 / EN 61643-11 10/350 current wave for SPDs Type 1, 10/350 & 8/20 for SPDs Type 1+2, spark-gap technology (no blow-out). Nb. of Impulse Follow Voltage Nominal Max. cont. Order Bbn Price Price Weight Pack poles current current protection voltage operating details 3660308 1 piece group 1 piece unit Iimp interrupting level voltage (10/350) If i Up Un Uc kA kArms kV V V Type code Order code EAN kg pc. Type 1 (Ifi = 50 kA) TNS, TNC 1 25 50 2.5 230 255 OVR T1 25 255 2CTB815101R0100 510877 0.25 1 IT (230 / 400 V), TNC (400 / 690 V) 1 25 50 2 400 440 OVR T1 25 440-50 2CTB815101R9300 514929 0.27 1 TNS (1 Ph+N) 2 25 (2) 50 2.5 230 255 OVR T1 2L 25 255 2CTB815101R1200 510891 0.50 1 2 25 (2) 50 2.5 230 255 OVR T1 2L 25 255 TS (3) 2CTB815101R1100 510945 0.60 1 TT (1 Ph+N), TNS 1+N 25/50 (1) 50/0.1 (1) 2.5/2 (1) 230 255/255 (1) OVR T1 1N 25 255 2CTB815101R1500 510921 0.50 1 1+N 25/50 (1) 50/0.1 (1) 2.5/2 (1) 230 255/255 (1) OVR T1 1N 25 255 TS (3) 2CTB815101R1000 510976 0.60 1 TNC 3 25 (2) 50 2.5 230 255 OVR T1 3L 25 255 2CTB815101R1300 510907 0.75 1 3 25 (2) 50 2.5 230 255 OVR T1 3L 25 255 TS (3) 2CTB815101R0600 510952 0.85 1 TNS (3 Ph+N) 4 25 (2) 50 2.5 230 255 OVR T1 4L 25 255 2CTB815101R1400 510914 1.00 1 4 25 (2) 50 2.5 230 255 OVR T1 4L 25 255 TS (3) 2CTB815101R0800 510969 1.10 1 TT (3 Ph+N), TNS 3+N 25/100 (1) 50/0.1 (1) 2.5/2 (1) 230 255/255 (1) OVR T1 3N 25 255 2CTB815101R1600 510938 1.00 1 3+N 25/100 (1) 50/0.1 (1) 2.5/2 (1) 230 255/255 (1) OVR T1 3N 25 255 TS (3) 2CTB815101R0700 510983 1.10 1 (1) L-N / N- . (2) per pole. (3) TS: telesignal contact for remote control of the status of the Surge Protective Device.

OVR Surge Protective Devices SPDsSystem pro M compact® T1+T2 T1 (N+PE) 2CSC400297F0201 2CSC400299F0201 2CSC400300F0201 2CSC400297F0201 2CSC400299F0201 2CSC400306F0201 Nb. of Impulse Follow Voltage Nominal Max. cont. Order Bbn Price Price Weight Pack poles current current protection voltage operating details 3660308 1 piece group 1 piece unit Iimp 75% level voltage (10/350) If i Up Un Uc kA kArms kV V V Type code Order code EAN kg pc. Type 1 (Ifi = 7 kA) TNS, TNC 1 25 7 2.5 230 255 OVR T1 25 255-7 2CTB815101R8700 514110 0.12 1 TT (3 Ph+N), TNS 3+N 25/100 (1) 7/0.1 (1) 2.5/1.5 (1) 230 255/255 (1) OVR T1 3N 25 255-7 2CTB815101R8800 514127 0.60 1 OVR HL (Type 1 with varistors) TT, TNS, TNC, IT 1 15 NA 1.4 400 440 OVR HL 15 440 s P TS 2CTB815201R0800 509802 0.25 1 TNS 2 15 NA 1.4 400 440 OVR HL 2L 15 440 s P TS 2CTB815303R0400 509826 0.5 1 Type 1+2 (Iimp = 25 kA) TNS, TNC 1 25 15 1.5 230 255 OVR T1+2 25 255 TS (3) 2CTB815101R0300 510884 0.30 1 Type 1+2 (Iimp = 15 kA) TNS, TNC 1 15 7 1.5 230 255 OVR T1+2 15 255-7 2CTB815101R8900 514134 0.12 1 TT (3 Ph+N), TNS 3+N 15/50 (1) 7/0.1 (1) 1.5/1.5 (1) 230 255/255 (1) OVR T1+2 3N 15 255-7 2CTB815101R9000 514141 0.60 1 Type 1+2 (Iimp = 7 kA) 1 7 0 0.9 230 275 OVR T1+2 7 275s P 2CTB815101R3900 513403 0.12 1 2 7 0 0.9/1.4 230 275 OVR T1+2 1N 7 275s P 2CTB815302R1000 515728 0.27 1 4 7 0 0.9/1.4 230 275 OVR T1+2 3N 7 275s P 2CTB815502R1000 515735 0.5 1 3 7 0 0.9 230 275 OVR T1+2 3L 7 275s P 2CTB815101R4000 513410 0.4 1 4 7 0 0.9 230 275 OVR T1+2 4L 7 275s P 2CTB815101R4100 513427 0.5 1 - 7 0 0.9 230 275 OVR T1+2 7 275s C 2CTB815101R3800 513458 0.1 1 - 7 0 1.4 230 275 OVR T1+2 70 NC 2CTB815101R5100 515742 0.05 1 Type 1 Neutral For TT networks when used in combination with phase SPDs Type 1 or Type 1+2 1 25 0.1 < 4 - 690 OVR T1 25 N 2CTB815101R9700 517043 0.25 1 1 50 0.1 1.5 - 255 OVR T1 50 N 2CTB815101R0400 510853 0.25 1 1 100 0.1 2 - 255 OVR T1 100 N 2CTB815101R0500 510860 0.25 1 (1) L-N / N- . (3) TS: telesignal contact for remote control of the status of the Surge Protective Device. Bus bar For TT (3Ph+N) networks, this bus bar can be used to connect four single pole Type 1 & Type 1+2 SPDs (except for Type 1 with Ifi = 7 kA) - - - - - - Bus bar 3N 2CTB815102R0400 516091 0.005 50 1N 4L 2CSC400299F0201 2CSC400299F0201

OVR Surge Protective Devices SPDsSystem pro M compact® T2 Surge Protective Devices, Type 2 Function: Type 2 SPDs are surge arresters. They can handle energy from distant/ indirect lightning strikes or from switching operations. Type 2 SPDs can not discharge high energies from direct lightning like Type 1 SPDs but they feature lower protec- tion level (Up). They are recommended at the incoming of installation for locations with no exposure to direct lightning impulses. Application: residential, commercial, industrial Standard: IEC 61643-1 / EN 61643-11 8/20 current wave, varistor technology poles discharge discharge protection voltage operating details 3660308 1 piece group 1 piece unit current current level Un voltage Imax In Up Uc (8/20) (8/20) kA kA kV V V Type code Order code EAN kg ppc. Type 2 (pluggable) TNS, TNC 1 15 5 1.0 230 275 OVR T2 15 275 P 2CTB803851R2400 512840 0.12 1 1 40 20 1.4 230 275 OVR T2 40 275 P 2CTB803851R2300 512833 0.12 1 1 40 20 1.4 230 275 OVR T2 40 275s P 2CTB803851R2000 512826 0.12 1 1 40 20 1.4 230 275 OVR T2 40 275 P TS 2CTB803851R1700 514363 0.14 1 1 40 20 1.4 230 275 OVR T2 40 275s P TS (3) 2CTB803851R1400 512802 0.15 1 1 70 30 1.5 230 275 OVR T2 70 275 s P 2CTB803851R1900 512819 0.12 1 1 70 30 1.5 230 275 OVR T2 70 275s P TS (3) 2CTB803851R1300 512796 0.15 1 IT, TNS 1 15 5 1.5 400 440 OVR T2 15 440 P 2CTB803851R1100 512772 0.12 1 1 40 20 1.9 400 440 OVR T2 40 440 P 2CTB803851R1200 512789 0.12 1 1 40 20 1.9 400 440 OVR T2 40 440 s P 2CTB803851R0800 512765 0.12 1 1 40 20 1.9 400 440 OVR T2 40 440 P TS 2CTB803851R0500 514370 0.14 1 1 40 20 1.9 400 440 OVR T2 40 440s P TS (3) 2CTB803851R0200 512741 0.15 1 1 70 30 2 400 440 OVR T2 70 440 s P 2CTB803851R0700 512758 0.12 1 1 70 30 2.0 400 440 OVR T2 70 440s P TS (3) 2CTB803851R0100 512734 0.15 1 TNS, TNC, IT 1 120 60 2.5 400 440 OVR T2 120 440s P TS (3) 2CTB803951R1300 517036 0.12 1 TT, TN-S (1 Ph+N) (Common + Differential mode protection) 1+N 15/70 (1) 5 (1) 1.0/1.4 (1) 230 275/255 (1) OVR T2 1N 15 275 P 2CTB803952R1200 513106 0.22 1 1+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 1N 40 275 P 2CTB803952R1100 513250 0.27 1 1+N 40 /70 (1) 20 (1) 1.4/1.4 230 275/ 255 OVR T2 1N 40 275s P 2CTB803952R0800 513090 0.27 1 1+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 1N 40 275 P TS 2CTB803952R0500 514387 0.27 1 1+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 1N 40 275s P TS (3) 2CTB803952R0200 513076 0.27 1 1+N 70 /70 (1) 30 (1) 1.5/1.4 230 275/ 255 OVR T2 1N 70 275 s P 2CTB803952R0700 513083 0.27 1 1+N 70/70 (1) 30 (1) 1.5/1.4 (1) 230 275/255 (1) OVR T2 1N 70 275s P TS (3) 2CTB803952R0100 513069 0.27 1 TNC (common mode protection) 3 15 (2) 5 (2) 1.0 230 275 OVR T2 3L 15 275 P 2CTB803853R3400 512987 0.35 1 3 40 (2) 20 (2) 1.4 230 275 OVR T2 3L 40 275 P 2CTB803853R2400 513366 0.35 1 3 40 (2) 20 (2) 1.4 230 275 OVR T2 3L 40 275sP 2CTB803853R2200 512963 0.35 1 3 40 (2) 20 (2) 1.4 230 275 OVR T2 3L 40 275 P TS 2CTB803853R2500 514400 0.40 1 3 40 (2) 20 (2) 1.4 230 275 OVR T2 3L 40 275s P TS (3) 2CTB803853R2300 512970 0.40 1 3 70 (2) 30 (2) 1.5 230 275 OVR T2 3L 70 275 s P 2CTB803853R4100 512994 0.35 1 3 70 (2) 30 (2) 1.5 230 275 OVR T2 3L 70 275s P TS (3) 2CTB803853R4400 513007 0.40 1 TNS (3 Ph+N) 4 15 (2) 5 (2) 1.0 230 275 OVR T2 4L 15 275 P 2CTB803853R6000 513038 0.45 1 4 40 (2) 20 (2) 1.4 230 275 OVR T2 4L 40 275 P 2CTB 803853R5600 513274 0.45 1 4 40 (2) 20 (2) 1.4 230 275 OVR T2 4L 40 275sP 2CTB803853R5400 513021 0.45 1 4 40 (2) 20 (2) 1.4 230 275 OVR T2 4L 40 275 P TS 2CTB803853R5200 514417 0.50 1 4 40 (2) 20 (2) 1.4 230 275 OVR T2 4L 40 275s P TS (3) 2CTB803853R5000 513014 0.50 1 4 70 (2) 30 (2) 1.5 230 275 OVR T2 4L 70 275 s P 2CTB803919R0200 513045 0.45 1 4 70 (2) 30 (2) 1.5 230 275 OVR T2 4L 70 275s P TS (3) 2CTB803919R0400 513052 0.50 1 TT, TN-S (3 Ph+N) (Common + Differential mode protection) 3+N 15/70 (1) 5 (1) 1.0/1.4 (1) 230 275/255 (1) OVR T2 3N 15 275 P 2CTB803953R1200 513151 0.45 1 3+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 3N 40 275 P 2CTB803953R1100 513267 0.45 1 3+N 40 /70 (1) 20 (1) 1.4/1.4 230 275/ 255 OVR T2 3N 40 275sP 2CTB803953R0800 513144 0.45 1 3+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 3N 40 275 P TS 2CTB803953R0500 514394 0.50 1 3+N 40/70 (1) 20 (1) 1.4/1.4 (1) 230 275/255 (1) OVR T2 3N 40 275s P TS (3) 2CTB803953R0200 513120 0.50 1 3+N 70/70 (1) 30 (1) 1.5/1.4 230 275/255 OVR T2 3N 70 275 s P 2CTB803953R0700 513137 0.45 1 3+N 70/70 (1) 30 (1) 1.5/1.4 (1) 230 275/255 (1) OVR T2 3N 70 275s P TS (3) 2CTB803953R0100 513113 0.50 1 (1) L-N / N- . (2) per pole. (3) TS: telesignal contact for remote control of the status of the Surge Protective Device. The safety reserve(s) ensures a preventive maintenance of the installation. TT*: in TT network for L/N protection only

OVR Surge Protective Devices SPDsSystem pro M compact® poles discharge discharge protection voltage operating details 3660308 1 piece group 1 piece unit current current level Un voltage Imax In Up Uc (8/20) (8/20) kA kA kV V V Type code Order code EAN kg ppc. TT (3 Ph+N), TNS 3+N 15 5 1.5/1.4 (1) 230 440/255 (1) OVR T2 3N 15-440 P 2CTB803953R1300 3660308516800 0.45 1 3+N 40 20 1.9/1.4 (1) 230 440/255 (1) OVR T2 3N 40-440 P 2CTB803953R1400 3660308516817 0.45 1 3+N 40 20 1.9/1.4 (1) 230 440/255 (1) OVR T2 3N 40-440 P TS(3) 2CTB803953R1500 3660308516824 0 .45 1 3+N 40 20 1.9/1.4 (1) 230 440/255 (1) OVR T2 3N 40-440s P TS(3) 2CTB803953R1600 3660308516831 0.45 1 3+N 70 30 2/1.4 (1) 230 440/255 (1) OVR T2 3N 70-440s P 2CTB803953R1700 3660308516848 0.45 1 3+N 70 30 2/1.4 (1) 230 440/255 (1) OVR T2 3N 70-440s P TS(3) 2CTB803953R1800 3660308516855 0.45 1 TNC (3 Ph), IT 3 40 20 1.9 230 440 OVR T2 3L 40-440 P 2CTB803853R2600 516879 0.35 1 3 40 20 1.9 230 440 OVR T2 3L 40-440 P TS 2CTB803853R2700 516886 0.40 1 3 70 30 2 230 440 OVR T2 3L 70-440s P 2CTB803853R4200 516893 0.35 1 3 70 30 2 230 440 OVR T2 3L 70-440s P TS 2CTB803853R4300 516909 0.40 1 TNS, IT (3 Ph+N) 4 40 20 1.9/1.4 (1) 230 440 OVR T2 4L 40-440 P 2CTB803853R5100 516916 0.45 1 4 40 20 1.9/1.4 (1) 230 440 OVR T2 4L 40-440 P TS 2CTB803853R5300 516923 0.50 1 4 70 30 2/1.4 (1) 230 440 OVR T2 4L 70-440s P 2CTB803853R7000 516930 0.45 1 4 70 30 2/1.4 (1) 230 440 OVR T2 4L 70-440s P TS 2CTB803853R7100 516947 0.50 1 Type 2 Neutral 1 70 30 1.4 230 255 OVR T2 70 N P 2CTB803953R1900 516862 OVR Type 2 Special 24/48V AC & DC These type 2 SPD’s can be used in very low voltages & data lines for current higher than 140mA. 1 15 5 0.3 57 75 OVR 15 75 P 2CTB813851R2800 504647 0.12 1 1 15 5 0.3 57 75 OVR 15 75 P TS 2CTB813851R2700 504630 0.13 1 2 15 5 0.3/0.6 57 75 OVR 2 15 75 P 2CTB813852R1700 504609 0.22 1 2 15 5 0.3/0.6 57 75 OVR 2 15 75 P TS 2CTB813852R1600 504593 0.23 1 2 15 5 0.3/0.6 57 75 OVR 2 15 75s P TS 2CTB813852R1300 504579 0.23 1 Back-up protection by fuse: 16A gG under AC, 16A gR under DC Replacement cartridges for Surge Protective Devices Type 2 Phase cartridge, 75 V - 15 5 0.3 57 75 OVR 15 75 C 2CTB813854R1400 508892 0.10 1 Phase cartridge, 275 V - 15 5 1.0 230 275 OVR T2 15 275 C 2CTB803854R1200 513168 0.10 1 - 40 20 1.4 230 275 OVR T2 40 275 C 2CTB803854R1000 513182 0.10 1 - 40 20 1.4 230 275 OVR T2 40 275s C (1) 2CTB803854R0900 513199 0.10 1 - 70 30 1.5 230 275 OVR T2 70 275s C (1) 2CTB803854R0700 513229 0.10 1 Neutral cartridge for products OVR T2 1N (..) & OVR T2 3N (..), 275 V - 70 30 1.4 - 440 OVR T2 70 N C 2CTB803854R0000 513243 0.05 1 Phase cartridge, 440 V - 15 5 1.5 400 440 OVR T2 15 440 C 2CTB803854R0600 513175 0.10 1 - 40 20 1.9 400 440 OVR T2 40 440 C 2CTB803854R0400 513205 0.10 1 - 40 20 1.9 400 440 OVR T2 40 440s C (1) 2CTB803854R0300 513212 0.10 1 - 70 30 2.0 400 440 OVR T2 70 440s C (1) 2CTB803854R0100 513236 0.10 1 2CSC400310F0201 2CSC400307F0201 2CSC400310F0201 2CSC400303F0201 poles discharge discharge protection protection combination voltage operating details 3660308 1 piece group 1 piece unit current current level level wave Un voltage Imax In Up Up Uoc Uc (8/20) (8/20) at Uoc kA kA kV kV kV V V Type code Order code EAN kg ppc. Type 2 & Type 3 (non pluggable) T2+T3 2CSC400309F0201 2CSC400309F0201 2CSC400309F0201

OVR Surge Protective Devices SPDsSystem pro M compact® poles discharge discharge protection voltage operating details 3660308 1 piece group 1 piece unit current current level Un voltage Imax In Up Uc (8/20) (8/20) kA kA kV V V Type code Order code EAN kg ppc. Surge Protective Devices, Low current The transmission line pluggable surge arresters (OVR TC P) provide protection against transient overvoltages for quipment connected to telephone lines (digital or analog), computer links or current loops, for applications such as RS-485, or 4-20 mA. 1 10 5 0.015 6 OVR TC 6V P 2CTB804820R0000 515230 0.05 1 1 10 5 0.02 12 OVR TC 12V P 2CTB804820R0100 515247 0.05 1 1 10 5 0.035 24 OVR TC 24V P 2CTB804820R0200 515254 0.05 1 1 10 5 0.07 48 OVR TC 48V P 2CTB804820R0300 515261 0.05 1 1 10 5 0.7 200 OVR TC 200V P 2CTB804820R0400 515278 0.05 1 1 10 5 0.3 200 OVR TC 200FR P 2CTB804820R0500 515285 0.05 1 - 10 5 0.015 7 OVR TC 6V C 2CTB804821R0000 515292 0.02 1 - 10 5 0.02 14 OVR TC 12V C 2CTB804821R0100 515308 0.02 1 - 10 5 0.035 27 OVR TC 24V C 2CTB804821R0200 515315 0.02 1 - 10 5 0.07 53 OVR TC 48V C 2CTB804821R0300 515322 0.02 1 - 10 5 0.7 220 OVR TC 200V C 2CTB804821R0400 515339 0.02 1 - 10 5 0.3 220 OVR TC 200FR C 2CTB804821R0500 515346 0.02 1 1 - - - - - Base OVR TC RJ11 2CTB804840R1000 515599 0.02 1 2 - - - - - Base OVR TC RJ45 2CTB804840R1100 515605 0.04 1 Surge Protective Devices, Photovoltaic The specific OVR PV range offer a safe and efficient protection against transient overvoltages for equipments on photovoltaic installations. The OVR PV range comply with the UTE C 61-740-51 on surge protective devices connected to photo- voltaic generators. 3 40 20 1.4 670 100 OVR PV 40 600 P 2CTC803953R5300 516510 0.27 1 3 40 20 1.4 670 100 OVR PV 40 600 P TS 2CTC803953R5400 516527 0.27 1 3 40 20 3.8 1000 100 OVR PV 40 1000 P 2CTC803953R6400 516534 0.27 1 3 40 20 3.8 1000 100 OVR PV 40 1000 P TS 2CTC803953R6500 516541 0.27 1 OVR PV 600 V PV OVR TC P 200 V in parallel OVR TC P / xx V /

200 FR in series

2CSC400309F0201 2CSC400309F0201 GND LN auto-protected Type 2 (non pluggable) 1 15 5 1 230 275 OVR T2 15 275 2CTB804200R0100 514882 0.12 1 1 40 20 1,4 230 275 OVR T2 40 275 2CTB804201R0100 514103 0.12 1 4 15 5 1 230 275 OVR T2 4L 15 275 2CTB804600R0500 515612 0.45 1 4 40 20 1.4 230 275 OVR T2 4L 40 275 2CTB804601R0500 515988 0.45 1 OVR Plus with integrated end of life protection (auto-protected) N+1 40*/40 20/40 1.6/1.5 230 320/255 OVR Plus N1 40 2CTB803701R0100 517005 0.26 1 N+3 15/60 5/40 1.3/1.5 230/400 320 OVR Plus N3 15 2CTB803701R0400 517081 0.79 1 N+3 40/60 20/40 2/1.5 230/400 320 OVR Plus N3 40 2CTB803701R0300 517074 0.79 1 *Im = Imax MOV Replacement cartridges for Surge Protective Devices OVR PV - 40 20 1.4 670 100 OVR PV 40-600 C 2CTB803950R0000 516558 0.10 1 - 40 20 1.9 1000 100 OVR PV 40-1000 C 2CTB803950R0100 516565 0.10 1 - 70 30 1.4 1000 - OVR PV MC* 2CTB803950R0300 516756 0.10 1 NEW Nb. of Maxi. Nominal Voltage Max. Short circuit Order Bbn Price Price Weight Pack poles discharge discharge protection Cont. DC current details 3660308 1 piece group 1 piece unit current current level Operating withstand Imax In Up Voltage Iscwpv (8/20) (8/20) Ucpv kA kA kV V A Type code Order code EAN kg ppc. 2CSC400309F0201 2CSC400309F0201 2CSC400309F0201

E 90 fuse switch disconnectors E 90 series fuse switch disconnectors are designed for switching circuits under load, providing protection against short circuits and overloads. The case is made of self-extinguishing thermoplastic material resistant to high temperatures (all materials are UL listed) while the contact clips are in silver plated copper. E 90 fuse switch disconnectors can be sealed or padlocked to ensure operator safety during maintenan- ce. Versions with blown fuse indicator allow to check whether the fuse is still working correctly or not. For easy and quick installation E 90 range is totally compatible with connecting bars, terminals and caps of S 200 MCBs. Thanks to cURus approval, they can be installed in UL certified machines. E 90 fuse switch disconnectors for 10.3 x 38 mm fuses (AC-22B) Poles Rated Modules Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1 32 1 E 91/32 2CSM200923R1801 009238 0.061 6 1 32 1 E 91/32s 2CSM202483R1801 024835 0.062 6 1+N 32 2 E 91N/32 2CSM200893R1801 008934 0.130 3 2 32 2 E 92/32 2CSM200883R1801 008835 0.122 3 3 32 3 E 93/32 2CSM204753R1801 047537 0.183 2 3+N 32 4 E 93N/32 2CSM204733R1801 047339 0.252 1 4 32 4 E 94/32 2CSM204723R1801 047230 0.244 1 s: version with blown fuse indicator light E 90 fuse switch disconnectors for 8.5 x 31.5 mm fuses (AC-22B) 1 20 1 E 91/20 2CSM200983R1801 009832 0.061 6 1 20 1 E 91/20s 2CSM202423R1801 024231 0.062 6 2 20 2 E 92/20 2CSM200953R1801 009535 0.122 3 3 20 3 E 93/20 2CSM200943R1801 009436 0.183 2 s: version with blown fuse indicator light System pro M compact® Selection tables Protection devices E 90 fuse switch disconnectors 31.5 mm Ø 8.5 mm 38 mm Ø 10.3 mm 2CSC400696F02012CSC400694F0201

Fuse [mm] 8 x 31 10 x 38 Current type a.c. / d.c. Rated frequency [Hz] = / 50-60 Rated current [A] 20 32 Max power dissipation [W] 2.5 3 Tightening torque [Nm] PZ2 2-2.5 Terminal cross section [mm2]2 5 Protection degree IP20 Can be padlocked (open) ■ Can be sealed (closed) ■ IEC 60947-3 Rated operating voltage [V] 400 400 Utilization category AC-22B Markings IMQ, NF Alternate current characteristics according to IEC 60947-3 Rated operating voltage [V] 400 690 Utilization category AC-22B Direct current characteristics according to IEC 60947-3 Rated operating voltage [V] 400 690 Utilization category DC-20B* IEC 60269-1 Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 400 690 IEC 60269-2 Fuse system F Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 250 440 Breaking capacity [kA] 200 (a.c.) – 100 (d.c.) IEC 60269-3 Fuse system B Rated a.c. voltage [V] 400 IEC 60269-4 Fuse system F Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 400 690 UL 4248 Markings cURus * If the product is used with direct current, switching under load is not permitted. In this case, the warning “do not open und er load” must be visible in the front of the device. E 90System pro M compact® Selection tables Protection devices E 90 fuse switch disconnectors Electrical symbols 1P 1P+N 2P 3P 3P+N 4P 2CSC400030F0202

pro M compact® Selection tables Protection devices E 90 fuse switch disconnectors Materials Plastic parts Case: Material PA 6 +30% glass fibre Self extinguishing class: V2 (UL94) Temperature resistance: 130 °C Opening handle Material PA 66 +25% glass fibre Self-extinguishing class V0 (UL94) Temperature resistance: 140 °C Metal parts Clips Silver plated copper Clip spring Stainless steel Terminals Galvanized steel The E 90 series is environmental friendly and protects the health of people: all used materials are conform to the RoHS and REACH directives and they completely exclude hazardous substances and halogen. Utilization category Current type Utilization category Typical applications Alternating current AC-20A - AC-20B Connecting and disconnecting under no load (in this case the devices must be marked “Do not disconnect under load”) AC-21A - AC-21B Switching of resistive loads, including moderate overloads AC-22A - AC-22B Switching of mixed resistive/inductive loads, including moderate overloads AC-23A - AC-23B Switching of motors and other highly inductive loads Direct current DC-20A - DC-20B Connecting and disconnecting under no load (in this case the devices must be marked “Do not open under load”) DC-21A - DC-21B Switching of resistive loads, including moderate overloads DC-22A - DC-22B Switching of mixed resistive / inductive loads, including moderate overloads DC-23A - DC-23B Switching of motors or other highly inductive loads Suffix A Frequent use Suffix B Infrequent use Supply Load Supply Load Wiring of E 90 with blown fuse indicator light in alternate current 2CSC400357F0902 For direct current systems please refer to E 90 PV wiring diagram

E 90h fuseholders are suitable for protection against overloads and short circuits. Available in a single module 1P+N version and in a three-module 3P+N version, they are designed for use with gG and aM cylindrical fuse links. The body is made from self-extinguishing material resistant to high temperatures, while the contact clips are in silver-plated copper. E 90h fuseholders can be sealed or padlocked to assure operator safety during maintenance. Versions with blown fuse indicator allow to check whether the fuse is still working correctly or not. E 90h fuseholders for 10.3 x 38 mm fuses Poles Rated Modules Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1+N 32 1 E 91hN/32 2CSM200913R1801 009139 0.070 6 1+N 32 1 E 91hN/32s 2CSM206573R1801 065739 0.071 6 3+N 32 3 E 93hN/32 2CSM204743R1801 047438 0.192 2 s: version with blown fuse indicator light E 90h fuseholders for 8.5 x 31.5 mm fuses 1+N 20 1 E 91hN/20 2CSM200963R1801 009634 0.070 6 1+N 20 1 E 91hN/20s 2CSM200703R1801 007036 0.071 6 3+N 20 3 E 93hN/20 2CSM200933R1801 009337 0.192 2 s: version with blown fuse indicator light System pro M compact® Selection tables Protection devices E 90h fuseholders Fuse indicator LED Electrical symbols 31.5 mm Ø 8.5 mm 38 mm Ø 10.3 mm 2CSC400695F0201 2CSC400698F0201 1P+N 3P+N Technical features Type E 90hN/20 E 90hN/32 Fuse [mm] 8 x 31 10 x 38 Current type a.c. / d.c. Rated frequency [Hz] = / 50-60 Rated current [A] 20 32 Max power dissipation [W] 2.5 3 Tightening torque [Nm] PZ2 0.8-1.2 Terminal cross section [mm2]1 6 Protection degree IP20 Can be padlocked (open) ■ Can be sealed (closed) ■ IEC 60269-1 Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 400 690 IEC 60269-2 Fuse system F Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 250 440 Breaking capacity [kA] 200 (a.c.) – 100 (d.c.) IEC 60269-3 Fuse system B Rated a.c. voltage [V] 400 Markings IMQ IEC 60269-4 Fuse system F Rated a.c. voltage [V] 400 690 Rated d.c. voltage [V] 400 690 UL 4248 Mark cURus Note: NF mark is available on cu- stom versions with left sided neutral for French market 2CSC400030F0202 2CSC400030F0202

E 90 PV fuse disconnectors E 90 PV series fuse disconnectors, designed for operating voltages of 1000 V d.c. with utilization category DC-20B, are particularly suited for protection against overcurrents of photovoltaic systems. The single-pole or two-pole E 90 PV disconnectors for 10.3 x 38 mm cylindrical fuse links offer a reliable, compact and affordable solution for photovoltaic installations. Versions with blown fuse indicator allow to check whether the fuse is still working correctly or not. E 90 PV fuse disconnectors for 10.3 x 38 mm fuses (DC-20B) Poles Rated Modules Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1 32 1 E 91/32 PV 2CSM204713R1801 047131 0.061 6 1 32 1 E 91/32 PVs 2CSM204693R1801 046936 0.062 6 2 32 2 E 92/32 PV 2CSM204703R1801 047032 0.122 3 2 32 2 E 92/32 PVs 2CSM256913R1801 569138 0.233 3 s: version with blown fuse indicator light System pro M compact® Selection tables Protection devices E 90 PV fuse disconnectors Electrical symbols 38 mm Ø 10.3 mm 2CSC400697F0201 Technical features Type E 90/32 PV Fuse [mm] 10 x 38 Current type d.c. Rated frequency [Hz] - Rated current [A] 32 Max power dissipation [W] 3 Tightening torque [Nm] PZ2 2-2.5 Terminal cross section [mm2]2 5 Protection degree IP20 Can be padlocked (open) ■ Can be sealed (closed) ■ IEC 60947-3 Rated operating voltage [V] 1000 Utilization category DC-20B Wiring of E 90 PV with blown fuse indicator light in direct current In direct current systems, since the LED allows the current to flow only from positive to negative, the wiring of the blown fuse indicator version should follow the current direction as shown in the diagram Note: CCC mark is available on cu- stom versions for Chinese market 2CSC400031F0202 2CSC400030F0202

Protection and disconnection of 1000 V DC lines String protection To avoid equipments damage on DC lines and to ensure isolation of the PV system in case of maintenance, E90 PV disconnec- tors fuses can be installed downstream the inverter to protect each single string. The fuses must be selected according to the ra- ted current of the line and to the maximum dissipated power. Back-Up Download When the Icc short circuit current, at the point of installation, is greater than 100 A DC, the OVR PVs Surge Protective Devices require a back-up protection with a specific type gR fuse. DC side of the inverter For small size photovoltaic systems, E 90 PV fuse disconnectors can be used to protect the DC side of the inverter. The fuse should be chosen according to the rated current of the inverter. E 90 PVSystem pro M compact® Selection tables Protection devices E 90 PV fuse disconnectors 2CSC400032F0202

The E 90 fuse carriers for Class CC cylindrical fuse links are specifically designed for the North American market in compliance with the UL standards. In accordance with the reference standards UL 4248-1 and UL 4248-4, they come in voltage and current ratings up to 600V and 30A. They are available in 1P , 1P+N, 2P , 3P , 3P+N and 4P versions. They can be padlocked open and sealed closed. The E 90 fuse carriers are the ideal solution for process control and industrial systems, automation systems, industrial installations and control circuits. The versions with blown fuse indicator light provide a visual signal of the fuse break condition E 90 for class CC cartridge fuses Poles Rated Modules Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1 30 1 E 91/30 2CSM205833R1801 058335 0,061 6 1 30 1 E 91/30s 2CSM251533R1801 515333 0,062 6 1+N 30 2 E 91N/30 2CSM200693R1801 006930 0,13 3 2 30 2 E 92/30 2CSM202443R1801 024439 0,122 3 3 30 3 E 93/30 2CSM200683R1801 006831 0,183 2 3+N 30 4 E 93N/30 2CSM202433R1801 024330 0,252 1 4 30 4 E 94/30 2CSM200673R1801 006732 0,244 1 s: version with blown fuse indicator light Technical features 30A Rated voltage Un [V] 600 a.c. /d.c. Rated current In [A] 30 Rated frequency [Hz] =/50-60 Fuse size [mm] 10.4 x 38.1 Tightening torque [Nm] PZ2 2-2.5 Rated temperature [°C] 75 Can be sealed closed ■ Can be padlocked open ■ Markings UL CSA Standards UL 4248-1 (General) UL 4248-4 (Class CC) System pro M compact® Selection tables Protection devices E 90 class CC fuseholders 38 mm Ø 10.4 mm 2CSC400695F0201 2CSC400701F02012CSC400699F0201

The E 930 fuse disconnector range, for current of 50 A and 125 A, is specifically intended for industrial circuit protection. The E 930 can carry any type of cylindrical fuses 14x51 and 22x58 mm, they are padlockable in open position to ensure operator safety during mainte- nance operations. The E 930 also support MCR microswitches, through which you can get a complete remote monitoring of the device state. The microswitch makes it possible to report: the fuse intervention, the opening of the drawer and the fuse absence with closed drawer. E 930 fuse disconnectors for 14 x 51 mm fuses (AC-20B) Poles Rated Modules Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1 50 1.5 E 931/50 2CSM361610R1801 446804 0.200 6 1+N 50 3 E 931N/50 2CSM365610R1801 446903 0.400 3 2 50 3 E 932/50 2CSM362610R1801 447009 0.400 3 3 50 4.5 E 933/50 2CSM363610R1801 447108 0.600 1 3+N 50 6 E 933N/50 2CSM367610R1801 447207 0.800 1 E 930 fuse disconnectors for 22 x 58 mm fuses (AC-20B) 1 125 2 E 931/125 2CSM371710R1801 447504 0.200 6 1+N 125 4 E 931N/125 2CSM375710R1801 447603 0.400 3 2 125 4 E 932/125 2CSM372710R1801 447702 0.400 3 3 125 6 E 933/125 2CSM373710R1801 447801 0.600 1 3+N 125 8 E 933N/125 2CSM377710R1801 447900 0.800 1 Microswitches for series E 930 fuse disconnectors 1 50 1 E 930/MCR1P50 2CSM060019R1801 451006 0.030 1 3 50 3 E 930/MCR3P50 2CSM060029R1801 451105 0.030 1 1 125 1 E 930/MCR1P125 2CSM070019R1801 451204 0.030 1 3 125 3 E 930/MCR3P125 2CSM070029R1801 451303 0.030 1 Technical features

50 A 125 A

Rated voltage Un [V] 750 a.c./d.c. Insulation voltage [V] 8000 Rated current In [A] 50 125 Short circuit current Icc [A] see fuse link Rated frequency [Hz] 50-60 Fuse size [mm] 14 x 51 22 x 58 Utilization category AC-20B/DC-20B Max power dissipation [W] 5 9.5 Terminals [mm 2] 25 35 Can be sealed closed ■ Can be padlocked open ■ Protection degree IP20 Markings UL, CSA Standards IEC 60947-3 System pro M compact® Selection tables Protection devices E 930 fuse disconnectors 2CSC400212F0201 2CSC400210F0201 51 mm Ø 15 mm 58 mm Ø 22 mm

N 1P+N 3P+N E 930System pro M compact® Selection tables Protection devices E 930 fuseholders State of the E 930/MCR microswitch contact Closed fuseholders with fuse Open fuseholders without fuse Padlocked in open position 2CSC400031F02022CSC400033F02022CSC400034F0202

a - fuse blown : indicates fuse break condition b - pre-opening: indicates when the fuseholders cover is open c - presence: indicates when the cover is closed but there is no fuse inside E 930System pro M compact® Selection tables Protection devices E 930 fuseholders Microswitch assembly and disassembly steps 1- assembly 2- disassembly 2CSC400035F02022CSC400036F0202

pro M compact® Selection tables Protection devices Cylindrical fuses E 9F Protection system selection Maximum fuse rated current Fuseholder Rated voltage E 90/20 8.5 x 31.5 mm E 90/32 10.3 x 38 mm E 930/50 14 x 51 mm E 930/125 22 x 58 mm 400 V a.c. gG 20 A 32 A 50 A 125 A aM 10 A 32 A 50 A 125 A 500 V a.c. gG - 25 A 40 A 100 A aM - 25 A 40 A 100 A 690 V a.c. gG - 10 A 25 A 80 A aM - - 25 A 80 A In the table above you will find indication about the highest rated current fuse that you can host inside a fuseholder, depending on the rated voltage of the circuit, the fuse size and the tripping curve characteristic. ABB fuses and fuseholders comply with all regulatory requirements and sometimes they allow to install a fuse with rated current higher than the one set by the Standard IEC EN 60269-2-1. Multiple poles pole installation E 91/32 E 91hN/32 Poles Maximum current Poles Maximum current more than 0.7 x In more than 10 0.6 x In Climate conditions Maximum temperature 20 °C 30 °C 40 °C 50 °C Maximum humidity 95% 90% 80% 50% Maximum current In In x 0.95 In x 0.9 In x 0.8 In case of several paired poles or installation in special climate conditions, take into account the derating parameters listed in the table according to rated current, the number of paired poles or temperature and relative humidity.

The E 9F gG cylindrical fuses, coupled with E 90 and E 930 fuse disconnectors, are the ideal solution for protection against overload and short-circuit. They feature a fast tripping curve that is ideal for protecting electronic devices, transformers and electric cables. The E 9F gG series is available for all the main sizes (8.5 x 31.5 mm, 10.3 x 38 mm, 14 x 51 mm e 22 x 58 mm) and with a wide range of rated current values (from 1 A to 125 A and up to 690 V a.c.). All the E 9F series fuses conform to the RoHS directive and are type-approved in accordance with the most important international naval marks. E 9F 8 gG cylindrical fuses 8.5 x 31.5 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 1 8.5x31.5 E 9F8 GG1 2CSM257573R1801 575733 0.004 10 2 8.5x31.5 E 9F8 GG2 2CSM256393R1801 563938 0.004 10 4 8.5x31.5 E 9F8 GG4 2CSM258663R1801 586630 0.004 10 6 8.5x31.5 E 9F8 GG6 2CSM257483R1801 574835 0.004 10 8 8.5x31.5 E 9F8 GG8 2CSM256303R1801 563037 0.004 10 10 8.5x31.5 E 9F8 GG10 2CSM277573R1801 775737 0.004 10 12 8.5x31.5 E 9F8 GG12 2CSM277353R1801 773535 0.004 10 16 8.5x31.5 E 9F8 GG16 2CSM277133R1801 771333 0.004 10 20 8.5x31.5 E 9F8 GG20 2CSM277503R1801 775034 0.004 10 E 9F 10 gG cylindrical fuses 10.3 x 38 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 0.5 10.3x38 E 9F10 GG05 2CSM277333R1801 773337 0.007 10 1 10.3x38 E 9F10 GG1 2CSM277113R1801 771135 0.007 10 2 10.3x38 E 9F10 GG2 2CSM258723R1801 587231 0.007 10 4 10.3x38 E 9F10 GG4 2CSM257543R1801 575436 0.007 10 6 10.3x38 E 9F10 GG6 2CSM256363R1801 563631 0.007 10 8 10.3x38 E 9F10 GG8 2CSM258633R1801 586333 0.007 10 10 10.3x38 E 9F10 GG10 2CSM257453R1801 574538 0.007 10 12 10.3x38 E 9F10 GG12 2CSM256273R1801 562733 0.007 10 16 10.3x38 E 9F10 GG16 2CSM277543R1801 775430 0.007 10 20 10.3x38 E 9F10 GG20 2CSM277323R1801 773238 0.007 10 25 10.3x38 E 9F10 GG25 2CSM277103R1801 771036 0.007 10 32 10.3x38 E 9F10 GG32 2CSM258713R1801 587132 0.007 10 E 9F 14 gG cylindrical fuses 14 x 51 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 2 14x51 E 9F14 GG2 2CSM277523R1801 775232 0.018 10 4 14x51 E 9F14 GG4 2CSM277303R1801 773030 0.018 10 6 14x51 E 9F14 GG6 2CSM277083R1801 770831 0.018 10 8 14x51 E 9F14 GG8 2CSM291003R1801 910039 0.018 10 10 14x51 E 9F14 GG10 2CSM290983R1801 909835 0.018 10 12 14x51 E 9F14 GG12 2CSM290963R1801 909637 0.018 10 16 14x51 E 9F14 GG16 2CSM258783R1801 587835 0.018 10 20 14x51 E 9F14 GG20 2CSM257603R1801 576037 0.018 10 25 14x51 E 9F14 GG25 2CSM256423R1801 564232 0.018 10 32 14x51 E 9F14 GG32 2CSM258693R1801 586937 0.018 10 40 14x51 E 9F14 GG40 2CSM257513R1801 575139 0.018 10 50 14x51 E 9F14 GG50 2CSM256333R1801 563334 0.018 10 E 9F gGSystem pro M compact® Selection tables Protection devices Cylindrical fuses E 9F gG 38 mm Ø 10.3 mm 31.5 mm Ø 8.5 mm 51 mm Ø 14 mm 2CSC400037F02022CSC400038F02022CSC400039F0202

pro M compact® Selection tables Protection devices Cylindrical fuses E 9F gG Technical features Rated voltage [V] 400, 500, 690 AC Rated current [A] 0,5…125 Breaking capacity [kA] 20, 80, 120 Overall dimensions [mm] 8.5x31.5 , 10.3x38 , 14x51 , 22x58 Weight [g] 4, 7, 18, 48 Standards IEC 60269-2; ROHS 2002/98/CE Marks LLOYD, NF, BV E 9F 8 gG cylindrical fuses 8.5 x 31.5 mm E 9F 10 gG cylindrical fuses 10.3 x 38 mm Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] E 9F8 GG1 1 400 20 E 9F10 GG05 0.5 500 120 E 9F8 GG2 2 400 20 E 9F10 GG1 1 500 120 E 9F8 GG4 4 400 20 E 9F10 GG2 2 500 120 E 9F8 GG6 6 400 20 E 9F10 GG4 4 500 120 E 9F8 GG8 8 400 20 E 9F10 GG6 6 500 120 E 9F8 GG10 10 400 20 E 9F10 GG8 8 500 120 E 9F8 GG12 12 400 20 E 9F10 GG10 10 500 120 E 9F8 GG16 16 400 20 E 9F10 GG12 12 500 120 E 9F8 GG20 20 400 20 E 9F10 GG16 16 500 120 E 9F10 GG20 20 500 120 E 9F10 GG25 25 500 120 E 9F10 GG32 32 400 120 E 9F 14 gG cylindrical fuses 14 x 51 mm E 9F 22 gG cylindrical fuses 22 x 58 mm Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] E 9F14 GG2 2 690 80 E 9F22 GG4 4 690 80 E 9F14 GG4 4 690 80 E 9F22 GG6 6 690 80 E 9F14 GG6 6 690 80 E 9F22 GG8 8 690 80 E 9F14 GG8 8 690 80 E 9F22 GG10 10 690 80 E 9F14 GG10 10 690 80 E 9F22 GG12 12 690 80 E 9F14 GG12 12 690 80 E 9F22 GG16 16 690 80 E 9F14 GG16 16 690 80 E 9F22 GG20 20 690 80 E 9F14 GG20 20 690 80 E 9F22 GG25 25 690 80 E 9F14 GG25 25 690 80 E 9F22 GG32 32 690 80 E 9F14 GG32 32 500 120 E 9F22 GG40 40 690 80 E 9F14 GG40 40 500 120 E 9F22 GG50 50 690 80 E 9F14 GG50 50 400 120 E 9F22 GG63 63 690 80 E 9F22 GG80 80 690 80 E 9F22 GG100 100 500 120 E 9F22 GG125 125 400 120 E 9F 22 gG cylindrical fuses 22 x 58 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 4 22x58 E 9F22 GG4 2CSM257183R1801 571834 0.048 10 6 22x58 E 9F22 GG6 2CSM259283R1801 592839 0.048 10 8 22x58 E 9F22 GG8 2CSM258103R1801 581031 0.048 10 10 22x58 E 9F22 GG10 2CSM256923R1801 569237 0.048 10 12 22x58 E 9F22 GG12 2CSM259403R1801 594031 0.048 10 16 22x58 E 9F22 GG16 2CSM258223R1801 582236 0.048 10 20 22x58 E 9F22 GG20 2CSM257043R1801 570431 0.048 10 25 22x58 E 9F22 GG25 2CSM259533R1801 595335 0.048 10 32 22x58 E 9F22 GG32 2CSM258353R1801 583530 0.048 10 40 22x58 E 9F22 GG40 2CSM257173R1801 571735 0.048 10 50 22x58 E 9F22 GG50 2CSM259393R1801 593935 0.048 10 63 22x58 E 9F22 GG63 2CSM258213R1801 582137 0.048 10 80 22x58 E 9F22 GG80 2CSM257033R1801 570332 0.048 10 100 22x58 E 9F22 GG100 2CSM259523R1801 595236 0.048 10 125 22x58 E 9F22 GG125 2CSM258343R1801 583431 0.048 10 58 mm Ø 22 mm 2CSC400040F0202

pro M compact® Selection tables Protection devices Cylindrical fuses E 9F gG Power dissipation [W] In [A] Size 10.3x38 14x51 22x58 0.5 2 1 2.5 3.4 2 0.70 1 1.20 4 0.80 1.10 1.30 6 0.90 1.20 1.40 8 1.10 1.50 1.65 10 1.35 1.80 2 12 1.55 2.10 2.40 16 1.90 2.55 3 20 2.30 3 3.40 25 2.80 3.50 3.80 32 3 3.80 4.30 40 4.40 5.10 50 4.70 5.50 63 6.70 80 8 100 9 125 12.5 It is important verify that the power dissipation by the fuse does not exceed the limit allowed by the fuse it is hosted. In blue are shown the maximum values of power dissipation according with the range E 90 and E 930 specifications. /MT49/MT48/MT45/MT49 /MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT49/MT48/MT45/MT50 /MT73/MT112/MT32/MT91/MT65/MT93 /MT116/MT32/MT91/MT115/MT93 /MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT45/MT51 /MT52/MT32/MT65 /MT54/MT32/MT65 /MT56/MT32/MT65 /MT49/MT48/MT32/MT65 /MT49/MT50/MT32/MT65 /MT49/MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT50/MT53/MT32/MT65 /MT51/MT50/MT32/MT65 /MT52/MT48/MT32/MT65 /MT53/MT48/MT32/MT65 /MT54/MT51/MT32/MT65 /MT50/MT32/MT65 /MT56/MT48/MT32/MT65 /MT49/MT48/MT48/MT32/MT65 /MT49/MT50/MT53/MT32/MT65 Characteristics tI 2CSC400041F0202

/MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT73/MT110/MT32/MT91/MT65/MT93 /MT116 /MT50 /MT115/MT32/MT40/MT65 /MT50 /MT115/MT41 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT53 /MT50/MT32/MT65 /MT52/MT32/MT65 /MT54/MT32/MT65 /MT56/MT32/MT65 /MT49/MT48/MT32/MT65 /MT49/MT50/MT32/MT65 /MT49/MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT50/MT53/MT32/MT65 /MT51/MT50/MT32/MT65 /MT52/MT48/MT32/MT65 /MT53/MT48/MT32/MT65 /MT54/MT51/MT32/MT65 /MT56/MT48/MT32/MT65 /MT49/MT48/MT48/MT32/MT65 /MT49/MT50/MT53/MT32/MT65 /MT80/MT114/MT101/MT97/MT114/MT99/MT105/MT110/MT103 /MT52/MT48/MT48/MT32/MT86 /MT53/MT48/MT48/MT32/MT86 /MT54/MT57/MT48/MT32/MT86 /MT79/MT112/MT101/MT114/MT97/MT116/MT105/MT110/MT103/MT32/MT73 /MT50 /MT116 Characteristics I2t E 9F gGSystem pro M compact® Selection tables Protection devices Cylindrical fuses E 9F gG °/MT67 /MT57/MT48 /MT56/MT48 /MT55/MT48 /MT54/MT48 /MT53/MT48 /MT52/MT48 /MT51/MT48 /MT50/MT48 /MT49/MT48 /MT49/MT48/MT46/MT51/MT32/MT120/MT32/MT51/MT56 /MT48/MT50/MT32/MT48/MT52/MT32/MT48/MT53/MT32/MT48/MT56/MT32 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT54/MT32 /MT50/MT48/MT32 /MT50/MT53/MT32 /MT51/MT50 /MT49/MT52/MT32/MT120/MT32/MT53/MT49 /MT48/MT50/MT32/MT48/MT52/MT32/MT48/MT53/MT32/MT48/MT56/MT32 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT54/MT32 /MT50/MT48/MT32 /MT50/MT53/MT32 /MT51/MT50/MT32 /MT52/MT48/MT32 /MT53/MT48 /MT50/MT50/MT32/MT120/MT32/MT53/MT56 /MT48/MT49/MT54/MT32/MT48/MT50/MT48/MT32/MT48/MT50/MT53/MT32/MT48/MT51/MT50/MT32/MT48/MT52/MT48/MT32/MT48/MT53/MT48/MT32/MT48/MT54/MT51/MT32/MT48/MT56/MT48/MT32 /MT49/MT48/MT48/MT32 /MT49/MT50/MT53 Temperature increase 2CSC400042F02022CSC400042F0202

The E 9F aM cylindrical fuses, coupled with E 90 and E 930 fuse disconnectors, are the ideal solution for protection against overload and short-circuit. They feature a delayed tripping curve and are the- refore ideal for protecting industrial motors that require high inrush current during the starting phase. The E 9F aM series is available for all the main sizes (8.5 x 31.5 mm, 10.3 x 38 mm, 14 x 51 mm e 22 x 58 mm) and with a wide range of rated current values (from 1 A to 125 A and up to 690 V a.c.). All the E 9F series fuses conform to the RoHS directive and are type-approved in accordance with the most important international naval marks. E 9F 8 aM cylindrical fuses 8.5 x 31.5 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 1 8.5x31.5 E 9F8 AM1 2CSM277283R1801 772835 0.004 10 2 8.5x31.5 E 9F8 AM2 2CSM277063R1801 770633 0.004 10 4 8.5x31.5 E 9F8 AM4 2CSM258743R1801 587439 0.004 10 6 8.5x31.5 E 9F8 AM6 2CSM257563R1801 575634 0.004 10 8 8.5x31.5 E 9F8 AM8 2CSM256383R1801 563839 0.004 10 10 8.5x31.5 E 9F8 AM10 2CSM258653R1801 586531 0.004 10 E 9F 10 aM cylindrical fuses 10.3 x 38 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 0.5 10.3x38 E 9F10 AM05 2CSM257473R1801 574736 0.007 10 1 10.3x38 E 9F10 AM1 2CSM256293R1801 562931 0.007 10 2 10.3x38 E 9F10 AM2 2CSM277563R1801 775638 0.007 10 4 10.3x38 E 9F10 AM4 2CSM277343R1801 773436 0.007 10 6 10.3x38 E 9F10 AM6 2CSM277123R1801 771234 0.007 10 8 10.3x38 E 9F10 AM8 2CSM258733R1801 587330 0.007 10 10 10.3x38 E 9F10 AM10 2CSM257553R1801 575535 0.007 10 12 10.3x38 E 9F10 AM12 2CSM256373R1801 563730 0.007 10 16 10.3x38 E 9F10 AM16 2CSM258643R1801 586432 0.007 10 20 10.3x38 E 9F10 AM20 2CSM257463R1801 574637 0.007 10 25 10.3x38 E 9F10 AM25 2CSM256283R1801 562832 0.007 10 32 10.3x38 E 9F10 AM32 2CSM277553R1801 775539 0.007 10 E 9F 14 aM cylindrical fuses 14 x 51 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 1 14x51 E 9F14 AM1 2CSM257533R1801 575337 0.018 10 2 14x51 E 9F14 AM2 2CSM256353R1801 563532 0.018 10 4 14x51 E 9F14 AM4 2CSM258623R1801 586234 0.018 10 6 14x51 E 9F14 AM6 2CSM257443R1801 574439 0.018 10 8 14x51 E 9F14 AM8 2CSM256263R1801 562634 0.018 10 10 14x51 E 9F14 AM10 2CSM277533R1801 775331 0.018 10 12 14x51 E 9F14 AM12 2CSM277313R1801 773139 0.018 10 16 14x51 E 9F14 AM16 2CSM277093R1801 770930 0.018 10 20 14x51 E 9F14 AM20 2CSM258703R1801 587033 0.018 10 25 14x51 E 9F14 AM25 2CSM257523R1801 575238 0.018 10 32 14x51 E 9F14 AM32 2CSM256343R1801 563433 0.018 10 40 14x51 E 9F14 AM40 2CSM258613R1801 586135 0.018 10 45 14x51 E 9F14 AM45 2CSM257433R1801 574330 0.018 10 50 14x51 E 9F14 AM50 2CSM256253R1801 562535 0.018 10 System pro M compact® Selection tables Protection devices Cylindrical fuses E 9F aM 38 mm Ø 10.3 mm 31.5 mm Ø 8.5 mm 51 mm Ø 14 mm 2CSC400039F0202 2CSC400038F0202 2CSC400037F0202

pro M compact® Selection tables Protection devices Cylindrical fuses E 9F aM E 9F 22 aM cylindrical fuses 22 x 58 mm Rated Size Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In mm Type code Order code EAN kg pc. 6 22x58 E 9F22 AM6 2CSM258603R1801 586036 0.048 10 8 22x58 E 9F22 AM8 2CSM257423R1801 574231 0.048 10 10 22x58 E 9F22 AM10 2CSM256243R1801 562436 0.048 10 12 22x58 E 9F22 AM12 2CSM277513R1801 775133 0.048 10 16 22x58 E 9F22 AM16 2CSM277293R1801 772934 0.048 10 20 22x58 E 9F22 AM20 2CSM277073R1801 770732 0.048 10 25 22x58 E 9F22 AM25 2CSM277493R1801 774938 0.048 10 32 22x58 E 9F22 AM32 2CSM277273R1801 772736 0.048 10 40 22x58 E 9F22 AM40 2CSM277053R1801 770534 0.048 10 50 22x58 E 9F22 AM50 2CSM259413R1801 594130 0.048 10 63 22x58 E 9F22 AM63 2CSM258233R1801 582335 0.048 10 80 22x58 E 9F22 AM80 2CSM257053R1801 570530 0.048 10 100 22x58 E 9F22 AM100 2CSM259543R1801 595434 0.048 10 125 22x58 E 9F22 AM125 2CSM258363R1801 583639 0.048 10 Technical features Rated voltage [V] 400, 500, 690 AC Rated current [A] 0,5…125 Breaking capacity [kA] 20, 80, 120 Overall dimensions [mm] 8.5x31.5, 10.3x38, 14x51, 22x58 Weight [g] 4, 7, 18, 48 Standards IEC 60269-2; ROHS 2002/98/CE Marks LLOYD, NF, BV E 9F8 aM cylindrical fuses 8.5 x 31.5 mm E 9F10 aM cylindrical fuses 10.3 x 38 mm Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] E 9F1 AM1 1 400 20 E 9F10 AM05 0.5 500 120 E 9F8 AM2 2 400 20 E 9F10 AM1 1 500 120 E 9F8 AM4 4 400 20 E 9F10 AM2 2 500 120 E 9F8 AM6 6 400 20 E 9F10 AM4 4 500 120 E 9F8 AM8 8 400 20 E 9F10 AM6 6 500 120 E 9F8 AM10 10 400 20 E 9F10 AM8 8 500 120 E 9F10 AM10 10 500 120 E 9F10 AM12 12 500 120 E 9F10 AM16 16 500 120 E 9F10 AM20 20 500 120 E 9F10 AM25 25 400 120 E 9F10 AM32 32 400 120 E 9F14 aM cylindrical fuses 14 x 51 mm E 9F22 aM cylindrical fuses 22 x 58 mm Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] Type Rated current [A] Rated voltage [V AC] Breaking capacity [kA] E 9F14 AM1 1 690 80 E 9F22 AM6 6 690 80 E 9F14 AM2 2 690 80 E 9F22 AM8 8 690 80 E 9F14 AM4 4 690 80 E 9F22 AM10 10 690 80 E 9F14 AM6 6 690 80 E 9F22 AM12 12 690 80 E 9F14 AM8 8 690 80 E 9F22 AM16 16 690 80 E 9F14 AM10 10 690 80 E 9F22 AM20 20 690 80 E 9F14 AM12 12 690 80 E 9F22 AM25 25 690 80 E 9F14 AM16 16 690 80 E 9F22 AM32 32 690 80 E 9F14 AM20 20 690 80 E 9F22 AM40 40 690 80 E 9F14 AM25 25 690 80 E 9F22 AM50 50 690 80 E 9F14 AM32 32 500 120 E 9F22 AM63 63 690 80 E 9F14 AM40 40 500 120 E 9F22 AM80 80 690 80 E 9F14 AM45 45 500 120 E 9F22 AM100 100 500 120 E 9F14 AM50 50 400 120 E 9F22 AM125 125 400 120 58 mm Ø 22 mm 2CSC400040F0202

Power dissipation [W] In [A] Size 10.3x38 14x51 22x58 0.5 0.50 0.75 1 0.13 0.18 0.20 2 0.20 0.25 0.30 4 0.30 0.40 0.50 6 0.45 0.55 0.65 8 0.55 0.65 0.75 10 0.65 0.75 0.85 12 0.75 0.85 1 16 0.90 1.20 1.40 20 1.10 1.50 1.70 25 1.40 1.80 2 32 2 2.10 2.60 40 2.60 3.20 45 2.80 50 2.90 3.90 63 4.60 80 5.60 100 6.50 125 9.50 It is important verify that the power dissipation by the fuse does not exceed the limit allowed by the fuse it is hosted. In blue are shown the maximum values of power dissipation according with the range E 90 and E 930 specifications. /MT49/MT48/MT45/MT49 /MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT49/MT48/MT45/MT50 /MT73/MT112/MT32/MT91/MT65/MT93 /MT116/MT32/MT91/MT115/MT93 /MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT45/MT51 /MT52/MT32/MT65 /MT54/MT32/MT65 /MT56/MT32/MT65 /MT49/MT48/MT32/MT65 /MT49/MT50/MT32/MT65 /MT49/MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT50/MT53/MT32/MT65 /MT51/MT50/MT32/MT65 /MT52/MT48/MT32/MT65 /MT53/MT48/MT32/MT65 /MT54/MT51/MT32/MT65 /MT50/MT32/MT65 /MT56/MT48/MT32/MT65 /MT49/MT48/MT48/MT32/MT65 /MT49/MT50/MT53/MT32/MT65 /MT49/MT32/MT65 Characteristics tI E 9F aMSystem pro M compact® Selection tables Protection devices Cylindrical fuses E 9F aM 2CSC400045F0202

°/MT67 /MT57/MT48 /MT56/MT48 /MT55/MT48 /MT54/MT48 /MT53/MT48 /MT52/MT48 /MT51/MT48 /MT50/MT48 /MT49/MT48 /MT49/MT48/MT32/MT120/MT32/MT51/MT56/MT49/MT52/MT32/MT120/MT32/MT53/MT49 /MT50/MT50/MT32/MT120/MT32/MT53/MT56 /MT48/MT49/MT32/MT48/MT50/MT32/MT48/MT52/MT32/MT48/MT54/MT32/MT48/MT56/MT32 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT54/MT32 /MT50/MT48/MT32 /MT50/MT53/MT32 /MT51/MT50/MT48/MT49/MT32/MT48/MT50/MT32/MT48/MT52/MT32/MT48/MT54/MT32/MT48/MT56/MT32 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT54/MT32 /MT50/MT48/MT32 /MT50/MT53/MT32 /MT51/MT50/MT32 /MT52/MT48/MT32 /MT53/MT48/MT48/MT49/MT32/MT48/MT50/MT32/MT48/MT52/MT32/MT48/MT54/MT32/MT48/MT56/MT32 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT54/MT32 /MT50/MT48/MT32 /MT50/MT53/MT32 /MT51/MT50/MT32 /MT52/MT48/MT32 /MT53/MT48/MT32 /MT54/MT51/MT32 /MT56/MT48/MT32 /MT49/MT48/MT48/MT32 /MT49/MT50/MT53 /MT49/MT48/MT48 /MT49/MT48/MT49 /MT49/MT48/MT50 /MT73/MT110/MT32/MT91/MT65/MT93 /MT116 /MT50 /MT115/MT32/MT40/MT65 /MT50 /MT115/MT41 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT53 /MT49/MT32/MT65 /MT50/MT32/MT65 /MT52/MT32/MT65 /MT54/MT32/MT65 /MT56/MT32/MT65 /MT49/MT48/MT32/MT65 /MT49/MT50/MT32/MT65 /MT49/MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT50/MT53/MT32/MT65 /MT51/MT50/MT32/MT65 /MT52/MT48/MT32/MT65 /MT53/MT48/MT32/MT65 /MT54/MT51/MT32/MT65 /MT49/MT48/MT48/MT32/MT65 /MT49/MT50/MT53/MT32/MT65 /MT80/MT114/MT101/MT97/MT114/MT99/MT105/MT110/MT103 /MT52/MT48/MT48/MT32/MT86 /MT53/MT48/MT48/MT32/MT86 /MT54/MT57/MT48/MT32/MT86 /MT79/MT112/MT101/MT114/MT97/MT116/MT105/MT110/MT103/MT32/MT73 /MT50 /MT116 /MT56/MT48/MT32/MT65 Characteristics I2t E 9F aMSystem pro M compact® Selection tables Protection devices Cylindrical fuses E 9F aM Temperature increase (testing in superior contact) 2CSC400046F02022CSC400046F0202

E 9F PV cylindrical fuses for photovoltaic applications The cylindrical fuses E 9F PV series are specifically used in overcurrent protection of photovoltaic applications up to 1000 V in direct current. Thanks to the wide current range from 1 A to 30 A, and to the high nominal voltage of 1000 V DC, the series E 9F PV is ideal to protect strings, inverters and OVR surge protections according to IEC 60269-6 “Supplementary requirements for fuse-links for the protection of solar photovoltaic energy systems”. E 9F PV cylindrical fuses 10.3 x 38 mm Rated Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit In Type code Order code EAN kg pc. 1 A E 9F1 PV 2CSM213455R1801 134558 0.007 10 2 A E 9F2 PV 2CSM213465R1801 134657 0.007 10 3 A E 9F3 PV 2CSM213475R1801 134756 0.007 10 4 A E 9F4 PV 2CSM213485R1801 134855 0.007 10 5 A E 9F5 PV 2CSM213495R1801 134954 0.007 10 6 A E 9F6 PV 2CSM213505R1801 135050 0.007 10 7 A E 9F7 PV 2CSM213515R1801 135159 0.007 10 8 A E 9F8 PV 2CSM213525R1801 135258 0.007 10 10 A E 9F10 PV 2CSM213535R1801 135357 0.007 10 12 A E 9F12 PV 2CSM213545R1801 135456 0.007 10 15 A E 9F15 PV 2CSM213555R1801 135555 0.007 10 20 A E 9F20 PV 2CSM213565R1801 135654 0.007 10 25 A E 9F25 PV 2CSM213575R1801 135753 0.007 10 30 A E 9F30 PV 2CSM213585R1801 135852 0.007 10 Technical features Rated voltage [V] 1000 DC Rated current [A] 1...30 Breaking capacity [kA] 50 Minimum breaking capacity From 1 A up to 7 A = 1.3 x In From 8 A up to 30 A = 2.0 x In Overall dimensions [mm] 10.3 x 38 Weight [g] 7 Standards IEC 60269-6; ROHS 2002/98/CE System pro M compact® Selection tables Protection devices Cylindrical Fuses E 9F gPV Type I 2t curve [A2s] Power consumption [W] E 9F1 PV - 0.32 E 9F2 PV - 0.43 E 9F3 PV - 1.4 E 9F4 PV - 1.3 E 9F5 PV - 1.4 E 9F6 PV - 1.5 E 9F7 PV - 1.5 E 9F8 PV 83 1.1 E 9F10 PV 127 1.5 E 9F12 PV 215 2.0 E 9F15 PV 495 3.0 E 9F20 PV 755 4.4 E 9F25 PV 970 5.3 E 9F30 PV 1650 5.8 38 mm Ø 10.3 mm 2CSC400047F0202

pro M compact® Selection tables Protection devices Cylindrical Fuses E 9F gPV t [s] Ip [A] t [s] Ip [A] L/R Time Constant [ms] DC Voltage Voltage capabilities vs. time constant Melting time - Current data Melting time - Current data 2CSC400048F0202

pro M compact® Selection tables Protection devices Fuse-switch-disconnectors ILTS 2CDC 052 038 F0003 Circuit ILTS-E1 2CDC 051 105 F0007 ILTS-E1 2CDC 051 106 F0007 ILTS-E/RE 2CDC 051 113 F0007 ILTS-E3 2CDC 051 107 F0007 ILTS-E/H11 2CDC 051 108 F0007 Switch-disconnector ILTS-E for D0 2-63 A fuse links “Drawer technology” User-friendly fuse-switch-disconnector in “drawer technology”:

  • Snap action
  • Fuse can be replaced only if the system is de-energized.
  • Captive fuse carrier
  • For D02 fuse links, D01 fuse link with reducing piece
  • Twin box terminal on both sides
  • User-friendly installation of cross-wiring in lower terminal
  • Auxiliary switch to indicate switching position Fuse-switch-disconnector Poles Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 ILTS-E1 2CDE 101 001 R1901 65347 3 13 0.210 3 2 ILTS-E2 2CDE 102 001 R1901 65348 0 13 0.420 2 3 ILTS-E3 2CDE 103 001 R1901 65349 7 13 0.630 1 3+N* ILTS-E3+N 2CDE 103 101 R1901 65350 3 13 0.790 1 Reducing piece ILTS-E/RE 2CDE 000 011 R1901 65407 4 13 0.001 20 Auxiliary switch 1NO/1NC LTS-E/H11 2CDE 000 012 R1901 65671 9 13 0.050 1 * N conductor leading make contact, late closing Technical data Standards: DIN VDE 0638, EN 60947-3, EN 660269-3-1 Approval: VDE No. of poles: 1, 2, 3 pole and 3 pole+N Rated voltage: 400 V AC, per pole 65 V DC (2 pole 130 V DC) Operating current In: acc. to fuse link D0 2-63 A Rated frequency: 50/60 Hz Rated short circuit capacity: 50 kA for AC (8 kA for DC) Power loss: 5.5 W/pole Utilization category: AC 22 B: 400 V AC 63 A according to IEC / EN 60947-3 (all versions) DC 22 B: 65 V DC 63 A according to IEC / EN 60947-3 (1 pole) DC 22 B: 130 V DC 63 A according to IEC / EN 60947-3 (2 pole) Leakage current resistance: CTI 200 Ambient temperature: – 5 °C up to + 40 °C Casing material: thermoplast; halogen-, phosphor-, silicone- and CFC-free Fire classification: UL 94 (self-extinguishing) Shock protection: according to DIN EN 50 274 (DIN VDE 0660 Part 514) BGV A3 Connection capacity: 1.5 – 35 mm2 finely stranded, directly clamped or with connector sleeve Twin-function terminal for simultaneous connection of two conductors (35 mm 2 and 16 mm2) or conductor and busbar Pick-up torque: 2,5 – 3 Nm Auxiliary switch indicating contact position Contacts: 1 NO contact + 1 NC contact Contact rating: AC 13: 2 A/400 V, 6 A/230 V DC 13: 1 A/220 V, 6 A/24V

pro M compact® Selection tables Protection devices D0 Fuse carrier ISS 2CDC 051 109 F0007 ISS 16/1 2CDC 051 110 F0007 ISS 63/1 2CDC 051 111 F0007 ISS 16/3 2CDC 051 112 F0007 ISS 63/3 D0 fuse carrier ISS with integrated red cover D0 fuse base for NEOZED fuse links D01 / D02. Touch-protection according to BGV A3. Twin box terminal on both sides for connection of two different conductor cross-sections or conductors and busbars. Conductor cross-sections incoming and outing 1.5 – 35 mm 2 , stranded. With integrated terminal cover. A separate cover for distribution board installation is not required.

  • IEC 60269-3 / VDE 0636-3
  • 1/3-pole
  • Fuse links, connector sleeves VDE 0636-3
  • Snap clip device for rail mounting to EN 60715
  • Twin function terminal
  • Connection cross-section 1.5 – 35 mm
  • Tightening torque 2.5 – 3 Nm Dimensions in mm ISS 16/3 ISS 63/3 ISS 16/1 ISS 63/1 D0 fuse carrier Poles Screw cover/ Order Bbn Price Price Weight Pack fuse details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 E14 D01 ISS 16/1 2CDE 101 001 R1902 65579 8 13 0.08 3 1 E18 D02 ISS 63/1 2CDE 161 001 R1902 65581 1 13 0.08 3 3 E14 D01 ISS 16/3 2CDE 113 001 R1902 65580 4 13 0.24 3 3 E18 D02 ISS 63/3 2CDE 163 001 R1902 65582 8 13 0.24 3 Technical data Size: D01 D02 Current type: AC (50 Hz) / DC AC (50 Hz) / DC Rated voltage: 400 V AC / 250 V DC 400 V AC / 250 V DC Rated current: 16 A 63 A Rated short-circuit current: 50 kA (AC) 8 kA (DC) 50 kA (AC) 8 kA (DC) For fuse links with losses per phase up to: 2.5 W 5.5 W

pro M compact® Busbars and accessories for ILTS-E and ISS End caps: PS 1/39/16 ILTS-E: END 1.1 PS 1/39/30 ILTS-E: PS-END 3.2 PS 3/39/16 ILTS-E: PS-END PS 3/39/30 ILTS-E: PS-END 3 Busbars for fuse-switch-disconnector ILTS-E and fuse carrier ISS: 1pole oder 3pole 16 1040 39 x 1 PS 1/39/16 ILTS-E 2CDL 010 101 R1639 66956 6 /L54706 0.43 15 0.23 10 30 1040 39 x 1 PS 1/39/30 ILTS-E 2CDL 010 101 R3039 66957 3 /L54706 0.74 15 0.487 5 16 1040 39 x 3 PS 3/39/16 ILTS-E 2CDL 030 101 R1639 66958 0 /L54706 1.3 15 0.59 10 30 1040 39 x 3 PS 3/39/30 ILTS-E 2CDL 030 101 R3039 66959 7 /L54706 1.95 15 1.222 5 /L54706 bbn-Nr. 40 16779 ISS, 1pole 2CDC 062 151 F0008 ISS, 3pole 2CDC 062 152 F0008 ILTS-E, 1pole 2CDC 062 149 F0008 ILTS-E, 3pole 2CDC 062 150 F0008 PS 1/39/16 ILTS-E PS 1/39/30 ILTS-E PS 3/39/16 ILTS-E PS 3/39/30 ILTS-E PS 1/39/16 ILTS-E PS 1/39/30 ILTS-E PS 3/39/16 ILTS-E PS 3/39/30 ILTS-E Cross- section mm2 Length mm No. of poles Order details Type code bbn 40 12233 EAN Cu factor Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code End caps 1 END 1.1 2CDL 200 011 R0011 63891 3 15 0.001 50 2/3 PS-END 2CDL 200 001 R0001 51472 9 15 0.001 50 2/3 PS-END 3 2CDL 200 001 R3001 65430 2 15 0.001 50 1 PS-END 3.2 2CDL 200 001 R3003 66960 3 15 0.001 50 D0 fuse links to DIN VDE 0636-3, IEC/EN 60269-3 suitable for D01/E14 2 pink 1.5 D01 x 2 gL GMN 977 120 P0011 60480 7 13 0.006 10 4 brown 1.5 D01 x 4 gL GMN 977 120 P0012 60490 6 13 0.006 6 green 1.5 D01 x 6 gL GMN 977 120 P0013 60500 2 13 0.006 10 red 1.8 D01 x 10 gL GMN 977 120 P0014 60510 1 13 0.006 16 grey 2.1 D01 x 16 gL GMN 977 120 P0015 60520 0 13 0.006 20 blue 2.3 D02 x 20 gL GMN 977 120 P0017 60530 9 13 0.011 10 25 yellow 2.6 D02 x 25 gL GMN 977 120 P0018 60540 8 13 0.012 35 black 2.9 D02 x 35 gL GMN 977 120 P0019 60550 7 13 0.013 50 white 3.5 D02 x 50 gL GMN 977 120 P0020 60560 6 13 0.014 63 copper 4.2 D02 x 63 gL GMN 977 120 P0021 60570 5 13 0.015 Suitable for D02/E18 D 01 2-10 A D 02 2-50 A Connector sleeves D 01 2-16 A Fuse links D 02 20-63 A D0 screw caps SK 0069 Z 01 SK 0070 Z 01 FD 1713 SK 0159 Z 91 16 for D01 – D01 DIN 49 525 K GMN 977 130 P0011 60790 7 13 0.015 20 63 for D02 – D02 DIN 49 525 K GMN 977 130 P0012 60800 3 13 0.015 20 D0 screw caps acc. to DIN VDE 0636-3, IEC/EN 60269-3, 400 V AC Plastic version, RAL 7037 2 pink – D01 x 2 GMN 977 125 P0001 60600 9 13 0.001 50 4 brown D01 x 4 GMN 977 125 P0002 60610 8 13 0.001 6 green D01 x 6 GMN 977 125 P0003 60620 7 13 0.001 10 red D01 x 10 GMN 977 125 P0004 60630 6 13 0.001 D0 connector sleeves to DIN VDE 0636-3, IEC/EN 60269-3 Suitable for D01/E14 2 pink – D02 x 2 GMN 977 125 P0011 60640 5 13 0.001 50 4 brown D02 x 4 GMN 977 125 P0012 60650 4 13 0.001 6 green D02 x 6 GMN 977 125 P0013 60660 3 13 0.001 10 red D02 x 10 GMN 977 125 P0014 60670 2 13 0.001 16 grey D02 x 16 GMN 977 125 P0015 60680 1 13 0.001 20 blue D02 x 20 GMN 977 125 P0016 60690 0 13 0.001 25 yellow D02 x 25 GMN 977 125 P0017 60700 6 13 0.001 35 black D02 x 35 GMN 977 125 P0018 60710 5 13 0.001 50 white D02 x 50 GMN 977 125 P0019 60720 4 13 0.001 Suitable for D02/E18 Spring clip for use of D01 fuses in D02 screw caps FD 1713 GMN 977 130 P0004 15120 7 ➀ 13 0.001 50 ➀ bbn-Nr. 40 16779 D0 fuses and accessories Rated current A Colour code Power loss W Order details Type code bbn 40 12233 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code S0223B91

pro M compact® Electronic Protection Devices for use behind 24 V DC Switch Mode Power Supplies EPD24-TB-101 The protection devices EPD24 extend the ABB product range of modular DIN rail components by electronic overcurrent protection modules for selective protection of 24V DC load circuits. This protection is achieved by a combination of active electronic current limitation in the case of a short circuit and an overload deactivation from 1.1 x In upwards. If a fault occurs in a load circuit, the protection device EPD24 will detect this rapidly and reliably, disable the power output transistor and hence interrupt the current flow in the defective circuit. The maximum possible overcurrent is always limited to 1.5…1.8 times the selected rated current. An activation of capacitive loads up to 20,000 μF is possible, deactivation only occurring in the case of overloads or short circuits. Selective deactivation of the defective current circuit means undefined error states and a complete system stop are prevented.

Features

  • Selective load protection, one electronic trip characteristics.
  • Active current limitation for safe connection of capacitive loads up to 20,000 μF and on over- load/short circuit.
  • Reliable overload disconnection with 1.1 x IN
  • Manual ON/OFF button
  • Clear status and failure indication through LED and auxiliary contact.
  • Integral fail-safe element adjusted to current rating.
  • Width per unit only 12.5 mm.
  • Rail mounting
  • Ease of wiring through busbar LINE+ and 0 V as well as signal bars.
  • UL- and CSA-approvals allow international use of the devices. 0.5 EPD24-TB-101-0.5A 2CDE 601 101 R2905 829960 0.065 4 1 EPD24-TB-101-1A 2CDE 601 101 R2001 829984 0.065 4 2 EPD24-TB-101-2A 2CDE 601 101 R2002 830003 0.065 4 3 EPD24-TB-101-3A 2CDE 601 101 R2003 830027 0.065 4 4 EPD24-TB-101-4A 2CDE 601 101 R2004 830041 0.065 4 6 EPD24-TB-101-6A 2CDE 601 101 R2006 830065 0.065 4 8 EPD24-TB-101-8A 2CDE 601 101 R2008 830089 0.065 4 10 EPD24-TB-101-10A 2CDE 601 101 R2010 830102 0.065 4 12 EPD24-TB-101-12A 2CDE 601 101 R2012 830126 0.065 4 Rated current In in A Order details Type code bbn 40 16779 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Selection table accessories Selection table Busbars for LINE+ and 0 V, grey insulation, length 500 mm EPD-BB500 2CDE 605 100 R0500 830140 0.20 10 Signal Bars for aux. contacts, grey insulation, length 21 mm EPD-SB21 2CDE 605 200 R0021 830164 0.04 10 1) Max. load with one line entry I max = 50 A (recommended: center-feeding) Max. load with two line entries Imax = 63 A Order details Type code bbn 40 16779 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code 2CDC055001S0010 2CDC051001S0010

pro M compact® Electronic Protection Devices Technical data (T amb. = 25 °C, U B = 24 V DC) for use behind 24 V DC Switch Mode Power Supplies EPD24-TB-101 Operating data Operating voltage UB: 24 V DC (18...32 V) Current rating IN: fixed current ratings: Closed current I0: ON condition: typically 20...30 mA depending on signal output Staus indication by means of: – multicolour LED: Green: – unit is ON (S1 = ON) – load circuit / Power-MOSFET is switched on Orange: – in the event of overload or short circuit until electronic disconnection Red: – unit electronically disconnected – load circuit/Power-MOSFET OFF – undervoltage (U B < 8 V) – after switch-on till the end of the delay period OFF: – manually switched off (S1 = OFF) or device is dead – potential-free auxiliary contact F – ON/OFF/ condition of switch S1 Signal output F Electrical data potential-free auxiliary contact max. 30 V DC/0.5 A, min. 10 V DC/10 mA ON condition LED green voltage UB applied, switch S1 is in ON position no overload, no short circuit OFF condition LED off – device switched off (switch S1 is in OFF position) – no voltage U B applied Fault condition LED orange overload condition > 1.1 x IN up to electronic disconnection Fault condition LED red – electronic disconnection upon overload or short circuit – Device switched off with control signal (switch S1 is in ON position) Aux. contact single signal, make contact contact open, terminal 13-14 Fault signal output fault conditions – no operating voltage U B – ON/OFF switch S1 is in OFF position – red LED lighted (electronic disconnection) Load circuit Load output Power-MOSFET switching output (high slide switch) Short-circuit current IK active current limitation (see table 1) Trip time see time/current characteristics For electronic disconnection typically 3 s at ILoad > 1.1 x IN typically 100 ms...3 s at ILoad > 1.8 x IN (or 1.5 x IN/1.3 x IN, ) Temperature disconnection internal temperature monitoring with electronic disconnection Low voltage monitoring load output with hysteresis, no reset required: load »OFF« at UB< 8 V Starting delay tStart typically 0.5 sec after every switch-on and after applying US Disconnection of load circuit electronic disconnection Free-wheeling circuit suitable external free-wheeling circuit to be used with inductive load Several load outputs must not be connected in parallel LINE+ 1

2 LOAD+

(single signal, NO) Operating condition: 13-14 closed Fault condition: 13-14 open 2CSC400050F0202

pro M compact® Electronic Protection Devices Technical data (T amb. = 25 °C, U B = 24 V DC) for use behind 24 V DC Switch Mode Power Supplies EPD24-TB-101 General data Fail-Safe element backup fuse for EPD24 not required because of the integral redundant fail-safe element Housing material moulded Mounting symmetrical rail to EN 50022-35x7.5 Ambient temperature 0...+50 °C (without condensation, see EN 60204-1) Storage temperature -20...+70 °C Humidity 96 hrs/95 % RH/40 °C to IEC 60068-2-78, test Cab. climate class 3K3 to EN 60721 Vibration 3 g, test to IEC 60068-2-6 test Fc Degree of protection housing: IP20 DIN 40050 terminals: IP20 DIN 40050 EMC (EMC directive, CE logo) emission: EN 61000-6-3 susceptibility: EN 61000-6-2 Isolations coordination (IEC 60934) 0.5 kV/pollution degree 2 reinforced insulation in operating area Dielectric strength max. 32 V DC (load circuit) Isolation resistance (OFF condition) n/a, only electronic disconnection Approvals/Declarations of conformity UL 2367 Solid State Overcurrent Protectors UL 1604, (class I, division 2, groups A, B, C, D) UL 508 CSA C22.2 No. 213 (class I, division 2) CSA C22.2 No. 142 CE logo Dimensions (B x H x T) 12.5 x 80 x 83 mm Weight approx. 65 g Terminals Line+/LOAD+/0V Screw terminals M4 Max. cable cross section flexible with wire end ferrule w/wo plastic sleeve 0.5 – 10 mm2 Multi-lead connection (2 identical cables) rigid/flexible 0.5 – 4 mm2 Flexible with wire end ferrule without plastic sleeve 0.5 – 2.5 mm2 Flexible with TWIN wire end ferrule with plastic sleeve 0.5 – 6 mm2 Wire stripping length 10 mm Tightening torque (EN 60934) 1.5 – 1.8 Nm Terminals aux. contacts Screw terminals M3 Max. cable cross section flexible with wire end ferrule w/wo plastic sleeve 0.25 - 2.5 mm2 Wire stripping length 8 mm Tightening torque (EN 60934) 0.5 Nm Table 1: voltage drop, current limitation, max. load current current rating typically voltage drop active current max. load current at 100 % ON duty IN UON at IN limitation (typically) T ambient = 40 °C T ambient = 40 °C 0.5 A 70 mV 1.8 x I N 0.5 A 0.5 A 1 A 80 mV 1.8 x I N 1 A 1 A 2 A 130 mV 1.8 x I N 2 A 2 A 3 A 80 mV 1.8 x I N 3 A 3 A 4 A 100 mV 1.8 x I N 4 A 4 A 6 A 130 mV 1.8 x I N 6 A 5 A 8 A 120 mV 1.5 x I N 8 A 7 A 10 A 150 mV 1.5 x I N 10 A 9 A 12 A 180 mV 1.3 x I N 12 A 10.8 A Attention: when mounted side-by-side without convection the EPD24 should not carry more than 80 % of its rated load with 100% ON duty due to thermal effects.

Solutions for the hospital sector ABB’s extensive experience in the hospital field is certified by several installations in leading hospitals, which represent the current leading-edge in safety and technology. Over the years, ABB has deve- loped an increasingly more complete product with higher performance to meet the needs of more demanding customers and guarantee patient and operator safety. H+Line products are specifically designed for group 2 medical environments in full compliance with Standard IEC 60364-7-710, specifically: - Intensive therapy wards, operating theatres, cardio surgical rooms, ICU… - Day hospitals, clinics, rest homes, dental and veterinary clinics, etc. H+Line product range ISOLTESTER Insulation monitoring device for IT-M 230 V circuits SELVTESTER Insulation monitoring device for SELV 24 V cir- cuits which supply scialitic lamps. QSD Remote signalling panel for visual and acoustic fault indication. TI Medical insulating transformers for insulated protection systems. QSO Wall mounting and floor standing switchboards for medical locations. Valid assistance for consultants Everyone knows what the regulations say. ABB tells you what they don’t say. The “Practical guide to group 2 medical locations” is designed to be a useful daily tool for consultants and installers to help them in each group 2 hospital electrical system designing and installation. The document was developed toghether with ABB customers with the intent to support key regula- tory questions with practical solutions, considerations and reccomendations on system design. This way, the “Practical guide to group 2 medical locations” is a valid tool, with plenty of of examples, to support consultants in their daily job. H like Hospital like health and first aid like the countless advantages of ABB products H+Line System pro M compact® Protection devices H+Line products H+Line

pro M compact® Selection tables Protection devices Insulation monitoring devices Assuring operational continuity in medical environments, even in presence of first earthing fault, it’s mandatory in operating theatre group 2 medical locations. For this reason an IT distribution system with insulating transformer is used to supply medical equipment. ISOLTESTER-DIG ISOLTESTER range of insulation monitoring device allows IT-M network monitoring, assuring safety for patients and medical personnel avoiding supply interruption in case of first earthing fault according to IEC 60364-7-710 Standard. The ISOLTESTER-DIG range assures safety to patients and medical personnel, signalling when a fault to earth occurs. Thanks to its innovative technology it is used to sense the insulation level of the network by far more efficiently compared to traditional insulation monitoring devices. Advanced features Order details Bbn Price Price Weight Packing 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. ISOLTESTER-DIG-RZ 2CSM244000R1501 884507 0.500 1 RS485, Max-Min values, Programmable relay ISOLTESTER-DIG-PLUS 2CSM341000R1501 884606 0.500 1 Display to see the value of the parameters under control and of the settings Led to indicate the display of the resi- stance insulation (kW) parameter of the transformer, flashing for parameter out of threshold Led to indicate the display of the impedance insulation of the transformer, flashing for parameter out of threshold Led to indicate the display of the tem- perature parameter of the transformer, flashing for parameter out of threshold Led to indicate the display of the tempe- rature parameter for the second sensor, flashing for parameter out of threshold Led to indicate the display of the current network parameter, flashing for parameter out of threshold Buttons to select the parameter to be seen and to program the device’s settings Button for the access to the device’s program and confirmation of the settings Button to test the device or the remote si- gnalling panels and to reset Led to indicate the device’s programming status Led to indicate status of the auxiliary relays output Led to indicate alarm due to an internal fault or to the missed wiring of the network to be controlled or to a fault of the tempe- rature probe Led of alarm indication for a parameter’s value out of threshold Functioning of the frontal operators 2CSC400126F0201 ISOLTESTER-DIG 2CSC400126F0201

pro M compact® Selection tables Protection devices Insulation monitoring devices ISOLTESTER-DIG Technical features ISOLTESTER-DIG-PLUS ISOLTESTER-DIG-RZ Rated 110 - 230 V/50-60 Hz Network voltage to be controlled 24÷230 V a.c. Voltage max. measure 24 V Current max. measure 1 mA Insulation voltage 2.5 kV/60 sec. Type of control’s signal Codified signal Direct component with digital filter Sensed measures Measure range 0 ÷ 999 kohm/HIGH - resolution 1 kohm Thermal-probe temperature PT100 0÷250 °C, accuracy 2% Current measure from external T.A. with secondary 5 A , accuracy 2% (selectable statement value T.A. 1÷200) Impedance measure 0 ÷ 999 Kohm/HIGH - resolution 1 Kohm (codified composed signal) Impedance measure 0 ÷ 999 Kohm/HIGH - resolution 1 Kohm (test signal 2500 Hz) Intervention threshold Low insulation 50 ÷ 500 kohm, accuracy 5%, hysteresis 5%, delay which can be setted Overtemperature 0 ÷200 °C, accuracy 2% Overload current 1 ÷ 999 A, accuracy 2% Low impedance (which can be disarmed) Link-Fail Available output Max. up to 4 QSD panels for remote signalling Max. up to 2 QSD panels for remote signalling Programmable auxiliary relays output NA-C-NC, 5 A, 250 VAC Serial output RS485, standard protocol Modbus-rtu - Displays Insulation resistance value with signalling of over fullscale value and direct earth fault Value of measured temperature 0 ÷ 200 °C per channel 1 Value of measured temperature 0 ÷ 200 °C per channel 2 Value of measured current 0 ÷ 999 A Value insulation impedance Value of network capacity to earth - Setting parameters Link-Fail Relays output status Memorization of min. insulation - Max. temperature and current values - Connection Max. section 2.5 sqmm Operating temperature -10 ÷ 60 °C Storage temperature -25 ÷ 70 °C, humidity < 90% Dimensions 6 modules DIN Weight 0.5 kg Housing Plastic self-extinguishing housing for 35 mm, with transparent sealable plate Protection degree IP20 Self-consumption 5 VA Reference standard IEC 61557-8, IEC 60364-7-710, IEC 60255-6

pro M compact® Selection tables Protection devices Insulation monitoring devices SELVTESTER QSD H+Line SELVTESTER for insulated networks at 24 V a.c/d.c. It is used to monitor permanently the insulation of safety extremely low voltage circuits (up to 24 V) especially scialitic lamps. Function Order details Bbn Price Price Weight Packing 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Insulation monitoring SELVTESTER-24 2CSM211000R1511 884705 0.250 1 QSD remote signalling panel They are installed in combination with insulation monitoring devices, to remotely report the signalling ge- nerated by these devices. They can be installed together with ISOLTESTER-DIG and SELVTESTER-24 and they are compatible also with former versions of insulating monitoring devices. Flush mounting box already included in the packaging. Version Order details Bbn Price Price Weight Packing 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Horizontal QSD-DIG 230/24 2CSM273063R1521 730637 0.800 1 Vertical QSD-DIG 230/24 V 2CSM257093R1521 570936 0.800 1 2CSC400404F0201 2CSC400693F0001

pro M compact® Selection tables Protection devices Insulation monitoring devices SELVTESTER QSD Technical features of SELVTESTER Network voltage and auxiliary power supply 24 V 50-60 Hz/d.c. ± 20% Max power dissipation 3 VA – 3 W Max measuring current max. 0,5 mA Internal impedance 50 kohm Activation threshold setting programmable to 10 ÷ 50 kohm (4 levels using microswitches) Activation delay about 1 second Signals led ON, led ALARM +, led ALARM - Output for up to 2 QSD-230/24-C, max. 24 V 1 A remote panels Operating / storage temperature -10 ÷ 60 °C / -20 ÷ 70 °C Relative humidity ≤ 95% Insulation test 2,5 kV 60 sec. / 4 kV imp. 1,2/50μs Terminal cross section 4 mm2 Front degree of protection IP40 with cover / IP20 container Modules 3 Weight 200 g Reference standards for safety IEC 60364-7-710, EN 61326-1, EN 61010-1 Technical features of QSD Signals green led network, red led overload ALARM, yellow led low insulation FAULT ALARM, acoustic signaller, emission 2400 Hz intermittence 2 Hz dB Buttons TEST and MUTE buttons Terminal cross section 2,5 mm Degree of protection IP30 Installation universal flush-mounted box Weight 200 g Operating temperature -10 ÷ 60 °C, max. humidity 95% Storage temperature -25 ÷ +80 °C Insulation 2500 Vrms 50 Hz 60 s Cables section 0.35 mm 2 for 300 m Compatibility ISOLTESTER-C, ISOLTESTER-RZ, ISOLTESTER-DIG-RZ, ISOLTESTER-DIG, PLUS, SELVTESTER-C, SELVTESTER-24 Reference standards safety EN 61010-1 product EN 61557-8 / IEC 60364-7-710 / UNE 20615 electromagnetic compatibility EN 61326-1

pro M compact® Selection tables Protection devices Switchboards and devices for medical locations TI Technical characteristics Rated output [KVA] 3 5 7,5 10 Frequency [Hz] 50-60 Power dissipation [W] 120 150 280 320 Electrical protection class 1 Thermal insulation class [°C] B 130 B 130 F 155 F 155 Operating temperature max [°C] 40 Primary winding voltage [V] 230 Secondary winding voltage [V] 230 No load current [A] < 0.39 < 0.65 < 0.98 < 1.3 Short circuit voltage drop <3% Inrush current [A] < 221 < 369 < 553 < 738 Power loss [W] 120 150 260 320 Winding separation double insulation Metallic shield ■ Reference standard IEC-EN 61558-1, IEC-EN 61558-2-15, IEC-EN 62041 Dimensions [mm] 205x340x150 240x380x150 240x380x160 277x380x260 Insulating transformers for medical locations Permanently connected to an IT power supply system, single-phase medical insulating transformers provide galvanic separation between the distribution network and the user load in accordance with IEC EN 61558-2-15 concerning power supply group 2 medical locations. Rated PT100 Order Bbn Price Price Weight Pack Output details 801254 1 piece group 1 piece unit KVA Type code Order code EAN kg pc. 3 TI 3 2CSM110000R1541 2896005 29.5 1 5 TI 5 2CSM120000R1541 2896104 44.0 1 7.5 TI 7.5 2CSM130000R1541 2896203 50.5 1 10 TI 10 2CSM140000R1541 2521204 73.0 1 3 ■ TI 3-S 2CSM210000R1541 2521402 29.5 1 5 ■ TI 5-S 2CSM220000R1541 2521501 44.0 1 7.5 ■ TI 7.5-S 2CSM230000R1541 2521600 50.5 1 10 ■ TI 10-S 2CSM240000R1541 2521709 73.0 1 Accessories for insulating transformers for medical locations Order Bbn Price Price Weight Pack details 801254 1 piece group 1 piece unit Type code Order code EAN kg pc. Shock absorber AMM 2CSM900000R1541 2557920 1 4 Serial number location 0 230 SCH

0 PC 230

0 -230: Primary SCH: Metal shield PE Secondary winding 0 -230: Secondary PC: Central socket Probe 1 Probe 2 4: to terminal 25 ISOLTESTER-DIG 5: to terminal 25 ISOLTESTER-DIG 6: to terminal 27 ISOLTESTER-DIG 1: to terminal 28 ISOLTESTER-DIG 2: to terminal 28 ISOLTESTER-DIG 3: to terminal 30 ISOLTESTER-DIG 2CSC400759F0001 2CSC400052F0202 2CSC400051F0202

pro M compact® Selection tables Protection devices Switchboards and components for medical locations QSO Electrical switchboard for medical locations Electrical switchboards for operating theatres incorporate all the latest ABB modular instrumenta- tion. They are the ideal solution for distribution within group II medical locations, allowing monitoring of all network parameters and control of the 24 V a.c. supply line to the scialitic lamp. ABB panels are assambled with ArTu switchgears and are provided with instruction manual and declaration of conformity required for commissioning, thus guaranteeing installers compliance with all regulations. Power PT100 SELV Order Bbn Price Price Weight Pack sensor circuit details 801254 1 piece group 1 piece unit KVA Type code Order code EAN kg pc. Wall mounted electrical switchboard for medical locations 3 QSO 3kVA 2CSM110000R1551 2376101 100.0 1 5 QSO 5kVA 2CSM120000R1551 2376200 104.5 1 7.5 QSO 7.5kVA 2CSM130000R1551 2376309 121.0 1 3 ■ QSO 3kVA-S 2CSM210000R1551 2526308 100.0 1 5 ■ QSO 5kVA-S 2CSM220000R1551 376200 104.5 1 7.5 ■ QSO 7.5kVA-S 2CSM230000R1551 2526506 121.0 1 Floor standing electrical switchboard for medical locations 3 ■ QSO 3kVA-S-PV 2CSM310000R1551 2526605 161.5 1 5 ■ QSO 5kVA-S-PV 2CSM320000R1551 2526704 176.0 1 7.5 ■ QSO 7.5kVA-S-PV 2CSM330000R1551 2526803 182.5 1 10 ■ QSO 10kVA-S-PV 2CSM340000R1551 2526902 205.0 1 3 ■ ■ QSO 3kVA-S-PV+24Vac 2CSM410000R1551 2614302 161.5 1 5 ■ ■ QSO 5kVA-S-PV+24Vac 2CSM420000R1551 2614401 176 1 7.5 ■ ■ QSO 7.5kVA-S-PV+24Vac 2CSM430000R1551 2614500 182.5 1 10 ■ ■ QSO 10kVA-S-PV+24Vac 2CSM440000R1551 2614609 205 1 Technical characteristics Rated voltage [V] 230 ± 15% a.c. Rated frequency [Hz] 50 Number of phases 1 + N ~/ PE Auxiliary circuits rated voltage [V] 230 a.c. Insulation rated voltage [V] 300 - 2,500 Distribution system TT / TN-S Max short circuit current [kA] 6 RMS sym Max altitude [m] 2000 a.s.l Contamination level 1 absent or only dry and non conducting Resistance to impact IK09 Protection degree IP65 front with door - IP31 front without door - IP20 on top Relative humidity 50% Operating temperature [°C] - 5 / + 40 Storage temperature [°C] - 25 / + 55 Reference standard IEC 60364-7-710; EN60439-1 H+Line 2CSC400759F00012CSC400759F0001

pro M compact® Selection tables Protection devices ISL industrial insulation monitoring devices ISL Insulation monitoring devices In IT electrical distribution networks with isolated neutral, the high insulation impedance prevents earth faults from generating currents that would dangerously elevate the potential of exposed conductive parts. Therefore, in case of earth leakage in an IT network it is not necessary to interrupt the supply, but it is still essential to continually monitor the insulation level in order to detect faults and restore optimal functioning of the system. In industrial installations, IT networks are used when operational continuity is an intrinsic requirement of the production process, due to both technical and economic considerations. Such applications include: metalworking and chemical industries, explosion risk locations, railway lines and vehicles, uninterruptible power supplies, cinema sets, emergency lines, fire water pumps and emergency lighting. Monitored Order Bbn Price Price Weight Pack line voltage details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Insulation monitoring devices for a.c. networks 220-240 V a.c. ISL-C 230 2CSM444000R1500 942801 0.300 1 380-415 V a.c. ISL-C 440 2CSM545000R1500 942900 0.300 1 60-760 V a.c. ISL-C 600 2CSM656000R1500 943006 0.500 1 Insulation monitoring devices for d.c. networks 100-144 V d.c ISL-A 115 2CSM222000R1500 942603 0.500 1 220 V d.c. ISL-A 230 2CSM333000R1500 942702 0.500 1 400-600 V d.c. ISL-A 600 2CSM249853R1500 498537 0.500 1 Insulation monitoring devices for a.c./d.c. networks Insulation monitoring devices for voltageless network Technical features ISL-A ISL-A 24-48 115 and 230 400-600 Power consumption [VA] 3 4 6 ALARM threshold [kΩ] 30 - 300 TRIP threshold [kΩ] 10 - 60 10 - 100 30 - 300 LED indications ON ■■■ TRIP ■■■ ALARM ■ +/- ■■■ Max trip delay [s] 0.2 2 2.5 Max measuring current [mA] 0.5 1.8 1.5 Max measuring voltage [V] 12 Internal impedance [kΩ] 50 100 880 k Ω L+/L - 450 kΩ L/PE TRIP relay output 1 NO-C-NC 2 NO-C-NC 1 NO-C-NC ALARM relay output 2 NO-C-NC Relay contact capacity max 250 V, 5 A Programmed functions Alarm output ■ Fail safe ■ Reset ■ Operating temperature [°C] -10 ÷ 60 Storage temperature [°C] -20 ÷ 70 Relative humidity ≤ 95% Max terminal section [mm2] 4 2.5 2.5 Protection degree IP40 front, IP20 enclosure Modules 366 Weight [g] 200 400 400 Reference standards EN 61010-1, EN 61557-8, EN 61326-1 2CSC400704F0201 2CSC400705F0201

Technical features ISL-C and ISL-MOT ISL-C ISL-MOT 230 440 600 1000 Power consumption [ V A ] 3353 TRIP threshold [kΩ] 100 10 -150 10-100 0.1 - 1000 LED indications ON ■■■■ TRIP ■■■■ ALARM ■ Max trip delay [s] 1 4 5 0.2 Max measuring current [mA] 0.1 0.1 0.25 0.0015 Max measuring voltage [V] 12 48 20 Internal impedance [kΩ] 250 250 200 1500 d.c. TRIP relay output 1 NO-C-NC 1 NO-C-NC 2 NO-C-NC 1 NO-C-NC Relay contact capacity max 250 V, 5 A Insulation test 2.5 kV60 sec. / 4 kV imp 1.2/50 μs Operating temperature [°C] -10 ÷ 60 Storage temperature [°C] -20 ÷ 70 Relative humidity ≤ 95% Max terminal section [mm2] 4 4 2.5 4 Protection degree IP40 front, IP20 enclosure Modules 3363 Weight [g] 200 200 500 200 Reference standards EN 61010-1, EN 61557-8, EN 61326-1 System pro M compact® Selection tables Protection devices ISL industrial insulation monitoring devices ISL

appliances. Families - E200 and E210 switches: these devices are suitable for commanding loads and they are realized according to the EN 60947-3 and EN 60669-1 respectively. - ESB and EN series contactors: they are devices suitable for loads to be automatically controlled through high number of operations - E250, E260 latching relays and E259 installation relays Their high performance in the single or multi-point control of lamps make them an ideal solution for lighting circuits. - AT electro-mechanical, D Line and DTS digital and TW and TWA twilight switches: They control circuit opening and closing according to scheduled programs (AT, D Line and DTS) or scheduled level of the ambient light (TW) or on the basis of the sun rising and setting (TWA) - E 232 staircase lighting time-delay switches: they are suitable to command the lighting in stairs in buildings - THS modular thermostats: these devices are suitable for the majority of HVAC applications. - ATT telephone attuator is suitable for remote control of electrical loads

pro M compact® Selection tables Command devices E 200 switches E 200 2CDC051496F0003 E 200 switches Isolator for panel installation onto DIN rail acc. to DIN EN 60715 Mounting depth: 70mm Mounting width: per pole = 17.5mm = 1module Colour: grey, RAL 7035 Colour of switch lever: red RAL 3000 (r); grey RAL 7000 (g) Special features - Fast removal without dismantling of the busbar - Captive screws with recessed/slotted head, Pozidriv size 2 - Add-on of up to 3 auxiliary contact S2C-H6R possible - Integrated lay-on edge for labeling system ILS - Locking device as accessories for unauthorized ON/OFF - Approval: VDE, CCC, KEMA Poles Rated Power Order Bbn Price Price Weight Pack voltage loss details 4016779 1 piece group 1 piece unit V AC W Type code Order code EAN kg pc. Rated current 16 A 1NO 230V 0 .15 E201/16g 2CDE281001R1016 645614 0 .095 10 1NO 230V 0 .15 E201/16r 2CDE281001R0016 645621 0 .095 10 2NO 400V 0 .30 E202/16g 2CDE282001R1016 645799 0 .190 5 2NO 400V 0 .30 E202/16r 2CDE282001R0016 645805 0 .190 5 3NO 400V 0 .45 E203/16g 2CDE283001R1016 645973 0 .290 3 3NO 400V 0 .45 E203/16r 2CDE283001R0016 645980 0 .290 3 4NO 400V 0 .60 E204/16g 2CDE284001R1016 646154 0 .390 2 4NO 400V 0 .60 E204/16r 2CDE284001R0016 646161 0 .390 2 Technical data Switching capacity 1.25 x I n; 1.1 x Un; cosϕ = 0.3 acc. to DIN VDE 0632 AC22-A/AC23-A acc. to VDE 0660 part 107, DIN EN 60947-3 resp. IEC 947-3, DC21-B for applications up to 60 V DC Protection fuse NH00 gL-gG ≤ rated current E 200 Positive opening acc. to DIN VDE 0113 Suitable for isolation acc. to DIN EN 60947-3 Short-circuit withstand capacity 25 kA eff in series with NH 00 ≤ 100 A gL-gG; 6 kA eff in series with NH 00 125 A gL-gG and S 2.. ≤63 A Rated voltage 230/400 V AC; 50/60 Hz Surge withstand capability Uimp 4 kV acc. to EN 60947-1 Ambient temperature -25 °C to +55 °C Storage temperature -40 °C to +70 °C Climatic resistance constant climate 23/83, 40/93, 55/20 [°C/RH] alternating climate 25/95 - 40/93 [°C/RH] Mounting position optional Degree of protection IP10, IP40 in panelboard Mechanical endurance 20000 switching cycles Electrical endurance 1000 switching cycles Min. voltage 12 V AC/DC at 0.1 VA Min. contact loading 24 V/4 mA Wire range 2.5 to 50 mm 2 Busbars cross section ≥ 16 mm2 Torque 2.5 Nm * protection fuse /L50872 rated current E200 2CDC052068F0007

pro M compact® Selection tables Command devices E 200 switches E 200 2CSC400065F0201 Rated current 25 A 1NO 230V 0 .30 E201/25g 2CDE281001R1025 645638 0 .095 10 1NO 230V 0 .30 E201/25r 2CDE281001R0025 645645 0 .095 10 2NO 400V 0 .60 E202/25g 2CDE282001R1025 645812 0 .190 5 2NO 400V 0 .60 E202/25r 2CDE282001R0025 645829 0 .190 5 3NO 400V 0 .90 E203/25g 2CDE283001R1025 645997 0 .290 3 3NO 400V 0 .90 E203/25r 2CDE283001R0025 646000 0 .290 3 4NO 400V 1 .20 E204/25g 2CDE284001R1025 646178 0 .390 2 4NO 400V 1 .20 E204/25r 2CDE284001R0025 646185 0 .390 2 Rated current 32 A 1NO 230V 0 .50 E201/32g 2CDE281001R1032 645652 0 .095 10 1NO 230V 0 .50 E201/32r 2CDE281001R0032 645669 0 .095 10 2NO 400V 0 .95 E202/32g 2CDE282001R1032 645836 0 .190 5 2NO 400V 0 .95 E202/32r 2CDE282001R0032 645843 0 .190 5 3NO 400V 1 .40 E203/32g 2CDE283001R1032 646017 0 .290 3 3NO 400V 1 .40 E203/32r 2CDE283001R0032 646024 0 .290 3 4NO 400V 1 .90 E204/32g 2CDE284001R1032 646192 0 .390 2 4NO 400V 1 .90 E204/32r 2CDE284001R0032 646208 0 .390 2 Rated current 40 A 1NO 230V 0 .70 E201/40g 2CDE281001R1040 645676 0 .095 10 1NO 230V 0 .70 E201/40r 2CDE281001R0040 645683 0 .095 10 2NO 400V 1 .40 E202/40g 2CDE282001R1040 645850 0 .190 5 2NO 400V 1 .40 E202/40r 2CDE282001R0040 645867 0 .190 5 3NO 400V 2 .10 E203/40g 2CDE283001R1040 646031 0 .290 3 3NO 400V 2 .10 E203/40r 2CDE283001R0040 646048 0 .290 3 4NO 400V 2 .80 E204/40g 2CDE284001R1040 646215 0 .390 2 4NO 400V 2 .80 E204/40r 2CDE284001R0040 646222 0 .390 2 Rated current 45 A 1NO 230V 0 .90 E201/45g 2CDE281001R1045 645690 0 .095 10 1NO 230V 0 .90 E201/45r 2CDE281001R0045 645706 0 .095 10 2NO 400V 1 .80 E202/45g 2CDE282001R1045 645874 0 .190 5 2NO 400V 1 .80 E202/45r 2CDE282001R0045 645881 0 .190 5 3NO 400V 2 .65 E203/45g 2CDE283001R1045 646055 0 .290 3 3NO 400V 2 .65 E203/45r 2CDE283001R0045 646062 0 .290 3 4NO 400V 3 .50 E204/45g 2CDE284001R1045 646239 0 .390 2 4NO 400V 3 .50 E204/45r 2CDE284001R0045 646246 0 .390 2 Rated current 63 A 1NO 230V 1 .65 E201/63g 2CDE281001R1063 645713 0 .095 10 1NO 230V 1 .65 E201/63r 2CDE281001R0063 645720 0 .095 10 2NO 400V 3 .30 E202/63g 2CDE282001R1063 645898 0 .190 5 2NO 400V 3 .30 E202/63r 2CDE282001R0063 645904 0 .190 5 3NO 400V 4 .90 E203/63g 2CDE283001R1063 646079 0 .290 3 3NO 400V 4 .90 E203/63r 2CDE283001R0063 646086 0 .290 3 4NO 400V 6,55 E204/63g 2CDE284001R1063 646253 0 .390 2 4NO 400V 6 .55 E204/63r 2CDE284001R0063 646260 0 .390 2

pro M compact® Selection tables Command devices E 200 switches E 200 E 200 DC switching capacity Terminal assignment 2CDC 052 131 F00052CDC 052 171 F0005 Rated current 80 A 1NO 230V 2 .60 E201/80g 2CDE281001R1080 645737 0 .095 10 1NO 230V 2 .60 E201/80r 2CDE281001R0080 645744 0 .095 10 2NO 400V 5 .15 E202/80g 2CDE282001R1080 645911 0 .190 5 2NO 400V 5 .15 E202/80r 2CDE282001R0080 645928 0 .190 5 3NO 400V 7 .75 E203/80g 2CDE283001R1080 646093 0 .290 3 3NO 400V 7 .75 E203/80r 2CDE283001R0080 646109 0 .290 3 4NO 400V 10 .30 E204/80g 2CDE284001R1080 646277 0 .390 2 4NO 400V 10 .30 E204/80r 2CDE284001R0080 646284 0 .390 2 Rated current 100 A 1NO 230V 3 .95 E201/100g 2CDE281001R1100 645751 0 .095 10 1NO 230V 3 .95 E201/100r 2CDE281001R0100 645738 0 .095 10 2NO 400V 7 .90 E202/100g 2CDE282001R1100 645935 0 .190 5 2NO 400V 7 .90 E202/100r 2CDE282001R0100 645942 0 .190 5 3NO 400V 11 .85 E203/100g 2CDE283001R1100 646116 0 .290 3 3NO 400V 11 .85 E203/100r 2CDE283001R0100 646123 0 .290 3 4NO 400V 15 .80 E204/100g 2CDE284001R1100 646291 0 .390 2 4NO 400V 15 .80 E204/100r 2CDE284001R0100 646307 0 .390 2 Rated current 125 A 1NO 230V 6 .10 E201/125g 2CDE281001R1125 645775 0 .095 10 1NO 230V 6 .10 E201/125r 2CDE281001R0125 645782 0 .095 10 2NO 400V 12 .20 E202/125g 2CDE282001R1125 645959 0 .190 5 2NO 400V 12 .20 E202/125r 2CDE282001R0125 645966 0 .190 5 3NO 400V 18 .30 E203/125g ➀ 2CDE283001R1125 646130 0 .33 3 3NO 400V 18 .30 E203/125r ➀ 2CDE283001R0125 646147 0 .33 3 4NO 400V 24 .35 E204/125g ➀ 2CDE284001R1125 646314 0 .44 2 4NO 400V 24 .35 E204/125r ➀ 2CDE284001R0125 646321 0 .44 2 ➀ without approvals

1 NO 2 NO 3 NO 4 NO

2CDC 052 021 F00052CDC 052 022 F0005

pro M compact® Selection tables Command devices E 463/3, E 480/3 switches E 463/3-KB E 480/3-KB E 463/3-SL E 463/3-KB, E 480/3-KB, E 463/3-SL switches Rated Power Order Bbn Price Price Weight Pack current loss details 7612270 1 piece group 1 piece unit A W Type code Order code EAN kg pc. 63 5 .4 E 463/3-KB 2CCE160300R0131 932528 0 .190 1 63 5 .5 E 463/3-SL 2CCE160301R0131 932535 0 .195 1 80 9 .9 E 480/3-KB 2CCE180300R0141 932542 0 .210 1 Padlock for E 463/3-SL with 2 keys Order Bbn Price Price Weight Pack details 7612270 1 piece group 1 piece unit Type code Order code EAN kg pc. SA 2 GJF1101903R0002 587704 0 .020 1 Technical features Switching capacity 1.25 In; 1.1 Un; cos ϕ = 0.6 according to DIN VDE 0632 Rated voltage 250/400 V a.c. Connection cross section 1 mm 2 stranded wire/0.5 mm2 wire up to 25 mm2 Pick-up torque 3 Nm max. Positive opening according to DIN VDE 0113 Ambient temperature -25°C to +55°C Storage temperature -40°C to +70°C Poles 3 NO Short-circuit withstanding capacity 10 kA, 400 V a.c. SK 0105 Z 97 2CSC400458F02012CSC400433F02012CSC400455F0201

pro M compact® Selection tables Command devices E 210 switches E 210 These devices are specifically made for commanding loads and signalling electrical conditions in any low-voltage switchboard. They are available in half module or 1 module, depending on the contact-layout. The devices with indicator lights are equipped with a LED, which grants an optimal illumination with very low consumption. The functions of these devices are particularly switching, pushing and signalling electrical conditions in any installations (low-voltage area) General new features /L50189 Space-saving through 9mm modules /L50189 All terminals equipped with Pozidrive 1 screws /L50189 Safe connection due to cage-clamp /L50189 LED with bright colours and available in three different voltage ranges /L50189 Different lens and button colours /L50189 Compliance to international standards E 211-... ON-OFF switches For example, such devices are used to switch indicators or other electrical components (like fan’s, air-conditions, e.g.). The new On-Off switches distinguish themselves through simple handling, easy mounting and optimal functionality. Contacts Rated Power Width Order Bbn Price Price Weight Pack voltage loss details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. Rated current = 16A 1 NO 250 0 .32 9 E211-16-10 2CCA703000R0001 938575 0 .035 10 2 NO 230/400 0 .82 9 E211-16-20 2CCA703005R0001 938582 0 .045 10 3 NO 230/400 1 .14 18 E211-16-30 2CCA703010R0001 938599 0 .080 10 4 NO 230/400 1 .64 18 E211-16-40 2CCA703015R0001 938605 0 .090 10 Rated current = 25A 1 NO 250 0 .75 9 E211-25-10 2CCA703001R0001 938612 0 .035 10 2 NO 230/400 1 .95 9 E211-25-20 2CCA703006R0001 938629 0 .045 10 3 NO 230/400 2 .70 18 E211-25-30 2CCA703011R0001 938636 0 .080 10 4 NO 230/400 3 .90 18 E211-25-40 2CCA703016R0001 938643 0 .090 10 Rated current = 32A 1 NO 250 1 .12 9 E211-32-10 2CCA703002R0001 938650 0 .035 10 2 NO 230/400 2 .73 9 E211-32-20 2CCA703007R0001 938667 0 .045 10 3 NO 230/400 3 .85 18 E211-32-30 2CCA703012R0001 938674 0 .080 10 4 NO 230/400 5 .46 18 E211-32-40 2CCA703017R0001 938681 0 .090 10

2CCC441036F00012CCC441015F0001 2CCC441035F00012CCC441016F0001 System pro M compact® Selection tables Command devices E 210 switches E 210 2CCC441010Z00012CCC441014Z0001 2CCC441011Z0001 2CCC441015Z0001 2CCC441012Z00012CCC441016Z0001 2CCC441013Z0001 Terminal assignment

1 NO 2 NO 3 NO

OFF switches with indicator lamps ON / OFF switch 2CCC441017Z00011 C/O 2 C/O 2CCC441018Z0001 Change-over switches E 211X-... ON-OFF switches with yellow LED for contact indication LED voltage 115-250 VAC Contacts Rated Power LED Width Order Bbn Price Price Weight Pack voltage loss colour details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. Rated current = 16A 1 NO 250 0 .50 yellow 9 E211X-16-10 2CCA703100R0001 938872 0 .040 10 2 NO 230/400 1 .00 yellow 18 E211X-16-20 2CCA703110R0001 938889 0 .050 10 3 NO 230/400 1 .50 yellow 18 E211X-16-30 2CCA703115R0001 938896 0 .060 10 Rated current = 25A 1 NO 250 1 .15 yellow 9 E211X-25-10 2CCA703101R0001 938902 0 .040 10 2 NO 230/400 2 .30 yellow 18 E211X-25-20 2CCA703111R0001 938919 0 .050 10 3 NO 230/400 3 .45 yellow 18 E211X-25-30 2CCA703116R0001 938926 0 .060 10 E 213-... Change over switches The new change-over switches distinguish themselves through simple handling, easy mounting and optimal functionality. Example applications include opening and closing of electrically operated flaps. Contacts Rated Power LED Width Order Bbn Price Price Weight Pack voltage loss colour details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. Rated current = 16A 1 CO 250 0 .32 - 9 E213-16-001 2CCA703040R0001 938698 0 .041 10 2 CO 250 0 .82 - 18 E213-16-002 2CCA703045R0001 938704 0 .082 10 Rated current = 25A 1 CO 250 0 .40 - 9 E213-25-001 2CCA703041R0001 938711 0 .041 10 2 CO 250 0 .88 - 18 E213-25-002 2CCA703046R0001 938728 0 .082 10

pro M compact® Selection tables Command devices E 210 switches E 210 2CCC441021Z0001 2CCC441019Z0001 2CCC441022Z0001 2CCC441020Z0001 2CCC441023Z00011-pole 2-pole 1 NO + 1 NC 2 NO + 2 NC 3 NO + 1 NC Group switches Control switches 2CCC441019F00012CCC441023F0001 2CCC441020F00012CCC441024F0001 Terminal assignment E 214-... Group switches (I-0-II, manual-OFF-automatic) The new Group switches can be used to control the main installation of an emergency supply. Such devices distinguish themselves through simple handling, easy mounting and optimal functionality. Contacts Rated Power Width Order Bbn Price Price Weight Pack voltage loss details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. Rated current = 16A 1 CO 250 0 .32 9 E214-16-101 2CCA703025R0001 938735 0 .041 10 2 CO 250 0 .82 18 E214-16-202 2CCA703030R0001 938742 0 .082 10 Rated current = 25A 1 CO 250 0 .40 9 E214-25-101 2CCA703026R0001 938759 0 .041 10 2 CO 250 0 .88 18 E214-25-202 2CCA703031R0001 938766 0 .082 10 E 218-... Control switches These devices can be used in distribution board for any control function. The new control switches distinguish themselves through simple handling, easy mounting and optimal functionality. Contacts Rated Power Width Order Bbn Price Price Weight Pack voltage loss details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. Rated current = 16A 1NO+1NC 250 0 .50 9 E218-16-11 2CCA703050R0001 938773 0 .041 10 2NO+2NC 250 1 .00 18 E218-16-22 2CCA703060R0001 938780 0 .082 10 3NO+1NC 250 1 .50 18 E218-16-31 2CCA703065R0001 938797 0 .082 10 Rated current = 25A 1NO+1NC 250 0 .75 18 E218-25-11 2CCA703051R0001 938803 0 .041 10

pro M compact® Selection tables Command devices E 210 switches E 210 E 210 DC switching capacity Resistive load NO contact NC contact Load with time constant t = 15ms (inductive load) NO contact NC contact 2CCC441028Z0001 500 400 300 200 100 U (V) 1 2 3 4 5 6 7 10 16 20 30 40 I (A)32 Technical features - Switches Switching capacity according to EN 60669-1 Isolating properties according to EN 60669-2-4; IEC/EN 60947-3 Utilization category AC-22A; DC-22A acc. IEC/EN60947-3 Short-circuit withstand capacity [kA] 3 Rated voltage Un [V] 250/400 in accordance with EN 240 in accordance UL 508 Lowest operat. voltage 24 V; 25 mA Rated current In [A] 16, 25, 32 LED current [mA] 5 Rated frequency [Hz] 50/60 Modules [No] 0.5 or 1 Sealable in ON and OFF position Climatic resistance according to IEC 60068-2-2 (Dry heat) IEC 60068-2-30 (Damp heat) IEC 60068-2-1 (Cold) Ambient temperature [°C/°F] -25°C/-13°F to +55°C/+131°F Storage temperature [°C] -40°C to +70°C Connection capacity [mm 2] from 1x1 mm2 to 1x6 mm2 or 2x2.5 mm2 massive; Flexible up 1x0.75 mm 2 to 2x1.5 mm2 with connector sleve or pin-endconnector Tightening torque [Nm] 1.2 - 1.5 Positive opening according to EN 60204-1 Standards DIN EN 60669-1 *VDE 0632-1 DIN EN 60669-2-4 *VDE 0632-2-4 UL 508 Approvals VDE, UL, GOST, CCC

pro M compact® Selection tables Command devices E 210 Pushbuttons with and without LEDs E 210 2CCC441029F00012CCC441048F0001 E 215-... Pushbuttons (6 different button colours) Pushbuttons without and with LED The new products are available in 9 mm widths (= 0.5 modules). The devices can be used in distribution boards and are all distinguished by their simple handling, ease of mounting and optimal functionality. The pushbuttons are used for remote control in all kinds of electrical installation (e.g. public, industrial). The range offers three different voltages. (Ranges: 12-48 V AC/DC; 115-250 V AC and 110-220 V DC). Rated current = 16A Contacts Rated Power Button Width Order Bbn Price Price Weight Pack voltage loss colour details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. 1NO+1NC 250 0 .50 grey 9 E215-16-11B 2CCA703150R0001 938810 0 .046 10 1NO+1NC 250 0 .50 red 9 E215-16-11C 2CCA703151R0001 938827 0 .046 10 1NO+1NC 250 0 .50 green 9 E215-16-11D 2CCA703152R0001 938834 0 .046 10 1NO+1NC 250 0 .50 yellow 9 E215-16-11E 2CCA703153R0001 938841 0 .046 10 1NO+1NC 250 0 .50 black 9 E215-16-11F 2CCA703154R0001 938858 0 .046 10 1NO+1NC 250 0 .50 blue 9 E215-16-11G 2CCA703155R0001 938865 0 .046 10 E 217-... Luminous Pushbuttons (5 different LED colours) Rated current = 16A Contacts Rated Power LED Width Order Bbn Price Price Weight Pack voltage loss colour details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. LED Voltage range = 115-250VAC 1 NO 250 1 .10 wh ite 9 E217-16-10B 2CCA703160R0001 938988 0 .050 10 1 NO 250 1 .10 red 9 E217-16-10C 2CCA703161R0001 938995 0 .050 10 1 NO 250 1 .10 green 9 E217-16-10D 2CCA703162R0001 939008 0 .050 10 1 NO 250 1 .10 yellow 9 E217-16-10E 2CCA703163R0001 939015 0 .050 10 1 NO 250 1 .10 blue 9 E217-16-10G 2CCA703164R0001 939022 0 .050 10 1 NC 250 1 .10 wh ite 9 E217-16-01B 2CCA703250R0001 939084 0 .050 10 1 NC 250 1 .10 red 9 E217-16-01C 2CCA703251R0001 939091 0 .050 10 1 NC 250 1 .10 green 9 E217-16-01D 2CCA703252R0001 939107 0 .050 10 1 NC 250 1 .10 yellow 9 E217-16-01E 2CCA703253R0001 939114 0 .050 10 1 NC 250 1 .10 blue 9 E217-16-01G 2CCA703254R0001 939121 0 .050 10

pro M compact® Selection tables Command devices E 210 Indicator Lights with LEDs E 210 2CCC441048F0001 E 217-... Luminous Pushbuttons (5 different LED colours) Rated current = 16A Contacts Rated Power LED Width Order Bbn Price Price Weight Pack voltage loss colour details 7612270 1 piece group 1 piece unit VAC W mm Type code Order code EAN EURO kg pc. LED Voltage range = 12-48VAC/DC 1 NO 250 0 .72 wh ite 9 E217-16-10B48 2CCA703170R0001 938933 0 .050 10 1 NO 250 0 .72 red 9 E217-16-10C48 2CCA703171R0001 938940 0 .050 10 1 NO 250 0 .72 green 9 E217-16-10D48 2CCA703172R0001 938957 0 .050 10 1 NO 250 0 .72 yellow 9 E217-16-10E48 2CCA703173R0001 938964 0 .050 10 1 NO 250 0 .72 blue 9 E217-16-10G48 2CCA703174R0001 938971 0 .050 10 1 NC 250 0 .72 wh ite 9 E217-16-01B48 2CCA703260R0001 939039 0 .050 10 1 NC 250 0 .72 red 9 E217-16-01C48 2CCA703261R0001 939046 0 .050 10 1 NC 250 0 .72 green 9 E217-16-01D48 2CCA703262R0001 939053 0 .050 10 1 NC 250 0 .72 yellow 9 E217-16-01E48 2CCA703263R0001 939060 0 .050 10 1 NC 250 0 .72 blue 9 E217-16-01G48 2CCA703264R0001 939077 0 .050 10 LED Voltage range = 110-220VDC 1 NO 250 1 .50 wh ite 9 E217-16-10B220 2CCA703165R0001 939138 0 .050 10 1 NO 250 1 .50 red 9 E217-16-10C220 2CCA703166R0001 939145 0 .050 10 1 NO 250 1 .50 green 9 E217-16-10D220 2CCA703167R0001 939152 0 .050 10 1 NO 250 1 .50 yellow 9 E217-16-10E220 2CCA703168R0001 939169 0 .050 10 1 NO 250 1 .50 blue 9 E217-16-10G220 2CCA703169R0001 939176 0 .050 10 1 NC 250 1 .50 wh ite 9 E217-16-01B220 2CCA703255R0001 939183 0 .050 10 1 NC 250 1 .50 red 9 E217-16-01C220 2CCA703256R0001 939190 0 .050 10 1 NC 250 1 .50 green 9 E217-16-01D220 2CCA703257R0001 939206 0 .050 10 1 NC 250 1 .50 yellow 9 E217-16-01E220 2CCA703258R0001 939213 0 .050 10 1 NC 250 1 .50 blue 9 E217-16-01G220 2CCA703259R0001 939220 0 .050 10 2CCC441075F0001 E 219-... Indicator Lights with LED (5 different colours) Indicator Lights with LED The new products are available in 9 mm width (= 0.5 modules) and can be used for indicating any operational condition such as signalling loss of a phase. The range offers three different voltages. (Ranges: 12-48 V AC/DC; 115-250 V AC and 110-220 V DC). LED Power Width Order Bbn Price Price Weight Pack colour loss details 7612270 1 piece group 1 piece unit W mm Type code Order code EAN EURO kg pc. LED Voltage range = 115-250VAC white 0 .47 9 E219-B 2CCA703400R0001 939282 0 .04 10 red 0 .47 9 E219-C 2CCA703401R0001 939299 0 .04 10 green 0 .47 9 E219-D 2CCA703402R0001 939305 0 .04 10 yellow 0 .47 9 E219-E 2CCA703403R0001 939312 0 .04 10 blue 0 .47 9 E219-G 2CCA703404R0001 939329 0 .04 10

pro M compact® Selection tables Command devices E 210 Accessories E 210 2CCC441024Z0001 2CCC441025Z0001 2CCC441026Z0001 2CCC441027Z0001 Terminal assignment Pushbutton Luminous Pushbutton Indicator Light Technical features - Pushbuttons and Indicator Lights Rated Voltage Un [V] 250/400 Lowest operat. voltage 24 V; 25 mA Rated current In [A] 16 LED current [mA] 5 Rated frequency [Hz] 50/60 Modules [No] 0.5 Tightening torque [Nm] 1.2 - 1.5 Standards EN 60669-1; EN 62094-1; UL 508 Approvals Pushbuttons: VDE, UL, GOST, CCC Indicator lights: VDE, UL, GOST LED Voltage range = 12-48VAC/DC white 0 .40 9 E219-B48 2CCA703420R0001 939237 0 .04 10 red 0 .40 9 E219-C48 2CCA703421R0001 939244 0 .04 10 green 0 .40 9 E219-D48 2CCA703422R0001 939251 0 .04 10 yellow 0 .40 9 E219-E48 2CCA703423R0001 939268 0 .04 10 blue 0 .40 9 E219-G48 2CCA703424R0001 939275 0 .04 10 LED Voltage range = 110-220VDC white 1 .00 9 E219-B220 2CCA703405R0001 939336 0 .04 10 red 1 .00 9 E219-C220 2CCA703406R0001 939343 0 .04 10 green 1 .00 9 E219-D220 2CCA703407R0001 939350 0 .04 10 yellow 1 .00 9 E219-E220 2CCA703408R0001 939367 0 .04 10 blue 1 .00 9 E219-G220 2CCA703409R0001 939374 0 .04 10 Accessories for E 210 device series Order Bbn Price Price Weight Pack details 7612270 1 piece group 1 piece unit Type code Order code EAN EURO kg pc. Dummy housing for 9 mm wide units The modular witht of 18 mm must be complied with to use the devices in the SMISSLINE socket system. The dummy housing is ready-made with two expanding connectors. Always snap on dummy housing on the left. E210-DH 2CCA703480R0001 404208 0 .18 10 Padlock to use for 9 and 18 mm wide units E210-ASV9 2CCA703648R0001 404215 10 2CCC441089F0001 9 mm 2CCC441088F0001

These luminous indicator devices provide an intuitive and readily visible front panel display of the state of an electrical line or load situated either remotely or inside the panel itself. The range of luminous indicator includes devices with 3, 4 or 12 LEDs with various supply voltage ratings, and fully-customisable plain labels. The version with 115 V d.c. supply rating, is ideal for installation on medium voltage panels and for non-standard applications, and complete an extensive range of easy-to-install indicator devices. Size Number Characteristics Label Order Bbn Price Price Weight Pack of LEDs of the LEDs details 801254 1 piece group 1 piece unit mm Type code Order code EAN kg pc. Indicator lamps 24 V a.c./d.c. 48 3 not included neutral SL-3-24V/48 2CSG211010R3001 2659501 0 .01 1 48 4 not included neutral SL-4-24V/48 2CSG221010R3001 2659600 0 .01 1 48 3 neutral SL-3-L1-L2-L3-24V/48 2CSG241020R3001 2659709 0 .01 1 48 3 in English SL-3-A-C-S-24V/48 2CSG251030R3001 2659808 0 .01 1 48 4 in English SL-3-A-C-S-E-24V/48 2CSG251040R3001 2659907 0 .01 1 Indicator lamps 48 V a.c./d.c. 48 3 not included neutral SL-3-48V/48 2CSG311010R3001 2660002 0 .01 1 48 4 not included neutral SL-4-48V/48 2CSG321010R3001 2658603 0 .01 1 48 3 neutral SL-3-L1-L2-L3-48V/48 2CSG341020R3001 2658702 0 .01 1 48 3 in English SL-3-A-C-S-48V/48 2CSG351030R3001 2658801 0 .01 1 48 4 in English SL-3-A-C-S-E-48V/48 2CSG351040R3001 2658900 0 .01 1 Indicator lamps 115 V a.c. 48 3 not included neutral SL-3-115V/48 2CSG411010R3001 2659006 0 .01 1 48 4 not included neutral SL-4-115V/48 2CSG421010R3001 2659105 0 .01 1 48 3 in English SL-3-A-C-S-115V/48 2CSG451030R3001 2659303 0 .01 1 48 4 in English SL-4-A-C-S-E-115V/48 2CSG451040R3001 2659402 0 .01 1 Indicator lamps 115 V d.c. 48 3 not included neutral SL-3-115V/48 DC 2CSG273233R3001 2659006 0 .01 1 48 4 not included neutral SL-4-115V/48 DC 2CSG273313R3001 2659105 0 .01 1 48 3 in English SL-3-A-C-S-115V/48 DC 2CSG273223R3001 2659303 0 .01 1 48 4 in English SL-4-A-C-S-E-115V/48 DC 2CSG273303R3001 2659402 0 .01 1 96 12 not included neutral SL12-115V/96 DC 2CSG273213R3001 2732136 0 .01 1 144 12 not included neutral SL12-115V/72-144 DC 2CSG273293R3001 2732938 0 .01 1 System pro M compact® Selection tables Command devices Luminous indicators for panel installation Wiring diagram C321 NLLL –+++ a.c. supply d.c. supply Key: C = Common 1 = Led 1 2 = Led 2 3 = Led 3 2CSC445165F0001 1CSC400060F0202

Panel Number Characteristics Label Order Bbn Price Price Weight Pack dimens. of LEDs of the LEDs details 801254 1 piece group 1 piece unit mm Type code Order code EAN kg pc. Luminous indicators 230 V a.c. 48 3 not included neutral SL-3-230V/48 2CSG511010R3001 2659501 0 .01 1 48 4 not included neutral SL-4-230V/48 2CSG521010R3001 2659600 0 .01 1 48 3 neutral SL-3-L1-L2-L3-230V/48 2CSG541020R3001 2659709 0 .01 1 48 3 in English SL-3-A-C-S-230V/48 2CSG551030R3001 2659808 0 .01 1 48 4 in English SL-3-A-C-S-E-230V/48 2CSG551040R3001 2659907 0 .01 1 96 12 not included alarm SL-12-24V/96 2CSG274050R3001 2660002 0 .03 1 96 12 not included alarm SL-12-48V/96 2CSG374050R3001 2660101 0 .03 1 96 12 not included alarm SL-12-115V/96 2CSG474050R3001 2660200 0 .03 1 96 12 not included alarm SL-12-230V/96 2CSG574050R3001 2660309 0 .03 1 144 12 not included alarm SL-12-24V/144 2CSG233050R3001 2660408 0 .35 1 144 12 not included alarm SL-12-48V/144 2CSG333050R3001 2660507 0 .35 1 144 12 not included alarm SL-12-115V/144 2CSG433050R3001 2660606 0 .35 1 144 12 not included alarm SL-12-230V/144 2CSG533050R3001 2660705 0 .35 1 Accessories for luminous indicators red LED 2CSG500060R3001 2660804 0 .05 5 pcs green LED 2CSG500070R3001 2660903 0 .05 5 pcs yellow LED 2CSG500080R3001 2661009 0 .05 5 pcs blue LED 2CSG500090R3001 2661108 0 .05 5 pcs white LED 2CSG500100R3001 2661207 0 .05 5 pcs Technical characteristics

Electrical characteristics

Supply [V] - a.c./d.c 24, 48 - a.c. 115, 230 - d.c. 115 Frequency [Hz] 0-1000 Power consumption [W] 0.5 max per input TEST input consumption [W] 4 max Other characteristics Operating temperature [°C] -20 +60 Storage temperature [°C] -20 +70 Relative humidity 30-95% Overall dimensions [mm] 48 x 48 x 56 (SL-3 e SL-4) 96 x 96 x 56 (SL...96) 72 x 144 x 70 (SL...72-144) Weight [gr] 100 (SL-3 e SL-4), Protection degree IP40 Label dimensions [mm] 30 x 9 System pro M compact® Selection tables Command devices Luminous indicators for panel installation 2CSC445169F0001

pro M compact® Selection tables Command devices ESB Installation contactors ESB Certifications and Approvals UL CSA CCC RMRS CEBV Application The ESB contactors are used mainly in buildings for switching and controlling lighting, heating, ventilation and pumps. They are part of the complete range of Din rail products and can be integrated easily in dedicated panels. ESB20 are AC coil operated. The ESB 24, 40, 63 contactors are used for the control of loads up to 24, 40, 63 A. Due to their DC solenoid actuator, the ESB 24 can be connected to AC or DC voltages. This provides the following benefits: Hum-free operating system, no vibration, silent in operation, low power consumption, integrated combination. Main accessories für ESB 24, 40, 63 Auxiliary contact blocks EH04. Main poles Nb of mo- dules Control coil voltage

50 Hz 60 Hz

pc.Order code Ordering Details ESB 20 2 N.O. 1 12 V 14 V ESB 20-20 GHE 321 1102 R1004 1230141 0.14 10 24 V 28 V ESB 20-20 GHE 321 1102 R0001 0263218 0.14 10 110 V 125...127 V ESB 20-20 GHE 321 1102 R0004 1230042 0.14 10 230 V 264 V ESB 20-20 GHE 321 1102 R0006 0263263 0.14 10 2 N.C. 1 12 V 14 V ESB 20-02 GHE 321 1202 R1004 1232145 0.14 10 24 V 28 V ESB 20-02 GHE 321 1202 R0001 0263812 0.14 10 110 V 125...127 V ESB 20-02 GHE 321 1202 R0004 1232046 0.14 10 230 V 264 V ESB 20-02 GHE 321 1202 R0006 0263867 0.14 10 1 N.O. 1 N.C. 1 12 V 14 V ESB 20-11 GHE 321 1302 R1004 1231148 0.14 10 24 V 28 V ESB 20-11 GHE 321 1302 R0001 0263515 0.14 10 110 V 125...127 V ESB 20-11 GHE 321 1302 R0004 1231049 0.14 10 230 V 264 V ESB 20-11 GHE 321 1302 R0006 0263560 0.14 10 Mounting positions +30° -30° Pos. 3 Pos. 2 Pos. 1 Pos. 4 Mounting positions +30° -30° Pos. 3 Pos. 2 Pos. 1 Pos. 4 Pos. 5 Main poles Nb of mo- dules Control coil voltage 40...450 Hz DC Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details ESB 24 2 N.O. 2 12 V 12 V ESB 24-20 GHE 329 1402 R0001 215193 0.28 5 4 N.O. 2 12 V 12 V ESB 24-40 GHE 329 1102 R1004 084478 0.28 5 24 V 24 V ESB 24-40 GHE 329 1102 R0001 084416 0.28 5 4 N.C. 2 12 V 12 V ESB 24-04 GHE 329 1202 R1004 084560 0.28 5 24 V 24 V ESB 24-04 GHE 329 1202 R0001 084515 0.28 5 2 N.O. 2 N.C. 2 12 V 12 V ESB 24-22 GHE 329 1302 R1004 084638 0.28 5 24 V 24 V ESB 24-22 GHE 329 1302 R0001 084584 0.28 5 3 N.O. 1 N.C. 2 12 V 12 V ESB 24-31 GHE 329 1602 R1004 084720 0.28 5 24 V 24 V ESB 24-31 GHE 329 1602 R0001 084676 0.28 5 1 N.O. 3 N.C. 2 12 V 12 V ESB 24-13 GHE 329 1702 R1004 218255 0.28 5 24 V 24 V ESB 24-13 GHE 329 1702 R0001 214783 0.28 5 1SBC103007F00141SBC103009F0014

pro M compact® Selection tables Command devices ESB series contactors ESB Mounting positions +30° -30° Pos. 3 Pos. 2 Pos. 1 Pos. 4 Pos. 5 Main poles Nb of mo- dules Control coil voltage 40...450 Hz DC Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details ESB 40 4 N.O. 3 12 V 12 V ESB 40-40 GHE 349 1102 R1004 149245 0.40 3 24 V 24 V ESB 40-40 GHE 349 1102 R0001 084829 0.40 3 2 N.O. 2 N.C. 3 24 V 24 V ESB 40-22 GHE 349 1302 R0001 379611 0.40 3 230 V 230 V ESB 40-22 GHE 349 1302 R0006 214332 0.40 3 3 N.O. 1 N.C. 3 24 V 24 V ESB 40-31 GHE 349 1602 R0001 316890 0.40 3 230 V 230 V ESB 40-31 GHE 349 1602 R0006 214349 0.40 3 3 N.O. 3 24 V 24 V ESB 40-30 GHE 349 1502 R0001 316890 0.39 3 230 V 230 V ESB 40-30 GHE 349 1502 R0006 214349 0.39 3 2 N.O. 3 24 V 24 V ESB 40-20 GHE 349 1402 R0001 212345 0.38 3 230 V 230 V ESB 40-20 GHE 349 1402 R0006 085314 0.38 3 Main poles Nb of mo- dules Control coil voltage 40...450 Hz DC Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details ESB 63 4 N.O. 3 12 V 12 V ESB 63-40 GHE 369 1102 R1004 218262 0.42 3 24 V 24 V ESB 63-40 GHE 369 1102 R0001 084935 0.42 3 3 N.O. 1 N.C. 3 110 V 110 V ESB 63-31 GHE 369 1602 R0004 ??? 0.42 3 230 V 230 V ESB 63-31 GHE 369 1602 R0006 ??? 0.42 3 3 N.O. 3 230 V 230 V ESB 63-30 GHE 369 1502 R0006 085376 0.41 3 400 V 400 V ESB 63-30 GHE 369 1502 R0007 260964 0.41 3 2 N.O. 3 24 V 24 V ESB 63-20 GHE 369 1402 R0001 291999 0.40 3 230 V 230 V ESB 63-20 GHE 369 1402 R0006 085369 0.40 3 1 N.O. 1 N.C. 3 230 V 230 V ESB 63-11 GHE 369 1802 R0006 214622 0.40 3 Mounting positions +30° -30° Pos. 3 Pos. 2 Pos. 1 Pos. 4 Pos. 5 1SBC103010F00141SBC103016F0014

O = OFF Automatic run I = ON System pro M compact® Selection tables Command devices EN series contactors EN Application The EN contactors are used mainly in buildings for switching and controlling lighting, heating, ven- tilation and pumps. They are part of the complete range of Din rail products and can be integrated easily in dedicated panels.

Description

EN contactors have a built-in toggle switch to select between three function modes: Off position, automatic run (normal contactor function), manual override with a return to Auto the next time the coil is energized. This offers many advantages as: You can make functionnal test before installation start-up. It can be used for maintenance operation, to change lamps and test it. It provides higher safety and drop out as you can switch the application manually. The toggle switch is also used for household application like water heating where double tariff of kWh is used. Mounting positions +30° -30° Pos. 3 Pos. 2 Pos. 1 Pos. 4 Certifications and Approvals UL CSA CCC CE Main poles Nb of mo- dules Control coil voltage pc.Order code Ordering Details 2 N.O. 1 24 V 28 V EN 20-20 GHE 322 1101 R0001 239038 0.14 10 230 V 264 V EN 20-20 GHE 322 1101 R0006 265069 0.14 10 Main poles Nb of mo- dules Control coil voltage 40...450 Hz DC Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details 4 N.O. 3 24 V 24 V EN 40-40 GHE 342 1101 R0001 262500 0.41 3 110 V 110 V EN 40-40 GHE 342 1101 R0004 261077 0.41 3 3 N.O. 1 N.C. 3 24 V 24 V EN 40-31 GHE 342 1601 R0001 337017 0.41 3 Main poles Nb of mo- dules Control coil voltage 40...450 Hz DC Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details 4 N.O. 2 24 V 24 V EN 24-40 GHE 326 1101 R0001 190469 0.24 5 3 N.O. 1 N.C. 2 24 V 24 V EN 24-31 GHE 326 1601 R0001 316906 0.24 5 1SBC103001F0014 1CSC400063F0202

pro M compact® Selection tables ESB/EN Installation Contactors Main Accessories ESB/EN ESB-DIS EH 04-20 Contact Blocks EH 04-20 EH 04-11 ESB-PLK 40/63 ESB-PLK 24 Contactor Type Contact blocks Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code Ordering Details ESB/EN 24, 40, 63 2 – EH 04-20 GHE 340 1321 R0001 084768 0.004 10 1 1 EH 04-11 GHE 340 1321 R0002 084768 0.004 10 Sealing cover Contactor Type Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code ESB/EN 24 ESB-PLK 24 GHE 320 1903 R0001 084171 0.002 10 ESB/EN 40,63 ESB-PLK 40/63 GHE 340 1903 R0002 085222 0.002 10 Distance piece Contactor Type Order details Type code bbn 4013614 EAN Price 1 piece Price group Weight 1 piece kg Pack unit pc.Order code ESB/EN 24, 40,63 ESB-DIS GHE 340 1902 R0001 085215 0.002 10 EH 04-20 ESB 24-40 ESB-PLK 24 ESB-PLK 40/63 Auxiliary Contact Blocks Sealing cover 1SBC103015F00141SBC103012F00141SBC103011F0014 1SBC103009F0014

pro M compact® Technical features ESB/EN Installation Contactors ESB Main Pole - Utilization Characteristics according to IEC Contactor types: AC operated ESB20/EN20 AC/DC operated ESB24/EN24 ESB40/EN40 ESB63 Rated operational voltage Ue max. V 250 400 Rated frequency limits Hz 50/60 40 ...450 Utilization category AC-1 / AC-7a for air temperature close to contactor < 55 °C (NO) A 20 24 40 63 Max. rated operational current Ie AC-1 / AC-7a (NC) A 20 24 30 30 Rated operational power AC-1 230 V - 1 phase kW 45 .38 .81 3 .8

400 V - 3 phases kW - 1 62 64 1

Utilization category AC-3 / AC-7b for air temperature close to contactor < 55 °C Max. rated operational current Ie AC-3/AC-7b

230 V - 1 phase A 9 9 22 30

400 V - 3 phases A - 9 22 30

Rated operational power AC-3 230 V - 1 phase kW 1.12 .25 .58

400 V - 3 phases kW - 4 11 15

Rated making capacity AC-3 10 x Ie / AC-3 Rated breaking capacity AC-3 8 x Ie / AC-3 Short-circuit protection for contactors gG type fuse A 20 35 63 80 Rated short-time withstand current Icw at 40 °C ambient temp., in free air, from a cold state 10 s A 72 176 240 Heat dissipation per pole I e / AC-1/AC-7a W 11 .53 6 Max. electrical switching frequency – for AC-1 / AC-7a cycles/h 300 – for AC-3 / AC-7b cycles/h 600 Electrical durability – for AC-1 / AC-7a cycles 150000 150000 150000 150000 – for AC-3 / AC-7b cycles 150000 500000 170000 240000 Mechanical durability – millions of operating cycles 1 .000.000 Magnet System Characteristics Contactor types: AC operated ESB20 AC/DC operated ESB24 ESB40 ESB63 Frequency range Hz 50/60 40 ... 450 Coil consumption Average pull-in value VA / W 8 / 5 4 / 4 5 / 5 65 / 65 Average holding value VA / W 3.2 / 1.2 4 / 4 5 / 5 4 .2 / 4.2 Connecting Characteristics Contactor types: AC operated ESB20 AC/DC operated ESB40 Main pole terminals Degree of protection acc. to IEC 60947-1 / EN 60947-1 and IEC 60529 / EN 60529 Protection against direct contact in acc. with EN 50274 All terminals IP20

pro M compact® Technical features ESB/EN Installation Contactors ESB EH04... Auxiliary Contact Block - Utilization Characteristics according to IEC Contactor types: AC operated ESB20 AC/DC operated ESB24 ESB40 ESB63 Rated operational voltage Ue max. V - 500 Conventional free air thermal current Ith θ < 40 °C A -6 Rated frequency limits Hz - 50/60 Rated operational current Ie / AC-15 acc. to IEC 60947-5-1 240 V 50/60 Hz A -4

415 V 50/60 Hz A -3

500 V 50/60 Hz A -2

Making capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15 Breaking capacity acc. to IEC 60947-5-1 - 11 x Ie AC-15 Short-circuit protection gI type fuse A -1 0 Minimum switching capacity with failure rate acc. to IEC 60947-5-4 V/mA - 17 / 5 Heat dissipation per pole at 6 A W -0 .1 Electrical durability AC-1 / 400 V / 3-phase for ESB 20, 24, 40, 63 80101 6350403024161,5 2 3 4 5 6 8 0.01 0.1 0.02 0.03 0.04 0.05 0.06 0.08 0.2 0.3 0.4 0.5 0.6 0.8 Millions of operating cycles Breaking current [A] ESB 24 ESB 40 ESB 63 ESB 20 AC-3 / 400 V / 3-phase for ESB 24, 40, 63 801016 3 50403024161.5 2.21.1 3 4 7.5 11 15 23 4 5 6 8 0.01 0.1 0.02 0.03 0.04 0.05 0.06 0.08 0.2 0.3 0.4 0.5 0.6 0.8 Millions of operating cycles Breaking current [A] Switching capacity [kW] ESB 24 ESB 40 ESB 63 1SBC500322F00001CSC400060F0202

pro M compact® Selection tables Command devices Relays selection E 250 E 259 Latching relays E250 Installation relays E259 Contacts switching on each impulse sent to the control coil. Contacts maintained in switched position only while the control coil is supplied. General characteristics Type of command Impulse (i.e. via pushbutton) Continuous (i.e. via switch) Energy consumption of command circuit Only on pickup For entire time contact switching is maintained Local control lever Yes Yes, temporary Main application Lighting command by pushbuttons Lighting command by switches, thermostats, time switches Rated current 16 A 32 A 16 A Single phase lamps load characteristics /L54706 Incandescent and halogen 3000 W 4000 W 1800 W Fluorescent power factor corrected in series 3000 VA 4000 VA 1800 VA Fluorescent power factor corrected in parallel 2500 VA 3200 VA 500 VA Fluorescent uncorrected power factor 1800 VA 2200 VA 900 VA Power contacts 1NA ■■ ■ 2NA ■■ ■ Sequential ■ 1NA+1NC ■■ 2NA+2NC with E250CM11 3NA, 4NA with E250CM20 with E250-32 CM20 ■ 1C/O, 2C/O ■■ 3C/O, 4C/O with E250CM002 ■ /L54706 See technical details for information on each lamp type Accessories for E250 series latching relays Accessories for E259 installation relays Accessories of E257C and E258C series latching relays Other accessories for E250 series latching relays Auxiliary con- tacts max. two per relay without other accessories No accessory for E255 Auxiliary contact max one if the relay is coupled with other accessories Power contact max one per relay Central command max one per relay Auxiliary contacts max two for E257 relay with single contact Auxiliary contacts max one for E257 with two or more contacts and for E258 relays Group module Can be connected to the central command circuit to create subgroups of relays. Suitable only for use with E257 and E258 devices, or with E250 equipped with the E257 CM accessory. See specific connection diagram. These accessories do not require any mechanical connection and can be used with all the latching relays. Compensator module To be connected in parallel with the command circuit if using illuminated pushbuttons with two terminals. See table for max. number of installable pushbuttons in technical details. Auxiliary contacts max one for E259 relay with 3 or 4 contacts Auxiliary contacts max two for E259 relay with 1 or 2 contacts E250H E255 E250H E257CM E251 E252 E256 E250H E257C 2 or more contacts E258C E250H E250CM E257C 1 or 2 contacts E250CP E250GM E259 3 or 4 contacts E259 1 or 2 contacts E250H E250H

E 259 Installation relays are 16 A contactors specifically engineered for residential and commercial applications. Their high performance in the control of lamps makes them ideal for lighting circuit applications. The front control lever indicates the position of the contacts and allows the relay to be commanded, for example for local testing of the circuit. In installations that require several E 259 relays side by side, it is advisable to use E 259 DIS half- module width spacer elements every second relay for heat dissipation. E 259, 16 A Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1NO 8 V a .c. E259 16-10/8 2CSM261123R0401 611233 0 .100 12 1NO+1NC 8 V a.c. E259 16-11/8 2CSM273673R0401 736738 0 .100 12 2NO 8 V a .c. E259 16-20/8 2CSM273563R0401 735632 0 .100 12 1CO 8 V a .c. E259 16-19/8 2CSM273533R0401 735335 0 .100 12 48 V a .c. / 24 V d.c. E259 16-19/48 2CSM274833R0401 748335 0 .100 12 System pro M compact® Selection tables Command devices E 259 installation relays E 259 34 24 32 22 31 21 32 24 8 6 7 5 4 2 A1 A2 3 1 24 14 22 12 A1 A2 21 11 22 14 A1 A2 4 2 A1 A2 3 1 A1 A2 E259 16-10 E259 16-20 E259 16-19 E259 16-29 E259 16-11 E250 H02 E250 H20 E250 H11 Auxiliary contacts E 8 6 7 5 44 34 42 32 41 31 42 34 E259 16-30 E259 16-40 E259 16-39 E259 16-49 4 2 A1 A2 3 1 A1 A2 24 14 22 12 A1 A2 21 11 22 14 A1 A2 2CSC400721F0201 1CSC400065F0202

pro M compact® Selection tables Command devices E 259 installation relays E 259 Technical features 1 - 2 contacts 3 - 4 contacts Rated voltage Un [V] 250 400 Rated frequency [Hz] 50 50 Rated current in AC1/AC-7a [A] 16 16 Control coil characteristics a.c. power supply voltage [V] 8, 12, 24, 48, 115, 230 12, 24, 48, 230 d.c. power supply voltage [V] 6, 12, 24, 48, 115 6, 12, 24, 115 Operation limits ±10% ±10% Power consumption a.c. pick-up [VA] 3.4 6.7 holding [VA] 1.8 3.4 d.c. [W] 2.1 3.9 Load specifications per phase Maximum load AC-1 [kW] 3 8.5 Maximum load AC-5b [kW] 1.8 1.8 Maximum load AC-7b [kW] 0.9 - Maximum load AC-3 (400V) [kW] - 2.2 Maximum load DC /L54708/L54708 Minimum load (under 5V) [W] 2 2 Short circuit fuse protection [gL] [A] 20 20 Lifetime in number of operations Electrical (in AC-1 at full load) [No.] 3 x 10 5 3 x 105 Mechanical [No.] 2 x 10 6 2 x 106 Max.lamp power /L54707 Incandescent and halogen (40-200W) [W] 1800 1800 Fluorescent Parallel p.f. correction (cosϕ=0.9) [VA] 500 500 p.f. uncorrected (cosϕ=0.5) [VA] 900 900 Width (number of DIN modules) [No.] 1 2 Cable cross section (Ø min/max) [mm2] 1.5 / 10 1.5 / 10 Maximum torque on terminals [Nm] 1 1 Min./Max. ambient T ° at installation point [°C] -20 … +45 -20 … +45 Standard IEC EN 60947-4-1, IEC EN 61095 /L54707 See technical details for lamp types /L54708 See chart in technical details 2CSC400723F0201 2CSC400722F0201 Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 3NO 230 V a .c. / 115 V DC E259 16-30/230 2CSM272983R0401 729839 0 .200 6 3CO 230 V a .c. / 115 V d.c. E259 16-39/230 2CSM274783R0401 747833 0 .200 6 Auxiliary contacts Rated Current Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit A Type code Order code EAN kg pc. 1NO+1NC 5 E 250 H11 2CSM004400R0201 534709 0 .033 16 2NO 5 E 250 H20 2CSM002400R0201 536901 0 .033 16 2NC 5 E 250 H02 2CSM008400R0201 536802 0 .033 16 Other accessories Spacer element for heat dissipation E 259-DIS 2CSM000800R0401 0 .04 25

E 250, 16 A Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1NO 8 V a.c. E 251-8 2CSM211000R0201 53050 3 0.114 12 1NO+1NC 8 V a.c. E 256-8 2CSM214000R0201 53190 6 0.116 12 2NO 8 V a.c. E 252-8 2CSM212000R0201 53100 5 0.116 12 System pro M compact® Selection tables Command devices E 250 latching relays E 250 E 251- A CONT ACT SWITCHING A E 252- A+B A+B A BA B CONT ACT SWITCHING E 256- 3 1 4 2 B A B A A B CONT ACT SWITCHING E 255- 1 3 B A+B A2 4 A B SEQUENCE OF CONT ACT SWITCHING E 256-2E 256-1 E 250 Latching relays Allow switching of the contacts in response to each pulse sent to the coil via the normally open pushbuttons. Their high performance in the single or multi-point control of lamps make them an ideal solution for lighting circuits. The manual control lever also gives an indication of the contact position. The relays come in versions with different coil voltages and contact configurations. The main modules, available in one-and two-contact versions, can be combined with two-pole power contact modules to obtain three-contact and four-contact devices. They can also be provided with auxiliary signal contacts. 2CSC400147F0001 A B AB A B AB A B AB A B AB A B AB 1CSC400066F0202

pro M compact® Selection tables Command devices E 250 latching relays E 250 8 6 7 5 42 32 44 34 41 31 44 32 8 6 7 5 E 250 CM20 E 250 CM11E 250 CM002 E 257 H02E 250 H20E 250 H11 ON OFF E 257 CM E 257 C30 E 257 C003 34 24 31 21 ON 32 22 OFF 32 24 6 4 5 3 ON OFF E 257 C20 E 257 C002 4 2 3 1 ON OFF A1 A2 24 14 21 11 ON 22 12 OFF A1 A2 22 14 4 2 A1 A2 3 1 24 14 22 12 A1 A2 21 11 22 14 A1 A2 4 2 A1 A2 3 1 A1 A2 E 251 E 252 E 255 E256 E 256.2 4 2 A1 A2 3 1 B A 12 ON

14 OFF

E 256.1 E 257 C10 E 257 C001 2CSC400202F0201 E 250, 32 A Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1NO 8 V a.c. E 251-32/8 2CSM231000R0201 91200 2 0.114 12 2NO 8 V a.c. E 252-32/8 2CSM232000R0201 91260 6 0.116 12 E 255, 16 A with 2 sequential contacts This particular version is equipped with two sequential switching contacts. In the initial stable position both contacts are open: one pulse causes the first contact (A) to close; the next pulse causes the second contact to also close (B); a third pulse causes contact A to open and a final pulse completes the cycle by also reopening contact B, thus returning both contacts to their initial state. The E255 relays cannot be combined with power contacts or auxiliary devices. They are equipped with two LEDs that give an indication of the contact position. E 255 Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 2 8 V a.c. E 255-8 2CSM219000R0201 53150 0 0.121 12 A B AB A B AB A B AB 1CSC400067F0202

E 257, 16 A Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 230 V a .c. / 115 V d.c. E 257 C20-230 2CSM112000R0211 53250 7 0 .174 8 2CO 12 V a System pro M compact® Selection tables Command devices E 250 latching relays E 250 2CSC400203F0201 E 257 - local and central command by push-buttons Each local push-button controls a single relay. Pressing the central ON(/OFF) button puts all the relays in the ON (/OFF) position irrespective of their previous state. OFF ON L N Connect the push-buttons on the same line for both local and central command. With alternating current use either the phase (L) or neutral (N) With direct current the positive (+) pole must be used. OFF ON L N Central Local OFF ON OFF ON Local E257 E257 E 257 - permanently supplied It is possible to permanently supply the central command, for example using a change-over switch to control the relay. L N In this configuration a local actuating coil cannot be used. OFF ON L N OFF ON OFF ON E257 1CSC400068F0202 Latching relays with central command function The E 257 C and E 258 C versions are latching relays which integrate a central command function (ON and OFF) that allows multiple relays to be controlled from a pair of normally open push-buttons. Using the E 250 GM group module it is also possible to create sub-groups of relays, so as to implement central command of individual subgroups as well as of the entire group of relays. The central command circuit can be permanently supplied, but in that case the circuit of the local coil is excluded. On E 257 C the central (ON/OFF) command needs to be supplied on the same line as the local pushbuttons (see diagram below). This is not required for E 258 C, which can thus also be supplied on the central command at a different voltage than the local pushbuttons circuit.

pro M compact® Selection tables Command devices E 250 latching relays E 250 2CSC400204F02012CSC400205F0201 Grouped central command: connection diagram for E 250 GM The E250 GM module allows the creation of subgroups of relays with a central command for each group of relays and a general command. This function requires using an E 250 GM for each subgroup. E257 E257 E257 E257 E257 E257 LN M A B C D E F Local: each relay can be individually commanded from the local pushbuttons. Group: each group can be centrally commanded, therefore the ON/OFF button controls relays while the ON/OFF button controls relays General: the ON/OFF buttons command both groups at simultaneously, allowing all the relays to be commanded.

1 A B C

long lines, it is recommended to protect them with an OVR surge arrester. 1CSC400069F0202 E 257, 32 A Contacts Coil voltage Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 230 V a .c. / 115 V d.c. E 257-32C20/230 2CSM132000R0211 91370 2 0 .174 8 E 258 C, 16 A Contacts Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 NO E 258 C10-230/24 2CSM211000R0231 78910 9 0 .226 6 2 NO E 258 C20-230/24 2CSM212000R0231 78830 0 0 .235 6 1 NO + 1 NC E 258 C11-230/24 2CSM213000R0231 78870 6 0 .232 6 1 NO + 1 NC +1 CO E 258 C111-230/24 2CSM215000R0231 78890 4 0 .239 6 2 NO +1 CO E 258 C201-230/24 2CSM214000R0231 78850 8 0 .241 6 2 CO E 258 C002-230/24 2CSM216000R0231 78960 4 0 .25 6 3 CO E 258 C003-230/24 2CSM217000R0231 78990 1 0 .256 6

pro M compact® Selection tables Command devices E 250 latching relays E 250 2CSC400723F0201 1CSC400067F0202 1 NO E 258 C10-230/230 2CSM111000R0231 78920 8 0 .233 6 2 NO E 258 C20-230/230 2CSM112000R0231 78840 9 0 .243 6 1 NO + 1 NC E 258 C11-230/230 2CSM113000R0231 78880 5 0 .24 6 1 NO + 1 NC +1 CO E 258 C111-230/230 2CSM115000R0231 78900 0 0 .244 6 2 NO +1 CO E 258 C201-230/230 2CSM114000R0231 78860 7 0 .247 6 2 CO E 258 C002-230/230 2CSM116000R0231 78970 3 0 .257 6 3 CO E 258 C003-230/230 2CSM117000R0231 79000 6 0 .262 6 1 NO E 258 C10-24/24 2CSM411000R0231 79010 5 0 .225 6 2 NO E 258 C20-24/24 2CSM412000R0231 78930 7 0 .234 6 2 NO +1 CO E 258 C201-24/24 2CSM414000R0231 78940 6 0 .241 6 2 CO E 258 C002-24/24 2CSM416000R0231 78950 5 0 .249 6 3 CO E 258 C003-24/24 2CSM417000R0231 78980 2 0 .256 6 8 6 7 5 42 32 44 34 41 31 44 32 8 6 7 5 E 250 CM20 E 250 CM11 E 250 CM002 E 257 H02 E 250 H20 E 250 H11 ON OFF E 257 CM Auxiliary components and accessories for E 250 Contacts Rated current Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Additional power contacts for all coil voltages 2NO 16A E 250 CM20 2CSM012100R0201 53460 0 0 .058 10 1NO+1NC 16A E 250 CM11 2CSM014100R0201 53450 1 0 .058 10 2CO 16A E 250 CM002 2CSM016100R0201 53440 2 0 .059 10 2NO 32A E 250-32 CM20* 2CSM032100R0201 91410 5 0 .058 10 * To be used only with 32 A latching relays Auxiliary contacts 1NO+1NC 5A E 250 H11 2CSM004400R0201 53470 9 0 .033 16 2NO 5A E 250 H20 2CSM002400R0201 53690 1 0 .033 16 2NC 5A E 250 H02 2CSM008400R0201 53680 2 0 .033 16 Other accessories central command for E251, E252 and E256 E 257 CM 2CSM000200R0211 53510 2 0 .033 16 group module E 250 GM 2CSM000600R0201 53700 7 0 .058 12 compensator module E 250 CP 2CSM000500R0201 53710 6 0 .058 12

pro M compact® Selection tables Command devices E 250 latching relays E 250 Technical characteristics E 251 / E 252 / E 256 E 255 Rated current In [A] 16 32 16 Rated voltage Un [V] 250 (1-2 contacts) 400 (3-4 contacts) 250 (1-2 contacts) 400 (3-4 contacts) 250 Rated frequency [Hz] 50/60 /L54706 50/60 /L54706 50/60 /L54706 Contacts main module NO 1 - 2 1 - 2 1 + 1 change-over 1 - 2 1 - 2 - NO+NC 1 + 1 1 + 1 - additional power contacts NO 2 2 - change-over 2 - - NO+NC 1+1 - - Width (no. of DIN modules) main module [mod.] 1 1 1 with additional power contacts [mod.] 2 2 - Control coil characteristics supply voltage: d.c / a.c. ratio /L54707 0,5 : 1 0,5 : 1 0,5 : 1 tolerance on supply voltage ±10% ±10% ±10% power consumption a.c. holding /L54708 [VA] 11 11,5 11 pick-up [VA] 14,5 16,5 14,5 power consumption d.c. [W] 7,5 8 7,5 Pulse durations minimum pulse duration (at Un) [s] 0,05 0,05 0,05 minimum pulse duration (90% Un) [s] 0,1 0,1 0,1 minimum interval between two pulses [s] 0,15 0,15 0,15 maximum number of pulses per minute 250 250 250 Lifetime in number of operations /L54709 electrical (in AC-1 at full load) 4 x 10 5 3 x 105 3 x 105 mechanical 2 x 10 6 2 x 106 2 x 106 Load characteristics maximum load in AC-1 per phase [A] 20 32 20 maximum load in DC [A] /L54711/L54711/L54711 minimum load per phase (under 5 V) [W] 2 2 2 short circuit protection fuse (gL) [A] 20 32 20 Maximum no. of lamps (103 operations/h) incandescent and halogen [W] 3000 4000 3000 fluorescent, corrected power factor (cosϕ = 0,9) series [VA] 4000 4000 3000 parallel [VA] 2500 3200 2500 fluorescent, uncorrected power factor (cosϕ = 0,5) [VA] 1800 2200 1800 Maximum number of buttons non illuminated unlimited unlimited unlimited illuminated 3 wires unlimited unlimited unlimited 2 wires /L54710 /L54710/L54710 General characteristics DIN rail mount yes yes yes hooking on bistable DIN rail yes yes yes two position knob yes yes - contact position indication yes yes yes label-holder yes yes yes cage terminals yes yes yes captive screws yes yes yes sealable terminals yes yes yes cable section (o min./max.) [mm 2] 1,5/10 (2P: 6) 1,5/10 (2P: 6) 1,5/10 /L54706 All latching relays can also be used at 60Hz. In this case and escluding E255, you can use maximum one auxiliary contact E250H but it is not possible to use power contacts E250CM. /L54708 The relays can withstand the “button stuck” condition. When the application calls for the relays to be permanently supplied, s pacers must be used on either side, making sure that the duty cycle allows the device to cool down to ambient temperature. /L54709 1 cycle = 2 operations per pole (closing + opening) /L54710 See table for use of the E 250 CP compensator modules /L54711 See chart in technical details

Rated voltage Un [V] 250 (1-2 contacts) 400 (3 contacts) 250 (1-2 contacts) 400 (3 contacts) 250 (1-2 contacts) 400 (3 contacts) Rated current In [A] 16 32 16 Rated frequency [Hz] 50/60 /L54706 50/60 /L54706 50/60 /L54706 NO+NC - - 1 + 1 Width (no. of DIN modules) [mod.] 1 - 2 1 - 2 2 Control coil characte- ristics supply voltage: d.c / a.c. ratio /L54707 0,5 : 1 0,5 : 1 0,5 : 1 tolerance on supply voltage ±10% ±10% ±10% power consumption a.c. holding /L54708 [VA] 11 14,5 14,5 pick-up [VA] 11 14,5 14,5 power consumption d.c. [W] 7,5 8 8 ON-OFF command characteristics supply voltage see control coil characteristics 24 V a.c./d.c. 230 V a.c./d.c. tolerance on supply voltage ±10% power consumption a.c. holding /L54708 [VA] 12 pick-up [VA] 12 power consumption d.c. [W] 12,5 Pulse durations minimum pulse duration (at Un) [s] 0,05 0,05 0,05 minimum pulse duration (90% Un) [s] 0,1 0,1 0,1 minimum interval between two pulses [s] 0,15 0,15 0,15 maximum number of pulses per minute 250 250 250 Lifetime in number of operations /L54709 electrical (in AC-1 at full load) 4 x 10 5 3 x 105 3 x 105 mechanical 2 x 10 6 2 x 106 2 x 106 Load characteristics maximum load in AC-1 per phase [A] 20 32 20 maximum load in DC [A] /L54711/L54711/L54711 minimum load per phase (under 5 V) [W] 2 2 2 short circuit protection fuse (gL) [A] 20 32 20 Maximum no. of lamps (103 operations/h) incandescent and halogen [W] 3000 4000 3000 fluorescent, corrected power factor (cosϕ = 0,9) series [VA] 3000 4000 3000 parallel [VA] 2500 3200 2500 fluorescent, uncorrected power factor (cosϕ = 0,5) [VA] 1800 2200 1800 Maximum number of buttons non illuminated unlimited unlimited unlimited illuminated 3 wires unlimited unlimited unlimited 2 wires /L54710/L54710/L54710 General characteristics DIN rail mount yes yes yes hooking on bistable DIN rail yes yes yes two position knob yes yes yes contact position indication yes yes yes label-holder yes yes yes cage terminals yes yes yes captive screws yes yes yes sealable terminals yes yes yes cable section (o min./max.) [mm /L54706 All latching relays can also be used at 60Hz. In this case and escluding E255, you can use maximum one auxiliary contact E250H but it is not possible to use power contacts E250CM. /L54708 The relays can withstand the “button stuck” condition. When the application calls for the relays to be permanently supplied, s pacers must be used on either side, making sure that the duty cycle allows the device to cool down to ambient temperature. /L54709 1 cycle = 2 operations per pole (closing + opening) /L54710 See table for use of the E 250 CP compensator modules /L54711 See chart in technical details System pro M compact® Selection tables Command devices E 250 latching relays E 250

pro M compact® Selection tables Command devices FLR latching relays Connection diagram Flush mounting latching relays Speed and ease of assembly, along with their compact size, make the FLR flush mounting latching relays suitable for installation inside flush mount or junction boxes. They are ideal for implementing multipoint command of lighting systems in residential and commercial installations, so as to simplify and reduce the cost of wiring. Contacts Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 FLR1-12 2CSM206365R0241 063650 0 .06 20 1 FLR1-230 2CSM206375R0241 063759 0 .06 20 2 FLR5-12 2CSM206385R0241 063858 0 .06 20 2 FLR5-230 2CSM206395R0241 063957 0 .06 20 Technical features FLR1 FLR5 Contact type 1NO 2NO Number of sequences [No.] 2 4 Rated voltage [V] 12 / 230 AC Rated load 10 A / 250 V AC Max. Peak current [A] 15 Max. switching power [VA] 2500 Max. switching voltage [V] 250 AC Incandescent lamp load [W] 805 Fluorescent lamp load [W] 345 Frequency [Hz] 50-60 Type of operation sequential - mechanical Protection degree IP20 Max. number of electrical operations [No.] 100000 Max. number of mechanical operations [No.] 300000 Insulation resistance [M Ω] 100 (500 V DC) Dielectric strength (contacts) [V] 2000 AC Dielectric strength (coil) [V] 3500 AC Power dissipation [VA] 4.5 Operating temperature [°C] -25…+55 Terminals screw Installation type wall/flush mounting Dimensions (LxWxH) [mm] 45 x 22 x 45 Standards EN 60669-1 ; EN 60669-2-1 L N P C1 A1 A2 13 42 Characteristics of the contact Type No. of pul- ses Sequences 1234 FLR1-12 2 FLR1-230 2 FLR5-12 2 FLR5-230 2 FLR1-12, FLR1-230 FLR5-12, FLR5-230 2CSC400720F0201 1CSC400070F0202 L N P C1 A1 A2 13 42

pro M compact® Selection tables Command devices E 260 latching relays E 260 Connection examples * E 260 C Caution! The same electr. potential must be applied to terminals A1, B1 and C1. E 261-230 2CDC 052 087 F0003 E 261 C-230 2CDC 052 089 F0003 E 266 C-230 2CDC 052 092 F0003 E 261 C-24 2CDC 052 088 F0003 E 261-24 2CDC 052 086 F0003 E 260 electronic latching relays The electronic version of latching relays guarantees maximum reliability, life, and noiseless operation. The E 260 C version also allows centralized reset function (ON/OFF). Contacts Power Order Bbn Price Price Weight Pack loss details 4016779 1 piece group 1 piece unit W /L54706 Type code Order code EAN kg pc. /L54706 Values in brackets indicate power loss when permanently excitated, rated voltage and rated contact loading. Latching relays with control electronics Coil voltage UC = 24 V AC/DC 1 NO 2 .4 (3.0) E 261-24 2CDE441000R0301 57592 8 0 .085 1 1 NO+1 NC 2.4 (3.5) E 266-24 2CDE444000R0301 57595 9 0 .096 1 2 NO 2 .4 (3.5) E 262-24 2CDE442000R0301 57593 5 0 .096 1 Coil voltage UC = 230 V AC 1 NO 1 .5 (2.0) E 261-230 2CDE141000R0301 57596 6 0 .085 1 1 NO+1 NC 1.7 (3.6) E 266-230 2CDE144000R0301 57598 0 0 .096 1 2 NO 1 .7 (3.6) E 262-230 2CDE142000R0301 57597 3 0 .096 1 2CSC400066F0201 2CSC400077F0201

pro M compact® Selection tables Command devices E 260 latching relays E 260 Latching relays with returning time They switch off automatically after expiry of preset delay time (1 to 60 min.) if the manual OFF command has not been received. Glow lamp current 50 mA. Coil voltage UC = 230 V AC 1 NO 1 .5 (2.0) E 261 SRV-230 2CDE111010R0301 57605 5 0 .07 1 Technical features E 260/E 260 C E 261 SRV-230 Rated load at 250 V AC 8 A 16 A Incandescent lamp load 1000 W 1600 W Fluorescent lamp load in twin-lamp circuit 1000 W 1000 W Fluorescent lamp load shunt compensated 350 W /L54706 500 W Fluorescent lamp load inductive or capacitive 500 W 1000 W Electronic ballast I on m 70 A/10 ms /L54707 I on m 70 A/10 ms /L54707 Inductive load, cosϕ = 0.6/230 V ~ 5 A 5 A Contact rating at DC 100 W 100 W Minimum contact rating 4 V AC/10 mA 4 V AC/10 mA Contact gap/contact material 0.5 mm/Ag Sn0 2 0.5 mm/Ag Sn02 Service life mecha nical switchover at 103/h > 10 7 > 107 Service life at rated load cosϕ = 1 and 103/h > 10 5 > 105 Service life with filament lamps at 103/h 800 W > 105 , 1000 W > 0.8x105 1000 W > 105 Service life at rated load cosϕ = 0.6 and 103/h > 10 4 > 104 Max. switching rate 10 3/h 10 3/h Bounce time 3 ms Connection capacity 2 x 1.5 mm 2 with connector sleeve 2 x 2.5 mm2 without connector sleeve Tightening torque 0.5 … 0.8 Nm 0.5 … 0.8 Nm ON duration at rated voltage 100 % 100 % Coil voltage range 0.9 to 1.1 U n 0.9 to 1.1 Un Minimum command time/interval between commands 50/1000 ms 50 ms Ambient temperature -20 °C / -4 °F to 50 °C / 122 °F -20 °C / - 4 °F to 50 °C / 122 °F Control current when controlled locally 230 V AC 115 mA, after 10s 8 mA ± 20 %

24 V UC 140 mA, after 10s 80 mA ± 20 %

Control current when controlled centrally 230 V AC 8 mA, after 10s 3 mA ± 20 %

24 V UC 17 mA ± 20 %

Max. parallel capacity of individual control wire at 230 V ~ 0.7 μF (ca. 2000 m) Max. parallel capacity of central control wire at 230 V ~ 0.2 μF (ca. 700 m) Max. glow lamp current – parallel to 230 V control buttons 10 mA 10 mA Max. induced voltage at 230 V control inputs 0.2 U n 120 V Latching relays for lamp installations on request. /L54706 E 260 C can not be used with fluorescent lamp load shunt compensated. /L54707 In the case of electronic control gear, take into account a 40-fold inrush current.

pro M compact® Selection tables Command devices E 260 latching relays E 260 Terminal assignment E 266 C E 261-SRV E 262 C 2CDC 052 055 F0003 2CDC 052 054 F0003 E 261- E 266 E 262 SK 0018 Z 92 E 261 E 266 E 261 C E 262 2CDC 052 093 F0003 E 261-SRV simple latching relay functionality returning time OFF Latching relays with control electronics for central ON/OFF switch The central commands have always priority and reliably switch on/off any given number of devices connected in parallel, irrespective of their previous switching position. Local control inputs are blocked when a central command is received. Same potential at central / local control input. Contacts Power Order Bbn Price Price Weight Pack loss details 4016779 1 piece group 1 piece unit W /L54706 Type code Order code EAN kg pc. /L54706 Values in brackets indicate power loss when permanently excitated, rated voltage and rated contact loading. Coil voltage UC = 24 V AC/DC 1 NO 2 .4 (3.0) E 261 C-24 2CDE441000R0311 57599 7 0 .085 1 1 NO+1 NC 2.4 (3.5) E 266 C-24 2CDE444000R0311 57601 7 0 .096 1 2 NO 2 .4 (3.5) E 262 C-24 2CDE442000R0311 57600 0 0 .096 1 Coil voltage UC = 230 V AC 1 NO 1 .5 (2.0) E 261 C-230 2CDE141000R0311 57602 4 0 .085 1 1 NO+1 NC 1.7 (3.0) E 266 C-230 2CDE144000R0311 57604 8 0 .096 1 2 NO 1 .7 (3.0) E 262 C-230 2CDE142000R0311 57603 1 0 .096 1 Release 2CDC 052 091 F0103 Snap-on 2CDC 052 066 F0103

pro M compact® Selection tables Command devices STD50 dimmers STD50 SK 0043 Z 96 Control power STD 50-3: 20-500 W/VA STD 50-4: 40-420 W/VA 2CSC400432F0201 Technical features Rated voltage 230 V ~ 50 Hz Ambient temperature 0 °C to + 35 °C Interference suppression CE Influence of ambient temperature on the control power The certified rated power is indicated on the dimmer. Where higher ambient temperatures occur, reduce values as is specified in the diagram. At 50 °C /122°F ambient temperature, the permissible load drops to 57%. STD50 dimmers for the control of lamps and ballast Description/ Power Order Bbn Price Price Weight Pack application loss details 4016779 1 piece group 1 piece unit W Type code Order code EAN kg pc. Dimmer for brightness control of filament lamps , 230 V tungsten halogen lamps, lv halogen lamps with conventional transformers (phase control) 5 /L54706 STD 50-3 GH V021 1370 R0074 02790 8 0 .155 1 Dimmer for brightness control of filament lamps , 230 V tungsten halogen lamps, lv halogen lamps with ABB electronic transformers (reverse phase) 4 /L54706 STD 50-4 GH V021 1370 R0075 03300 8 0 .105 1 /L54706 power loss = 1% of connected load (4 or 5 W max)

pro M compact® Selection tables Command devices STD50 dimmers STD50 SK 0190 Z 99 Electronic potentiometer SK 0190 Z 99 SK 0189 Z 99 2CSC400445F0201 Brightness control of fluorescent lamps with 1 -10 V control input. Control of more than one memory touch controller STD-MTS via one push- button. Brightness control of a fluorescent lamp with 1 - 10 V DC control input with memory touch controller STD-MTS with external pushbutton, e.g. E 225 Dimmer STD 50-4 in two-way circuit, lv halogen lamps via electronic transformer Electronic potentiometer for electronic control gear with control input 0/1 - 10 V DC, control current 50 mA DC Rated current (terminal 3 and 4) 4 A cosϕ = 0.9; switching capacity 700 VA Description/ Power Order Bbn Price Price Weight Pack application loss details 4016779 1 piece group 1 piece unit W Type code Order code EAN kg pc. 5 /L54706 STD-EP GH V021 1370 R0076 27050 2 0 .073 1 Memory touch controller for electronic control gear Rated voltage/switching output 4 A (~ 10 electronic control gear units) cosϕ = 0.9; 3 A cosϕ = 0.5, switching capacity 700 VA for electronic 1 STD-MTS GH V021 0881 R0004 27070 0 0 .110 1 control gear with control input 1 – 10 V DC control current 50 mA max. /L54706 power loss = 1% of connected load (7 W max)

pro M compact® Selection tables Command devices Universal dimmer for phase control and reverse phase control STD 2CDC 052 081 F0207 Connected load / ambient temperature diagram Universal dimmer for phase control and reverse phase control Universal dimmer STD-500 U and the connected power extension unit STD-420 E are suitable for the brightness control of: - glow lamps - 230 V halogen glow lamps - lv halogen glow lamps with conventional transformer (phase control) - electronic transformers for lv halogen glow lamps (reverse phase control) e.g.: ABB ETR-70-230, 105-230, 150-230 The STD-500 U dimmer can be operated by one or more unlit pushbuttons (N- or L-controlled) or via a data line: - EIB control element SB/S - Powernet control element PSB Power unit STD-420 E is used to boost the connected load and is controlled exclusively by the preset command of the STD-500 U dimmer. The parallel connection of the outputs of the universal high- performance dimmer and the pertaining power extensions (up to 6 units; connection with enclosed RJ 12 line cut to length) allow for a dimming power of 3,000 W/VA max at one load line. Not suitable for dimming fluorescent lamps, transformers with current monitor and high-reactance transformers. Description/ application Power loss W Order details Type code Order code Bbn 4011395 EAN Price 1 piece Price group Weight 1 piece kg Pack. unit pc. high-performance dimmer 6 STD-500 U GJB0 006 590 A0178 06692 8 1 extension 6 STD-420 E GJB0 006 590 A0179 06693 5 1 rotary operation element – STD-OCD GJB0 006 590 A0183 06698 0 1 button operation element – STD-OCP GJB0 006 590 A0181 06695 9 1 timer operation element – STD-OCT GJB0 006 590 A0185 07056 7 1 Note: Load and control cables must not be laid in one cable. Technical features Rated voltage 230 V ~ ± 10%, 50/60 Hz Rated current STD U 2.17 A STD E 1.83 A Max. connected load U 500 W/VA E 420 W/VA Power extension 1 U + max. 6 E/phase = > max. 3 kVA Min. connected load STD U 60 W/VA STD E 200 W/VA Max. line length 100 m pushbutton cable, 2 m data line Interference suppression CE Ambient temperature 0 to + 45°C, higher temperatures reduce the power Electronic protection against short circuit, overload, excessive temperature, automatic load recognition, soft- OFF function optional, memory function, minimum brightness control, visual overload indication 2CDC051101F00062CDC051102F0006 2CDC051104F0006 2CDC051167F00062CDC051103F0006

Universal dimmer for phase control and reverse phase control STDSystem pro M compact® 2CDC 052 073 F0207 STD-500 U, SB/S or PSB/S STD-500 U U U 2CDC 052 129 F0208 2CDC 052 138 F0006 STD-500 U Plug-in operation elements: pushbutton operation element (STD-OCP) rotary operation element (STD-OCD) timer (STD-OCT) Application Remove dimmer cap and snap on operation element to provide for control of dimmer with central pushbutton or rotary operation. Local operation elements are still active. Apart from the manual local control feature, the timer also allows for time-programmed operations. Basic timer functions: - year time switch with 48 time programs - optional with/without decentralized pushbutton control - special programs: adjustable background brightness, cycle, display and emergency light, holiday program - running reserve: 5 hours

pro M compact® Selection tables Command devices E 234 electronic timers E 234 1) Functions: ON-delay, OFF-delay with auxiliary voltage, Impulse-ON, Impulse-OFF with auxiliary voltage, Flasher starting with ON, Flasher starting with OFF, Pulseformer E 234 electronic timers Rated Control Order Bbn Price Price Weight Pack control input details 1 piece group 1 piece unit voltage V Type code Order code EAN kg pc. Multifunction timers E 234 CT-MFD: 7 functions 1), 7 time ranges (0.05 s- 100 h), 2 c/o contacts, 2 LEDs 12-240 AC/DC yes E 234 CT-MFD.21 1SVR 500 020 R1100 0 .065 1 E 234 CT-MFD: 7 functions 1) , 7 time ranges (0.05 s- 100 h), 1 c/o contact, 2 LEDs 24-48 DC, 24-240 AC yes E 234 CT-MFD.12 1SVR 500 020 R0000 0 .060 1 ON-delay timers E 234 CT-ERD: 7 time ranges (0.05 s- 100 h), 2 c/o contacts, 2 LEDs 24-48 DC, 24-240 AC E 234 CT-ERD.22 1SVR 500 100 R0100 0 .065 1 E 234 CT-ERD: 7 time ranges (0.05 s- 100 h), 1 c/o contact, 2 LEDs 24-48 DC, 24-240 AC E 234 CT-ERD.12 1SVR 500 100 R0000 0 .060 1 OFF-delay timers E 234 CT-AHD: 7 time ranges (0.05 s- 100 h), 2 c/o contacts, 2 LEDs 24-48 DC, 24-240 AC yes E 234 CT-AHD.22 1SVR 500 110 R0100 0 .065 1 E 234 CT-AHD: 7 time ranges (0.05 s- 100 h), 1 c/o contact, 2 LEDs 24-48 DC, 24-240 AC yes E 234 CT-AHD.12 1SVR 500 110 R0000 0 .060 1 2CDC251089F0b062CDC251088F0b062CDC251092F0b062CDC251093F0b06

Rated Control Order Bbn Price Price Weight Pack control input details 1 piece group 1 piece unit voltage V Type code Order code EAN kg pc. Impulse-ON E 234 CT-VWD: 7 time ranges (0.05 s- 100 h), 1 c/o contact, 2 LEDs 24-48 V DC, 24-240 V AC E 234 CT-VWD.12 1SVR 500 130 R0000 0 .060 1 Flasher, starting with the ON time E 234 CT-EBD: 7 time ranges (0.05 s- 100 h), 1 c/o contact, 2 LEDs 24-48 V DC, 24-240 V AC E 234 CT-EBD.12 1SVR 500 150 R0000 0 .060 1 Pulse generators E 234 CT-TGD: 2x7 time ranges (0.05 s- 100 h) 2), 2 c/o contacts, 2 LEDs 24-48 V DC, 24-240 V AC yes E 234 CT-TGD.22 1SVR 500 160 R0100 0 .065 1 E 234 CT-TGD: 2x7 time ranges (0.05 s- 100 h) 2), 1 c/o contact, 2 LEDs 24-48 V DC, 24-240 V AC yes E 234 CT-TGD.12 1SVR 500 160 R0000 0 .060 1 Star-delta change-over E 234 CT-SDD: 4 time ranges (0.05 s- 10 min), transition time 50 ms fixed, 2 n/o contacts,

3 LEDs

24-48 V DC, 24-240 V AC E 234 CT-SDD.22 1SVR 500 211 R0100 0 .065 1 E 234 CT-SAD: 4 time ranges (0.05 s- 10 min), transition time adjustable, 2 n/o contacts, 24-48 V DC, 24-240 V AC E 234 CT-SAD.22 1SVR 500 210 R0000 0 .065 1 2) ON and OFF times adjustable independently, 2x7 time ranges 0.05 s - 100 h System pro M compact® Selection tables Command devices E 234 electronic timers E 234 2CDC251095F0b062CDC251096F0b062CDC251098F0b062CDC251099F0b06

pro M compact® Selection tables Command devices E 234 electronic timers E 234 Technical data Data at Ta = 25 °C and rated values, if nothing else indicated Type CT-D with 1 c/o contact CT-D with 2 c/o contacts Input circuit - Supply circuit Rated control supply voltage U S A1-A2 24-240 V AC / 24-48 V DC A1-A2 - 12-240 V AC/DC (CT-MFD.21) Rated control supply voltage US tolerance -15...+10 % Rated frequency AC/DC versions DC or 50/60 Hz AC versions 50/60 Hz Frequency range AC/DC versions DC or 47/63 Hz AC versions 47/63 Hz Typical power consumption 24 V DC 0.6 W on request 230 V AC 1.3 VA on request 115 V AC 1.3 VA on request Power failure buffering time min. 20 ms min. 30 ms Input circuit - Control circuit Voltage-related triggering Control input, Control function A1-Y1/B1 start timing external Maximum cable length to the control input 50 m - 100 pF/m Minimum control pulse length 30 ms Control voltage potential see rated control supply voltage Current consumption of the control input max. 4 mA on request Parallel load / polarized yes / yes Timing circuit 7.) 5-100 h (CT-SDD, CT-SAD) 4.) 0.5-10 min Recovery time < 50 ms Repeat accuracy (constant parameters) Δt < ±0.5 % Accuracy within the rated control supply voltage tolerance Δt < 0.005 % / V Accuracy within the temperature range Δt < 0.06 % / °C Star-delta transition time CT-SDD fixed 50 ms CT-SAD adjustable: 20-100 ms in steps of 10 ms Star-delta transition time tolerance CT-SDD, CT-SAD ±3 ms Indication of operational states Control supply voltage / timing U: green LED : control supply voltage applied : timing Relay status R: yellow LED : output relay 1 or 2 energized Output circuit Kind of output 15-16/18 relay, 1 c/o contact - 15-16/18; 25-26/28 - relay, 2 c/o contacts 17-18; 17-28 relay, 2 n/o contacts (CT-SDD, CT-SAD) Contact material Cd-free, see data sheet Rated operational voltage U e 250 V Minimum switching voltage / minimum switching current 12 V / 100 mA Maximum switching voltage / maximum switching current see load limit curves Rated operational current Ie AC12 (resistive) at 230 V 6 A 5 A (IEC 60947-5-1 ) AC15 (inductive) at 230 V 3 A 3 A /L54706 for category DC12 (resistive) at 24 V 6 A 5 A DC13 (inductive) at 24 V 2 A 3 A /L54706 Mechanical lifetime 30 x 10 6 switching cycles Short-circuit proof / n/c contact 6 A fast-acting maximum fuse rating (IEC/EN 60947-5-1) n/o contact 10 A fast-acting /L54706 CT-MFD.2x on request

pro M compact® Selection tables Command devices E 234 electronic timers E 234 Technical data Data at Ta = 25 °C and rated values, if nothing else indicated Type CT-D with 1 c/o contact CT-D with 2 c/o contacts General data Duty time 100% Dimensions (W x H x D) 17.5 mm x 70 mm x 58 mm 17.5 mm x 80 mm x 58 mm Weight see ordering details Mounting DIN rail (EN 60715), snap-mounting without any tool Mounting position any Minimum distance to other units horizontal / vertical no / no Degree of protection enclosure / terminals IP50 / IP20 Electrical connection Wire size fine-strand with wire end ferrule 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG) 1 x 0.5-2.5 mm 2 (1 x 20-14 AWG) without wire end ferrule 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG) 1 x 0.5-2.5 mm 2 (1 x 20-14 AWG) rigid 2 x 0.5-1.5 mm 2 (2 x 20-16 AWG) 1 x 0.5-4 mm 2 (1 x 20-12 AWG) Stripping length 7 mm (0.28 inches) Tightening torque 0.5-0.8 Nm Environmental data Ambient temperature range operation -20 ... +60 °C storage -40 ... +85 °C Damp heat (cyclic) (IEC/EN 60068-2-30) 6 x 24 h cycles, 55 °C, 95 % RH Shock (half-sine) (IEC/EN 60068-2-27) 100 m/s 2, 11 ms Isolation data Rated impulse withstand voltage Uimp 4 kV; 1.2/50 μs between all isolated circuits (VDE 0110, IEC/EN 60664-1) Pollution category (IEC/EN 60664-1, VDE 0110, UL 508) 3 Overvoltage category (IEC/EN 60664-1, VDE 0110, UL 508) III Rated insulation voltage Ui input circuit / output circuit 300 V output circuit 1 / output circuit 2 300 V Basic insulation (IEC/EN 61140) input circuit / output circuit 300 V Protective separation input circuit / output circuit 250 V (VDE 0106 part 101 and part 101/A1; IEC/EN 61140) Test voltage between all isolated circuits (type test) 2.5 kV, 50 Hz, 1 s Standards Product standard IEC 61812-1, EN 61812-1 + A11, DIN VDE 0435 part 2021 Low Voltage Directive 2006/95/EC EMC Directive 2004/108/EC RoHS Directive 2002/95/EC Electromagnetic compatibility Interference immunity IEC/EN 61000-6-1, IEC/EN 61000-6-2 electrostatic discharge (ESD) IEC/EN 61000-4-2 Level 3 (6 kV / 8 kV) electromagnetic field IEC/EN 61000-4-3 Level 3 (10 V/m) (HF radiation resistance) fast transients (Burst) IEC/EN 61000-4-4 Level 3 (2 kV / 5 kHz) powerful impulses (Surge) IEC/EN 61000-4-5 Level 4 (2 kV L-L) HF line emission IEC/EN 61000-4-6 Level 3 (10 V) Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4 electromagnetic field IEC/CISPR 22, EN 55022 B (HF radiation resistance) HF line emission IEC/CISPR 22, EN 55022 B

pro M compact® Selection tables Command devices E 234 electronic timers E 234 Technical diagrams Load limit curves AC load (resistive) DC load (resistive) CT-D.1x CT-D.1x CT-D.2x CT-D.2x Derating factor F Contact l ifetime for inductive AC load DC current [A] resistive load DC voltage [V] 2CDC 252 121 F0206 AC current [A] resistive load AC voltage [V] 2CDC 252 122 F0206 Switching current [A] 250 V resistive load Switching cycles 2CDC 252 123 F0206 cos ϕ 0.5 0.6 0.7 0.8 0.9 1.0 Derating factor F 2CDC 252 124 F0206 DC current [A] resistive load DC voltage [V] 2CDC 252 045 F0207 AC current [A] resistive load AC voltage [V] 2CDC 252 044 F0207

CT-MFD.21 CT-MFD.12 CT-ERD.22 CT-ERD.12 CT-AHD.22 CT-AHD.12 CT-VWD.12 CT-EBD.12 CT-TGD.22 CT-TGD.12 CT-SDD.22 CT-SAD.22 Wiring notes for devices with control input A parallel load to the control input is possible System pro M compact® Selection tables Command devices E 234 electronic timers E 234 18 16 Y1/B1 1816 Y1/ 2CDC 252 113 F0b06 18 16 Y1/B1 1816 Y1/ 2CDC 252 116 F0b06 18 16 15 25 1816 2CDC 252 115 F0b06 18 16 Y1/B1 2826 Y1/ 2CDC 252 118 F0b06 A2 18 28 28 18 A2 2CDC 252 160 F0b06 Y1/B1 Y1/ 2CDC 252 114 F0b06 2CDC 252 177 F0b05 Y1/B1 Y1/ 2CDC 252 117 F0b06 2CDC 252 179 F0b05 2CDC 252 180 F0b05 Y1/B1 Y1/ 2CDC 252 119 F0b06 A2 18 28 28 18 A2 2CDC 252 160 F0b06 L(+) N(-) A1 Y1/B1 2CDC 252 102 F0b06

pro M compact® Selection tables Command devices E 234 electronic timers E 234 Remarks Legend Control supply voltage not applied / Output contact open Control supply voltage applied / Output contact closed A1-Y1/B1 Control input with voltage-related triggering Terminal designations on the device and in the diagrams The 1st c/o contact is always designated 15-16/18. The 2nd c/o contact is designated 25-26/28. The n/o contacts of the star-delta timers are designated with 17-18 and 17-28. Control supply voltage is always applied to terminals A1-A2. Function of the yellow LED The yellow LED R glows as soon as the output relay energizes and turns off when the output relay de-energizes. ON-delay (Delay on make) CT-ERD, CT-MFD This function requires continuous control supply voltage for timing. Timing begins when control supply voltage is applied. The green LED flashes during timing. When the selected time delay is complete, the out put relay energizes and the flashing green LED turns steady. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. Control input A1-Y1/B1 of the CT-MFD is disabled when this function is selected. OFF-delay with auxiliary voltage (Delay on break) CT-AHD, CT-MFD This function requires continuous control supply voltage for timing. If control input A1-Y1/B1 is closed, the output relay energizes immediately. If control input A1-Y1/B1 is opened, the time delay starts. The green LED flashes during timing. When the selected time delay is complete, the output relay de-energizes and the flashing green LED turns steady. If control input A1-Y1/B1 recloses before the time delay is complete, the time delay is reset and the output relay does not change state. Timing starts again when control input A1-Y1/B1 re-opens. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. A1-A2 15-16, 25-26 15-18, 25-28 t< t 2CDC 252 106 F0206 green LED t = adjusted time delay A1-A2 15-16, 25-26 15-18, 25-28 t A1-Y1/B1 < t 2CDC 252 107 F0206 green LED t = adjusted time delay Impulse-ON (Interval) CT-VWD, CT-MFD This function requires continuous control supply voltage for timing. The output relay energizes immediately when control supply voltage is applied and de-energizes after the set pulse time is complete. The green LED flashes during timing. When the selected pulse time is complete, the flashing green LED turns steady. If control supply voltage is inter- rupted, the output relay de-energizes and the time delay is reset. Control input A1-Y1/B1 of the CT-MFD is disabled when this function is selected. Impulse-OFF with auxiliary voltage (Trailing edge interval) CT-MFD This function requires continuous control supply voltage for timing. If control supply voltage is applied, opening control input A1-Y1/B1 energizes the output relay immediately and starts timing. The green LED flashes during timing. When the selected pulse time is complete, the output relay de-energizes and the flashing green LED turns steady. Closing control input A1-Y1/B1, before the time delay is complete, de- energizes the output relay and resets the time delay. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. A1-A2 15-16, 25-26 15-18, 25-28 t< t 2CDC 252 108 F0206 green LED t = adjusted pulse time A1-A2 15-16, 25-26 15-18, 25-28 t A1-Y1/B1 < t 2CDC 252 109 F0206 green LED t = adjusted pulse time Flasher, starting with the ON time (Recycling equal times, ON first) CT-EBD, CT-MFD Applying control supply voltage starts timing with symmetrical ON & OFF times. The cycle starts with an ON time first. The ON & OFF times are displayed by the flashing green LED, which flashes twice as fast during the OFF time. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. Control input A1-Y1/B1 of the CT-MFD is disabled when this function is selected. Flasher, starting with the OFF time (Recycling equal times, OFF first) CT-MFD Applying control supply voltage starts timing with symmetrical ON & OFF times. The cycle starts with an OFF time first. The ON & OFF times are displayed by the flashing green LED, which flashes twice as fast during the OFF time. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. Control input A1-Y1/B1 of the CT-MFD is disabled when this function is selected. A1-A2 15-16, 25-26 15-18, 25-28 t t 2CDC 252 029 F0206 green LED t = adjusted flashing time A1-A2 15-16, 25-26 15-18, 25-28 t t 2CDC 252 030 F0206 green LED t = adjusted flashing time

pro M compact® Selection tables Command devices E 234 electronic timers E 234 K1T K1T Y /L50876N N I 2CDC 252 128 F0b06 -K1-K3 -F1 -K2 -F2 M 3 ~ -M1 2CDC 252 012 F0b07 Pulse former (Single shot) CT-MFD This function requires continuous control supply voltage for timing. Closing control input A1-Y1/B1 energizes the output relay immediately and starts timing. Operating the control contact switch A1-Y1/B1 during the time delay has no effect. The green LED flashes during timing. When the selected ON time is complete, the output relay de-energizes and the flashing green LED turns steady. After the ON time is complete, it can be restarted by closing control input A1-Y1/B1. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. Pulse generator, starting with the ON or OFF time (Recycling unequal times, ON or OFF first) CT-TGD This function requires continuous control supply voltage for timing. Applying control supply voltage, with open control input A1-Y1/B1, starts timing with an ON time first. Applying control supply voltage, with closed control input A1-Y1/B1, starts timing with an OFF time first. The ON & OFF times are displayed by the flashing green LED, which flashes twice as fast during the OFF time. The ON & OFF times are indepen- dently adjustable. If control supply voltage is interrupted, the output relay de-energizes and the time delay is reset. Star-delta change-over (Star-delta starting) CT-SDD, CT-SAD This function requires continuous control supply voltage for timing. Applying control supply voltage to terminals A1-A2, energizes the star contactor connected to terminals 17-18 and begins the set starting time t 1. The green LED flashes during timing. When the starting time is complete, the first output contact de-energizes the star contactor. Now, the transition time t2 starts. When the transition time is complete, the second output contact energizes the delta contactor connected to terminals 17-28. The delta contactor remains energized as long as control supply voltage is applied to the unit. A1-A2 15-16, 25-26 15-18, 25-28 tt A1-Y1/B1 2CDC 252 110 F0206 green LED t = adjusted pulse time A1-A2 A1-Y1/B1 15-16, 25-26 15-18, 25-28 t1 t1t2 t2 2CDC 252 111 F0206 green LED t1 = adjusted OFF time t2 = adjusted ON time A1-A2 t1 t2 2CDC 252 112 F0206 green LED t1 = adjusted starting time t2 = transition time CT-SDD: t2 = 50 ms CT-SAD: t2 adjustable 17-18 17-28 Power circuit diagramControl circuit diagram

pro M compact® Selection tables Command devices AT electro-mechanical time switches AT AT electro-mechanical time switches They control circuit opening and closing according to the scheduled program. Available both on daily and weekly version and equipped with a 16A contact, they can be set on the scheduled program or on the permanent ON function (ON-OFF only for three modules versions). The AT1-R, AT3-R and AT3-7R versions are equipped with a built-in battery, generally charged by the network voltage, which allows the devices to maintain the set time also in case of long (up to 200h) power supply failures. The products fit applications such as shop lighting systems, public buildings, schools, heating and irrigation systems and so forth. Contacts Running Version Order Bbn Price Price Weight Pack reserve details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1NO - da ily AT1 2CSM204205R0601 042051 0,095 1 1NO 200h da ily AT1-R 2CSM204215R0601 042150 0,095 1 1CO - da ily AT3 2CSM204225R0601 042259 0,180 1 1CO 200h da ily AT3-R 2CSM204235R0601 042358 0,180 1 1CO 200h weekly AT3-7R 2CSM204245R0601 042457 0,180 1 Technical features AT1 AT1-R AT3 AT3-R AT3-7R Rated supply voltage [V] 230 AC + 10% Contact type 1NO 1NO 1CO 1 CO 1CO Switching capacity resistive load [A] 16 inductive load [A] 44333 Rated frequency [Hz] 50-60 Time base quartz Minimum switching time [min] 15 15 15 15 120 Max number of commands per cycle 96 96 96 96 84 Running reserve [h] - 200 - 200 200 Accurary ± 1sec / 24h Power consumption [VA] 0.5 Max. switching power [W] 4000 Terminal size for cable [mm²] 4 Terminals loss-proof screw Mounting on DIN rail Operating temperature [°C] -10….+55 Modules 11333 Reference standards EN 60730-1 ; EN 60730-2-7 L N 246 1 0 1 2 M AT1, AT1-R AT3, AT3-R, AT3-7R 2 4 L N 2CSC400735F00012CSC400732F0001 1CSC400075F0202

Programming AT3 - AT3-R - AT3-7R System pro M compact® Selection tables Command devices AT electro-mechanical time switches AT 15'23 I 0 I I 0 I I 0 II = automatic I = ON permanently I 0 I 0 I I 0 I 0 I 3-position selector: 0 = permanently OFF = automatic programmed operation I = permanently ON. 1CSC400075F02021CSC400076F0202 Program setting Manual override Setting the time Programming Manual overrideTime settingSwitching dial

pro M compact® Selection tables Command devices AT2 electro-mechanical time switches AT AT2 electro-mechanical time switches The AT2 versions are particularly useful where there is the need to have a complete visibility of the programmable dial in only two modules.They control, as well as the AT1 and AT3 ones, circuit opening and closing according to a scheduled program and are available both on daily and weekly version with a 16A change-over contact. They can be set on the scheduled program or on permanent ON and the versions AT2-R and AT2-7R are equipped with a built-in battery, generally charged by the network voltage, which allows the devices to maintain the set time also in case of long (up to 150h) power supply failures. The products fit applications such as store lighting system, public buildings, schools, heating and irrigation systems and so forth. Contacts Running Version Order Bbn Price Price Weight Pack reserve details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc.

1 CO - da ily AT2 2CSM204105R0601 041054 0,118 1

1 CO 150h da ily AT2-R 2CSM204115R0601 041153 0,118 1

1 CO 150h weekly AT2-7R 2CSM204125R0601 041252 0,118 1

Rated supply voltage [V] 230 AC Contact type 1 CO Switching capacity resistive load [A] 16 inductive load [A] 4 Rated frequency [Hz] 50-60 Time base quartz Minimum switching time [min] 30 30 210 Max number of commands per cycle 48 Running reserve [h] - 150 150 Accuracy ± 1sec / 24h Power consumption [VA] 0.5 Potenza commutabile massima [W] 3500 Terminal size for cable [mm²] 2.5 Terminals loss-proof screw Mounting on DIN rail Operating temperature [°C] -10 …+50 Storage temperature [°C] -10 …+50 Modules 2 Reference standards EN 60730-1 ; EN 60730-2-7 2CSC400734F00012CSC400733F0001 1CSC400077F0202

GB Example: 3 = Wednesday 14:45 Type mode Switching dial = Working according to the scheduled program 1 = Permanent ON System pro M compact® Selection tables Command devices AT2 electro-mechanical time switches AT 1CSC400078F02021CSC400079F0202

D Line digital time switches D LineSystem pro M compact D Line digital time switches The unique design, with white backlit LCD display, and extreme ease of use with two lines of text menu and only four buttons, make D LINE ideal to automate the installation functions. Thanks to the innovative management of time vacation, the D Line digital time switches allow the exclusion of the normal weekly program in one or more periods of several years or between two different years. The range includes 1 and 2 channel versions, equipped with large capacity internal battery to maintain operation without power supply and permanent memory EEPROM, to avoid the risk of program loss and to maintain the date and time settings in the event of power failure, irrespective of its duration. The “Plus” version can transfer different type of program by using a D KEY to be quickly copied in No digital time switches, avoiding the errors due to future modification. The “SYNCHRO” version can be coupled to the D DCF77 antenna, that allows an automatic synchronization of the digital time switch with the Frankfurt DCF77 time signal, or can be coupled to the D GPS antenna to allows synchronization received from the Global Positioning System. The D Line is particularly useful in environments and situations where user management is required with a time schedule flexible enough to predict or exclude activities according to time and day of week or month. Channels no. Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 D1 2CSM258763R0621 587637 0 .140 1 1 D1 PLUS 2CSM257583R0621 575832 0 .140 1 1 D1 SYNCHRO 2CSM257493R0621 574934 0 .140 1 2 D2 2CSM256313R0621 563136 0 .140 1 2 D2 PLUS 2CSM277583R0621 775836 0 .140 1 2 D2 SYNCHRO 2CSM277363R0621 773634 0 .140 1 1CSC400080F02021CSC400081F0202

D Line digital time switches D LineSystem pro M compact Innovations Main features Furthermor, the PLUS and SYNCHRO High contrast LCD monitor for excellent visibility in all conditions due to timed back- lighting Clear display of each contact status Wide range of programs: standard, cyclic, casual and holiday GPS or DCF77 signal reception indication Captive glass with hinge opening 1-2 swapped contact(s) Occupies the space of 2 DIN modules 1-2 external input(s) for the connection of one or more remote controls, for example: Switches and buttons 1-2 external input(s) for DCF77 or GPS receiver connection (for SYNCHRO) Permanent or temporary manual deviation, directly activated with a single touch Sealable glass and keypad lock to prevent tampering by unauthorised personnel. Programming key slot to run, copy or save programs Terminals for wires up to 6 mm Holiday management with the possibility of programming them in various period throughout the year Product warranty management: the internal clock and battery start at the first installation Menu programming with 4 simple keys Minimum switch time is 1 second Multilingual menu with 11 language choices Connected load maintenance management: According to the “count down”, it sends an alert on the display after a set number of operating hours Zero load switching to guarantee higher load relay working life. Load reserves for 6 years from the first start-up guaranteed by the lithium batter D KEY programming key to run programs saved on the key, program transfer from timer switch to key and vice versa to read programs on key. D SW programming software lets you quickly, simply and easily create complex programs from your desktop. Once created, the program can be printed or saved to file. The D DCF77 antenna that receives the DCF77 radio synchronisation signal transmitted by the atomic clock installed c/o Mainflingen, near Frankfort, increases digital clock precision. The GPS antenna that receives time from the Global Positioning System, that offers a more accurate value than land transmissions in addition to the possibility of receiving the signal anywhere in the world.

D Line digital time switches D LineSystem pro M compact Technical specifications D1 D1 PLUS D1 SYNCHRO D2 D2 PLUS D2 SYNCHRO Rated voltage [V] 230 AC ± 10% Rated pulsating voltage [kV] 4 Contact type Contact relay in free exchange from potential Programming key - ■■ - ■■ External input - ■ -- ■ - DCF77 antenna -- ■ -- ■ GPS antenna -- ■ -- ■ Programming software - ■■ - ■■

250 V contact capacity

Ohm loads [A] 16 16 Inductive loads [A] 10 2 Rated frequency [Hz] 50-60 Time base quartz Minimum switching [sec.] 1 Max programs per cycle [n°] 64 (can be coupled in day blocks) Load reserve [anni] 6 from the first start-up (lithium battery) External input [n°] 1-2- Activity suspension From 1 day to 12 months Operating precision sec./ giorno ± 0.5 Max. dissipated power [VA] 6.5 7.8 Max. switch power [VA] 3500 Incandescent LP power [W] 3000 Non-rephased fluorescent tube LP power [W] 1100 Fluorescent tube LP power rephased in parallel [W] 900 Fluorescent tube LP power with electronic reactor [W] 7 ÷ 23 (max. 23 lamp.) Fluorescent tube LP power rephased in series [W] 1100 Protection grade [IP] 20 Max. terminal section [mm²] 6 Terminals In positive safety with captive screw Installation type DIN rail Operating temperature [°C] -5 … +55 Storage temperature [°C] -10 … +65 Modules [n°] 2 MENU resetOK 1 2 3 4 5 6 7 06 12 18 24 MENU resetOK 1 2 3 4 5 6 7 1 2 06 12 18 24 D1 PLUS D1 SYNCHRO D2 PLUS D2 SYNCHROD1 D2 MENU resetOK 1 2 3 4 5 6 7 06 12 18 24 MENU resetOK 1 2 3 4 5 6 7 1 2 06 12 18 24 1CSC400082F0202

Programming menu with programming key Selection tables Command devices D Line digital time switches D LineSystem pro M compact Programming menu without programming key Languages Italiano English Deutsch Français Español Swedish Portugues Dutch Polish Russian Greek Menu Standard prog Random prog Cyclic prog Holiday prog Prog list Delete Manual Options Standard/ Random program Input - program no. - channel (dual channel only) - day - hour on HH:MM:SS - hour off HH:MM:SS - end/yearly Verify Edit Copy Cancel Cyclic program Input - program no. - channel (dual channel only) - day - time on - time off - end/yearly Verify Edit Copy Cancel Holiday program Input - program no. - channel (dual channel only) - hour off - day and month off - hour on - day and month on Verify Edit Copy Cancel Program list Verify Edit Copy Cancel Delete Single prog All programs Holiday Manual over- riding Channel (dual channel only) Auto Permanent on/off Temp on/off Options Language Date/time Aux input * Maintenance Hour counter Backlight Guaranty Date/time Year Month Day Time HH:MM:SS Summer/winter time Auxiliary input Channel (dual channel only) Permanet on/off Temp on/off Timer on/off Maintenance C1 000000 C2 000000 (dual channel only) Hour counter C1 000000 C2 000000 (dual channel only) Backlit Permanent on Permanent off Timer 6 sec Guaranty Days 0000 Languages Italiano English Deutsch Français Español Swedish Portugues Dutch Polish Russian Greek Menu Standard prog Random prog Cyclic prog Holiday prog Prog list Delete Manual Options Standard/ Random program Input - program no. - channel (dual channel only) - day - hour on HH:MM:SS - hour off HH:MM:SS - end/yearly Verify Edit Copy Cancel Cyclic program Input - program no. - channel (dual channel only) - day - time on - time off - end/yearly Verify Edit Copy Cancel Holiday program Input - program no. - channel (dual channel only) - hour off - day and month off - hour on - day and month on Verify Edit Copy Cancel Program list Verify Edit Copy Cancel Delete Single prog All programs Holiday Manual over- riding Channel (dual channel only) Auto Permanent on/off Temp on/off Options Language Date/time Aux input * Maintenance Hour counter Backlight Guaranty EMD memory key Date/time Year Month Day Time HH:MM:SS Summer/winter time Auxiliary input Channel (dual channel only) Permanet on/off Temp on/off Timer on/off Maintenance C1 000000 C2 000000 (dual channel only) Hour counter C1 000000 C2 000000 (dual channel only) Backlit Permanent on Permanent off Timer 6 sec Guaranty Days 0000 EMD memory key Run on EMD Save on EMD Copy on clock EMD read Save holiday only Copy holiday only Erase EMD * not allowed for SYNCHRO type * not allowed for SYNCHRO type

D Line digital time switches D LineSystem pro M compact Accessories for D Line digital time switches Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Programming key D KEY 2CSM277143R0621 771432 0 .005 1 Programming software D SW 2CSM299973R0621 999737 0 .020 1 DCF77 antenna D DCF77 2CSM299983R0621 999836 0 .150 1 GPS antenna D GPS 2CSM299993R0621 999935 0 .150 1 Technical features D DCF77 D GPS Rated supply voltage [V] 230 AC ±20% Rated frequency [Hz] 50/60 Power loss [W] 0.1 2 Operating temperature [°C] -10…+70 -10…+40 Storage temperature [°C] -30…+90 -40…+85 Power consumption [VA] 9.2 2 Time of the signal 1 sending / min. min 30 sendings/hour ; max 50 sendings/hour Protection degree [IP] 65 65 Max. number of connected devices [No.] 10 10 Max. wiring length [m] 1000 1000 Mounting pole/wall pole/wall Wiring diagram C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N L1 IE D1 and D1 PLUS N L C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N L1 IE1IE2 D2 and D2 PLUS N L C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N D1 SYNCHRO N L D DCF77 D GPS D2 SYNCHRO N L D DCF77 D GPS C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N 1CSC400060F0202 2CSC400714F0001 1CSC400083F0202

D Line digital time switches D LineSystem pro M compact Programming key Allows to run a program in EMD external memory automati- cally, to save the programs in the clock or to create programs using the D SW software, on the EMD external memory or viceversa. Furthermore, the holiday programs can be loaded and unlo- aded on D KEY. DCF77 and GPS antenna wirings The D DCF77 or D GPS antenna allows you to control up to 10 instruments. The polarity of the first instrument is regardless, while the others have to respect the polarity of the first one. C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N D1 SYNCHRO D2 SYNCHRO C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N D1 SYNCHRO D2 SYNCHRO C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N D1 SYNCHRO D2 SYNCHRO D DCF77 D GPS 1 3 5 7 L C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 2 4 6 8 N C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N Save Upload Upload Upload C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N C1 OFF P24 0 6 12 18 24 1 2 3 4 5 6 7 RESETMENU OK 1 3 5 7 L 2 4 6 8 N Save Upload Upload Upload 1CSC400084F02021CSC400085F0202

Operating principle: This antenna receives scheduled messages broa- dcasted from the Frankfurt on Main (Germany) based DCF77 emitter. Thanks to this signal, the time switches are auto- matically setted to: hour, date and proper daylight saving time. The broadcast power is 50 kW and the range is approximately 2500 kilometers from Frankfurt on Main. Sometimes the signal is received intermittently and not in all locations, especially in countries far enough from the D DCF77 emitter. For optimal signal reception the arrow marked side of the antenna must be rotated towards Frankfurt on Main. GPS antenna Operating principle: The Global Positioning System provides an accurate location and time information for an unlimited number of people in all weather, day or night, anywhere in the world. The synchronization received from GPS is far more precise regarding to terrestrial broadcast. The GPS system relays upon time from satellite based atomic clocks, constantly controlled and corrected from a ground stations network. The time is derived from different sources simulta- neously, the digital time switches can automatically compensate for propagation delays and other problems by providing more precise values than terrestrial. Selection tables Command devices D Line digital time switches D LineSystem pro M compact 2500 km 2000 km 1500 km 1000 km 500 km DCF77 1CSC400085F02021CSC400086F0202

DTS series yearly digital time switches are available in 3 or 4 channel versions. Used for more sophi- sticated configurations, they are able to control multiple loads or even groups of independent loads that require time-differentiated commands, but with a common clock reference. An EPROM memory eliminates the risk of program loss in the event of power failure, irrespective of its duration. DTS yearly digital time switches are ideal in large buildings that have variable needs over the course of the year (public lighting, heating of public buildings, distribution chains, shopping centres, etc...). Channels Order Bbn Price Price Unit Pack details 8012542 1 piece group weight unit No. Type ABB Code EAN kg pc. 3 DTS7/3Y 2CSM133100R0601 507000 0 .380 1 4 DTS7/4Y 2CSM134100R0601 538509 0 .410 1 Accessories for DTS yearly digital time switches DTS time switches can be programmed directly from the user’s PC using the DTS/PRG-SW software, which allows quick and easy configuration. The program can in fact be transferred from the PC to a portable memory unit, and then copied from there to multiple devices, thus avoiding reprogramming errors. DTS/PRG-SW software also allows the device to be used as a conventional astronomical time switch. By defining the latitude and longitude of the geographical place of installation, it is possible to auto- matically control the switching of circuits based on the time when the sun rises and sets. DTS/DCF antenna, used in conjunction with the device, enables it to be automatically synchronised with the official DCF77 Frankfurt time signal, broadcast via long wave radio. The range of the DCF77 signal is about 2500 km from Frankfurt. Order Bbn Bbn Price Price Unit Pack details 8012542 1 piece group weight unit Type ABB code EAN kg pc. DTS/DCF 2CSM000010R0601 538608 0 .230 1 DTS/PRG-SW 2CSM000050R0601 538707 0 .350 1Technical characteristics DTS7/3Y DTS7/4Y Rated voltage Un 230 AC +10%/-15% Contact type 3CO 4CO Contact capacity ohmic loads [A] 16 inductive loads [A] 2.5 Rated frequency [Hz] 50/60 Time reference quartz Minimum ON/OFF setting unit [min] 1 Max. operations per cycle 400 Pulse duration 1 sec … 99 min Battery life [years] 6 Operating accuracy ± 1 sec/day Power consumption [W] 5 Terminals captive screw Installation type DIN rail Protection degree [IP] 20 Storage temperature [°C] -25…+55 Can be sealed ■ Modules 6 Standards EN 60730-1, IEC 730-1, CEI 107-70, VDE0633 Selection tables Command devices DTS digital time switches DTSSystem pro M compact 2CSC400141F0001

The removable control panel allows the device to be conveniently pro- grammed at the desk. Connection diagram DTS/PRG-SW: simple installation Removable control panel /L54706 Install the DTS/PRG-SW software on the PC. The system requirements are a 486 processor or higher, with Windows 95/98/2000/NT/XP and at least 4 MB free disk space. /L54707 Connect one end of the serial cable to the PC serial port, and the other end to the portable memory unit. /L54708 Using the DTS/PRG-SW software, copy the yearly program from the PC to the portable memory unit. /L54710 Disconnect the portable memory unit and insert it into the infrared slot on the device. /L54711 Copy the program from the portable memory unit to the device. At this point the portable memory unit can be removed from the device and the procedure repeated on another de- vice. In addition to pasting programs onto multiple devices, it is also possible to copy a program from a device to the portable memory unit. Selection tables Command devices DTS digital time switches DTSSystem pro M compact /L54706 /L54707 e /L54708 /L54709 e /L54710 1CSC400086F02021CSC400087F02021CSC400060F0202

Day Prog. Prior. 7654321 +1 h I/O I/O I/O I/O Reset Manual switch Reset Select days of the week: 1 = monday 2 = tuesday 3 = ... select cycle select pulse set standard/ daylight saving time up to, for date field select: day month year hours minutes minutes/seconds and pulse/cycle function set current date, time start programming priority cancel IR transmit / receive Month (US day) Pulse (seconds) Cycle (seconds) Year Block number Priority Summer time / winter time switchover Automatic operation DCF 77 radio reception Pulse Cycle 1234567 = day of the week 12h/24h time display Minute Hours Year number Day (US month) Pulse (minutes) Cycle (minutes) Channel 1 Channel 2 Channel 3 Channel 4 Continuous operation Manual operation Automatic operation Switching state 1CSC400088F02021CSC400089F0202

The DTS/PRG-SW programming software makes it easy to set up a yearly program that can subsequently be copied to the DTS7/3Y or DTS7/4Y digital timers. Part two:

  • Define the program
  • Define the contact number
  • Define the switching time
  • Enter the type of input (ON-OFF, PULSE or CYCLE)
  • Add the extra information The DTS/PRG-SW software can also be used for configuring the astronomical function, for viewing a clear graphical representation of the entire yearly program, with detail access to individual days, as well as for printing a summary of the program to be kept for reference near the installed deviced or archived. Graphical representation It is possible to view a clear representation of the yearly program, and of the days and weeks that have been defined. The active parts are highlighted in different colours, as can be seen in the example at left. Program summary After setting up and checking the program, it is possible to print out a summary of the pro- gram to keep near the installed device or as a reference. The program printout shows the following details:
  • Number of switching ope- rations
  • Duration of ON and OFF operations
  • Pulse duration
  • Cycle duration
  • Power consumption in kWh (requires correct entry of load values) Astronomical function Using the DTS/PRG-SW software, the DTS7/3Y and DTS7/4Y models can be configured to control one or more contacts based on the sunrise or sunset times of each day of the year, thus replacing the functions of a conventional twilight switch. The device will start to operate once the date, time and the latitude and longitude of the place of installation have been entered. The astronomical function is ideal where: - The distance between the sensor and the time switch is more than 100 m, or if an external sensor cannot be used (panel installed inside a basement...). - The external sensor cannot be installed away from light sources (amusement parks, campsites,...). - The external sensor cannot be installed because it is potentially subject to interference from pollution or exposed to vandalism. Part one:
  • Select the application
  • Define the contact number
  • Select the contact symbol
  • Define the designations
  • Enter the rated power Programming in a few easy steps 2CSC400724F0001 1CSC400091F02021CSC400090F0202 1CSC400092F0202

pro M compact® Selection tables Command devices E 232 staircase lighting time-delay switches E 232 staircase lighting time-delay switches Staircase lighting time-delay switches are usually operated by pushbuttons, often fitted with a glow lamp. Switches are designed for a glow lamp current of up to 150 mA and thus perfectly suitable for installations in multi-storey buildings. The E 232-230 staircase lighting time-delay switch includes an electro-mechanical timer with a syn- chronous motor drive to ensure high operational safety in whatever mounting position. The time range is adjustable in increments of 15 seconds from 1 to seven minutes. Resettable after 30 seconds. E 232E–230N and E 232E-8/230N devices feature electronic time delays. A high switching capacity, 150 mA glow lamp current parallel to the pushbuttons, steplessly adjustable time range from 0.5 to 20 min, as well as low switching noise make these devices so special. Devices of the E 232E-230 Multi 10 and E 232E-8/230 Multi 10 series are multi-functional products with 10 functions to choose from that can be adjusted from the front. Through an electronically controlled connection of the load at voltage zero, a very high switching capacity of 3,600 W (load of filament lamp) is reached. The devices include an integrated warning feature (warning by blinking) according to DIN 18015-2 as well as a 60 minute long-time function. The E 232E-8/230N and E 232E-8/230 Multi 10 staircase lighting time-delay switches offer an ad- ditional metallically separated control input for 8…240 V AC/DC. The electronic E 232-HLM half-light module is a supplementary device for staircase lighting time-delay switches for semi-light control according to DIN 18015-2. The module switches filament lamps and

230 V halogen lamps up to 2,300 W in the warning phase to an output voltage that is reduced by

50%. Adjustable time range from 20 – 60 seconds. 2CSC400470F0201 Technical features E 232-230 E 232E-230N E 232E-8/230N E 232E-230 Multi 10 E 232E-8/230 Multi 10 E 232E-HLM Time range (stepless) 1 – 7 min. in 15 sec. increments 0.5 – 20 min. stepless 0.5 – 20 min. stepless 0.5 – 20 min. stepless 0.5 – 20 min. stepless 20 – 60 sec. stepless Control voltage 230 V AC ■■■■■ Universal voltage in addition 8 … 240 V AC/DC 8…240 V AC/DC Glow lamp load 50 mA 150 mA 150 mA 150 mA 150 mA 3/4 conductor operated switches automatically automatically automatically automatically Steady-light switch ■■■■■ Advance warning acc. DIN 18015-2 ■■■ Long-time range of 60 min. ■■ Multi-functional device (10 functions) ■■ Rated voltage 230 V AC 240 V AC 240 V AC 240 V AC 240 V AC 240 V AC 50Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz Power loss 1 VA 6 VA 6 VA 6 VA 6 VA 6 VA Rated switching capacity 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC 16 A, 230 V AC 10 A, 230 V AC Filament lamp load 2,300 W 2,300 W 2,300 W 3,600 W 3,600 W 2,300 W Halogen lamp load 2,300 W 2,300 W 2,300 W 3,600 W 3,600 W 2,300 W Fluorescent lamps series compensated / uncorrected 2,300 VA 2,300 VA 2,300 VA 3,600 VA * 3,600 VA * not permitted Fluorescent lamps inductive or capacitive 2,300 VA 2,300 VA 2,300 VA 3,600 VA * 3,600 VA * not permitted Fluorescent lamps shunt compensated 1,300 VA (70 μF) 400 VA (42 μF) 400 VA (42 μF) 1,200 VA (120 μF) * 1,200 VA (120 μF) * not permitted Electronic controlgear 9x7 W, 6x11 W 9x7 W, 7x11 W, 9x7 W, 7x11 W, 34x7 W, 27x11 W, 34x7 W, 27x11 W, not permitted 5x15 W, 5x20 W 7x20 W, 7x23 W 7x20 W, 7x23 W 24x15 W, 22x23 W 24x15 W, 22x23 W Inductive load (cos ϕ = 0.6/230 V AC) 2,300 2,300 2,300 2,300 2,300 not permitted Contact material AgSnO2 AgSnO2 AgSnO2 AgSnO2 AgSnO2 AgSnO2 Contact gap ≥ 3 mm < 3 mm < 3 mm < 3 mm < 3 mm < 3 mm Mech. serviceable life > 106 > 107 > 107 > 107 > 107 > 107 Serviceable life at rated load, cos ϕ =1 > 105 > 2x105 > 2x105 > 2x105 >2x105 > 105 Serviceable life at rated load, cos ϕ =0.6 > 104 > 4x104 > 4x104 > 4x104 > 4x104 > 104 Terminal capacity 10.7 mm² 13 mm² 13 mm² 13 mm² 13 mm² 13.6 mm² Max. conductor capacity 6 mm² 4 mm² 4 mm² 4 mm² 4 mm² 6 mm² ON duration Resettable after 30 sec. 100 % 100 % 100 % 100 % 100% Ambient temperature – 10 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C – 25 °C to + 50 °C – 10 °C to + 50 °C Housing and insulation material heat resistant, self-extinguishing thermoplast heat resistant, self-extinguishing thermoplast heat resistant, self-extinguishing thermoplast heat resistant, self-extinguishing thermoplast heat resistant, self-extinguishing thermoplast heat resistant, self-extinguishing thermoplast Control current at 230 V AC 4.5 mA 26 mA 26 mA 26 mA (min. 8 mA at 8 V AC) 26 mA (min. 8 mA at 8 V AC) Minimum command duration 10 ms 20 ms 20 ms 20 ms / 50 ms for multi voltage input 20 ms / 50 ms for multi voltage input * no disconnection advance warning possible for this application.

pro M compact® Selection tables Command devices E 232 staircase lighting time-delay switches E 232 Time Power Order Bbn Price Price Weight Pack range loss details 4013614 1 piece group 1 piece unit W Type code Order code EAN kg pc. 1 … 7 m in. 1 V A E 232-230 2CDE 110 000 R0501 54824 3 0.081 10 20 min 6 V A E 232 E-230N 2CDE 110 003 R0511 65416 6 0.095 10 20 min 6 V A E 232 E-8/230N 2CDE 010 003 R0511 65417 3 0.11 0 20 min 6 V A E 232 E-230 Multi 10 2CDE 110 013 R0511 65418 0 0.095 10 20 min 6 V A E 232 E-8/230 Multi 10 2CDE 010 013 R0511 65419 7 0.11 0 20 … 60 sec. 6 V A E 232-HLM 2CDE 150 000 R0521 54828 1 0.075 10 SK176B02 2CDC051105F0201 Wiring diagrams E 232-230 3 conductor E 232E-8/230 Multi 10 3 conductor E 232E -230 Multi 10, 8/230 Multi 10 2CDC 052 030 F0007 E 232-230 4 conductor 2CDC 052 031 F0007 2CDC 052 034 F0007 E 232E-8/230 Multi 10 4 conductor 2CDC 052 035 F0007 2CDC052043F0207

E 232E-230 Multi 10 3 conductor 2CDC 052 032 F0007 System pro M compact® Selection tables Command devices E 232 staircase lighting time-delay switches E 232 2CDC 052 215 F0203 warning function of E 232E-8/230 Plustiming of a staircase lighting time-delay switch with semi-light module E 232-HLM 2CDC 052 214 F0203 Wiring diagrams DIN 18015-2 provides that "that the automatic disconnection of lighting equipment fitted in staircases of apartment buildings must provide for warning signals, e.g. dimming, in order to avoid sudden unexpected darkness". E 232 HLM 3 conductor E 232 HLM 4 conductor Staircase lighting time-delay switches E 232 HLM E 232E-230 Multi 10 4 conductor 2CDC 052 033 F0007 E 232E-8/230 Multi 10 3 conductor E 232E 8/230 3 conductor E 232E 230 Multi 10 3 conductor E 232E 230 N 3 conductor E 232-230 3 conductor 2CDC 052 037 F0007 E 232E-8/230 Multi 10 4 conductor E 232E 8/230 4 conductor E 232E 230 Multi 10 4 conductor E 232E 230 N 4 conductor E 232-230 4 conductor 2CDC 052 039 F0007

pro M compact® Selection tables Command devices TW twilight switches TW TW modular twilight switches They allow to switch on and switch off lighting devices according to a scheduled level of the ambient light. They are used in combination with a sensor to detect if the ambient light is higher or lower than the set level. TW2/10K, equipped with three different types of adjustment range (2:100, 2:1000, 2:10000), fits well the daylight applications where the Lux value is very high. This range, thanks to its features, fits all the applications (for example shop windows and lights) where the rationalization of the energy consumption is required. Brightness Order Bbn Price Price Weight Pack range details 8012542 1 piece group 1 piece unit lx Type code Order code EAN kg pc. 2 : 100 TW1 2CSM204135R1341 041351 0 .107 1 2 : 10.000 TW2/10K 2CSM204145R1341 041450 0 .215 1 Accessories for TW modular twilight switches The photosensor is supplied in the same package of the switch, but it’s also available separately as spare part. The upper part of the external case (with screw locking), made up of thermoplastic material, bears up against ultraviolet rays to guarantee an homogeneous diffusion of the daylight internally. The photosensor, wall mounted, is supplied with a cable gland. Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. LS-SP 2CSM204195R1341 041955 0 .035 1 Technical features TW1 TW2/10K Rated supply voltage [V] 230 AC Contact type 1NO 1CO Switching capacity resistive load [A] 16 inductive load cosϕ 0.6 [A] 3 incandescent lamps cos ϕ 1 max 960 W max 1080 W fluorescent lamps cos ϕ 0.8 max 720 W max 720 W fluorescent - duo./electronic lamps cos ϕ 0.9 max 200 W max 200 W Rated frequency [Hz] 50-60 Programs ON-OFF -- Switching delay ON [s] 8 ±10% 8 ±10% Brightness range [lx] 2:100 2:100 2:1,000 2:10,000 Accuracy -- Protection degree twilight switch IP20 IP20 sensor IP65 IP65 Operating temperature twilight switch [°C] 0…+55 0…+55 Power consumption [VA] 4.5 2.5 Max. commutable power [W] 3500 Terminal size for cable [mm²] 2.5 Terminals loss-proof screw Mounting on DIN rail Switching status indication/brightness range red Led / green Led Max wiring length [m] 100 Modules 12 Reference standards EN 60669-1 ; EN 60669-2-1 2CSC40071F00011CSC400095F02021CSC400096F0202

230 V~ L N TW1 230 V~ L N 35L N 2468 1 0 TW2/10K System pro M compact® Selection tables Command devices TW twilight switches TW Electrical connection and fixing of the sensor TW1 and TW2/10K operating principle Programmed threshold Red contact LED LuxLux ~10 sec~10 sec tt Green threshold LED OFF OFF OFF ON ON ON Cable retaining nut Cable holder seal Base with cable holder Terminals Sensor-holder card Cable Fixing bracket Fixing screw Seal on base Seal on screw Cover 1CSC400098F02021CSC400099F0202 1CSC400097F0202

pro M compact® Selection tables Command devices TWP pole mounting twilight switch TWP TWP pole mounting twilight switch The TWP pole twilight switch, equipped internally with a preset sensor of 10 Lux, is the ideal solution for the management of external light systems such as the public ones. The sensor is extractable from the base and allows an easy and efficient maintenance without needing further wiring. Brightness Order Bbn Price Price Weight Pack range details 4016779 1 piece group 1 piece unit lx Type code Order code EAN kg pc. 2 : 200 TWP 2CSM204165R1341 041658 0,155 1 Accessory for TWP pole mounting twilight switch The LS-65 sensor, supplied also individually as spare part, is equipped with internal connections Fast-On which are fast to extract. The sensor, with the upper part of the external case made up of thermoplastic material, bears up against ultraviolet rays to guarantee an homogeneous diffusion of the daylight internally. LS-65 2CSM204185R1341 041856 0,085 1 Technical features TWP Rated supply voltage [V] 230 AC Contact type 1NO polarized Switching capacity resistive load [A] 16 inductive load cosϕ 0.6 [A] 3 incandescent lamps cos ϕ 1 max 960 W fluorescent lamps cos ϕ 0.8 max 720 W fluorescent - duo./electronic lamps cos ϕ 0.9 max 200 W Rated frequency [Hz] 50-60 Switching delay ON [s] 25 ± 10% OFF [s] 25 ± 10% Brightness range [lx] 2:200 Protection degree IP65 Operating temperature [°C] -30…+60 Storage temperature [°C] -30…+65 Power consumption [VA] 7.5 Max. commutable power [W] 3500 Terminal size for cable [mm²] 2.5 Terminals screw Mounting pole Switching status indication/ brightness range - / red Led Reference standards EN 60669-1 ; EN 60669-2-1 2CSC400714F00011CSC400100F0202 1CSC400060F0202

pro M compact® Selection tables Command devices TWP pole mounting twilight switch TWP L N A 230 V~ L N L N B 230 V~ L N 1CSC400097F02021CSC400084F02021CSC400084F0202

pro M compact® Selection tables Command devices TWA twilight switches TWA TWA twilight astronomical switches They allow to control automatically the light systems according to the hour when the sun rises and sets. The programming is made defining the longitude and latitude parameters of the geographical area whe- re the switch is mounted. Thanks to its features the TWA fits applications such as public lighting system, shop windows, monuments, signs and so forth and particularly when the external sensor is subjected to strong external inconveniences like in area with high level of pollution or in area exposed to vandalic acts. Contacts Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc.

1 CO TWA-1 2CSM204365R1341 043652 0,160 1

2 CO TWA-2 2CSM204375R1341 043751 0,160 1

Rated supply voltage [V] 230 AC ± 15% Contact type 1CO 2 CO Switching capacity resistive load [A] 16 inductive load cosϕ 0.6 [A] 10 Max. number of lamps incandescent and halogen fluorescent [W] 2300 compensated (max. 45μF) [W] 400 non-compensated, series compensated[W] 1000 compact fluorescent [W] 500 Rated frequency [Hz] 50-60 Time base quartz Minimum time between two steps [min] 1 Program steps 56 Power reserve [years] 5 Accuracy ± 1,5sec / 24h Astronomical time accuracy [min] ± 10 Power consumption [VA] 6 Terminal size for cable 4 flexible [mm²] 1 to 6 rigid [mm²] 1.5 to 10 Terminals loss-proof screw Mounting on DIN rail Operating temperature [°C] -10…+55 Storage temperature [°C] -20…+60 Protection degree IP20 Modules 2 Reference standards NFC 15 100; IEC 60 634-1 Connection diagram 1 35 7 24 68 L N 2 channels L/+ N/- 1 35 7 24 68 1 channel TWA-1 TWA-2 2CSC400729F0001 1CSC400097F0202

6 Programming example

pro M compact® Selection tables Command devices TWA twilight switches TWA Keys menu : select ion of operating mode. auto : mode of running according to the program selected. prog : new for programming mode. prog : modif to modify an existing program. : check ing of the program. : modification of time, date and selection of the winter/summer timechange mode astro : astrono mical mode. : indicates that the channelis in astronomical mode. + and - : nav igation or setting of values. - (TWA-1) C1 , C2 (TWA-2) : in auto mode, selection of overrides, or waivers. enter : to val idate flashing information on display. : to return to the prev ious step. enter menu C2C1 enter menu 3 14 DT-VK TWA-2TWA-1 0354065709501021531051561 15 45 60 5010957 120 135 150 165 180 4545 0351 A R C T I C O C E A N N O R T H P A C I F I C O C E A N S O U T H P A C I F I C O C E A N S O U T H A T L A N T I C O C E A N I N D I A N O C E A N N O R T H P A C I F I C O C E A N N O R T H A T L A N T I C O C E A N Beaufort Sea A R C T I C O C E A N Greenland Sea East Siberian Sea Bering Sea Tasman Sea Great Australian Bight Arabian Sea Philippine Sea Lake Baikal Gulf of Mexico Caribbean Sea Labrador Sea Gulf of Guinea Mozambique Channel Mediterranean Sea Black Sea Barents Sea Norwegian Sea North Sea Denmark Strait Davis Strait Baffin Bay Hudson Bay Kara Sea Laptev Sea Sea of Okhotsk Sea Coral Bay of Bengal South China Sea Sea of Japan Persian Gulf Red Sea Aral Sea Caspian Sea Chukchi Sea UDT Lo La COLOMBIA BOLIVIA MOROCCO IRELAND NORWAY SWEDEN FINLAND POLANDGERMANY FRANCE BEL. EST. LAT. LITH. RUS. BULGARIA CZ. REP. SLO. HUNG. SLOV.. AUS. SWITZ BOS.& CYPRUS SYRIA LEB. IRAQ GEORGIA AZERBAIJAN ROMANIA UKRAINE BELARUS TURKEY ITALY PORTUGAL SPAIN UNITED ICELAND R U S S I A SAUDI LIBERIA SIERRA LEONE SRI BANGLADESH MONGOLIA JAPAN PHILIPPINES CAMBODIA NORTH KOREA UNITED ARAB EMIRATES BAHRAIN LANKA MALI TANZANIA KENYA MAURITANIA SENEGAL GUINEA-BISSAU GUINEA TOGO ARABIA EGYPT ZAMBIA SOUTH ANGOLA NAMIBIA GABON CENTRAL AFRICAN REPUBLIC EQUATORIAL GUINEA BENIN CÔTE D'IVOIRE GHANA SWAZILAND LESOTHO BURUNDI RWANDA NIGER THE GAMBIA CAPE VERDE NIGERIA SUDAN CHAD LIBYAALGERIA SOMALIA ETHIOPIA DJIBOUTI ERITREA SAO TOME AND PRINCIPE YEMEN CAMEROON AFRICA MOZAMBIQUE MADAGASCAR ZIMBABWE BOTSWANA UGANDA URUGUAY PARAGUAY GUYANA SURINAME PERU VENEZUELA ECUADOR HONDURAS CUBA BELIZE GUATEMALA PANAMACOSTA EL SALVADORL RICA NICARAGUA JAMAICA THE BAHAMAS HAITI REPUBLIC DOMINICAN SOUTH KOREA THAILAND LAOS M A L A Y S I A BURMA VIETNAM I N D O N E S I A BHUTANNEPAL I R A N AFGHANISTAN PAKISTAN TURKMENISTAN UZBEKISTAN KYRGYSTAN TAJIKISTAN ARMENIA OMAN JORDAN ISRAEL CRO. HER. ALB. GREECE MOLDOVA NETH. LUX. KINGDOM DENMARK U.S.. MEXICO K I R I B A T I PALAU EAST TIMOR FEDERATED STATES OF MICRONESIA MARSHALL SOLOMON ISLANDSPAPUA NEW GUINEA NEW ZEALAND NAURU TONGA ISLANDS TUVALU SAMOA VANUATU BRUNEI U.S. ARGENTINAA CHILE (DENMARK) Greenland (NORWAY) (PORT.) (SPAIN) Western Sahara (EQ. GUI.) SEYCHELLES (U.K.) (INDIA) (INDIA) MALDIVES British Ind ian Ocean Territory Cocos (Keel ing) Islands (AUSTL.) French Southern and Antarct ic Landsr (FRANCE) (SOUTH AFRICA) (AUSTL.) (FRANCE) F r e n c h P o l y n e s i a (CHILE) (CHILE) French Guiana (FRANCE) (FRANCE) Jan Mayen (NORWAY) MALTA MAURITIUS COMOROS (AUST.) Pitcairn Islands (U.K) Falkland Islands (Islas Malv inas) South Georg ia and the South Sandw ich Islands (administered by U .K. claimed by ARGENTINA) (YEMEN) Svalbard U.S. C A N A D A B R A Z I L U N I T E D S T A T E S C H I N A I N D I A A U S T R A L I A Macau S.A.R TUNISIA (N.Z.) SINGAPORE St. Pierre and Miquelon (AUSTL.) New FIJI (FRANCE) Caledon ia Coral Sea Islands Bermuda (U.K.) (administered by U .K. claimed by ARGENTINA) occup ied by the SOVIET UNION in 1945 administered by RUSSIA, cla imed by JAPAN Northern Mariana Islands (U.S.) (U.S.) Guam Cook Islands (N.Z.) (N.Z.) Reunion (FRANCE) (ECUADOR) BURKINA FASO MALAWI QATAR KUWAIT SER. & MONT. (St. Helena) (St . Helena) (St. Helena) (Fr . S and Ant . Lands) (Fr . S and Ant . Lands) (French Polynesia) (INDIA) K I R I B A T I (N.Z.) Tokelau Johnston Atoll (U.S.) REP. OF THE CONGO DEM. REP. OF THE CONGO Hong Kong S.A.R. KAZAKHSTAN (U.K.) (St. Helena) St. Helena (PORT.)T (JAPAN) São Paulo Los Angeles Chicago New York Québec Mumbai (Bombay) Edmonton Winnipeg St. Petersburg Omsk Yakutsk Petropavlovsk- Kamchatskiy Vladivostok Sydney Perth Moscow London Tokyo Manila Istanbul. Manaus Kinshasa Toronto Samara Izhevsk Alice Springs Qaanaaq (Thule) Nuuk (Godthåb) Itseqqortoomiit (Scoresbysund) (Frobisher Bay) Iqaluit Kisangani Kolkata (Calcutta) Anchorage Dawson Denver Dallas Brasilia Magadan Perm' Novosibirsk Astana Lima Buenos Aires Mexico Paris Rome Lagos Nairobi Cairo Shanghai Beijing Tehran Casablanca AZORES ISLANDS LAKSHADWEEP ANDAMAN NICOBAR ISLANDS ISLANDS PRINCE EDWARD ISLANDS ARCHIPIÉLAGO JUAN FERNÁNDEZ Newfoundland Island of LAND FRANZ JOSEF NOVAYA ZEMLYA SEVERNAYA ZEMLYA NEW SIBERIAN ISLANDS Wrangel Island Gough Island Lord Howe Island Easter Island ILES MARQUISES Socotra WEST EAST add 24 hours subtract 24 hours + 9 1/2 + 31/2 + 41/2 + 5 1/2 + 6 1/2 + 51/2 + 61/2 + 101/2 11 1/2 Norffolk Island 0 500 1000 K ilometers 0 500 1000 M iles Annobon Eastward across Date Line Westward across Date Line - 31/2 -9 1/2 ILES CROZET Subtract time zone number from UDT to obtain local time. CHATHAM ISLANDS +12 3/4 - 11 - 10 - 9 - 8 - 7 - 6 - 5 - 4 - 3 - 2 - 1 0 +1 5 +4 +2 + + 6 + 7 + 8 + 9 + 10 + 11 + 12 - 12 - 11+ 3 LINE ISLANDS HAWAIIN ISLANDS + 53/4 RYUKYU IS LA N D S Miller Cylindrical Projection Scale 1:85,000,000 at 0o ISLANDS KERMADEC ILES KERGUELEN ALEUTI AN I SLANDS Tasmania Sakhalin GALAPAGOS ISLANDS - 9 - 8 - 7 - 6 - 5 + 11 + 10 + 12 + 9+ 8 + 5 + 5 + 6 + 5 + 2 +1 + 3 + 4+ 3 - 1 - 1 + 8 + 7+ 5 + 3 + 3 + 11 + 10 + 10 + 12+ 9 - 3 - 4 - 4 - 5 - 5 - 4 - 6 - 6 - 7 - 10 - 3 - 10 - 9 + 4 -11 KIRIBATI (GILBERT ISLANDS) RAWAKI (PHOENIX ISLANDS) - 10 -10 -10 + 6 -12 - 12 Add time zone number to UDT yo obtain local time Ascension TRISTAN DA CUNHA CANARY ISLANDS MADEIRA St. Helena KURIL ISLANDS International Date Line International Date Line Repulse Bay TRINIDAD AND TOBAGO SOUTH NORTH Universal DayTime (UDT) T = Latitude 45o North Longitude Latitude North 180o 90o 90o South T = Longitude 60o East North South Equator T WEST T SOUTH NORTH EASTG reenw ich m eridian Longitude Latitude Universal Date Time = +1 hour + 1 Lo La UDT Ex: Rome 12° EAST 41° NORTH 1CSC400102F02021CSC400103F0202

pro M compact® Selection tables Command devices THS modular thermostats THS modular thermostats The THS series modular thermostats are suited for a wide array of refrigeration and heating ap- plications. The THS-C and THS-W models, both with a potential-free switching contact, are ideal for controlling temperature in heating systems, industrial settings or difficult-to-access locations, as well as for temperature regulation in refrigeration systems, refrigerated counters, greenhouses, dryers, etc.... The THS-S model, with two independent potential-free contacts, allows regulation of cooling between +20 and +60 °C and anti-condensation between 0 and +10 °C. The THS-S thermostat is supplied with remote sensor and is ideal for temperature control of electrical cabinets. Temperature Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit °C Type code Order code EAN kg pc. -20…+40 THS-C 2CSM251163R1380 511632 0 .20 1 0…+60 THS-W 2CSM207083R1380 070832 0 .20 1 *+20…+60 / 0…+10 THS-S 2CSM236803R1380 368038 0 .17 1 * cooling / anticondensation Temperature sensors for THS-C and THS-W thermostats The remote sensors (supplied separately) are used in conjunction with the THS-C and THS-W series thermostats to detect temperature overshoot or undershoot from the programmed setpoint. The THS-1 and THS-4 models work in a temperature range between -30 °C and +130 °C and are respectively 1.5 and 4 metres long. Length Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit m Type code Order code EAN kg pc. 1.5 THS-1 2CSM202033R1380 020332 0 .05 1 4 THS-4 2CSM277603R1380 776031 0 .12 1 Technical features THS-C THS-W THS-S Rated voltage [V] 230 AC Type of contact 1 change-over 2NO Contact capacity ohmic load [A] 16 inductive load cosϕ 0.6 [A] 3 Frequency [Hz] 50-60 Number of temperature setpoints 1 continuously adjustable 2 continuously adjustable Max switching power [W] 3500 Differential [°C] fixed Δt = 1 fixed Δt = 2 Thermal gradient 1 °K / 15 minutes Type of operation ON / OFF fixed differential Max cable section at terminals [mm2] 2.5 Protection degree IP20 Relay ON/OFF indication LED indicator Temperature tolerance [°C] ±1 T limits in operation [°C] 0 ÷ +50 0 ÷ +70 Type of installation DIN rail Case / color thermoplastic / grey RAL 7035 Power consumption [VA] 3 Application type services / industrial Programming graduated scale with mechanical pointer 2CSC400718F0001 2CSC400719F0001

pro M compact® Selection tables Command devices THS modular thermostats 230 V~ L N 35LN 2468 1 0 L 230 V~ L N 35LN 2468 1 0 230 V~ L N 35L N 24 68 1 0 Heating Cooling Yellow LED: “Sensor short-circuit indication” green LED: “Load state indication” Temperature regulation knob (scale differs depending on the model) THS-C, THS-W THS-S THS-C, THS-W THS-S Green LED: cooling load state indication Green LED: heating load state indication Cooling temperature setpoint knob Adjustment range: +20°C to +60°C Heating temperature setpoint knob Adjustment range: 0°C to +10°C 1CSC400105F02021CSC400106F0202

pro M compact® Selection tables Command devices THS modular thermostats Mode of operation Mode of operation Time Δt = 1°C Load ON OFF ON Panel temp. Time Δt = 2 °C Cooling ON ON Δt = 2 °C Heating ON ON Set: tMax Set: tMin As shown in the figure, the THS-S switches on: - The fan or air conditioner when the temperature in the panel exceeds the maximum setpoint pro- grammed with the upper knob. - The heating device when the panel temperature falls below the minimum setpoint programmed with the lower know Sensor installation The remote temperature sensor is waterproof and able to withstand temperatures in the range from -30°C to +85°C; it has a maximum connection length of 100m. When the THS-C detects a temperature below the programmed setpoint, it closes contact 1 until the temperature returns above the setpoint. It then reo- pens the contact, and when the temperature again drops below the differential, the cycle is repeated. THS-W operates in a similar manner, but the relay closes contact 5 when the temperature exceeds the programmed setpoint. Sensor installation The THS-1 and THS-4 remote temperature sensors (supplied separately) are waterproof and encap- sulated in silicone rubber. They have an operating temperature range between -30°C and +130°C and are respectively 1.5 and 4 meters long. 1CSC400107F02021CSC400107F0202

pro M compact® Selection tables Command devices ATT GSM modules ATT GSM modules The ATT modules are GSM telephone actuators for remotely controlling electrical loads over the mobile phone network, which answer the installation requirements of a variety of application settings. In particular, the ATT-22 version consists of a control module with 2 outputs and 2 inputs for resi- dential, services-sector and industrial installations, while the ATT-81 alarm module, with 8 inputs and one output, is suitable for status and alarm monitoring in industrial and services-sector installations. Instructions and alarms can be sent via SMS message, free phone call ring, fax or e-mail according to need. Configuration can be accomplished by SMS messages or using the ATT-Tool software. All the ATT modules are supplied with backup lithium battery, ATT-Tool programming software and PC connecting cable. In addition, the ATT-22E and ATT-81E models are equipped with a pre-wired external antenna – essential if the module is installed in locations that do not assure adequate GSM coverage, such as cellars, enclosed metal structures, etc. The modules can be supplied with an ABB type TS 25/12-24 C modular transformer and are com- patible with the GSM SIM cards of all mobile telephone operators. Inputs Outputs Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 2 analog or digital 2 NO ATT-22 2CSM322000R1371 944904 0 .200 1 8 digital 1 NO ATT-81 2CSM381000R1371 945000 0 .200 1 2 analog or digital 2 NO ATT-22E 2CSM208345R1371 083450 0 .200 1 8 digital 1 NO ATT-81E 2CSM208355R1371 083559 0 .200 1 Technical characteristics GSM module Dual band EGSM900 and GSM1800 for data, sms, fax and voice applications. Full Type Approved conforming to ETSI GSM Phase 2+ Output power Class 4 (2 W@900 MHz ) Class 1 (1 W@1800 MHz ) Commands sent by SMS, call rings, DTMF tones, GPRS connection Incoming alarms SMS, call rings, e-mail, fax Inputs digital self-powered max. 20 V d.c., 2 mA analog (only ATT-22) input voltage 0...10 V input impedance < 10 Kohm / 100 nF sampling rate 90 Ksps Outputs relay NO 4 A 250 V a.c. - max 2500 VA minimum load 100 mA, 12 V GSM indicator LED OFF device not supplied STEADY ON device under power not connected to mobile network, SIM pin code missing or incorrect SLOW BLINK device under power, connected to mobile network FAST BLINK communication in progress Power supply [V] 12 ±10% a.c. /d.c. Power consumption when transmitting [W] 2.5 in stand-by [W] 0.4 Terminal section 2.5 mm Temperature ambient [°C] -20...55 storage [°C] -30...85 Relative humidity ambient 5...95% non condensing storage 5...95% only external condensation Modules 4 Protection degree IP40 2CSC400731F0001 1CSC400108F0202

A: Power supply input 2x2.5 mm2 (AWG14) B: Input and output terminals 14x2.5 mm2 (AWG14) C: Red LED, input status indicator D: Green LED, output status indicator X: External antenna (type ATT22-E) RG174 + FME male jack S: GSM indicator LED A: Power supply input 2x2.5 mm2(AWG14) B: Input and output terminals 14x2.5 mm2 (AWG14) C: Red LED, input status indicator D: Green LED, output status indicator X: External antenna (type ATT-81E) RG174 + FME male jack S: GSM indicator LED ATTSystem pro M compact® Selection tables Command devices ATT GSM modules 1CSC400109F0202

CL range logic relays are suitable for small and medium-sized control tasks and are able to substitute logic wiring in a quick and simple manner. They can be used for applications in control as well as for timing functions, e. g. - in buildings, lighting systems, air-conditioning systems, general control functions, - in small machines and systems or - as stand-alone control module for small applications. Steps to the application of CL range - CL range can be used easily, rapidly and comfortably without any time-consuming planning and programming. - The user can discover the advantages and the benefit of these logic relays in no time at all. - CL range provides for the control statements according to a simple circuit diagram. - Setup, storage, simulation and documentation are performed using the compact and user-friendly CL-SOFT software (CL-LAS.PS002). Software characteristics (CL-SOFT) - display on a PC monitor according to IEC, ANSI - up to 10 languages to choose from - easy installation on all Microsoft Windows TM operating systems Further Documentation (download from the internet: www.abb.com/lowvoltage - Control Products - Electronic Relays and Controls) Technical catalogue Electronic Products and Relays 2CDC 110 004 C0205 Manuals Logic relay manual 1SVC 440 795 M0100 Remote display manual 1SVC 440 795 M2100 Display system manual 1SVC 440 795 M1100 1SVC 110 000 F 0554 S1 K1 S4 K1 K2 T1 Logic links instead of wiring Technical Data overview Logic relays - 8 or 12 digital inputs - 4 or 6 digital relay outputs - optionally with 4 or 8 transistor outputs - 128 rungs - 3 contacts as n/o or n/c contacts in series plus 1 coil per rung - optionally with 2 or 4 analog inputs (not 100-240 V AC version) - power flow display for checking the circuit diagram (devices with display) - expansions for local or remote level - enclosure color RAL 7035 - DIN rail mounting Display system - useable as compact HMI logic relay - fully graphic, backlit display module - 12 digital inputs - 4 digital relay outputs - optionally with 4 transistor outputs - 265 rungs - 4 contacts as n/o or n/c contacts in series plus 1 coil per rung - optionally with 4 analog inputs (not 100-240 V AC version) - networking-compatible via CL-NET - front panel mounting - expansion for local Remote display - Remote display up to a distance of 5 m - Illustration of text and status displays - Remote adjustment via keypad - Front panel mounting Software - 16 timing relays 0.01-99:59 h - 16 counting relays for up-, down counting - 8 weekly timer, 8 annual timers - 16 analog value comparators - 16 freely editable text display - 32 markers or auxiliary relays System pro M compact® Selection tables Command devices Logic relays, display system CL 2CDC315039F0b06

Stand alone with I/O module Display system Compact HMI logic relay Expansion of logic relays Logic relays ... 4 4 CL-NET 2CDC 312 025 F0b06 2CDC 312 027 F0b06 Power 6, 8b 71b1a 6, 8b 2CDC 312 036 F0b07 2CDC 312 037 F0b07 1a Logic relay CL-LS.. 1b Logic relay CL-LM.. 2 Power supply CL-LAS.SD00... 4 Coupler unit CL-LEC.. for remote expansion of logic relays CL-LM.. 5 Memory module CL-LAS.MD003 for logic relays CL-LS.., CL-LM.. 6 Connecting cable CL-LAS.TK001, CL-LAS.TK002 to connect PC 7 CL-LINK plug CL-LAS.TK011 to connect expansion to logic relays CL-LM.. 8a Remote display connection module CL-LDC.S.. 8b Connecting cable CL-LAD.TK007 to connect a remote displays to a logic relay 9 Display module CL-LDD.. System overview 1 Logic relay CL-LM.. 2 I/O expansion CL-LER.., CL-LET.. 2a local expansion 2b remote expansion 3 Coupler unit CL-LEC.. for remote expansion of logic relays CL-LM.. 4 CL-LINK plug CL-LAS.TK011for expansion of logic relays CL-LM.. 5 up to 30 m 1 Display module CL-LDD.. 2 Display base module CL-LDC.LN.. 3 Display I/O module CL-LDR.., CL-LDT.. 4 Termination resistor CL-LAD.TK009 5 I/O expansion CL-LER.., CL-LET.. 6 Coupler unit CL-LEC.. for remote expansion 7 Memory module CL-LAD.MD004 for display base module 8 Connecting cable CL-LAD.TK002, CL-LAD.TK003, CL-LAD.TK004 9 Connecting cable CL-LAD.TK001, CL-LAD.TK011 to connect PC 10 CL-LINK plug CL-LAS.TK011 for expansion of logic relays CL-LM.. ■ e.g. door of switchgear cabinet 1 Display CL-LDD..

2 Remote display connection module

CL-LDC.S.. incl. connecting cable 3 Display base module CL-LDC.L.. Communication via CL-NET 1 Display CL-LDD.. 2 Display base module CL-LDC.LN.. for CL-NET 3 Display I/O module CL-LDR.., CL-LDT.. 4 Connecting cable CL-LAD.TK002, CL-LAD.TK003, CL-LAD.TK004 5 Termination resistor CL-LAD.TK009 ... 5 5 CL-NET 2CDC 312 026 F0b06 System pro M compact® Selection tables Command devices Logic relays, display system CL

Rated Pack. Price Weight operational unit 1 piece 1 piece Type voltage Order code pieces kg/lb Logic relays – 8 inputs, 4 relay outputs CL-LSR.C12AC1 24 V AC • • 1SVR 440 712 R0300 1 0.20/0.44 CL-LSR.CX12AC1 24 V AC • 1SVR 440 712 R0200 1 0.20/0.44 CL-LSR.12AC2 100-240 V AC • 1SVR 440 713 R0100 1 0.20/0.44 CL-LSR.C12AC2 100-240 V AC • • 1SVR 440 713 R0300 1 0.20/0.44 CL-LSR.CX12AC2 100-240 V AC • 1SVR 440 713 R0200 1 0.20/0.44 CL-LSR.C12DC1 12 V DC • • 1SVR 440 710 R0300 1 0.20/0.44 CL-LSR.CX12DC1 12 V DC • 1SVR 440 710 R0200 1 0.20/0.44 CL-LSR.12DC2 24 V DC • 1SVR 440 711 R0100 1 0.20/0.44 CL-LSR.C12DC2 24 V DC • • 1SVR 440 711 R0300 1 0.20/0.44 CL-LSR.CX12DC2 24 V DC • 1SVR 440 711 R0200 1 0.20/0.44 Logic relays – 8 inputs, 4 transistor outputs CL-LST.C12DC2 24 V DC • • 1SVR 440 711 R1300 1 0.20/0.44 CL-LST.CX12DC2 24 V DC • 1SVR 440 711 R1200 1 0.20/0.44 Logic relays – 12 inputs, 6 relay outputs CL-LMR.C18AC1 24 V AC • • • 1SVR 440 722 R0300 1 0.36/0.79 CL-LMR.CX18AC1 24 V AC • • 1SVR 440 722 R0200 1 0.36/0.79 CL-LMR.C18AC2 100-240 V AC • • • 1SVR 440 723 R0300 1 0.36/0.79 CL-LMR.CX18AC2 100-240 V AC • • 1SVR 440 723 R0200 1 0.36/0.79 CL-LMR.C18DC1 12 V DC • • • 1SVR 440 720 R0300 1 0.36/0.79 CL-LMR.CX18DC1 12 V DC • • 1SVR 440 720 R0200 1 0.36/0.79 CL-LMR.C18DC2 24 V DC • • • 1SVR 440 721 R0300 1 0.36/0.79 CL-LMR.CX18DC2 24 V DC • • 1SVR 440 721 R0200 1 0.36/0.79 Logic relays – 12 inputs, 8 transistor outputs CL-LMT.C20DC2 24 V DC • • • 1SVR 440 721 R1300 1 0.36/0.79 CL-LMT.CX20DC2 24 V DC • • 1SVR 440 721 R1200 1 0.36/0.79 Display + Keypad Timer Expandable Rated Pack. Price Weight operational unit 1 piece 1 piece Type voltage Order code pieces kg/lb Expansion – 2 relays outputs CL-LER.2O - 1SVR 440 709 R5000 1 0.07/0.15 Expansions – 12 inputs, 6 relay outputs CL-LER.18AC2 100-240 V AC 1SVR 440 723 R0000 1 0.26/0.57 CL-LER.18DC2 24 V DC 1SVR 440 721 R0000 1 0.22/0.49 Expansion - 12 inputs, 8 transistor outputs CL-LET.20DC2 24 V DC 1SVR 440 721 R1000 1 0.21/0.46 Coupler unit for remote expansion with a distance of up to 30 m CL-LEC.CI000 - 1SVR 440 709 R0000 1 0.07/0.15 CL-LSR CL-LMR CL-LST CL-LMT CL-LER CL-LEC System pro M compact® Selection tables Command devices Logic relays CL 2CDC311034F0b062CDC311033F0b062CDC311036F0b062CDC311035F0b062CDC311037F0b062CDC311038F0b06

Pack. Price Weight unit 1 piece 1 piece Type Description Order code pieces kg/lb Software CL-SOFT for programming and control of CL range devices CL-LAS.PS002 Installation CD-ROM 1SVR 440 799 R8000 1 0.10/0.21 for Microsoft Windows TM Memory module for logic relays CL-LAS.MD003 Memory size: 32 kB 1SVR 440 799 R7000 1 0.02/0.04 Connecting cable with serial interface to connect PC and logic relay CL-LAS.TK001 Length: 2 m 1SVR 440 799 R6000 1 0.10/0.22 Connecting cable with USB interface to connect PC and logic relay CL-LAS.TK002 Length: 1SVR 440 799 R6100 1 Connecting cable for point-to-point connection of remote-display connection module and logic relay CL-LAD.TK007 Length: 5 m, adaptable 1SVR 440 899 R6600 1 0.20/0.44 Fixing brackets for screw mounting of logic relay, expansion, display base module CL-LAS.FD001 content: 9 fixing brackets 1SVR 440 799 R5000 1 0.01/0.01 Connecting plug CL-LINK for connection of logic relay to expansion CL-LAS.TK011 CL-LINK 1SVR 440 799 R5100 1 0.10/0.22 CL-LAS.PS002 CL-LAS.MD003 CL-LAS.TK001 CL-LAS.TK011 System pro M compact® Selection tables Command devices Accessories for logic relays CL Pack. Price Weight Rated input Rated output unit 1 piece 1 piece Type voltage voltage/current Order code pieces kg/lb Input-/ output simulator with wall power supply, fits to CL-LSR and CL-LST CL-LAS.TD001 100-240 V AC 24 V DC 1SVR 440 793 R0000 1 0.19/0.43 Primary switch mode power supplies CL-LAS.SD001 100-240 V AC 24 V DC / 0.35 A 1SVR 440 703 R0000 1 0.10/0.22

12 V DC / 20 mA

CL-LAS.SD002 100-240 V AC 24 V DC / 1.25 A 1SVR 440 713 R0000 1 0.20/0.44 Pack. Price Weight unit 1 piece 1 piece Type Rated operational voltage Order code pieces kg/lb Graphic display modules 132 x 64 pixel CL-LDD.XK without keyboard 1SVR 440 839 R4500 1 0.14/0.30 CL-LDD.K with keyboard 1SVR 440 839 R4400 1 0.13/0.29 Remote display connection modules to displace the display from the logic relay, incl. connecting cable CL-LAD.TK007, 5 m, length adaptable CL-LDC.SDC2 24 V DC 1SVR 440 841 R0000 1 0.16/0.36 CL-LDC.SAC2 100-240 V AC 1SVR 440 843 R0000 1 0.16/0.36 CL-LAS.SD.. CL-LDC.S.. 2CDC311012F0b072CDC311013F0b072CDC311014F0b072CDC311031F0b072CDC311016F0b072CDC311017F0b07

Pack. Price Weight unit 1 piece 1 piece Type Rated operational voltage Order code pieces kg/lb Grafic Display modules 132 x 64 pixel CL-LDD.XK without keyboard 1SVR 440 839 R4500 1 0.14/0.30 CL-LDD.K with keyboard 1SVR 440 839 R4400 1 0.13/0.29 Display base modules - CPU / power supply CL-LDC.LDC2 24 V DC 1SVR 440 821 R0000 1 0.16/0.36 CL-LDC.LAC2 100-240 V AC 1SVR 440 823 R0000 1 0.16/0.36 Display base modules - CPU / power supply, networking-compatible (CL-NET) CL-LDC.LNDC2 24 V DC 1SVR 440 821 R1000 1 0.17/0.38 CL-LDC.LNAC2 100-240 V AC 1SVR 440 823 R1000 1 0.17/0.38 Display I/O modules - 8 inputs, 4 relay outputs CL-LDR.16AC2 100-240 V AC 1SVR 440 853 R0000 1 0.17/0.38 CL-LDR.16DC2 24 V DC 1SVR 440 851 R0000 1 0.17/0.38 Display I/O modules - 8 inputs, 4 relay outputs, 1 analog output CL-LDR.17DC2 24 V DC 1SVR 440 851 R2000 1 0.17/0.38 Display I/O module - 8 inputs, 4 transistor outputs CL-LDT.16DC2 24 V DC 1SVR 440 851 R1000 1 0.14/0.30 Display I/O module - 8 inputs, 4 transistor outputs, 1 analog output CL-LDT.17DC2 24 V DC 1SVR 440 851 R3000 1 0.14/0.30 CL-LDD.K CL-LDC.LN.. CL-LDR System pro M compact® Selection tables Command devices Display system CL 2CDC311028F0b062CDC311031F0b062CDC311032F0b06

Pack. Price Weight unit 1 piece 1 piece Type Description Order code pieces kg/lb Memory module for display base modules CL-LAD.MD004 Memory size: 256 kB 1SVR 440 899 R7000 1 0.02/0.03 Connecting cable with serial interface to connect PC and display base module CL-LAD.TK001 Length: 2 m 1SVR 440 899 R6000 1 0.11/0.23 Connecting cable with USB interface to connect PC and display base module CL-LAD.TK011 Length: 1SVR 440 899 R6700 1 Network cable (CL-NET) to connect 2 display base modules CL-LAD.TK002 Length: 0.3 m 1SVR 440 899 R6100 1 0.05/0.12 CL-LAD.TK003 Length: 0.8 m 1SVR 440 899 R6200 1 0.07/0.14 CL-LAD.TK004 Length: 1.5 m 1SVR 440 899 R6300 1 0.08/0.18 Connecting cable for point-to-point connection of remote display connection modules and display base module CL-LAD.TK005 Length: 5 m, adaptable 1SVR 440 899 R6400 1 0.20/0.44 Connecting cable for point-to-point connection of 2 display base modules, length adaptable CL-LAD.TK006 Length: 5 m 1SVR 440 899 R6500 1 0.12/0.26 Termination resistor CL-LAD.TK009 content: 2 pieces 1SVR 440 899 R6900 1 0.01/0.02 Protective covers, transparent CL-LAD.FD001 for harsh environmental 1SVR 440 899 R1000 1 0.03/0.07 conditions and application in the food industry CL-LAD.FD011 sealable 1SVR 440 899 R2000 1 0.03/0.07 Assembly tool for mounting of display modules CL-LAD.FD002 - 1SVR 440 899 R3000 1 CL-LAD.MD004 CL-LAD.TK009 System pro M compact® Selection tables Command devices Accessories for display system CL 2CDC311018F0b072CDC311021F0b07

category react automatically to variations of parameters and other events in the system to allow plant optimization. - E 450 priority switches: the priority switch disconnects the long-term load as long as the short-term consumer is switched on. - RAL overload relays: they monitor the power consumption in the system and signals if the threshold value is reached - LSS1/2 load shedding switch: it switches off a maximum of two non- prioritary loads when the preset threshold of power consumption is exceeded - SQZ3 phase and sequence relay: it performs the continue monitoring in three-phases networks for the phase sequence, phase failure, minimum voltage. - E 236 undervoltage monitoring relays control the three-phase undervoltage (each phase to neutral) of switchgear.

pro M compact® Selection tables Load management devices E 450 priority switches E 450 E 450 priority switches The priority switch is used in wiring systems where existing lead cross sections or the size of the power supply service box do not allow for simultaneous operation of two powerful loads (e.g. storage heating and flow-type heater). The priority switch disconnects the long-term load (storage heating) for as long as the short-term consumer (flow-type heater) is switched on. The coil of the priority switch is connected in series to the short-term load. When this load is switched on, the NC contact of the priority switch disconnects e.g. the heating system contactor. Rated Power Order Bbn Price Price Weight Pack current loss details 4016779 1 piece group 1 piece unit range W Type code Order code EAN kg pc. For pneumatically controlled flow-type heaters For electronically controlled flow-type heaters SK 0078 Z 00 SK 0086 B 97 2CSC400457F0201

Technical characteristics E 451-5.7 E 452-5.7 Operating coil Range of rated current 6.7 … 39 A equivalent to 1.5 … 9 kW at 230 V, 4.6 … 27 kW at 230/400 V Threshold current 3.1 … 5.3 A OFF delay (max.) 0 main half waves 2 main half waves Max. continuous current 43 A Therm. continuous capacity at 40 °C/104 °F 5 W Contact assembly Control contact 1 NC contact Rated contact current at 250 V 1 A Contact material solid silver Max. switching voltage 400 V Max. switching capacity 230 VA Max. switched current 1 A Max. inrush current peak 5 A Electr. service life > 10 5 operations Mechanical service life ca. 2 x 10 6 operations Max. electrical switching rate ca. 1800 operations/hour ON duration 100 % Ambient temperature – 20 °C/– 4 °F to + 40 °C/104 °F Response time 10 … 20 ms Release time 5 … 20 ms ≥ 20 ms Test voltage contact/coil 2.5 kV Clearance and creepage distance C/250 V AC cording to IEC 669-1-23 Degree of protection IP 40 Protection against electric shock according to DIN VDE 0106 Part 100 (BGV A2) Terminal contact series coil up to 16 mm 2, control contact up to 2.5 mm2 System pro M compact® Selection tables Load management devices E 450 priority switches E 450

pro M compact® Selection tables Load management devices RAL overload relays RAL RAL overload relays Installed downstream of the main circuit-breaker in a single-phase system, they constantly compare the actual power consumption to the preset threshold. An acoustic alarm alerts that some applian- ces must be switched off to avoid tripping the main circuit-breaker whenever the preset threshold is exceeded. The device calibration is 3 kW. RAL built in relay output contact allows the following functions to be implemented: a) remote signalling (acoustic or lighting) b) opening a divisional circuit-breaker to disable a non essential electrical appliance. Function b) allows one or more appliances to be automatically switched off in order to keep the power consumption within the preset limit and avoid unwanted tripping of the current-limiting device installed outside the home (e.g. in the basement). RAL must be reset manually. Adjustable Order Bbn Price Price Weight Pack range details 8012542 1 piece group 1 piece unit kW Type code Order code EAN kg pc. 0/3 RAL 3 2CSM111200R1301 400509 0.200 1 0/6 RAL 6 2CSM121200R1301 400608 0.200 1 Technical characteristics RAL3 RAL6 Rated voltage Un [V] a.c. 230 Rated current In [A] 18.3 27.5 Rated contact capacity In [A] 12 cos ϕ=1; 4 cosϕ=0.8 Rated frequency [Hz] 50 Power consumption [W] 10 Modules [No.] 2 Intervention delay instantaneous 2CSC400510F0201

230 V~ RAL overload relay cannot be connected to a contactor. Main circuit breaker Shunt trip (230 V a.c.) in case of circuit-breaker tripping Dedicated socket Lights RAL L N 230 V a.c. OEPM0052 OEPM0051 Acoustic warning Load release System pro M compact® Selection tables Load management devices RAL overload relays RAL

pro M compact® Selection tables Load management devices LSS1/2 load shedding switch LSS1/2 Technical characteristics Rated voltage Un [V] a.c. 230 Rated capacity In [A] 90 Rated contact capacity In [A] 16 each NPL1 and NPL2 (terminals 12 and 14) Rated frequency [Hz] 50/60 Regulating thresholds [A] 5...30 10...60 15...90 Load reinsertion delay 5-7 min. (NPL1); 4-5, 50 min. (NPL2) Load disinsertion delay about 2 sec. Indicators 1 green LED = supply voltage available 2 red LEDs = loads switched off Load OFF remote signalling [A] 1 (terminals 11 and 13) Terminals Primary load 35 mm Non prioritary loads 10 mm 2 Power consumption [W] 5 Modules [No.] 5 LSS1/2 load shedding switch Installed downstream of the main circuit-breaker, it compares the actual power consum- ption of the system to a preset maximum permitted value, and prevents tripping of the main circuit-breaker by sequentially switching off a maximum of two non-prioritary loads (NPL1 and NPL2) when the preset threshold is exceeded. A green LED indicates the pre- sence of the supply voltage, and two red LEDs indicate the load OFF conditions. At preset time intervals, the device automatically attempts to reconnect the previously disabled loads. Note: In unbalanced threephase systems same function of LSS1/2 can be implemented via DMTME multimeters. Digital outputs of the multimeter can be set to trip with an user defined delay to switch off - by means of external contactors - non prioritary loads of arbitrary consumption. See for details page 10/142. Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. LSS1/2 2CSM112500R1311 274407 0.400 1 2CSC400511F0201 - The device must be inserted into the network downstream of the main circuit breaker - PL= Primary Load - NPL= Non Prioritary Load

NL 230V~ PL NPL1 NPL2 Auxiliary remote signalling Auxiliary forced NPL1 and NPL2 switch off Single-phase wiring diagram 1 3 5 7 9 11 13 15 2 4 6 8 10 12 14 16 PL TA/5A 380 V NPL1 NPL2 Le2Le1E 220 V Balanced three-phase wiring diagram System pro M compact® Selection tables Load management devices LSS1/2 load shedding switch LSS1/2 OEPM0150 /MT76/MT79/MT65/MT68 /MT49 /MT32 /MT51 /MT53 /MT32/MT55 /MT32/MT57/MT49 /MT49 /MT32 /MT49 /MT51 /MT32 /MT49 /MT53 /MT50 /MT32 /MT52 /MT54/MT32 /MT56 /MT49/MT48/MT32 /MT49/MT50/MT32 /MT49/MT52/MT32 /MT49/MT54 /MT78/MT76/MT50/MT51/MT48/MT32/MT86/MT126 /MT80/MT76 /MT78/MT80/MT76/MT50 /MT65/MT117/MT120/MT105/MT108/MT105/MT97/MT114/MT121 /MT114/MT101/MT109/MT111/MT116/MT101 /MT115/MT105/MT103/MT110/MT97/MT108/MT108/MT105/MT110/MT103 /MT65/MT117/MT120/MT105/MT108/MT105/MT97/MT114/MT121 /MT102/MT111/MT114/MT99/MT101/MT100/MT32/MT78/MT80/MT76/MT49 /MT97/MT110/MT100/MT32/MT78/MT80/MT76/MT50 /MT115/MT119/MT105/MT116/MT99/MT104/MT32/MT111/MT102/MT102 /MT78/MT80/MT76/MT49 Single-phase wiring diagram for non prioritary loads with 16 A or more current consumption

pro M compact® Selection tables Load management devices E 235 mains disconnection relays E 235 Technical features Short circuit rupturing capacity 16 A/230 V a.c. Rated frequency 50/60 Hz Range of control voltage 0.9 to 1.1 Un Load of filament lamps 2300 W Fluorescent lamp load: twin lamp circuit 100 W shunt compensated 56 W electronic ballast max. 36 W, dependent on manufacturer Induce load 6 A cos ϕ = 0.6 Max. switching capacity (cosϕ 0.5) 3500 VA Intrinsic consumption ca. 1 W Control voltage 5 V a.c. Adjustable making capacity 2 - 15 VA Breaking capacity 0.66 x making capacity ON delay 50 ms OFF delay ca. 3 sec. Contact assembly 1 NO contact Service life at rated load > 100000 switching cycles Ambient temperature - 10 °C/14 °F to +45 °C/113 °F Connection capacity (clamping terminal) max 2.5 mm E 235 mains disconnection relays - Bioswitch Constant exposure of electrical interference fields originating from live conductors - as is the case e.g. in bedrooms - may impair the well-being of people, experts say. With the extra base load adapter E235-GLA, the mains disconnection relays can be switched on manually. For the permanent installation of loads that switch on independently of the supply voltage, such as fluorescent lamps, a E235-GLE PTC base load element is available. Description Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. mains disconnection relay E 235-NFS 2CDE110000R1701 571821 0.065 1 base load element E 235-GLE 2CDE100500R1711 571814 0.001 1 base load adapter E 235-GLA 2CDE100510R1711 571869 0.070 1 Wiring diagram 2CDC 052 106 F0003 2CDC 052 107 F0003 use with dim- mer (potential-free NO contact) 2CSC400466F02012CSC400467F0201

pro M compact® Selection tables Load management devices SQZ3 phase and sequence relay SQZ3 SQZ3 phase and sequence relay SQZ3 relay performs the following continue monitoring functions on three-phase networks at 400 V a.c.: - phase sequence - phase failure - minimum voltage (adjustable up to 70% of Vn). If one of the three failures is detected, the output relay (safety switching contact) intervenes with a delay adjustable from 2 to 20 seconds for minimum voltage only and controls the following: - acoustic alarms - motor controlling contactors - circuit-breakers with coils. Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. SQZ3 2CSM111310R1331 372004 0.300 1 Technical features Supply voltage [Vn] 400 V a.c. Frequency [Hz] 50/60 Contact type [A] 1 CO, 250 V, 10 A (cos ϕ=1) safety switching Minimum voltage adjustment trimmer [%] 100 to 70% of Vn Intervention delay adjustment trimmer [s] 2 to 20 (only for min. voltage) Protection degree [IP] 20 Operating temperature [°C] -10…+55 Power consumption [W] 1.5 Modules [No.] 3 Output contact Three-phase motor Automatic circuit breaker 789 1234 56 SQZ3 400V 50-60Hz 10 11 12 Phases Sequence 400V 50Hz OK OK OK Three phases Min Voltage Min Voltage Delay (s) 70% 100% 22 0 NO NC C

10 A 250 V

pro M compact® Selection tables Load management devices Maximum and minimum current/voltage relays RH/RL Maximum and minimum current/voltage relays These relays are used for monitoring current and voltage on single-phase electrical networks, to ensure perfect protection of the devices installed on the system. The range includes:

  • maximum current (RHI) and maximum voltage (RHV) relays. The control relay remains on as long as the measured quantity stays below the preset threshold value.
  • minimum current (RLI) and minimum voltage (RLV) relays. The control relay remains on as long as the measured quantity stays above a preset threshold value. Both types of relays have trimmers for adjusting the switch-off delay and the hysteresis (from 1 to 45%). The 100 V and 5 A relay inputs allow indirect connection of external CTs and VTs for monitoring voltage and current values exceeding the maximum device scale Type Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. maximum current relay RHI 2CSM121310R1321 334309 0.300 1 maximum voltage relay RHV 2CSM111310R1321 334101 0.300 1 minimum current relay RLI 2CSM122310R1321 334200 0.300 1 minimum voltage relay RLV 2CSM112310R1321 334002 0.300 1 Technical characteristics Rated voltage Un [V] a.c. 230 Contact type 1 CO, 250 V, 16 A Rated frequency [Hz] 50/60 Current relay alarm thresholds [A] 2, 5, 10 Voltage relay alarm thresholds [V] 100, 300, 500 Adj. calibration of In and Vn% [%] 30...100 Adjustable hysteresis value [%] 1...45 Time delay [s] 1...30 Power consumption [W] 2 Modules [No.] 3 Control relay alarm indication red LED on = alarm Power supply lighting indication green LED on = ON Alarm indication blinking green LED = alarm 2CSC400513F0201

C N L Supply 230 V~ OEPM0060 OEPM0059 Hysteresis Δ I % 100 Current I % 70 90 Operating time (s) Power ON 230 V~ 50...60Hz 16A (cos 1) Alarm RHI Hysteresis Δ V % 100 Voltage V % 70 90 Operating time (s) Power ON 230 V~ 50...60Hz 16A (cos 1) Alarm RHV OEPM0062 123456 789 1 0 1 1 1 2 CN C N O Output 10A C N L Supply 230 V~ OEPM0061 System pro M compact® Selection tables Load management devices Maximum and minimum current/voltage relays RH/RL Maximum voltage relay (RHV) application example Monitoring a load with the following ratings: In = 5 A (standard rated operating current) Vn = 230 V a.c. (standard rated operating voltage) Vmax = 250 V a.c. (RHV relay intervention voltage) 1. Connect as in the diagram (since V max=250 V). 2. Set the “Voltage%” trimmer to 83.33%, since: V% = x100=83.33% being terminal 7-11 wired. 3. Set the “hysteresis %” trimmer; choosing 5% gives a intervention range from 237.5 to 250 V (250-5%=237.5 V). The relay will switch at 250 V and return to its normal state at 237.5 V 4. Adjust the “delay” trimmer to select the desired relay intervention delay (1…30 sec). During this delay the “Power ON” LED blinks; at the end of the delay the “Alarm” LED becomes steadily lit and the relay intervenes. 250 (V max) 300 (Vset) NOTE Generally connect terminals: 7-10 if Vmax is ≤100 V 7-11 if Vmax is >100 V and ≤300 V 7-12 if Vmax is >300 V and ≤500 V A 12 56 43 78 1 1 1 2 109 AlarmSupply voltage 230 V a.c. F N LOAD RHV Network to be measured Vmax 250 V a.c. C Vmax=250 V 237.5 V Vn=230 V Regular operation Alarm on Alarm on as within of the hysteresis window Alarm off as out of the hysteresis window Selected hysteresis window =5% OEPM0124

pro M compact® Selection tables Load management devices E 236 undervoltage monitoring relays E 236 Technical features US 1 US 2 Rated voltage 250 V a.c. Frequency 48-63 Hz Measuring range: supply voltage 3N 400/230 V a.c. (terminals N-L1-L2-L3) overload capacity 3N 459/265 V a.c. Switching capacity device in series (distance < 5 mm): 750 VA (3 A/250 V a.c.); device not in series (distance > 5 mm): 1250 VA (5 A/250 V a.c.) Rated insulation voltage 250 V a.c. (corresponds with IEC 664-1) Rated surge voltage 4 kV Tripping delay ca. 100 ms Clearence and creepage distance > 6 mm (between contact and electronics) Mechanical service life 20 x 10 6 operations Electrical service life at 10000 VA 2 x 10 5 operations Max. switching rate max. 6/min (1000 VA Ohmic load); max. 60/min (100 VA Ohmic load) Ambient temperature -25 °C/-13 °F to +55 °C/131 °F Overvoltage category III Accuracy in non-changing environment: setting tolerance (US 2) ≤ 5 % repeat accuracy ±1 % temperature effect ≤ 0.1 %/°C Terminals up to 4 mm Specifications VDE 0110 and VDE 0435 EMC tests EM 50081-1 and EN 50082-2 Displays LED green= supply voltage applied; LED yellow= relay status Power loss 1.7 W E 236 undervoltage monitoring relays Function The green LED is lit when the supply voltage is applied. If each phase voltage exceeds 195 V (US1) or exceeds the preset threshold value (US2) with respect to the neutral including the hysteresis when switching the device on, the relay switches immediately into the working position. The yellow LED is lit. If at least one phase voltage falls below the threshold value, the relay goes back into its normal position and the yellow LED goes out. If also phase 2 fails, the green LED goes out, too. It is indispensable to connect the neutral conductor! Application - devices with 2CO contacts For the control of three-phase undervoltage (each phase to neutral) of switchgear, also for installa- tions according to DIN VDE 0100-718 (power installations in hospitals and rooms used for medical purposes outside of hospitals) and DIN VDE 0108-100 (power installations and safety supply in buildings where many people gather). US 1: 3 phases to neutral with fixed threshold at 195 V; hysteresis fixed 5 % US 2: 3 phases to neutral with fixed threshold at 160 – 240 V; hysteresis fixed 5 % 2CSC400462F02012CSC400463F0201 E 236 US 1 E 236 US 2 SK 0148 Z 00 Contact Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. 2CO E 236-US 1 2CDE165000R2001 511087 0.095 5 2CO E 236-US 2 2CDE165010R2001 511094 0.095 5

pro M compact® Selection tables Load management devices E 236 undervoltage monitoring relays E 236 Devices for panel installation onto mounting rails (35 mm) according to DIN EN 60715 mounting depth: 68 mm mounting width: 17.5 mm = 1 module color: gray, RAL 7035 Application - devices with 1CO contact For three-phase undervoltage monitoring (each phase connected to a neutral conductor) of switch- gear. Devices with fixed threshold value (US 1.x and US 1.1 D) also for installations according to DIN VDE 0100-718 (for medical purposes) and DIN VDE 0108-100 (power installations and safety supply in installations for gathering of people). US 1.1: 3 phases to neutral conductor with fixed threshold value at 195 V; hysteresis fixed at 5 % US 2.1: 3 phases to neutral conductor with threshold value range of 160 – 240 V; hysteresis fixed at 5 % US 1.1D: 3 phases to neutral conductor with fixed threshold value at 195 V; hysteresis fixed at 5 %, but with switch-on delay of 0.1 (6 sec.) to 10 min Technical features US 1.1 US 2.1 US 1.1D Supply circuit Supply voltage (= measured voltage): 3N~ 400/230 V AC (terminals N-C1-C2-C3) Overvoltage permanent: 3N~ 459/265 V AC Frequency: 48 – 63 Hz (AC sinus) Rated surge voltage: 4 kV Overvoltage category: III Output circuit (isolated two-way-switch) Rated voltage: 250 V AC Switiching capacity: 1250 VA (5 A/250 V AC) Continuous current: 1250 VA (5 A/250 V AC) Fuse protection: 5 A flink Serviceable life, mechanical: 15x10 6 switchover cycles Serviceable life, electric: 2x10 5 switchover cycles at 1,000 VA resistive load Max. switching rate: max. 6/min at 1,000 VA resistive load max. 60/min at 100 VA resistive load Trip delay: ca. 200 ms Pick-up delay (US 1.1D) 0.1 – 10 min Accuracy under constant conditions – setting accuracy (US 2.1/1.1D): ≤ 5 % of full scale value – repeat accuracy: ≤ 2 % – temperature effect: ≤ 1 % Ambient temperature: – 25° to + 55 °C Terminals: 1 x 0.5 to 2.5 mm² with/without connector sleeve 1 x 4 mm² without connector sleeve 2 x 0.5 to 1.5 mm² with/without connector sleeve 2 x 2.5 mm² without connector sleeve Pick-up torque: max. 1 Nm Mounting position: optional Vibration resistance: 10 to 55 Hz 0.35 mm (IEC 68-2-6) Shock resistance: 15 g 11 ms (IEC 68-2-27) Standards: VDE 0110 und VDE 0435 EMC tests: EN 61000-6-2 and EN 61000-6-4 Back-up fuse ≤ 16 A Displays: green LED U/t ON all 3 voltages ok green LED U/t flashes time-out indication yellow LED ON/OFF position of output relay All measured inputs have to be connected to one phase each. If no three-phase measurement should be carried out, measured inputs have to be connected to one phase to apply the required voltage to all measured inputs. If a load causes inverse voltage exceeding the threshold value U phase failures cannot be identified. A neutral conductor must be connected in any case! E 236-US 1.1 2CDC 051 234 F0005 E 236-US 1.1D E 236-US 2.1 2CDC 051 236 F0005 2CDC 051 235 F0005

Undervoltage monitoring device with pick-up delay E 236-US 1.1D If the measurement of the voltage of all phases connected exceeds the switching threshold U s, including the hysteresis, the time delay (t) starts to run and the (green LED U/t) flashes. Upon expiry of the time delay (t), the output relay R picks up (yellow LED on, green LED U/t flashes). If the measured voltage of one of the connected phases falls below the switching threshold U s, the output relay de-energizes (yellow LED is off, green LED U/t is off). Contact Order Bbn Price Price Weight Pack details 4016779 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 two-way switch E 236-US 1.1 2CDE165001R2001 651776 0.05 10 1 two-way switch E 236-US 2.1 2CDE165011R2001 651783 0.05 10 1 two-way switch E 236-US 1.1D 2CDE165001R2011 651790 0.05 10E 236-US 1.1 2CDC 051 234 F0005 E 236-US 1.1D E 236-US 2.1 2CDC 051 236 F0005 2CDC 051 235 F0005 Function E 236-US 1.1D System pro M compact® Selection tables Load management devices E 236 undervoltage monitoring relays E 236 Function E 236-US 1.1 and US 2.1 Wiring E 236-US 1.1 and US 2.1 Wiring E 236-US 1.1D 2CSC400120F0202

pro M compact® Selection tables Load management devices LEE 230 extractable power failure signalling lamp LEE 230 Technical characteristics 2P 10 A plug distance between pins 19 mm, pin ø 4 mm Supply [V] 230 a.c., 50-60 Hz Recharge time [h] 24 Endurance [h] 3 Lighting level [mcd] 3000 Operating temperature [°C] 0…+45 Min. life cycle 5 years (battery) LEE 230 extractable power failure signalling lamp The LEE 230 lamp is an automatic electronic lamp that can be installed in any modular socket or wiring accessory socket conforming to the German VDE Schuko standard (e.g. ABB M1173 or M1175), to the Italian standard P11 10A, or to the 10/16 A italian dual standard. The device functions both as a power failure signalling lamp and as a lighting device, to be used for example during maintenance activities or when seeking faults in the panel. Pack Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Blister LEE-230 2CSM111000R1361 507406 0.100 1 Additional technical features LEE-230 lamp automatically switches on when the voltage fails; the built-in rechargeable battery guarantees the supply. It is particularly useful thanks to its construction and functional characteristics: – it can be extracted from the socket and used as a torch with ON-OFF button on its frontal side – when necessary it can work with standard sockets – it can be moved when it is needed – it has a long operation endurance, up to three hours – it is ready to use, it does not require installation – with a screw (ø 3.5 mm, L 16 mm) it is possible to fix it preventing the extraction from the M1173 ABB sockets with central hole – the projecting part of the Schuko profile is very small (8 mm). The two LEDs placed on the frontal side of the lamp indicate its operation condition: – the red LED indicates the recharge activity and that, in the case of a network voltage back-out, the lamp will remain off – the green LED indicates the recharge activity and that, in the case of a network voltage black-out, the lamp will switch on (it will automatically switch off when the voltage returns). By pushing the frontal pushbutton it is possible to change the status; if you do not use the lamp for a prolonged time it is suggested to set the first condition in order to preserve the battery life. 2CSC400265F0201

ABB offers a wide range of analogue voltmeters, ammeters, frequency meters, power factor meters, available in modular or front panel version. Voltmeters, ammeters and frequency meters are also available in a digital range (both modular and front panel version) that also includes voltmeters and ammeters equipped with output relay. ABB multimeters allow the measurement of the main electrical parameters in three phase networks. The range is divided in: - DMTME - modular version - DMTME-72 and DMTME-96 - front panel version also available with RS485 Modbus RTU port for communicating the measured parameters over a Modbus network. ABB offers a front panel range of network analyzers that perform true rms value of the principal electrical quantitites in single and three phase networks. ANR is able to measure and record network parameters, information and alarms, routing data towards supervision and monitoring systems. ABB also provides a range of electronic energy meters for single-phase (ODINsingle and DELTAsingle Meter) and three-phase systems (ODIN Meter, DELTAplus and DELTAmax). For all these measurement devices ABB provides a wide range of accessories like current transformers (CT range), voltage transformers (TV range) and shunts (SNT).

Multimeters and network analysers Analogue and digital instruments Electronic energy meters Hour counters Current transformer Accessories for analogue and digital instruments Other modular devices Measurement devices ABB

Modular and front panel multimeters Front panel network analysers DMTME DMTME-72 DMTME-96 ANR96 ANR144 Overall dimensions 6 DIN modules 72x72x90 96x96x103 96x96x130 144x144x66 Display LED LCD graphic backlit a.c./d.c. 85-265 V a.c./d.c. TRMS voltage Electrical parameters measurement TRMS current Frequency Power factor Cosϕ Active power Reactive power Apparent power Active energy Reactive energy Apparent energy Peak value Min/Max/Avg Timer and count-down Power 4Q Power quality Energy 4Q Neutral current Current THD Voltage THD Password set up Tariff Energy management Maximum demand Harmonic analysis up to 31° Wave form visualisation Memory 1 MB Outputs Digital Digital Digital and analog Inputs Digital Serial port RS485 RS485 RS232 Protocols Modbus RTU Modbus RTU Profibus DP Modbus RTU Ethernet TCP/IP Profibus DP System pro M compact® Selection tables Measurement devices Selection table DMTME MTME ANR

pro M compact® Selection tables Measurement devices DMTME multimeters DMTME DMTME-96 DMTME-72 DMTME multimeters The instruments DMTME are digital multimeters that allow the measurement (in TRMS mode) of the principal electrical parameters in three-phase 230/400 Vac networks, including the max/min/average detection of the main electrical parameters and the active and reactive energy count. The different measured variables are displayed locally on four red 7-segment LED displays providing easy readability and simultaneous display of multiples measures. The instruments DMTME combine also (in a single instrument) the functions of a voltmeter, amme- ter, power factor meter, wattmeter, varmeter, frequency meter, active and reactive energy meters, allowing remarkable financial savings thanks to the reduction of space required for the panels and also of time required for cabling. The DMTME-I-485, DMTME-I-485-96 and DMTME-I-485-72 models are additionally equipped with two relays, fully programmable as either pulse outputs for remote metering of energy consumption, or as alarm outputs. There is also an RS485 port for communicating the measured parameters over a Modbus net- work. All versions come complete with Mini CD containing the instruction manual, technical documentation, communication protocol and the DMTME-SW software. DMTME modular multimeters TRMS measure of VL-L, VL-N, A, W, Var, VA, kWh, kVar, PF in 230/400 V a.c. lines. Indirect connection Auxiliary RS485 Program. Order Bbn Price Price Weight Pack supply Serial digital details 8012542 1 piece group 1 piece unit port output V d.c. Type code Order code EAN kg pc. 110-230 - - DMTME 2CSM170040R1021 975700 0.450 1 110-230 ■ 2 DMTME-I-485 2CSM180050R1021 975809 0.450 1 DMTME-96 panel multimeters Auxiliary supply 230 V a.c. and 110 V a.c. RS485 Program. Dimension Order Bbn Price Price Weight Pack Serial digital details 8012542 1 piece group 1 piece unit port output Type code Order code EAN kg pc. - - 96x96 DMTME-96 2CSG133030R4022 046752 0.450 1 ■ 2 96x96 DMTME-I-485-96 2CSG163030R4022 046851 0.450 1 DMTME-72 panel multimeters Auxiliary supply 230 V a.c. and 400 V a.c. - - 72x72 DMTME-72 2CSG132030R4022 046554 0.450 1 ■ 2 96x96 DMTME-I-485-72 2CSG162030R4022 046653 0.450 1 2CSC400136F0201 2CSC400751F00012CSC400752F0001

pro M compact® Selection tables Measurement devices DMTME multimeters DMTME DMTME-96 DMTME-72 Technical characteristics Rated voltage [V rms] 230 +15% - 10% DMTME, DMTME-72 and DMTME-96 [V rms] 400 +15% - 10% DMTME-72 [V rms] 115 +15% - 10% DMTME , DMTME-96 Frequency [Hz] 45…65 Power consumption [VA] <6 Fuse protection T0.1A Voltage measuring inputs Range [V rms] 10…500 V (L-N) Max. non destructive [V rms] 550 Impedance (L-N) [MΩ]> 8 Current measuring inputs (only external CTs .../5 A) Range [A rms] 0.05…5 Overload 1.1 permanent Measurement accuracy Voltage ±0.5% F.S. ±1 digit in range Current ±0.5% F.S. ±1 digit in range Frequency ±0.2% ±0.1Hz from 40.0 to 99.9 Hz ±0.2% ±1Hz from 100 to 500 Hz Energy metering Maximum metered value for single phase 4,294.9 MWh (MVarh) with KA = KV = 1 Maximum metered value for three phase 4,294.9 MWh (MVarh) with KA = KV = 1 Accuracy Class 1 Max. power consumption [VA] 1.4 for each input (with Imax = 5A rms) Digital outputs Pulse duration 50 ms OFF (min)/ 50 ms ON Vmax on contact 48 V (d.c. or a.c. peak) Wmax dissipation 450 mW Max frequency 10 pulses/sec Imax contact 100 mA (d.c. or a.c. peak value) Insulation 750 Vmax Programmable parameters kVT transformer ratio Vprim/Vsec 1…500 kCT transformer ratio Iprim/Isec 1…1,250 Free hour counter [h] 0…10,000,000, resettable Countdown [h] 1…32,000 Operating temperature [°C] 0…+50 Storage temperature [°C] -10…+60 Relative humidity 90% max. (non condensing) at 40°C Overall dimensions [mm] 105x90x58 DMTME [mm] 96x96x103 DMTME-96 [mm] 72x72x90 DMTME-72

Wiring diagrams only for low voltage system System pro M compact® Selection tables Measurement devices DMTME multimeters DMTME DMTME-96 DMTME-72 6 6 6 6 6 6 / / / 1 $8; '070('070( 9± 9DF '070( 9± 9DF 7KUHHSKDVHZLWKQHXWUDODQG&7V 6 6 6 6 6 6 / / / 1 $8; '070('070( 9± 9DF '070( 9± 9DF 7KUHHSKDVHZLWKQHXWUDODQG&7VDQG97V 8SWR9SKDVHQHXWUDODGLUHFWFRQQHFWLRQLVSRVVLEOH 6 6 6 6 6 6 / / / 1 $8; '070('070( 9± 9DF '070( 9± 9DF $URQW\\SHWKUHHSKDVHZLWK&7VDQG97V 6 6 6 6 6 6 / / / 1 $8; '070('070( 9± 9DF '070( 9± 9DF 7KUHHSKDVHZLWK&7V 287 287 9DX[ 9DF GFPD[ ([WHUQDO UHOD\\ 287 287 9DX[ 9DF GFPD[ 3XOVH DGTXLVLWLRQ 6 6 6 6 6 6 / / / 1 $8; '070('070( 9± 9DF '070( 9± 9DF 6LQJOHSKDVHZLWKQHXWUDODQG&7V'LJLWDORXWSXWXVHGDVDODUPZLWKH[WHUQDO UHOD\\VIRUORDGFRPPDQG 'LJLWDORXWSXWXVHGDVSXOVHV :LWKV\\PPHWULFDQGXQEDODQFHGQHWZRUN&7VDQG XSWR9EH\\RQGWKLVYDOXHPXVWXVH97 2CSC400125F0202

pro M compact® Selection tables Measurement devices Network analyser ANR ANR Network analyser ABB has extended its range of front panel devices with the introduction of the new ANR electrical network analysers - measuring instruments that permit advanced analysis of single and three-phase electrical distribution networks. In particular, the ANR devices are able to measure and record network parameters, information and alarms, routing data towards supervision and monitoring systems. Available in 96 x 96 mm or 144 x 144 mm front panel format, they are equipped with a backlit graphic LCD display. The ANR analysers measure current and voltage in TRMS, frequency and temperature, calculate concatenate voltage and three-phase system voltage and current, power factor and cosϕ, apparent, active and reactive power, THD total harmonic distortion up to the 31 st harmonic, and measure active energy consumed and cogenerated, submetering the counters in total counter, programmable by the user. All codes have RS485/232 built in as a standard. All the parameters can be stored in the 128 kbyte internal memory, expandable to up to 1 Mbyte for the ANR144 and ANR96P versions. The devices come with a mini-CD containing: - Instruction manual - Technical datasheet - SW-01 software for managing the recorded data. All ANR versions have 2 programmable digital outputs and RS485/RS232 serial port. ANR96PRF models have Profibus DP protocol built in. Auxiliary Program. Storage Expandable Order Bbn Price Price Weight Pack supply digital with add-on details 8012542 1 piece group 1 piece unit 20÷60 2 128 Kb ANR96-24 2CSG113000R4051 943402 0.430 1 85÷265 2 128 Kb ANR96-230 2CSG213000R4051 943501 0.430 1 20÷60 4 1 Mb ANR96P-24 2CSG123000R4051 943600 0.430 1 85÷265 4 1 Mb ANR96P-230 2CSG223000R4051 943709 0.430 1 85÷265 2 128 Kb ■ ANR144-24 2CSG114000R4051 943808 0.430 1 20÷60 2 128 Kb ■ ANR144-230 2CSG214000R4051 943907 0.430 1 20÷60 2 128 kb ANR96PRF-24 2CSG258333R4051 583332 0.430 1 85÷265 2 128 kb ANR96PRF-230 2CSG257153R4051 571537 0.430 1 Expandable range for versions ANR144-24 and ANR144-230 1 Mb internal memory board ANR-1MB 2CSG000010R4051 944003 0.100 1 6 digital input board ANR-6I 2CSG000020R4051 944102 0.100 1 4 digital output board ANR-4O 2CSG000030R4051 944201 0.100 1 2 dig. input + 2 dig. output board ANR-2I2O 2CSG000040R4051 944300 0.100 1 2 analogue output board ANR-2AN 2CSG000050R4051 944409 0.100 1 4 analogue output board ANR-4AN 2CSG000060R4051 944508 0.100 1 RS232/485 board ANR-CM2 2CSG000070R4051 944607 0.100 1 Profibus DP board ANR-PRF 2CSG000080R4051 944706 0.100 1 Ethernet Modbus RTU board ANR-LAN 2CSG000090R4051 944805 0.100 1 2CSC400753F00012CSC400754F0001

pro M compact® Selection tables Measurement devices Network analyser ANR Technical features Dimensions Overall dimensions [mm] 96 x 96 x 130 - 144 x 144 x 66 IEC 61554 Max cable section [mm2] 2.5 Protection degree IP52 on front - IP20 on terminal EN 60529 Weight [g] 430 Display Graphic LCD Backlit 128 x 128 pixel graphic LCD display Display dimensions [mm] ANR96: 50 x 50 - ANR144: 70 x 70 Voltage (TRMS) Direct measurement [V] 10 - 600 Ratio transformer range kVT [V] 0.01 - 5,000.00 Max over voltage [V] 750, beyond this value must use VT Consumption [VA] 0.2 Input resistor [MΩ]> 2 Current (TRMS). always use external CT .../5A 3 isolated inputs [A] 0.01 - 5 Min current value [mA] 10 Consumption [VA] 0.2 Max over current [A] 10 (100 A for 1 second) Ratio transformer range kCT 0.01 - 5,000.00 THD Voltage and current Up to 31st harmonic Frequency Range [Hz] 30 - 500 Accuracy class Current [%] <0.5 EN 61036 Voltage [%] <0.5 Power [%] <1 Power factor [%] <1 Active energy [%] <1 IEC 62052-11 IEC 62053-11 Reactive energy [%] 2 IEC 62053-23 Auxiliary supply ANR96-230, ANR96P-230, ANR144- 230 ANR96-24, ANR96P-24, ANR144-24 [V] 20 ÷ 60 a.c./d.c. Internal fuse 5x20 mm 315 mA 250 V Fast Operating environment Operating temperature [°C] -10 ÷ +50 Storage temperature [°C] -15 ÷ +70 Operating humidity [°C] 90% without condensation Insulation Voltage insulation 3,700 V a.c. rms for 1 minute Serial output RS485 Baud rate [bps] 1,200 - 19,200 Protocols Modbus RTU, ASCII Internal memory For ANR96 and ANR144 [kbytes] 128 (usable: 80) For ANR96P [Mbytes] 1 Memory Non-volatile data storage using internal battery Data retention 5 years at 25 °C Internal clock RTC clock IEC 61038 Class of accuracy [ppm] 5 Digital output Connection area [mm² ] 0 ÷ 2.5 External pulse voltage [V] 12 ÷ 230 V a.c./d.c. Max current [mA] 150 Digital input Voltage [V] 12 - 24 d.c.

Wiring diagrams ANR96 and ANR144 4 wires insertion 3 wires insertion Insertion with 3 CTs and 3 VTs Insertion with 2 CTs Insertion with 3 CTs Insertion with 2 CTs and 2 VTs (Aron) Insertion with 3 CTS and 2 VTs System pro M compact® Selection tables Measurement devices Network analyser ANR /2$' 1 3 3 6 6 Single phase insertion with 1CT 2CSC400120F0202

pro M compact® Selection tables Measurement devices Serial converter RS485 / RS232 serial converter The CUS multifunction serial converter has applications in all those situations which require converting or managing EIA -232 (RS-232) , EIA-485 (RS-485) or EIA-422 (RS-422) serial lines. The communi- cation links between devices that use these types of buses (for example PLCs, measurement and control instruments, peripherals and computers running specific software applications, etc.) often call for converting between different serial interfaces, ampliying the signal on the line, isolating different parts of the communication network, etc. These diverse application requirements are readily met by the CUS converter, thanks to its configurability and operational flexibility. The CUS assures galvanically-isolated interface conversion between the RS-232 side, the RS422- 485 side and the power supply source. Its versatility permits following operating modes: - Full duplex conversion of RS-232 to RS-422 - Half duplex conversion of RS-232 to single-pair RS-485 - Half duplex conversion of RS-232 to two-pair RS-485 - RS-485 repeater (and monitoring function on RS-232) The principal applications are: - Multipoint data transmission networks - Long distance serial links - Galvanic separation of peripherals - Extension of RS-485 lines CUS serial converter/serial repeater Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. serial converter - signal repeater CUS 2CSM200000R1031 333807 0.5 1 Technical features Supply voltage [V] 230 V ac ±20% Frequency [Hz] 50-60 Power consumption [VA] 7 max Power loss [W] 3.5 Fuse 500 mA internal Supply terminal dimensions [mm2] 2.5 max RS485-422 terminal dimensions [mm2] 2.5 max RS232 connection Sub-D 9 female poles (DB9) Max RS232 line length [m] 15 Max RS485-422 line length [m] 1200 Connection of multidrop units Max 32 Operating temperature [°C] -20…+60 Storage temperature [°C] -20...+80 Modules [No.] 6 CUS 2CSC400126F0202

pro M compact® Selection tables Measurement devices Serial converter CUS Connection diagram Application example 2CSC400127F02022CSC400128F0202 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 C B A R C B A R C SGN GND GND Ch1-RS485 Ch2-RS485 PE Jumper N L Channel 1 RS485 Channel 2 RS485 Aux supply DB9 connector pin 1 = not connected pin 2 = TXD transmit data pin 3 = RXD receive data pin 4 = DTR pin 5 = GND signal ground pin 6 = DSR pin 7 = RTS pin 8 = CTS pin 9 = not connected 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 C B A R C B A R C SGN GND GND Ch1-RS485 Ch2-RS485 PE Jumper N L 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 C B A R C B A R C SGN GND GND Ch1-RS485 Ch2-RS485 PE Jumper N L 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Line 1 - max 1200 m, 32 units Repeater Line 2 - max 1200 m, 32 units Line 3 - max 1200 m, 32 units Converter R 2 (tx) 3 (rx) 5 (gnd)

Measure Technology Characteristics Mounting Insertion Accessories Type Voltage Analog a.c. and d.c. 3 modules Direct MCV voltage switches VLM pag.8/12 48x48, 72x72, 96x96 Direct MCV voltage switches VLM-1 VLM-2 pag.8/15 48x48, 72x72, 96x96 Indirect TV voltage transformers MCV voltage switches VLM1-TV VLM2-TV pag.8/15 Digital a.c. and d.c. Auxiliary supply 230 V a.c. 3 modules Direct MCV voltage switches VLMD pag.8/26 36x72 Direct MCV voltage switches VLMD P pag.8/27 Current Analog a.c. and d.c. 3 modules Direct MCA current switches AMT pag.8/12 Indirect CT a.c. current transformer SNT shunt for d.c. SCL interchangeable scale MCA current switches AMT1/A AMT2 pag.8/12 48x48, 72x72, 96x96 Direct MCA current switches AMT1-A1 AMT2-A2 pag.8/17 Indirect CT a.c. current transformer SNT shunt for d.c. SCL interchangeable scale MCA current switches AMT1-A1 AMT1-A5 AMT2-A2 pag.8/17 Digital a.c. and d.c. Auxiliary supply 230 V a.c. 3 modules Indirect CT a.c. current transformer SNT shunt for d.c. MCA current switches AMTD pag.8/26 36x72 Indirect CT a.c. current transformer SNT shunt for d.c. MCA current switches AMTD P pag.8/27 Frequency Analog a.c. 3 modules Direct FRZ1 pag.8/12 48x48, 72x72, 96x96 Direct FRZ pag.8/19 Digital Auxiliary supply 230 V a.c. 3 modules Direct FRZ-DIG pag.8/26 Cosϕ Analog 3 modules Indirect CNV-C phase meter transducer CSF1 pag.8/12 48x48, 72x72, 96x96 Indirect CNV-C phase meter transducer COS pag.8/19 System pro M compact Selection tables Measurement devices Analogue and digital instruments

pro M compact® Selection tables Measurement devices Analogue instruments VLM, AMT FRZ and CSF Technical features Rated voltage Un [V] a.c. 300, 500; d.c. 100, 300 Indirect reading full scale values 5...2500 Indirect reading full scale values 5...500 Frequency [Hz] 50/60 Overload capacity [%] 20 compared to the voltage or to the rated current Accuracy class [%] 1.5 (0.5 for frequency meters) Ammeters power consumption [VA] 5 A: 0.3 VA; 10 A: 0.6 VA; 25 A:1 VA; 30 A: 1.2 VA Voltmeters power consumption [VA] 300 V: 1.5 VA; 500 V: 4 VA Frequency meters power consumption [VA] <1.5 VA Modules [No.] 3 Protection degree IP20 Standards EN 60051 The range provided includes analogue and digital instruments. In addition to standard measurement devices for electric quantities (voltmeters, ammeters, frequency meters, power factor meters), and a set of accessories are available, including ammetric transformers, which increase the functions of these instruments. Analogue instruments for alternated current Suitable for direct or indirect measurement through the appropriate accessories. Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Direct voltmeters 300 V VLM1/300 2CSM110190R1001 007906 0.200 1 500 V VLM1/500 2CSM110220R1001 000006 0.200 1 Direct ammeters 5 A AMT1/5 2CSM310030R1001 000709 0.200 1 10 A AMT1/10 2CSM310040R1001 000105 0.200 1 15 A AMT1/15 2CSM310050R1001 000204 0.200 1 20 A AMT1/20 2CSM310060R1001 000303 0.200 1 25 A AMT1/25 2CSM310070R1001 000402 0.200 1 30 A AMT1/30 2CSM310080R1001 000501 0.200 1 Ammeters without scale for C.T. (sec. 5 A) For scale SCL1 Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. A1 AMT1/A1 2CSM320250R1001 000600 0.200 1 A5 AMT1/A5 2CSM320260R1001 000808 0.200 1 100/280V 45-65 Hz frequency meter with scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. FRZ1 2CSM810310R1001 008606 0.200 1 Power factor meter with scale for transducer (1 mA input) CSF1 2CSM720310R1001 028000 0.300 1 2CSC400497F02012CSC400517F0201

A 12 34 N A 12 34 N A 12 34 N V System pro M compact® Selection tables Measurement devices Analogue instruments VLM, AMT FRZ and CSF Analogue instruments for direct current Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Direct voltmeters 100 V VLM2/100 2CSM210130R1001 008002 0.200 1 300 V VLM2/300 2CSM210190R1001 008101 0.200 1 Direct ammeters 10 mA AMT2/0.01 2CSM410330R1001 028307 0.200 1 100 mA AMT2/0.1 2CSM410340R1001 028406 0.200 1 1000 mA AMT2/1 2CSM410020R1001 028505 0.200 1 5 A AMT2/5 2CSM410030R1001 028604 0.200 1 10 A AMT2/10 2CSM410040R1001 028703 0.200 1 15 A AMT2/15 2CSM410050R1001 028802 0.200 1 20 A AMT2/20 2CSM410060R1001 028901 0.200 1 25 A AMT2/25 2CSM410070R1001 029007 0.200 1 30 A AMT2/30 2CSM410080R1001 029106 0.200 1 Ammeters without scale for shunt…/60 mV For scale SCL2 Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. AMT2 2CSM420270R1001 029205 0.200 1 Wiring diagrams Direct insertion Insertion by shuntIndirect insertion through C.T. OEPM0065

pro M compact® Selection tables Measurement devices Interchangeable scales for analogue instruments SCL Interchangeable scales for analogue instruments Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Scales SCL 1 for analogue ammeters in a.c. AMT1 A1-5A SCL 1/5 2CSM110021R1041 001201 0.010 10 A1-10A SCL 1/10 2CSM110032R1041 001300 0.010 10 A1-20A SCL 1/20 2CSM110075R1041 001409 0.010 10 A1-25A SCL 1/25 2CSM110096R1041 030706 0.010 10 A1-30A SCL 1/30 2CSM110107R1041 001508 0.010 10 A1-40A SCL 1/40 2CSM110128R1041 030805 0.010 10 A1-50A SCL 1/50 2CSM110149R1041 001607 0.010 10 A1-60A SCL 1/60 2CSM110159R1041 030904 0.010 10 A1-75A SCL 1/75 2CSM110169R1041 031000 0.010 10 A1-80A SCL 1/80 2CSM110179R1041 001706 0.010 10 A1-100A SCL 1/100 2CSM110189R1041 001805 0.010 10 A1-150A SCL 1/150 2CSM110209R1041 001904 0.010 10 A1-200A SCL 1/200 2CSM110229R1041 002000 0.010 10 A1-250A SCL 1/250 2CSM110249R1041 031109 0.010 10 A1-300A SCL 1/300 2CSM110259R1041 002109 0.010 10 A1-400A SCL 1/400 2CSM110279R1041 002208 0.010 10 A1-500A SCL 1/500 2CSM110299R1041 002307 0.010 10 A1-600A SCL 1/600 2CSM110309R1041 031208 0.010 10 A1-800A SCL 1/800 2CSM110329R1041 002406 0.010 10 A1-1000A SCL 1/1000 2CSM110339R1041 002505 0.010 10 A1-1500A SCL 1/1500 2CSM110359R1041 274704 0.010 10 A1-2000A SCL 1/2000 2CSM110379R1041 274803 0.010 10 A1-2500A SCL 1/2500 2CSM110389R1041 274902 0.010 10 Scale SCL 1/A5 for analogue ammeters in a.c. AMT1 A5-5A SCL 1/A5/5 2CSM120021R1041 031307 0.010 10 A5-10A SCL 1/A5/10 2CSM120032R1041 031406 0.010 10 A5-20A SCL 1/A5/20 2CSM120075R1041 031505 0.010 10 A5-30A SCL 1/A5/30 2CSM120107R1041 031604 0.010 10 A5-50A SCL 1/A5/50 2CSM120149R1041 031703 0.010 10 A5-80A SCL 1/A5/80 2CSM120179R1041 031802 0.010 10 A5-100A SCL 1/A5/100 2CSM120189R1041 031901 0.010 10 A5-150A SCL 1/A5/150 2CSM120209R1041 032007 0.010 10 Scales SCL 2 for analogue ammeters in d.c. AMT2 A1-5A SCL 2/5 2CSM230025R1041 032106 0.010 10 A1-6A SCL 2/6 2CSM230345R1041 032205 0.010 10 A1-10A SCL 2/10 2CSM230035R1041 032304 0.010 10 A1-20A SCL 2/20 2CSM230075R1041 032403 0.010 10 A1-30A SCL 2/30 2CSM230105R1041 032502 0.010 10 A1-50A SCL 2/50 2CSM230145R1041 032601 0.010 10 A1-80A SCL 2/80 2CSM230179R1041 032700 0.010 10 A1-100A SCL 2/100 2CSM230189R1041 032809 0.010 10 A1-150A SCL 2/150 2CSM230209R1041 032908 0.010 10 A1-200A SCL 2/200 2CSM230229R1041 033004 0.010 10 A1-250A SCL 2/250 2CSM230249R1041 033103 0.010 10 A1-300A SCL 2/300 2CSM230259R1041 033202 0.010 10 A1-400A SCL 2/400 2CSM230279R1041 033301 0.010 10 A1-500A SCL 2/500 2CSM230299R1041 033400 0.010 10 100 90° SCL1/A5/100 Full scale at 78° (with extra scale) SCL1/ A1/100 Full scale at 90° OEPM0068 100 78° 2CSC400521F0201

pro M compact® Selection tables Measurement devices Front panel analogue instruments VLM Available in both alternating current and direct current versions, they come in three standard sizes, 48 mm x 48 mm, 72 mm x 72 mm and 96 mm x 96 mm (special versions available on request). Ammeters without scale for indirect connection must be completed with the interchangeable scale according to the full scale. Analogue voltmeters for alternating current Size Insertion Scale VT type Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm V a.c. Type code Order code EAN kg pc.

48 D 50 VLM-1-50/48 2CSG111100R4001 541707 1

48 D 60 VLM-1-60/48 2CSG111110R4001 541806 1

48 D 80 VLM-1-80/48 2CSG111120R4001 541905 1

48 D 100 VLM-1-100/48 2CSG111130R4001 542001 1

48 D 150 VLM-1-150/48 2CSG111150R4001 542100 1

48 D 200 VLM-1-200/48 2CSG111160R4001 542209 1

48 D 250 VLM-1-250/48 2CSG111180R4001 542308 1

48 D 300 VLM-1-300/48 2CSG111190R4001 542407 1

48 D 400 VLM-1-400/48 2CSG111210R4001 542506 1

48 D 500 VLM-1-500/48 2CSG111220R4001 542605 1

48 D 600 VLM-1-600/48 2CSG111230R4001 542704 1

48 I 200 110/100 VLM1-TV-110-100/200/48 2CSG121140R4001 743705 1

48 I 300 230/100 VLM1-TV-230-100/300/48 2CSG121170R4001 542803 1

48 I 500 380/100 VLM1-TV-380-100/500/48 2CSG121200R4001 542902 1

48 I 500 400/100 VLM1-TV-400-100/500/48 2CSG121210R4001 743804 1

48 I 600 500/100 VLM1-TV-500-100/600/48 2CSG121220R4001 543008 1

48 I 800 600/100 VLM1-TV-600-100/800/48 2CSG121230R4001 743903 1

48 I 1100 1000/100 VLM1-TV-1000-100/1100/48 2CSG121240R4001 744009 1

72 D 50 VLM-1-50/72 2CSG112100R4001 544104 1

72 D 60 VLM-1-60/72 2CSG112110R4001 544203 1

72 D 80 VLM-1-80/72 2CSG112120R4001 544302 1

72 D 100 VLM-1-100/72 2CSG112130R4001 544401 1

72 D 150 VLM-1-150/72 2CSG112150R4001 544500 1

72 D 200 VLM-1-200/72 2CSG112160R4001 544609 1

72 D 250 VLM-1-250/72 2CSG112180R4001 544708 1

72 D 300 VLM-1-300/72 2CSG112190R4001 544807 1

72 D 400 VLM-1-400/72 2CSG112210R4001 544906 1

72 D 500 VLM-1-500/72 2CSG112220R4001 545002 1

72 D 600 VLM-1-600/72 2CSG112230R4001 545101 1

72 I 200 110/100 VLM1-TV-110-100/200/72 2CSG122140R4001 744108 1

72 I 300 230/100 VLM1-TV-230-100/300/72 2CSG122170R4001 545200 1

72 I 500 380/100 VLM1-TV-380-100/500/72 2CSG122200R4001 545309 1

72 I 500 400/100 VLM1-TV-400-100/500/72 2CSG122210R4001 744207 1

72 I 600 500/100 VLM1-TV-500-100/600/72 2CSG122220R4001 545408 1

72 I 800 600/100 VLM1-TV-600-100/800/72 2CSG122230R4001 744306 1

72 I 1100 1000/100 VLM1-TV-1000-100/1100/72 2CSG122240R4001 744405 1

D: direct connection I: indirect connection with VT, CT and shunt, according to the type

Summing current transformers /1 A System pro M compact® Selection tables Measurement devices Front panel analogue instruments VLM

96 D 50 VLM-1-50/96 2CSG113100R4001 546702 1

96 D 60 VLM-1-60/96 2CSG113110R4001 546801 1

96 D 80 VLM-1-80/96 2CSG113120R4001 546900 1

96 D 100 VLM-1-100/96 2CSG113130R4001 547006 1

96 D 150 VLM-1-150/96 2CSG113150R4001 547105 1

96 D 200 VLM-1-200/96 2CSG113160R4001 547204 1

96 D 250 VLM-1-250/96 2CSG113180R4001 547303 1

96 D 300 VLM-1-300/96 2CSG113190R4001 547402 1

96 D 400 VLM-1-400/96 2CSG113210R4001 547501 1

96 D 500 VLM-1-500/96 2CSG113220R4001 547600 1

96 D 600 VLM-1-600/96 2CSG113230R4001 547709 1

96 I 200 110/100 VLM1-TV-110-100/200/96 2CSG123140R4001 744504 1

96 I 300 230/100 VLM1-TV-230-100/300/96 2CSG123170R4001 547808 1

96 I 500 380/100 VLM1-TV-380-100/500/96 2CSG123200R4001 547907 1

96 I 500 400/100 VLM1-TV-400-100/500/96 2CSG123210R4001 744603 1

96 I 600 500/100 VLM1-TV-500-100/600/96 2CSG123220R4001 548003 1

96 I 800 600/100 VLM1-TV-600-100/800/96 2CSG123230R4001 744702 1

96 I 1100 1000/100 VLM1-TV-1000-100/1100/96 2CSG123240R4001 744801 1

Analogue voltmeters for direct current Size Insertion Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm V d.c. Type code Order code EAN kg pc.

48 D 10 VLM-2-10/48 2CSG211040R4001 549307 1

48 D 15 VLM-2-15/48 2CSG211050R4001 549406 1

48 D 25 VLM-2-25/48 2CSG211070R4001 549505 1

48 D 40 VLM-2-40/48 2CSG211090R4001 549604 1

48 D 60 VLM-2-60/48 2CSG211110R4001 549703 1

48 D 80 VLM-2-80/48 2CSG211120R4001 549802 1

48 D 100 VLM-2-100/48 2CSG211130R4001 549901 1

48 D 150 VLM-2-150/48 2CSG211150R4001 550006 1

48 D 200 VLM-2-200/48 2CSG211160R4001 550105 1

48 D 250 VLM-2-250/48 2CSG211180R4001 550204 1

48 D 400 VLM-2-400/48 2CSG211210R4001 550303 1

48 D 600 VLM-2-600/48 2CSG211230R4001 550402

72 D 10 VLM-2-10/72 2CSG212040R4001 551003 1

72 D 15 VLM-2-15/72 2CSG212050R4001 551102 1

72 D 25 VLM-2-25/72 2CSG212070R4001 551201 1

72 D 40 VLM-2-40/72 2CSG212090R4001 551300 1

72 D 60 VLM-2-60/72 2CSG212110R4001 551409 1

72 D 80 VLM-2-80/72 2CSG212120R4001 551508 1

72 D 100 VLM-2-100/72 2CSG212130R4001 551607 1

72 D 150 VLM-2-150/72 2CSG212150R4001 551706 1

72 D 200 VLM-2-200/72 2CSG212160R4001 551805 1

72 D 250 VLM-2-250/72 2CSG212180R4001 551904 1

72 D 400 VLM-2-400/72 2CSG212210R4001 552000 1

72 D 600 VLM-2-600/72 2CSG212230R4001 552109

96 D 10 VLM-2-10/96 2CSG213040R4001 552703 1

96 D 15 VLM-2-15/96 2CSG213050R4001 552802 1

96 D 25 VLM-2-25/96 2CSG213070R4001 552901 1

96 D 40 VLM-2-40/96 2CSG213090R4001 553007 1

96 D 60 VLM-2-60/96 2CSG213110R4001 553106 1

96 D 80 VLM-2-80/96 2CSG213120R4001 553205 1

96 D 100 VLM-2-100/96 2CSG213130R4001 553304 1

96 D 150 VLM-2-150/96 2CSG213150R4001 553403 1

96 D 200 VLM-2-200/96 2CSG213160R4001 553502 1

96 D 250 VLM-2-250/96 2CSG213180R4001 553601 1

96 D 400 VLM-2-400/96 2CSG213210R4001 553700 1

96 D 600 VLM-2-600/96 2CSG213230R4001 553809 1

Size Insertion Scale VT type Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm V a.c. Type code Order code EAN kg pc.

pro M compact® Selection tables Measurement devices Front panel analogue instruments AMT Analogue ammeters for alternating current Size Insertion Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm A a.c. Type code Order code EAN kg pc.

48 D 1 AMT1-A1-1/48 2CSG311020R4001 543107 1

48 D 5 AMT1-A1-5/48 2CSG311030R4001 543206 1

48 D 10 AMT1-A1-10/48 2CSG311040R4001 543305 1

48 D 15 AMT1-A1-15/48 2CSG311050R4001 543404 1

48 D 20 AMT1-A1-20/48 2CSG311060R4001 543503 1

48 D 25 AMT1-A1-25/48 2CSG311070R4001 543602 1

48 D 30 AMT1-A1-30/48 2CSG311080R4001 543701 1

48 D 40 AMT1-A1-40/48 2CSG311090R4001 543800 1

48 I 1In/5 AMT1-A1/48 2CSG321250R4001 543909 1

48 I 5In/5 AMT1-A5/48 2CSG321260R4001 544005 1

72 D 1 AMT1-A1-1/72 2CSG312020R4001 545507 1

72 D 5 AMT1-A1-5/72 2CSG312030R4001 545606 1

72 D 10 AMT1-A1-10/72 2CSG312040R4001 545705 1

72 D 15 AMT1-A1-15/72 2CSG312050R4001 545804 1

72 D 20 AMT1-A1-20/72 2CSG312060R4001 545903 1

72 D 25 AMT1-A1-25/72 2CSG312070R4001 546009 1

72 D 30 AMT1-A1-30/72 2CSG312080R4001 546108 1

72 D 40 AMT1-A1-40/72 2CSG312090R4001 546207 1

72 D 50 AMT1-A1-50/72 2CSG312100R4001 546306 1

72 D 60 AMT1-A1-60/72 2CSG312110R4001 546405 1

72 I 1In/5 AMT1-A1/72 2CSG322250R4001 546504 1

72 I 5In/5 AMT1-A5/72 2CSG322260R4001 546603 1

96 D 1 AMT1-A1-1/96 2CSG313020R4001 548102 1

96 D 5 AMT1-A1-5/96 2CSG313030R4001 548201 1

96 D 10 AMT1-A1-10/96 2CSG313040R4001 548300 1

96 D 15 AMT1-A1-15/96 2CSG313050R4001 548409 1

96 D 20 AMT1-A1-20/96 2CSG313060R4001 548508 1

96 D 25 AMT1-A1-25/96 2CSG313070R4001 548607 1

96 D 30 AMT1-A1-30/96 2CSG313080R4001 548706 1

96 D 40 AMT1-A1-40/96 2CSG313090R4001 548805 1

96 D 50 AMT1-A1-50/96 2CSG313100R4001 548904 1

96 D 60 AMT1-A1-60/96 2CSG313110R4001 549000 1

96 I 1In/5 AMT1-A1/96 2CSG323250R4001 549109 1

96 I 5In/5 AMT1-A5/96 2CSG323260R4001 549208 1

D: direct connection I: indirect connection with VT, CT and shunt, according to the type

Analogue ammeters for direct current Size Insertion Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm A d.c. Type code Order code EAN kg pc.

48 D 0,5 AMT2-A2-0,5/48 2CSG411010R4001 550501 1

48 D 1 AMT2-A2-1/48 2CSG411020R4001 550600 1

48 D 5 AMT2-A2-5/48 2CSG411030R4001 550709 1

48 D 10 AMT2-A2-10/48 2CSG411040R4001 550808 1

48 I In/60mV AMT2-A2/48 2CSG421270R4001 550907 1

72 D 0,5 AMT2-A2-0,5/72 2CSG412010R4001 552208 1

72 D 1 AMT2-A2-1/72 2CSG412020R4001 552307 1

72 D 5 AMT2-A2-5/72 2CSG412030R4001 552406 1

72 D 10 AMT2-A2-10/72 2CSG412040R4001 552505 1

72 I In/60mV AMT2-A2/72 2CSG422270R4001 552604 1

96 D 0,5 AMT2-A2-0,5/96 2CSG413010R4001 553908 1

96 D 1 AMT2-A2-1/96 2CSG413020R4001 554004 1

96 D 5 AMT2-A2-5/96 2CSG413030R4001 554103 1

96 D 10 AMT2-A2-10/96 2CSG413040R4001 554202 1

96 I In/60mV AMT2-A2/96 2CSG423270R4001 554301 1

pro M compact® Selection tables Measurement devices Front panel analogue instruments VLM 2CSC445065F0001 2CSC445068F0001 2CSC445064F0001D: direct connection I: indirect connection with VT, CT and shunt, according to the type

pro M compact® Selection tables Measurement devices Front panel analogue instruments COS FRZ Analogue power factor meters Size Insertion Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm V a.c. Type code Order code EAN kg pc. 48 1mA 90° COS-90/48 2CSG721310R4001 555001 1 transducer 48 1mA 240° COS-240/48 2CSG721320R4001 555100 1 transducer 72 1mA 90° COS-90/72 2CSG722310R4001 555209 1 transducer 72 1mA 240° COS-240/72 2CSG722320R4001 555308 1 transducer 96 1mA 90° COS-90/96 2CSG723310R4001 555407 1 transducer 96 1mA 240° COS-240/96 2CSG723320R4001 555506 1 transducer Analogue frequency meters Size Insertion Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm V a.c. Type code Order code EAN kg pc.

48 D 90° FRZ-90/48 2CSG811310R4001 555605 1

72 D 90° FRZ-90/72 2CSG812310R4001 555704 1

72 D 240° FRZ-240/72 2CSG812320R4001 555902 1

96 D 90° FRZ-90/96 2CSG813310R4001 555803 1

96 D 240° FRZ-240/96 2CSG813320R4001 556008 1

2CSC445076F00012CSC445069F00012CSC445075F0001 2CSC445078F00012CSC445071F00012CSC445077F0001 D: direct connection I: indirect connection with VT, CT and shunt, according to the type

Rated max. reference voltage for insulation [V] 650 Test voltage [V] 2000 eff. (50 Hz/1 min) Precision class 1.5 (0.5 for frequency meters) Overload capacity /L54706 - ammetric windings up to In x 10/< sec. up to In x 2/permanent - voltmetric windings up to Un x 2/< 5 sec. up to Un x 1.2/permanent Operating temperature [°C] -20...+40 Storage temperature [°C] -40...+70 Average and max. relative /L54707 65% (yearly average) humidity (DIN 40040) 85% (+35 °C/60 days a year) Vibration resistance (IEC 50-1) [g Degree of protection IP52 indoors IP00 on the terminals (IEC 144. DIN 40050) IP40 with suitable terminal covers Materials - cases and front edge self-extinguishing thermosetting material in accordance with UL94 V-0, fungus and termite resistant - pointers (DIN 43802) /L54708 molded aluminium - terminals brass Assembly vertical/horizontal with special screw-on brackets /L54709 Dimensions W x H x D (DIN 43700/43718) [mm] 48 x 48 X 53 72 x 72 x 53 96 x 96 X 53 Applicable standards IEC EN 61010-1 /L54706 The overload can be greater for instruments enabled by a CT because the transformer generally keeps secondary current peaks to within 10 In. /L54707 Tropicalization enables the instruments to withstand up to 95% max. relative humidity (+35 °C/60 days). In accordance with DIN standard 40040, they must be protected against any penetration of humidity inside the device. Terminals, screws, washers, bolts and magnets are galvanically protected against rust, while the electrical circuits are painted with the special Multicolor PC52 varnish. /L54708 The pointer damping time is 1 second. The recorded values are cleared by pressing the control provided. /L54709 With 0.5 mm -19 mm thick panels, the screws must be attached in the fixing position nearest to the front edge of the me- asuring device, whereas the 20 mm - 39 mm thick panels require the screws to be fixed in the position furthest away from the front edge. System pro M compact® Selection tables Measurement devices Front panel analogue instruments Insertion via VT N Direct insertion N Direct insertion Direct insertion N Insertion via CT N S1 S2 P1 P2 Direct insertion Insertion with Shunt Voltmeter for alternating current Volt meter for direct current Ammeter for alternating current A mmeter for direct current 2CSC400129F0202

pro M compact® Selection tables Measurement devices Interchangeable scales for front panel instrument SCL Interchangeable scales Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit A a.c. Type code Order code EAN kg pc. Scales 48 x 48 mm, SCL-A1 for AMT1-A1/48 a.c. ammeters 1 SCL-A1-1/48 2CSG111010R5011 769408 0.010 10 5 SCL-A1-5/48 2CSG111021R5011 769507 0.010 10 10 SCL-A1-10/48 2CSG111032R5011 769606 0.010 10 15 SCL-A1-15/48 2CSG111054R5011 769705 0.010 10 20 SCL-A1-20/48 2CSG111075R5011 769804 0.010 10 25 SCL-A1-25/48 2CSG111096R5011 769903 0.010 10 30 SCL-A1-30/48 2CSG111107R5011 770008 0.010 10 40 SCL-A1-40/48 2CSG111128R5011 770107 0.010 10 50 SCL-A1-50/48 2CSG111149R5011 770206 0.010 10 60 SCL-A1-60/48 2CSG111159R5011 770305 0.010 10 80 SCL-A1-80/48 2CSG111179R5011 770404 0.010 10 100 SCL-A1-100/48 2CSG111189R5011 560500 0.010 10 150 SCL-A1-150/48 2CSG111209R5011 560609 0.010 10 200 SCL-A1-200/48 2CSG111229R5011 560708 0.010 10 250 SCL-A1-250/48 2CSG111249R5011 560807 0.010 10 300 SCL-A1-300/48 2CSG111259R5011 560906 0.010 10 400 SCL-A1-400/48 2CSG111279R5011 561002 0.010 10 500 SCL-A1-500/48 2CSG111299R5011 561101 0.010 10 600 SCL-A1-600/48 2CSG111309R5011 561200 0.010 10 800 SCL-A1-800/48 2CSG111329R5011 561309 0.010 10 1000 SCL-A1-1000/48 2CSG111339R5011 561408 0.010 10 1500 SCL-A1-1500/48 2CSG111359R5011 561507 0.010 10 2000 SCL-A1-2000/48 2CSG111379R5011 561606 0.010 10 2500 SCL-A1-2500/48 2CSG111389R5011 561705 0.010 10 3000 SCL-A1-3000/48 2CSG111399R5011 561804 0.010 10 4000 SCL-A1-4000/48 2CSG111409R5011 561903 0.010 10 5000 SCL-A1-5000/48 2CSG111419R5011 562009 0.010 10 6000 SCL-A1-6000/48 2CSG111429R5011 562108 0.010 10 8000 SCL-A1-8000/48 2CSG111439R5011 562207 0.010 10 10000 SCL-A1-10000/48 2CSG111449R5011 562306 0.010 10 Scales 48 x 48 mm, SCL-A5 for AMT1-A5/48 a.c. ammeters 1 SCL-A5-1/48 2CSG121010R5011 770503 0.010 10 5 SCL-A5-5/48 2CSG121021R5011 770602 0.010 10 10 SCL-A5-10/48 2CSG121032R5011 770701 0.010 10 15 SCL-A5-15/48 2CSG121054R5011 770800 0.010 10 20 SCL-A5-20/48 2CSG121075R5011 770909 0.010 10 25 SCL-A5-25/48 2CSG121096R5011 771005 0.010 10 30 SCL-A5-30/48 2CSG121107R5011 771104 0.010 10 40 SCL-A5-40/48 2CSG121128R5011 771203 0.010 10 50 SCL-A5-50/48 2CSG121149R5011 771302 0.010 10 60 SCL-A5-60/48 2CSG121159R5011 771401 0.010 10 80 SCL-A5-80/48 2CSG121179R5011 771500 0.010 10 100 SCL-A5-100/48 2CSG121189R5011 562405 0.010 10 150 SCL-A5-150/48 2CSG121209R5011 562504 0.010 10 200 SCL-A5-200/48 2CSG121229R5011 562603 0.010 10 250 SCL-A5-250/48 2CSG121249R5011 562702 0.010 10 300 SCL-A5-300/48 2CSG121259R5011 562801 0.010 10 400 SCL-A5-400/48 2CSG121279R5011 562900 0.010 10 500 SCL-A5-500/48 2CSG121299R5011 563006 0.010 10 600 SCL-A5-600/48 2CSG121309R5011 563105 0.010 10 800 SCL-A5-800/48 2CSG121329R5011 563204 0.010 10 1000 SCL-A5-1000/48 2CSG121339R5011 563303 0.010 10 1500 SCL-A5-1500/48 2CSG121359R5011 563402 0.010 10 2CSC445111F0001 2CSC445111F0001

pro M compact® Selection tables Measurement devices Interchangeable scales for front panel instrument SCL 2000 SCL-A5-2000/48 2CSG121379R5011 563501 0.010 10 2500 SCL-A5-2500/48 2CSG121389R5011 563600 0.010 10 3000 SCL-A5-3000/48 2CSG121399R5011 563709 0.010 10 4000 SCL-A5-4000/48 2CSG121409R5011 563808 0.010 10 5000 SCL-A5-5000/48 2CSG121419R5011 563907 0.010 10 6000 SCL-A5-6000/48 2CSG121429R5011 564003 0.010 10 8000 SCL-A5-8000/48 2CSG121439R5011 564102 0.010 10 10000 SCL-A5-10000/48 2CSG121449R5011 564201 0.010 10 Scales 72 x 72 mm, SCL-A1 for AMT1-A1/72 a.c. ammeters 1 SCL-A1-1/72 2CSG112010R5011 771609 0.010 10 5 SCL-A1-5/72 2CSG112021R5011 771708 0.010 10 10 SCL-A1-10/72 2CSG112032R5011 771807 0.010 10 15 SCL-A1-15/72 2CSG112054R5011 771906 0.010 10 20 SCL-A1-20/72 2CSG112075R5011 772002 0.010 10 25 SCL-A1-25/72 2CSG112096R5011 772101 0.010 10 30 SCL-A1-30/72 2CSG112107R5011 772200 0.010 10 40 SCL-A1-40/72 2CSG112128R5011 772309 0.010 10 50 SCL-A1-50/72 2CSG112149R5011 772408 0.010 10 60 SCL-A1-60/72 2CSG112159R5011 772507 0.010 10 80 SCL-A1-80/72 2CSG112179R5011 772606 0.010 10 100 SCL-A1-100/72 2CSG112189R5011 572305 0.010 10 150 SCL-A1-150/72 2CSG112209R5011 572404 0.010 10 200 SCL-A1-200/72 2CSG112229R5011 572503 0.010 10 250 SCL-A1-250/72 2CSG112249R5011 572602 0.010 10 300 SCL-A1-300/72 2CSG112259R5011 572701 0.010 10 400 SCL-A1-400/72 2CSG112279R5011 572800 0.010 10 500 SCL-A1-500/72 2CSG112299R5011 572909 0.010 10 600 SCL-A1-600/72 2CSG112309R5011 573005 0.010 10 800 SCL-A1-800/72 2CSG112329R5011 573104 0.010 10 1000 SCL-A1-1000/72 2CSG112339R5011 573203 0.010 10 1500 SCL-A1-1500/72 2CSG112359R5011 573302 0.010 10 2000 SCL-A1-2000/72 2CSG112379R5011 573401 0.010 10 2500 SCL-A1-2500/72 2CSG112389R5011 573500 0.010 10 3000 SCL-A1-3000/72 2CSG112399R5011 573609 0.010 10 4000 SCL-A1-4000/72 2CSG112409R5011 573708 0.010 10 5000 SCL-A1-5000/72 2CSG112419R5011 573807 0.010 10 6000 SCL-A1-6000/72 2CSG112429R5011 573906 0.010 10 8000 SCL-A1-8000/72 2CSG112439R5011 574002 0.010 10 10000 SCL-A1-10000/72 2CSG112449R5011 574101 0.010 10 Scales 72 x 72 mm, SCL-A5 for AMT1-A5/72 a.c. ammeters 1 SCL-A5-1/72 2CSG122010R5011 772705 0.010 10 5 SCL-A5-5/72 2CSG122021R5011 772804 0.010 10 10 SCL-A5-10/72 2CSG122032R5011 772903 0.010 10 15 SCL-A5-15/72 2CSG122054R5011 773009 0.010 10 20 SCL-A5-20/72 2CSG122075R5011 773108 0.010 10 25 SCL-A5-25/72 2CSG122096R5011 773207 0.010 10 30 SCL-A5-30/72 2CSG122107R5011 773306 0.010 10 40 SCL-A5-40/72 2CSG122128R5011 773405 0.010 10 50 SCL-A5-50/72 2CSG122149R5011 773504 0.010 10 60 SCL-A5-60/72 2CSG122159R5011 773603 0.010 10 80 SCL-A5-80/72 2CSG122179R5011 773702 0.010 10 100 SCL-A5-100/72 2CSG122189R5011 574200 0.010 10 150 SCL-A5-150/72 2CSG122209R5011 574309 0.010 10 200 SCL-A5-200/72 2CSG122229R5011 574408 0.010 10 250 SCL-A5-250/72 2CSG122249R5011 574507 0.010 10 300 SCL-A5-300/72 2CSG122259R5011 574606 0.010 10 400 SCL-A5-400/72 2CSG122279R5011 574705 0.010 10 2CSC445111F0001 2CSC445111F0001 Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit A a.c. Type code Order code EAN kg pc.

pro M compact® Selection tables Measurement devices Interchangeable scales for front panel instrument SCL 500 SCL-A5-500/72 2CSG122299R5011 574804 0.010 10 600 SCL-A5-600/72 2CSG122309R5011 574903 0.010 10 800 SCL-A5-800/72 2CSG122329R5011 575009 0.010 10 1000 SCL-A5-1000/72 2CSG122339R5011 575108 0.010 10 1500 SCL-A5-1500/72 2CSG122359R5011 575207 0.010 10 2000 SCL-A5-2000/72 2CSG122379R5011 575306 0.010 10 2500 SCL-A5-2500/72 2CSG122389R5011 575405 0.010 10 3000 SCL-A5-3000/72 2CSG122399R5011 575504 0.010 10 4000 SCL-A5-4000/72 2CSG122409R5011 575603 0.010 10 5000 SCL-A5-5000/72 2CSG122419R5011 575702 0.010 10 6000 SCL-A5-6000/72 2CSG122429R5011 575801 0.010 10 8000 SCL-A5-8000/72 2CSG122439R5011 575900 0.010 10 10000 SCL-A5-10000/72 2CSG122449R5011 576006 0.010 10 Scales 96 x 96 mm, SCL-A1 for AMT1-A1/96 a.c. ammeters 1 SCL-A1-1/96 2CSG113010R5011 773801 0.010 10 5 SCL-A1-5/96 2CSG113021R5011 773900 0.010 10 10 SCL-A1-10/96 2CSG113032R5011 774006 0.010 10 15 SCL-A1-15/96 2CSG113054R5011 774105 0.010 10 20 SCL-A1-20/96 2CSG113075R5011 774204 0.010 10 25 SCL-A1-25/96 2CSG113096R5011 774303 0.010 10 30 SCL-A1-30/96 2CSG113107R5011 774402 0.010 10 40 SCL-A1-40/96 2CSG113128R5011 774501 0.010 10 50 SCL-A1-50/96 2CSG113149R5011 774600 0.010 10 60 SCL-A1-60/96 2CSG113159R5011 774709 0.010 10 80 SCL-A1-80/96 2CSG113179R5011 774808 0.010 10 100 SCL-A1-100/96 2CSG113189R5011 584100 0.010 10 150 SCL-A1-150/96 2CSG113209R5011 584209 0.010 10 200 SCL-A1-200/96 2CSG113229R5011 584308 0.010 10 250 SCL-A1-250/96 2CSG113249R5011 584407 0.010 10 300 SCL-A1-300/96 2CSG113259R5011 584506 0.010 10 400 SCL-A1-400/96 2CSG113279R5011 584605 0.010 10 500 SCL-A1-500/96 2CSG113299R5011 584704 0.010 10 600 SCL-A1-600/96 2CSG113309R5011 584803 0.010 10 800 SCL-A1-800/96 2CSG113329R5011 584902 0.010 10 1000 SCL-A1-1000/96 2CSG113339R5011 585008 0.010 10 1500 SCL-A1-1500/96 2CSG113359R5011 585107 0.010 10 2000 SCL-A1-2000/96 2CSG113379R5011 585206 0.010 10 2500 SCL-A1-2500/96 2CSG113389R5011 585305 0.010 10 3000 SCL-A1-3000/96 2CSG113399R5011 585404 0.010 10 4000 SCL-A1-4000/96 2CSG113409R5011 585503 0.010 10 5000 SCL-A1-5000/96 2CSG113419R5011 585602 0.010 10 6000 SCL-A1-6000/96 2CSG113429R5011 585701 0.010 10 8000 SCL-A1-8000/96 2CSG113439R5011 585800 0.010 10 10000 SCL-A1-10000/96 2CSG113449R5011 585909 0.010 10 Scales 96 x 96 mm, SCL-A5 for AMT1-A5/96 a.c. ammeters 1 SCL-A5-1/96 2CSG123010R5011 774907 0.010 10 5 SCL-A5-5/96 2CSG123021R5011 775003 0.010 10 10 SCL-A5-10/96 2CSG123032R5011 775102 0.010 10 15 SCL-A5-15/96 2CSG123054R5011 775201 0.010 10 20 SCL-A5-20/96 2CSG123075R5011 775300 0.010 10 25 SCL-A5-25/96 2CSG123096R5011 775409 0.010 10 30 SCL-A5-30/96 2CSG123107R5011 775508 0.010 10 40 SCL-A5-40/96 2CSG123128R5011 775607 0.010 10 50 SCL-A5-50/96 2CSG123149R5011 775706 0.010 10 60 SCL-A5-60/96 2CSG123159R5011 775805 0.010 10 80 SCL-A5-80/96 2CSG123179R5011 775904 0.010 10 100 SCL-A5-100/96 2CSG123189R5011 586005 0.010 10 2CSC445111F0001 2CSC445111F0001 Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit A a.c. Type code Order code EAN kg pc.

pro M compact® Selection tables Measurement devices Interchangeable scales for front panel instrument SCL 150 SCL-A5-150/96 2CSG123209R5011 586104 0.010 10 200 SCL-A5-200/96 2CSG123229R5011 586203 0.010 10 250 SCL-A5-250/96 2CSG123249R5011 586302 0.010 10 300 SCL-A5-300/96 2CSG123259R5011 586401 0.010 10 400 SCL-A5-400/96 2CSG123279R5011 586500 0.010 10 500 SCL-A5-500/96 2CSG123299R5011 586609 0.010 10 600 SCL-A5-600/96 2CSG123309R5011 586708 0.010 10 800 SCL-A5-800/96 2CSG123329R5011 586807 0.010 10 1000 SCL-A5-1000/96 2CSG123339R5011 586906 0.010 10 1500 SCL-A5-1500/96 2CSG123359R5011 587002 0.010 10 2000 SCL-A5-2000/96 2CSG123379R5011 587101 0.010 10 2500 SCL-A5-2500/96 2CSG123389R5011 587200 0.010 10 3000 SCL-A5-3000/96 2CSG123399R5011 587309 0.010 10 4000 SCL-A5-4000/96 2CSG123409R5011 587408 0.010 10 5000 SCL-A5-5000/96 2CSG123419R5011 587507 0.010 10 6000 SCL-A5-6000/96 2CSG123429R5011 587606 0.010 10 8000 SCL-A5-8000/96 2CSG123439R5011 587705 0.010 10 10000 SCL-A5-10000/96 2CSG123449R5011 587804 0.010 10 Scales 48 x 48 mm, SCL-A2 for AMT2-A2/48 d.c. ammeters 20 SCL-A2-20/48 2CSG231075R5011 595908 0.010 10 100 SCL-A2-100/48 2CSG231189R5011 596004 0.010 10 150 SCL-A2-150/48 2CSG231209R5011 596103 0.010 10 200 SCL-A2-200/48 2CSG231229R5011 596202 0.010 10 250 SCL-A2-250/48 2CSG231249R5011 596301 0.010 10 300 SCL-A2-300/48 2CSG231259R5011 596400 0.010 10 400 SCL-A2-400/48 2CSG231279R5011 596509 0.010 10 500 SCL-A2-500/48 2CSG231299R5011 596608 0.010 10 600 SCL-A2-600/48 2CSG231309R5011 596707 0.010 10 800 SCL-A2-800/48 2CSG231329R5011 596806 0.010 10 1000 SCL-A2-1000/48 2CSG231339R5011 596905 0.010 10 Scales 72 x 72 mm, SCL-A2 for AMT2-A2/72 d.c. ammeters 20 SCL-A2-20/72 2CSG232075R5011 597001 0.010 10 100 SCL-A2-100/72 2CSG232189R5011 597100 0.010 10 150 SCL-A2-150/72 2CSG232209R5011 597209 0.010 10 200 SCL-A2-200/72 2CSG232229R5011 597308 0.010 10 250 SCL-A2-250/72 2CSG232249R5011 597407 0.010 10 300 SCL-A2-300/72 2CSG232259R5011 597506 0.010 10 400 SCL-A2-400/72 2CSG232279R5011 597605 0.010 10 500 SCL-A2-500/72 2CSG232299R5011 597704 0.010 10 600 SCL-A2-600/72 2CSG232309R5011 597803 0.010 10 800 SCL-A2-800/72 2CSG232329R5011 597902 0.010 10 1000 SCL-A2-1000/72 2CSG232339R5011 598008 0.010 10 Scales 96 x 96 mm, SCL-A2 for AMT2-A2/96 d.c. ammeters 20 SCL-A2-20/96 2CSG233075R5011 598107 0.010 10 100 SCL-A2-100/96 2CSG233189R5011 598206 0.010 10 150 SCL-A2-150/96 2CSG233209R5011 598305 0.010 10 200 SCL-A2-200/96 2CSG233229R5011 598404 0.010 10 250 SCL-A2-250/96 2CSG233249R5011 598503 0.010 10 300 SCL-A2-300/96 2CSG233259R5011 598602 0.010 10 400 SCL-A2-400/96 2CSG233279R5011 598701 0.010 10 500 SCL-A2-500/96 2CSG233299R5011 598800 0.010 10 600 SCL-A2-600/96 2CSG233309R5011 598909 0.010 10 800 SCL-A2-800/96 2CSG233329R5011 599005 0.010 10 1000 SCL-A2-1000/96 2CSG233339R5011 599104 0.010 10 2CSC445111F0001 Scale Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit A a.c. Type code Order code EAN kg pc.

2CSC445131F00012CSC445130F0001 2CSC445224F00012CSC445223F00012CSC445222F0001 System pro M compact® Selection tables Measurement devices Caps and terminal covers COP Caps and terminal covers Providing protection against accidental bumping or contact, they also assure a degree of protection to IP55. They come in three standard sizes, 48 mm x 96 mm, 72 mm x 72 mm and 96 mm x 96 mm. Size Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm Type code Order code EAN kg pc. Caps 48 x 96 Trasparent cover COP-48-96 2CSG300000R5041 611608 1 IP55 for instruments 72 x 72 Trasparent cover COP-72 2CSG400000R5041 611707 1 IP55 for instruments 96 x 96 Trasparent cover COP-96 2CSG500000R5041 611806 1 IP55 for instruments Size Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit mm Type code Order code EAN kg pc. Terminal covers 48 x 48 Terminal cover COP-M-48 2CSG300000R5051 619901 1 72 x 72 Terminal cover COP-M-72 2CSG400000R5051 620006 1 96 x 96 Terminal cover COP-M-96 2CSG500000R5051 620105 1

pro M compact® Selection tables Measurement devices Digital instruments VLMD, AMTD, FRZ-DIG Digital instruments The wide range of digital instrument starts with single phase instrument, for measuring voltage, current and frequency. d.c. current, and frequency meter. Ammeters measure in indirect insertion thanks to measuring accessories, like current transformer for a.c. and shunt for d.c. The full scale is programmable by the user. Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. a.c./d.c. digital voltmeter VLMD-1-2 2CSM110000R1011 620402 0,300 1 a.c. digital ammeter AMTD-1 2CSM320000R1011 620501 0,300 1 d.c. digital ammeter AMTD-2 2CSM420000R1011 620600 0,300 1 Digital frequency meter FRZ-DIG 2CSM710000R1011 620709 0,300 1 Digital instruments with alarm relay The range comprises 3 instruments, one voltmeter and two ammeters, that display and monitor a value, tripping a relay contact and signalling the alarm condition if it over- or undershoots a program- mable threshold. The alarm threshold as either a minimum or a maximum limit, the peak maximum and minimum values measured are stored in the non volatile instrument memory. The contact type is NO, so that the contact is open when the instrument is powered off, but it is possible to obtain positive safety operation via a software setting which determines whether the alarm condition is with an open or closed contact. The instrument with relay can be used as either a minum or maximum relay, but not for both functions simultaneously. Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. a.c./d.c. digital voltmeter with alarm relay VLMD-1-2-R 2CSM274693R1011 746935 0,300 1 a.c. digital ammeter with alarm relay AMTD-1-R 2CSM274773R1011 747734 0,300 1 d.c. digital ammeter with alarm relay AMTD-2-R 2CSM261073R1011 610731 0,300 1 2CSC400527F02012CSC400528F02012CSC400748F00012CSC400527F02012CSC400528F0201

pro M compact® Selection tables Measurement devices Front panel digital instruments VLMD P AMTD P Front panel digital instruments The wide range of digital instrument starts with single phase instrument, for measuring voltage and current. d.c. current. Ammeters measure in indirect insertion thanks to measuring accessories, like current transformer for a.c. and shunt for d.c. The full scale is programmable by the user. Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. a.c./d.c. digital voltmeter VLMD P 2CSG213605R4011 136057 0,300 1 a.c. digital ammeter AMTD-1 P 2CSG213615R4011 136156 0,300 1 d.c. digital ammeter AMTD-2 P 2CSG213625R4011 136255 0,300 1 Front panel digital instruments with alarm relay The range comprises 3 instruments, one voltmeter and two ammeters, that display and monitor a value, tripping a relay contact and signalling the alarm condition if it over- or undershoots a program- mable threshold. The alarm threshold as either a minimum or a maximum limit. The peak maximum and minimum values measured are stored in the non volatile instrument memory. The contact type is NO, so that the contact is open when the instrument is powered off, but it is possible to obtain positive safety operation via a software setting which determines whether the alarm condition is with an open or closed contact. The instrument with relay can be used as either a minum or maximum realy, but not for both functions simultaneously. Version Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. a.c./d.c. digital voltmeter with alarm relay VLMD-R P 2CSG213635R4011 136354 0,300 1 a.c. digital ammeter with alarm relay AMTD-1-R P 2CSG213645R4011 136453 0,300 1 d.c. digital ammeter with alarm relay AMTD-2-R P 2CSG213655R4011 136552 0,300 1 2CSC400130F02022CSC400131F0202 Alarm activation logic Device status NO polarity (default) NC polarity Instrument not supplied Instrument supplied - no alarm Instrument supplied - alarm condition

pro M compact® Selection tables Measurement devices Digital instruments Wiring diagrams for digital instruments, both modular and front panel Technical features Power supply [V] 230 V a.c. Rated frequency [Hz] 50÷60 Ammeter full scale value [A] 5, 20, 25, 40, 60, 100, 150, 200, 250, 400, 600 Voltmeter full scale value [V] 300, 500 Frequency meter range [Hz] 35...400 Tripping delay [s] 1, 5, 10, 20, 30 Hysteresis [%] 5, 10, 20, 30 set threshold Output pins 3-4 Output relay NO Rated voltage relay [V] 230 V a.c. Rated current relay [A] AC1 16, AC15 3 Relay configuration NO relay closes in alarm status NC relay opens in alarm status, positive safety Overload [In/Vn] 1, 2 Accuracy class [%] ±0,5 full scale ±1digit at 25 °C Display 3 digit LED display Operating temperature [°C] -10…+55 Storage temperature [°C] -40...+70 Protection degree IP20 Power consumption [VA] 4 Modules 3 Overall dimensions front panel devices [mm] 36x72x61.5 (51.5 depth inside the switchboard) Standard IEC EN 61010 VLMD-1-2 and VLMD-1-2-R VLMD P and VLMD-R P /MT49/MT50 /MT53/MT54/MT51/MT52 /MT49/MT50 /MT53/MT54/MT51/MT52 /MT49/MT50 /MT53/MT54/MT51/MT52 /MT49/MT50 /MT53/MT54/MT51/MT52 FRZ-DIG AMTD-1 and AMTD-1-R AMTD-1 P and AMTD-1-R P AMTD-2 and AMTD-2-R AMTD-2 P and AMTD-2-R P *Only for instruments with output relay 2CSC400132F0202

Digital measurement instruments with relays Control of a load with the following characteristics: In = 5 A (rated normal operating current) Vn = 230 V a.c. (rated normal operating voltage) Vmin = 200 V a.c. (RLV relay trip) To scroll through the menu items press briefly (<3sec); to confirm press and hold (>3sec). 1 Connect as shown in the diagram (Vmin = 200 V). 2 Press and hold the key to enter the programming menu.

3 Scroll to the ACC menu item and confirm, then choose CC to select direct current operation, and

confirm.

4 Set the full scale value to 300 V

5 Set the alarm threshold at 70 and confirm.

6 Adjust the Delay trimmer: scroll to the dLY menu item and confirm, then select the relay tripping

delay (1…30 sec).

7 Program the alarm reset hysteresis (HySTeresis) at 10% of the threshold: scroll to the HSt menu

item, confirm, and select the value 10. This results in a trip window between 200 and 220 V. The relay will be tripped at 200 V and return to normal operation at 220 V.

8 Set the alarm output polarity: scroll to the OUt menu item and confirm, then choose whether the

contact opens or closes when an alarm is triggered (N.O. by default). V 12 56 VLMD-1-2-R power supply input 230 V a.c. signal input Vn=230 V 220 V Vmin=200 V Normal operation Alarm condition Alarm because inside hysteresis window No alarm because outside hysteresis window Selected hysteresis window = 10% ACC AC CC MENU dLY 1 HSt 5 OUt nO nC tHL/tHH 10...590 rES MENU tA --- 100 150 200 250 400 600 dLY 1 HSt 5 OUt nO nC rES tHL/tHH ---...600 Voltmeters menu layout Ammeters menu layout System pro M compact® Selection tables Measurement devices Digital instruments 2CSC400134F0202 2CSC400135F0202 2CSC400133F0202

pro M compact® Selection tables Measurement devices Modular voltmetric and current switches MCV and MCA MCV - MCA voltmetric and current switches Cam rotary switches are suitable for mounting on EN 50022 rail. In three-phase systems they enable the use of a single measurement instrument (single-phase) for viewing the current or voltage value set through the switch itself. Range Power Order Bbn Price Price Weight Pack loss details 4034656 1 piece group 1 piece unit W Type code Order code EAN kg pc. Voltmeter switches L1, L2, L3 0.5 MCV 4 1SCA 022 404 R4740 52246 9 0.095 1 L1, L2, L3, N 0.5 MCV 7 1SCA 022 647 R7840 52243 8 0.110 1 Current switches 0-1-2-3 0.5 MCA 4 1SCA 022 404 R4821 52245 2 0.110 1 R S T 537 R S T 6 593 N R S T 951 V L1-L2 L2-L3 L3-L1 A V L1-L2 10 12 L2-L3 L3-L1 L1-N L2-N L3-N MCV4 MCA4 MCV7 OEPM0067 Technical features Insulation voltage [V] 600 Rated thermal current [A] 12 Mechanic operations [No.] 1000000 Power consumption [VA] 0.23 Modules [No.] 3 2CSC400519F02012CSC400520F0201

pro M compact® Selection tables Measurement devices Front panel voltage and current switches QCV QCA Front panel QCV - QCA voltage and current switches For use in three-phase systems, to allow a single device to measure the voltage and current settings adjusted by the switches. Measure Position Order Bbn Price Price Weight Pack details 4034656 1 piece group 1 piece unit Type code Order code EAN kg pc. Voltage 4 QCV-4/48 1SCA022780R0770 527990 0.150 1 Current 4 QCA-4/48 1SCA022780R0690 528003 0.150 1 Voltage 7 QCV-7/48 1SCA022780R0850 527983 0.150 1 2CSC445148F00012CSC445150F0001 2CSC400136F0202 Wiring diagrams QCV-4 QCA-4 QCV-7 264 R S T 15 V N 951 1 1 R S T O 10 12 V 826 R S T 13 A

ODINsingle electronic energy meters ODINsingle ODINsingle electronic single phase energy meters ODINsingle is intended for mounting on a DIN rail and is designed in accordance with the ABB Pro M standard. General Features ODINsingle is an active energy, single phase meter for direct metering up to 65A. The LCD display has 6 digits, 6 mm high to ensure easy reading. ODINsingle is made compact, only 2 modules (35 mm) to save space in the installation. A red LED at the front flashes proportionally to the energy consumed. ODINsingle has a temperature range from -25 to +55 (storage +70 °C) Communication ODINsingle has 3 ways to communicate depending on type. - Display at front - Pulse output (option) - IR interface for serial communication (together with serial communication adapter) Type Approval ODINsingle is type approved according to IEC standards, IEC 62052-11 and IEC 62053-21. ODIN- single is also type approved and verified according to MID (2004/22/EC), EN 50470-1 and EN 50470-3. Verification report is available on request. The standards cover all technical aspects of the meter including climate conditions, electromagnetic compatibility (EMC), electrical and mechanical requirements and accuracy. Technical data according to IEC is written within parenthesis in the Technical features. Voltage Pulse output Order Bbn Price Price Weight Pack (V) frequency details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. OD1065 direct connected, single phase meter 65A 230 - OD1065 2CMA131040R1000 310406 0.145 1 OD1365 direct connected, single phase meter 65A, pulse output and resetable 230 100 imp/kWh OD1365 2CMA131041R1000 310413 0.145 1 Technical features Rated voltage Un [V] a.c. 230, -23% to +20% Direct insertion current [A] up to 65 Protection fuse [A] 63 Rated frequency [Hz] 50 (50/60) Starting current [mA] 20 Pulse output frequency [imp] 100 Pulse output max current [mA] 100 Pulse output impulse length [ms] 100 LED frequency [imp] 1000 LED impulse length [ms] 40 Accuracy rating [%] 1 Power consumption [W] 1.0 VA Protection degree [IP] 20 Operating temperature [°C] -25 to +55 Modules [No] 2 Standards EN 50470-1, EN 50470-3 (IEC 62052-11, IEC 62053-21) System pro M compact® ODINsingle wiring diagrams Direct connection

DELTAsingle electronic energy meters DELTAsingleSystem pro M compact DELTAsingle electronic single phase energy meters DELTAsingle is an electronic electricity meter for single phase metering. The meter has an internal clock for handling tariffs. The setting is done with push buttons. DELTAsingle is intended for mounting on a DIN rail and is designed in accordance with the ABB ProM standard. General Features DELTAsingle is an active energy, single phase meter for direct metering up to 80 A. The LCD display has 6 digits, 6 mm high to ensure easy reading. DELTAsingle is made compact, only 4 modules (72 mm) to save space in the installation. In case of power failure, the meter is equipped with a Super Cap power backup that will run the clock for 48 hours. A red LED at the front flashes proportionally to the energy consumed. DELTAsingle has a temperature range from –40 to +55 (storage +70 °C) Communication DELTAsingle has 3 ways to communicate depending on type. - Display at front - Pulse output - IR interface for serial communication (together with serial communication adapter) Programming Selection of information to be shown on the display is easily achieved by using push buttons. The programming / push button can be sealed. Tariffs The DELTAsingle range includes 1, 2 and 4 tariffs meters. Type Approval DELTAsingle is type approved according to IEC standards, IEC 62052-11 and IEC 62053-21. DELTAsingle is also type approved and verified according to MID (2004/22/EC), EN 50470-1 and EN 50470-3. Verification report is available on request. The standards cover all technical aspects of the meter including climate conditions, electromagnetic compatibility (EMC), electrical and me- chanical requirements and accuracy. Technical data according to IEC is written within parenthesis in the Technical features. Description Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. 1 tariff without pulse output FBU 11200 2CMA180891R1000 808910 0.150 1 1 tariff with pulse output FBB 11200 2CMA180892R1000 808927 0.150 1 2 tariff without pulse output FBU 11205 2CMA180893R1000 808934 0.150 1 2 tariff with pulse output FBB 11205 2CMA180894R1000 808941 0.150 1 4 tariff without pulse output FBU 11206 2CMA180895R1000 808958 0.150 1 4 tariff with pulse output FBB 11206 2CMA180896R1000 808965 0.150 1 2CSC400142F0201

DELTAsingle electronic energy meters System pro M compact Technical features General features Voltage [V] 230 AC Voltage range -23 % to +20 % Max current [A] 80 Start current [mA] 40 Power consumption of current circuit [VA] < 1.3 Frequency [Hz] 50 (50/60) ± 5 % Accuracy of measurement ± 1 % Memory backup EEprom Clock backup Super Cap. 48h Clock accuracy IEC 62054-21 Standard EN 50470-1 and EN 50470-3 (IEC 62052-11 and IEC 62053-21) Temperature range [°C] -40 to +55 Material of front cover Polycarbonate Material of back cover Polycarbonate/glass fibre Resistance to heat and fire IEC 60695-2-10 Protection against penetration of dust and water [IP] 20 Connection area in the current connecting terminals [mm 2] 1 - 25 Weight [gr] 150 Pulse output Connection area in the connecting terminal [mm 2] 0.5 - 2.5 External pulse voltage [V] 5 - 40 DC Max. current [mA] 100 Pulse length [ms] 100 Pulse frequency 100 imp/kWh Standard IEC 62053-31 (S0) LED Pulse frequency 1000 imp/kWh Pulse length [ms] 40 Display LCD with 6 digits, 6 mm

ODIN Meter electronic energy meters ODIN MeterSystem pro M compact ODIN Meter electronic three-phase energy meters ODIN Meter is a compact three-phase meter for measuring active energy, designed for mounting on DIN rail, on panel and for flush mounting in distribution switchboard or standard boxes. It is designed and developed to offer extremely easy application and it is equipped with terminals with transparent scores and strong holding screws for connecting cables and terminal boards, phase bus connectors, easy to read 7-digit display, current direction indicator, clear mounting instructions with text and diagrams on the device. ODIN Meter is a highly reliable and strong meter that maintains the highest measuring accuracy in time. Type Approval ODIN is type approved according to IEC standards, IEC 62052-11 and IEC 62053-21. ODIN is also type approved and verified according to MID (2004/22/EC), EN 50470-1 and EN 50470-3. Verifica- tion report is available on request. The standards cover all technical aspects of the meter including climate conditions, electromagnetic compatibility (EMC), electrical and mechanical requirements and accuracy. Technical data according to IEC is written within parenthesis in the Technical features. Active energy meter 3x230/400 (three-phase+N) Description Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. direct up to 65A, impulsive OD4165 2CMA131024R1000 310246 0.38 1 output 100 Imp./kWh indirect with CT/5A, impulsive OD4110 2CMA131025R1000 310253 0.40 1 output 10 Imp./kWh Technical features Direct measuring/connection Connection through A.T. Voltage 3x230/400 V, 3x230/400 V, Current 65 A 10 A Frequency 50 (50/60) Hz 50 (50/60) Hz Selection of insertion currents through 5/5, 75/5, 100/5, 150/5, 200/5, 700/5, 750/5, 800/5, 900/5 A Starting current 25 mA 15 mA Pulse output max. current 100 mA 100 mA Pulse output impulse length 100 ms 100 ms Pulse output frequency 100 imp/kWh 10 imp/kWh LED frequency 100 imp/kWh 1000 imp/kWh LED pulse length 40 ms 40 ms Accuracy rating ±2% ±2% Display 7-digit LCD 7-digit LCD Protection degree IP 20 IP 20 Operating temperature -25 + 55 °C 25 + 55 °C Standards EN 50470-1, EN 50470-3 EN 50470-1, EN 50470-3 IEC 62052-11 and IEC 62053-21 IEC 62052-11 and IEC 62053-21 ODIN series wiring diagrams 11 36920 21 11 147 N L1 L2 L3 N L1 L2 L3 - Direct connection - Indirect connection (through C.T.) 11 36920 21 11 147 25 8 PE N P1 P2 S1 S2 2CSC400280F0201 2CSC400137F0202

pro M compact® Selection tables Measurement devices DELTAplus/DELTAmax electronic energy meters DELTAplusSystem pro M compact DELTAplus DELTAmax DELTAplus electronic three-phase energy meters DELTAplus meters are designed to offer extremely easy and simple application. Suitable for mounting on DIN rail, lightweight and small, they are ideal for the installation on switchboards, feeder panels and enclosed. The range includes devices for measuring active energy, and the combination of active and reactive energy. Type Approval DELTAplus is type approved according to IEC standards, IEC 62052-11 and IEC 62053-21 (IEC 62053-23). DELTAplus is also type approved and verified according to MID (2004/22/EC), EN 50470-1 and EN 50470-3. Verification report is available on request. The standards cover all technical aspects of the meter including climate conditions, electromagnetic compatibility (EMC), electrical and mechanical requirements and accuracy. Technical data according to IEC is written within parenthesis in the Technical features. Description Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Energy meters for direct connection up to 80 A, class 2 3 x 100-500 V AC (3P) DBB 22000 2CMA180802R1000 808026 0.338 1 3 x 57-288/100-500 VAC (3P+N) DBB 23000 2CMA180800R1000 808002 0.338 1 3 x 57-288/100-500 VAC (3P+N) + active/reactiv DDB 13000 2CMA180810R1000 808101 0.338 1 Energy meters for connection through C.T. /5 A, class 2 3 x 100-500 V AC (3P) DAB 12000 2CMA180807R1000 808071 0.304 1 3 x 57-288/100-500 VAC (3P+N) DAB 13000 2CMA180806R1000 808064 0.304 1 3 x 57-288/100-500 VAC (3P+N) + active/reactiv DCB 13000 2CMA180808R1000 808088 0.304 1 DELTAmax advanced electronic three-phase energy meter DELTAmax is a further enhancement of DELTAplus. Additional features for DELTAmax are: Four quadrant metering (import and export of energy) Time dependent functions including - Load profile (15, 30, 60 min interval) - Max demand - Event and quality logs - Monthly or Daily values (selectable) Total Harmonic Distortion (THD) up to 9th harmonic (50 Hz network) Type Approval DELTAmax is type approved according to IEC standards, IEC 62052-11 and IEC 62053-21 (IEC 62053-23). DELTAmax is also type approved and verified according to MID (2004/22/EC), EN 50470-1 and EN 50470-3. Verification report is available on request. The standards cover all technical aspects of the meter including climate conditions, electromagnetic compatibility (EMC), electrical and mechanical requirements and accuracy. Technical data according to IEC is written within parenthesis in the Technical features. Description Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Energy meters for direct connection up to 80 A 3x57-288/100-500 VAC (3P+N) DFB 13007 2CMA139504R1000 395045 3x57-288/100-500VAC (3P+N) DFM 13007 2CMA139507R1000 + M-Bus 3x100-500 VAC (3P) + M-Bus DFM 12007 2CMA139508R1000 3x57-288/100-500 VAC (3P+N) DHB 13007 2CMA139520R1000 + active/reactive 2CSC400549F02012CSC400161F0201

pro M compact® Selection tables Measurement devices DELTAplus/DELTAmax electronic energy meters DELTAplus DELTAmax Technical features - DELTAplus and DELTAmax Voltage [V] 3 x 57-288 / 100-500 (4-wire, 3-element) 3 x 100-500 (3 wire, 2-element) 1 x 57-288 (Single phase) Current [A] ≤80 (direct connection); ≤6 (indirect connection through C.T.) Frequency [Hz] 50 (50/60) Starting current [mA] 20 (direct connection), 2 (C.T. connection) Pulse output frequency [imp/kWh] programmable Pulse output inpulse length [ms] 100 LED frequency [imp/kWh] 1000 (direct connection), 5000 (C.T. connection) Pulse output -max. current [mA] 100 -max. cable section [mm 2] 2.5 -standards IEC 62053-31 for pulse output Standards EN 50470-1 and EN 50470-3 (IEC 62052-11 and IEC 62053-21 for active energy meters; IEC 62053-23 for reactive energy meters) Accuracy 1 or 2% Display LCD (liquid crystal) with 7 digits, h=7mm Terminal holder 10 mm 2 (insertion through C.T.); 25 mm2 (direct insertion) Protection degree IP51 (IP20 on the terminal holder without cover) Operating temperature [°C] -40 +70 Power consumption <1 VA, 1 W Modules [No] 7 Description Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Energy meters for connection through C.T. /5A 3x57-288/100-500 VAC (3P+N) DEB 13007 2CMA139497R1000 3x57-288/100-500VAC (3P+N) DEM 13007 2CMA139500R1000 + M-Bus 3x100-500 VAC (3P) + M-Bus DEM 12007 2CMA139549R1000 3x57-288/100-500 VAC (3P+N) DGB 13007 2CMA139511R1000 + active/reactive Auxiliary elements/accessories Long cover DELTA/CPL 2CMA132633R1000 326339 1 DIN rail DELTA/DIN 2CMA132540R1000 325400 1 Front mounting kit DELTA/FRQ 2CMA132635R1000 325417 1 2CSC400120F0202

DELTAplus/DELTAmax electronic energy meters DELTAplus DELTAmax System pro M compact Wiring diagrams - DELTAplus and DELTAmax 20 21 kWh Ω 22 21 hVarh Ω kWh Ω 2-pole balanced or 3-pole unbalanced output for sending to a personal computer information from energy meter, encoded as numerical signal. Some types enable to connect an external voltage to control teleset Notes For connections through current transformer, C.T. must have 5 A or 1 A secondary and be connected according to correct polarities: P1->P2, S1->S2 Secondary measurement for Imax < 6 A Connection through external current transformer to the three-phase network without neutral (3 cables) 230/400 V Max. cable section: 10 mm Adjustable transformation ratio 1 23456789 L 1 L 2 L 3 DEB 12 XX XX DAB 12 XX XX Direct measurement up to Imax = 80 A Direct connection to the three-phase network without neutral (3 cables) 230/400 V Max. cable section: 25 mm 1 23456789 L 1 L 2 L 3 DBB 22 XX XX DFB 12 XX XX 1 23456789 1 1 L 1 L 2 L 3 N DDB 23 XX XX DHB 13 XX XX Direct measurement up to Imax = 80 A Direct connection to the three-phase network with neutral (4 cables) 230/400 V Max. cable section: 25 mm 1 23456789 1 1 L 1 L 2 L 3 N DAB 13 XX XX DEB 13 XX XX Secondary measurement for Imax < 6 A Connection through external current transformer to the three-phase network with neutral (4 cables) 230/400 V Max. cable section: 10 mm Adjustable transformation ratio OEPM0077

Accessories for electronic energy meters Accessories for electronic energy meters System pro M compact Module Protocol/Media Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Serial Communication Adapter M-bus M-Bus/M-Bus CTM 04000 2CMA137090R1000 370905 0.090 1 RS232 M-Bus/RS232 CRM 04000 2CMA137091R1000 370912 0.090 1 Twisted pair Ethernet M-Bus over TCP or CEM 05100 2CMA137121R1000 0.090 1 UDP , built in web- server EIB/KNX EIB/KNX/Twisted Pair ZS/S 2CDG110083R1011 0.100 1 SCA GSM/GPRS M-bus The GSM/GPRS communication adapter is a quard band GSM/GPRS device, which enables AMR with GSM or GPRS over GSM 850/900 and GSM 1800/1900 networks. Further more the ABB GSM/GPRS communication adapter support remote configuration using Short Message Service (SMS) and Over The Air (OTA) downloading of application, which provides flexible configuration and easy upgrading of the adapter. The adapter is powered with 100-240 VAC (-15/+10%). Module Protocol/Media Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Serial Communication Adapter GSM/GPRS M-Bus over CSD/GSM CGM 05000 2CMA137104R1000 371049 0.105 1 M-Bus over TCP or UDP/GPRS SCA M-bus extender The CMM 05000 is an M-Bus over IR to M-Bus 2-wire communication module. The CMM 05000 gives the possibilities to connect up to 32 M-Bus slaves to one serial communication adapter. The module is mounted between a serial communicationa dapter (e.g. CEM 05100 or CGM 05000) and the meter. Module Protocol/Media Order Bbn Price Price Weight Pack details 7392696 1 piece group 1 piece unit Type code Order code EAN kg pc. Serial Communication Adapter M-Bus M-Bus over IR/ CMM 05000 2CMA137120R1000 371209 0.105 1 extender M-Bus over TP MID - Measuring Instrument Directive From October 30, 2006 common rules applies in European Union for electricity meters for domestic, business and light industry through the measurement instruments directive (MID). ABB and its accredited laboratory (SE1818) are certified to performed first time verification of Active Electrical Energy Meters (MI-003) according to Annex D and the equivalent clauses of ISO 9001. The MID approvals are automatically valid in the entire EU and EEA. All our meters are type approved according to standards EN 50470-1 and EN 50470-3. MID approved and verified products are marked with the MID symbol (e.g. CE M09 0122) on the product and packaging label. 2CMC480005F0006

pro M compact® Selection tables Measurement devices E 233 hour counters E 233 E 233 electro-mechanical hour counters Hour counters are used to record operating times as well as to determine idle times and off times of industrial machinery and plant, for commercial purposes or in domestic installations. No reset functionality. Rated Order Bbn Price Price Weight Pack voltage details 4012233 1 piece group 1 piece unit Type code Order code EAN kg pc. AC 230 V/50 Hz E 233-230 2CDE100000R1601 63000 4 0.05 10 AC 24 V/50 Hz E 233-24 2CDE400000R1601 63010 3 0.05 10 DC 12 V ... 48 V E 233-12/48 2CDE300010R1601 63020 2 0.05 10 AC 240 V/60 Hz E 233-240/60 Hz* 2CDE100021R1601 36590 1 /L54706 0.05 10 AC 120 V/60 Hz E 233-120/60 Hz* 2CDE600021R1601 36600 7 /L54706 0.05 10 AC 24 V/60 Hz E 233- 24/60 Hz* 2CDE400021R1601 36610 6 /L54706 0.05 10 Other rated voltages upon request. /L54706 Bbn No. 40 16779 * U L approval Wiring diagram SK 0011 Z 96 elapsed-time meter E 233-12/48 DC SK 0129 Z 96 Technical features AC equipment DC equipment Rated voltage 50 Hz: 24 V, 230 V DC 12 V ... 48 V

60 Hz: 24 V, 120 V, 240 V*

Voltage tolerance ±15 % ±10 % Power consumption 1.5 VA ca. 20 mW (at 12 V DC) Counting capacity 99.999 h 99.999 h Precision class 0.01 h 0.1 h Operation display fast running LED blinking Protection against electric shock according to DIN VDE 0106 according to DIN VDE 0106 Part 100 (BGV A2) Part 100 (BGV A2) Terminal size up to 10 mm 2 up to 10 mm 2 * UL approval 2CSC400459F0201

pro M compact® Selection tables Measurement devices HMT hour counters HMT HMT electro-mechanical hour counters Equipped with 7-digit indicator (99.999,99) and available in two modules. They cannot be reset. Rated Order Bbn Price Price Weight Pack voltage details 8012542 1 piece group 1 piece unit V AC Type code Order code EAN kg pc. 24 HMT 1/24 2CSM111000R1601 030300 0.200 6 110 HMT 1/110 2CSM121000R1601 030409 0.200 6 220 HMT 1/220 2CSM131000R1601 030508 0.200 6 230 HMT 11 2CSM133000R1601 030607 0.200 1 Technical features Rated voltage Un [V] a.c. 24 a.c. 110 a.c. 230 Displayed digits (in hours) [n°] 99,999.9 (for HMT1 and HMT11) Accuracy class [%] 0.5 Frequency [Hz] 50 Modules [No.] 2 Wiring diagram 2CSC400524F0201 9+] 9a+]+07 K 9+] K K +07 HMT 1 HMT 11 2CSC400138F0202

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments TMD Temperature control units TMD are used measure and control the temperature levels and efficiency of electric machines, power transformers, motors, etc. The temperature is measured by four PT100 type sensors. Each measuring channel has two programmable alarm thresholds which trip two output relays to remotely signal that a critical temperature has been reached. The measured values and any alarm conditions are shown on the dual 3-digit display on the front of the device, which also has five programming keys for configuring its operation. The control unit is also able to store in memory maximum values and a log of all trip-events. Temperature measured Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. 4 TMD-4/96 2CSG524000R2021 560203 0.8 1 Technical features Auxiliary supply Alternating current [V] 20÷250 ±15% Direct current [Hz] 115-230-400 50-60 Power consumption [VA] 4 max Input Sensor PT100 RTD (not included) Type 3 wires (2 and 4 wires types are also supported) Error 1 degree every 0,39 Ω Measure range [°C] 0...220 ± 2 Compensation [Ω] 20 max Trip delay/hysteresis [s/°C] 5/2 Output Number 4 Type NO-CO-NC Vmax [V] 12 d.c. Imax [A] 8 (resistive load) Functions Alarm, trip, cooling, auto-test Programmable functions Alarm, tip, hold, fan, temp. max Display 7 segments LED Connections Terminals removable screw Max section [mm2] 2.5 Insulation voltage [V] 2500/50 Hz - 1 min Protection degree Front IP52 Rear IP20 Operation temperature [°C] -10...+55, relative humidity max 90% Storage temperature [°C] -25...+80 Reference IEC EN 50081-2, IEC EN 50082-2, IEC EN 60255 2CSC400140F0202

pro M compact® Selection tables Measurement devices Measurement modular current transformers TRF M 2CSC400522F0201 Modular current transformers with Ø 29 mm through primary, secondary .../5A TFR M are modular current transformers with through primary for measuring instruments. Their compact size and quick DIN rail plug allow easy installation along with great measurement preci- sion. Primary Accurancy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. 40 3 1 TRFM/40 2CSM100050R1111 046912 0.721 4 60 1 2 TRFM/60 2CSM100070R1111 047018 0.744 4 100 0.5 2 TRFM/100 2CSM100090R1111 047117 0.744 4 150 0.5 3 TRFM/150 2CSM100100R1111 047216 0.712 4 250 0.5 4 TRFM/250 2CSM100120R1111 047315 0.746 4 400 0.5 6 TRFM/400 2CSM100140R1111 047407 0.780 4 600 0.5 7 TRFM/600 2CSM100160R1111 047506 0.859 4 Technical features Frequency 50÷60 Hz Insulation reference voltage 0,72 kV Test voltage 3 kV x 1’ 50 Hz Insulation class B Protection degree IP20 Permanent overcurrent 1,2 In Thermal short-time current 40 In Operating temperature -25 ÷ +50 °C Storage temperature -40 ÷ + 80 °C Reference standards IEC EN 60044-1, IEC 61010-1

Standard secondary current [A] 5 Max. voltage for operation /L54706 [kV] 1.2 Test voltage /L54707 [kV] 6 at 50 Hz/1 min. Short circuit rated thermal current Imin /L54708 [IpN] 40 for 1 sec. Short circuit rated dynamic current Imin /L54709 [I ter] 2.5 for 1 sec. Permanent overload [IpN] 1.2 Safety factor /L54710 [Fs] ≤2 at ≤10 according to version and capacity Frequency [Hz] 50/60 Air insulation E class Terminals /L54711 primary = P1, P2 (K-L) secondary = s1, s2 (k-l) P1 (K)=primary wound input P2 (L)=primary wound output s1 (k)=secondary wound input s2 (l)=secondary wound output with double ration on secondary s1-s2=lower ratio, s1-s3=higher ratio Housing ABS resin Protection degree IP30 Operating temperature [°C] -20…+50 Max. temperature on bars [°C] +70 Storage temperature [°C] -40…+80 Relative humidity 80% Reference standard EN 61010, IEC-EN 60044-1 /L54706 Max. voltage (effective value) the transformer can bear. /L54707 Industrial frequency voltage in relation to insulation the transformer bears for 1 min. between the primary and the secondary. /L54708 Max. primary current (effective value) the transformer bears for 1 sec. with counter-circuited secondary without overload-induced damages. /L54709 Max. primary current (effective value) the transformer bears for 1 sec. with counter-circuited secondary without damaged due to electromagnetic efforts. /L54710 Ratio between primary current causing nucleus saturation and the rated primary current value: the lower the Sf the higher the protection level on the transformer. /L54711 Brass terminals CuZn37, M4x6 screws with torsion value 1.9 Nm, tensile value 440 N/mm2 and elasticity limit 340 N/mm2. During the installation control the correct input (P1-K) and output (P2-L) direction of the primary cable. On versions with primary and secondary on terminals pay attention the connection of the primary with the secondary is not inve rted. In the case of a detachment from measurement devices of the transformer in a connected plant counter-circuit the two terminals of the transformer. It is suggested to earth the transformers. System pro M compact® Selection tables Measurement devices Current transformers CT CTA CT and CTA current transformers Used to transform primary currents (max. 6000 A) into .../5 A low secondary currents indirectly sup- plying power to analogue and digital measurement devices. They are available both with wound and through primary. In the first case they are provided along with the bar or the primary terminal; in the second case they have a hole to insert in the bar or the cable which forms the primary.

Wound primary max section [mm] cable 8 horizontal bar - vertical bar - CTA1 series Wound primary max section [mm] cable - horizontal bar 25 vertical bar - CTA2 series Wound primary max section [mm] cable - horizontal bar 25 vertical bar - 2CSC400214F0201 CTA/25 2CSC400213F0201 CTA1 2CSC400214F0201 CTA2 2CSC400214F0201 System pro M compact® Selection tables Measurement devices Measurement current transformers with wound primary CTA Standard type current transformers …/5 A with wound primary Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. CTA .../5 A series, wound primary with insertion on Ø8 MA bolt 5 0.5 5 CTA/5 2CSG111020R1141 661306 0.290 1 10 0.5 5 CTA/10 2CSG111030R1141 661405 0.290 1 15 0.5 5 CTA/15 2CSG111040R1141 661504 0.290 1 20 0.5 5 CTA/20 2CSG111050R1141 661603 0.290 1 25 0.5 5 CTA/25 2CSG111060R1141 661702 0.290 1 40 0.5 5 CTA/40 2CSG111080R1141 661801 0.290 1 50 0.5 5 CTA/50 2CSG111090R1141 661900 0.290 1 60 0.5 5 CTA/60 2CSG111100R1141 662006 0.290 1 80 0.5 5 CTA/80 2CSG111110R1141 662105 0.290 1 100 0.5 5 CTA/100 2CSG111120R1141 662204 0.290 1 CTA1 .../5 A series, wound primary with insertion on 25 mm bar 5 0.5 10 CTA1/5 2CSG211020R1141 662303 0.440 1 10 0.5 10 CTA1/10 2CSG211030R1141 662402 0.440 1 15 0.5 10 CTA1/15 2CSG211040R1141 662501 0.440 1 20 0.5 10 CTA1/20 2CSG211050R1141 662600 0.440 1 25 0.5 10 CTA1/25 2CSG211060R1141 662709 0.440 1 40 0.5 10 CTA1/40 2CSG211080R1141 662808 0.440 1 50 0.5 10 CTA1/50 2CSG211090R1141 662907 0.440 1 60 0.5 10 CTA1/60 2CSG211100R1141 663003 0.440 1 80 0.5 10 CTA1/80 2CSG211110R1141 663102 0.440 1 100 0.5 10 CTA1/100 2CSG211120R1141 663201 0.440 1 150 0.5 10 CTA1/150 2CSG211130R1141 663300 0.440 1 200 0.5 10 CTA1/200 2CSG211140R1141 663409 0.440 1 250 0.5 10 CTA1/250 2CSG211150R1141 663508 0.440 1 300 0.5 10 CTA1/300 2CSG211160R1141 663607 0.440 1 400 0.5 10 CTA1/400 2CSG211170R1141 663706 0.440 1 500 0.5 10 CTA1/500 2CSG211180R1141 663805 0.440 1 CTA2 .../5 A series, wound primary with insertion on 25 mm bar 5 0.5 20 CTA2/5 2CSG311020R1141 663904 0.440 1 10 0.5 20 CTA2/10 2CSG311030R1141 664000 0.440 1 15 0.5 20 CTA2/15 2CSG311040R1141 664109 0.440 1 20 0.5 20 CTA2/20 2CSG311050R1141 664208 0.440 1 25 0.5 20 CTA2/25 2CSG311060R1141 664307 0.440 1 40 0.5 20 CTA2/40 2CSG311080R1141 664406 0.440 1 50 0.5 20 CTA2/50 2CSG311090R1141 664505 0.440 1 60 0.5 20 CTA2/60 2CSG311100R1141 664604 0.440 1 80 0.5 20 CTA2/80 2CSG311110R1141 664703 0.440 1 100 0.5 20 CTA2/100 2CSG311120R1141 664802 0.440 1 150 0.5 20 CTA2/150 2CSG311130R1141 664901 0.440 1 200 0.5 20 CTA2/200 2CSG311140R1141 665007 0.440 1 250 0.5 20 CTA2/250 2CSG311150R1141 665106 0.440 1 300 0.5 20 CTA2/300 2CSG311160R1141 665205 0.440 1 400 0.5 20 CTA2/400 2CSG311170R1141 665304 0.440 1 500 0.5 20 CTA2/500 2CSG311180R1141 665403 0.440 1

pro M compact® Selection tables Measurement devices Current transformers CT Breaker choice Modular S200, S500 S280, S800 Tmax T1,T2,T3,T4 T5 T6, T7 Emax E1, E2 E1 E2 E1 E2, E3, E4, E6 E3, E4 Rated current choice Rated Current [A] CT3 CT4 CT6 CT8 CT8-V CT12 CT12-V 40 2CSG121060R1101 3CT3/40 50 2CSG121070R1101 3CT3/50 60 2CSG121080R1101 3CT3/60 80 2CSG121090R1101 3CT3/80 100 2CSG121100R1101 2CSG221100R1101 1CT3/100 CT4/100 150 2CSG121110R1101 2CSG221110R1101 0.5CT3/150 CT4/150 200 2CSG121120R1101 2CSG221120R1101 0.5CT3/200 CT4/200 250 2CSG121130R1101 2CSG221130R1101 2CSG421130R1101 0.5CT3/250 CT4/250 CT6/250 300 2CSG121140R1101 2CSG221140R1101 2CSG421140R1101 2CSG521140R1101 0.5CT3/300 CT4/300 CT6/300 CT8/300 400 2CSG221150R1101 2CSG421150R1101 2CSG521150R1101 2CSG631150R1101 0.5CT4/400 CT6/400 CT8/400 CT8-V/400 500 2CSG221160R1101 2CSG421160R1101 2CSG521160R1101 2CSG631160R1101 2CSG721160R1101 0.5CT4/500 CT6/500 CT8/500 CT8-V/500 CT12/500 600 2CSG221170R1101 2CSG421170R1101 2CSG521170R1101 2CSG631170R1101 2CSG721170R1101 0.5CT4/600 CT6/600 CT8/600 CT8-V/600 CT12/600 800 2CSG421180R1101 2CSG521180R1101 2CSG631180R1101 2CSG721180R1101 2CSG831180R1101 0.5CT6/800 CT8/800 CT8-V/800 CT12/800 CT12-V/800 1000 2CSG421190R1101 2CSG521190R1101 2CSG631190R1101 2CSG721190R1101 2CSG831190R1101 0.5CT6/1000 CT8/1000 CT8-V/1000 CT12/1000 CT12-V/1000 1200 2CSG421200R1101 2CSG521200R1101 2CSG631200R1101 2CSG721200R1101 2CSG831200R1101 0.5CT6/1200 CT8/1200 CT8-V/1200 CT12/1200 CT12-V/1200 1250 2CSG831210R1101 0.5CT12-V/1250 1500 2CSG421220R1101 2CSG521220R1101 2CSG631220R1101 2CSG721220R1101 2CSG831220R1101 0.5CT6/1500 CT8/1500 CT8-V/1500 CT12/1500 CT12-V/1500 2000 2CSG421230R1101 2CSG521230R1101 2CSG721230R1101 2CSG831230R1101 0.5CT6/2000 CT8/2000 CT12/2000 CT12-V/2000 2500 2CSG721240R1101 2CSG831240R1101 0.5CT12/2500 CT12-V/2500 3000 2CSG721250R1101 2CSG831250R1101 0.5CT12/3000 CT12-V/3000 4000 2CSG831260R1101 0.5CT12-V/4000 5000 2CSG721270R1101 CT12/5000 6000 2CSG721280R1101 CT12/6000 Primary choice CT3 CT4 CT6 CT8 CT8-V CT12 CT12-V Through primary max section [mm] 21 25 50 2x30 2x35 2x50 2x35 class30x10 40x10 60x20 80x30 - 125x50 - 20x10 40x10 - - 3x80x5 - 4x125x5

Through primary max section [mm] cable 21 horizontal bar 30x10 vertical bar 20x10 CT4 series Through primary max section [mm] cable 32 horizontal bar 40x10 vertical bar 40x10 CT3 2CSC400122F0201 System pro M compact® Selection tables Measurement devices Measurement current transformers with through primary CT CT3 .../5 A series, through primary 40 3 2 CT3/40 2CSG121060R1101 602408 0.340 1 50 3 2 CT3/50 2CSG121070R1101 602507 0.340 1 60 3 2 CT3/60 2CSG121080R1101 602606 0.340 1 80 3 3 CT3/80 2CSG121090R1101 602705 0.340 1 100 1 2 CT3/100 2CSG121100R1101 602804 0.340 1 150 0.5 3 CT3/150 2CSG121110R1101 602903 0.340 1 200 0.5 3 CT3/200 2CSG121120R1101 603009 0.340 1 250 0.5 5 CT3/250 2CSG121130R1101 603108 0.340 1 300 0.5 6 CT3/300 2CSG121140R1101 603207 0.340 1 400 0.5 6 CT3/400 2CSG121150R1101 603306 0.340 1 500 0.5 6 CT3/500 2CSG121160R1101 603405 0.340 1 600 0.5 6 CT3/600 2CSG121170R1101 603504 0.340 1 CT4 .../5 A series, through primary 100 1 3 CT4/100 2CSG221100R1101 603603 0.500 1 150 1 3 CT4/150 2CSG221110R1101 603702 0.500 1 200 1 4 CT4/200 2CSG221120R1101 603801 0.500 1 250 1 6 CT4/250 2CSG221130R1101 603900 0.500 1 300 0.5 6 CT4/300 2CSG221140R1101 604006 0.500 1 400 0.5 10 CT4/400 2CSG221150R1101 604105 0.500 1 500 0.5 10 CT4/500 2CSG221160R1101 604204 0.500 1 600 0.5 10 CT4/600 2CSG221170R1101 604303 0.500 1 800 0.5 10 CT4/800 2CSG221180R1101 604402 0.500 1 1000 0.5 10 CT4/1000 2CSG221190R1101 604501 0.500 1 Standard type current transformers …/5 A with through primary Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. CT4 2CSC400126F0201

Through primary max section [mm] cable 50 horizontal bar 60x20 vertical bar - CT8 series Through primary max section [mm] cable 2x30 horizontal bar 80x30 vertical bar - CT8-V series Through primary max section [mm] cable 2x35 horizontal bar - vertical bar 80x30 3x80x5 System pro M compact® Selection tables Measurement devices Measurement current transformers with through primary CT CT6 .../5 A series, through primary 250 0.5 5 CT6/250 2CSG421130R1101 605508 1.000 1 300 0.5 5 CT6/300 2CSG421140R1101 605607 1.000 1 400 0.5 6 CT6/400 2CSG421150R1101 605706 1.000 1 500 0.5 6 CT6/500 2CSG421160R1101 605805 1.000 1 600 0.5 10 CT6/600 2CSG421170R1101 605904 1.000 1 800 0.5 10 CT6/800 2CSG421180R1101 606000 1.000 1 1000 0.5 20 CT6/1000 2CSG421190R1101 606109 1.000 1 1200 0.5 20 CT6/1200 2CSG421200R1101 606208 1.000 1 1500 0.5 30 CT6/1500 2CSG421220R1101 606307 1.000 1 2000 0.5 30 CT6/2000 2CSG421230R1101 606406 1.000 1 2500 0.5 30 CT6/2500 2CSG421240R1101 606505 1.000 1 CT8 .../5 A series, through primary 300 0.5 5 CT8/300 2CSG521140R1101 606604 1.000 1 400 0.5 6 CT8/400 2CSG521150R1101 606703 1.000 1 500 0.5 10 CT8/500 2CSG521160R1101 606802 1.000 1 600 0.5 10 CT8/600 2CSG521170R1101 606901 1.000 1 800 0.5 10 CT8/800 2CSG521180R1101 607007 1.000 1 1000 0.5 10 CT8/1000 2CSG521190R1101 607106 1.000 1 1200 0.5 15 CT8/1200 2CSG521200R1101 607205 1.000 1 1500 0.5 20 CT8/1500 2CSG521220R1101 607304 1.000 1 2000 0.5 20 CT8/2000 2CSG521230R1101 607403 1.000 1 2500 0.5 20 CT8/2500 2CSG521240R1101 607502 1.000 1 3000 0.5 20 CT8/3000 2CSG521250R1101 607601 1.000 1 CT8-V .../5 A series, through primary 400 0.5 6 CT8-V/400 2CSG631150R1101 608707 0.800 1 500 0.5 10 CT8-V/500 2CSG631160R1101 608806 0.800 1 600 0.5 10 CT8-V/600 2CSG631170R1101 608905 0.800 1 800 0.5 10 CT8-V/800 2CSG631180R1101 609001 0.800 1 1000 0.5 10 CT8-V/1000 2CSG631190R1101 609100 0.800 1 1200 0.5 10 CT8-V/1200 2CSG631200R1101 609209 0.800 1 1500 0.5 10 CT8-V/1500 2CSG631220R1101 609308 0.800 1 2000 0.5 20 CT8-V/2000 2CSG631230R1101 609407 0.800 1 2500 0.5 20 CT8-V/2500 2CSG631240R1101 609506 0.800 1 CT8 2CSC400125F0201 CT8/V 2CSC400159F0201 CT6 2CSC400124F0201 Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc.

Through primary max section [mm] cable 2x50 horizontal bar 125x50 vertical bar - CT12-V series Through primary max section [mm] cable 3x35 horizontal bar - vertical bar 125x30 3x100x10 4x125x5 CT12 2CSC400160F0201 System pro M compact Selection tables Measurement devices Measurement current transformers with through primary CT CT12 .../5 A series, through primary 500 0.5 10 CT12/500 2CSG721160R1101 607700 1.600 1 600 0.5 10 CT12/600 2CSG721170R1101 607809 1.600 1 800 0.5 15 CT12/800 2CSG721180R1101 607908 1.600 1 1000 0.5 20 CT12/1000 2CSG721190R1101 608004 1.600 1 1200 0.5 20 CT12/1200 2CSG721200R1101 608103 1.600 1 1500 0.5 20 CT12/1500 2CSG721220R1101 608202 1.600 1 2000 0.5 30 CT12/2000 2CSG721230R1101 608301 1.600 1 2500 0.5 40 CT12/2500 2CSG721240R1101 608400 1.600 1 3000 0.5 40 CT12/3000 2CSG721250R1101 608509 1.600 1 4000 0.5 50 CT12/4000 2CSG721260R1101 608608 2.000 1 5000 0.5 50 CT12/5000 2CSG721270R1101 745600 3.000 1 6000 0.5 50 CT12/6000 2CSG721280R1101 745709 3.000 1 CT12-V .../5 A series, through primary 800 0.5 10 CT12-V/800 2CSG831180R1101 609605 0.700 1 1000 0.5 10 CT12-V/1000 2CSG831190R1101 609704 0.700 1 1200 0.5 10 CT12-V/1200 2CSG831200R1101 609803 0.700 1 1250 0.5 10 CT12-V/1250 2CSG831210R1101 609902 0.700 1 1500 0.5 12 CT12-V/1500 2CSG831220R1101 610007 0.700 1 2000 0.5 15 CT12-V/2000 2CSG831230R1101 610106 1.000 1 2500 0.5 20 CT12-V/2500 2CSG831240R1101 610205 1.000 1 3000 0.5 20 CT12-V/3000 2CSG831250R1101 610304 1.000 1 4000 0.5 20 CT12-V/4000 2CSG831260R1101 745808 1.000 1 Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. CT12/V 2CSC400120F0202

pro M compact® Selection tables Measurement devices Split core measurement current transformers CTO Split core measurement current transformers with throug primary Split core measurement current transformers are used in distribution panels or power centers for maintenance or system expansion. They can be installed easily and they allows to save a lot of time, avoiding bar disconnection. All transformers are complete with terminal caps and fastening acces- sories, both on bar and on wall. Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. CT30/...5 A Split core current transformers 100 3 1.5 CT30/100 2CSG101100R1101 887805 0.85 1 150 3 2 CT30/150 2CSG101110R1101 887904 0.85 1 250 0.5 1.5 CT30/250 2CSG101130R1101 888109 0.85 1 400 0.5 2.5 CT30/400 2CSG101150R1101 888000 0.85 1 Technical features Frequency [Hz] 50-60 Insulation voltage [kV] 0.72 Test voltage 3 kV x 1’ 50 Hz Thermal insulation class E Protection grade IP20 Permanent overload 1.2 In Short circuit thermal rated current Ith 60 In Short circuit dynamic rated current Idin 2.5 x Ith Safety factor <5 Case V0 self-extinguishing thermoplastic material Operating temperature [°C] -5 +50 Storage temperature [°C] -20 +80 Standards IEC-EN 60044-1 CT30 series Through primary max section [mm] cable horizontal bar vertical bar 2x30x10 2CSC400141F0202

pro M compact® Selection tables Measurement devices Split core measurement current transformers CTO Primary Accuracy Rated Order Bbn Price Price Weight Pack rated class power details 8012542 1 piece group 1 piece unit current Iprim A VA Type code Order code EAN kg pc. CT80/...5 A Split core current transformers 250 0.5 1 CT80/250 2CSG201130R1101 888208 1.1 1 400 0.5 1.5 CT80/400 2CSG201150R1101 888307 1.1 1 500 0.5 2.5 CT80/500 2CSG201160R1101 888406 1.1 1 600 0.5 2.5 CT80/600 2CSG201170R1101 888505 1.1 1 800 0.5 3 CT80/800 2CSG201180R1101 888604 1.1 1 1000 0.5 5 CT80/1000 2CSG201190R1101 888703 1.1 1 2000 0.5 35 CT80/2000 2CSG301230R1101 888802 1.1 1 2500 0.5 40 CT80/2500 2CSG301240R1101 888901 1.1 1 CT120/...5 A Split core current transformers 400 0.5 1.5 CT120/400 2CSG401150R1101 889007 1.3 1 500 0.5 2.5 CT120/500 2CSG401160R1101 889106 1.3 1 600 0.5 2.5 CT120/600 2CSG401170R1101 889205 1.3 1 800 0.5 3 CT120/800 2CSG401180R1101 889304 1.3 1 1000 0.5 5 CT120/1000 2CSG401190R1101 889403 1.3 1 1200 0.5 6 CT120/1200 2CSG401200R1101 889502 1.3 1 500 0.5 8 CT120/1500 2CSG401220R1101 889601 1.3 1 CT80 series Through primary max section [mm] cable horizontal bar vertical bar 3x80x10 CT120 series Through primary max section [mm] cable horizontal bar vertical bar 4x120x10 2CSC400142F0202 2CSC400142F0202

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments CTSM Summing current transformers They are used for calculating the vector sum of currents of two or more lines of a single voltage system. Installation on DIN rail. The insulation reference voltage is 0.72 kV – 3 kV. Summing current transformers return a correct measure when the input lines have the same rated capacity. The transforming ratio to be set on the instrument is equal to the sum of the lines capacity divided by 5. In case you want to measure different lines you must use a special summing current transformer. Summing current transformers…/5 A (6 DIN modules) No. of Type Power Order Bbn Price Price Weight Pack lines details 8012542 1 piece group 1 piece unit VA Type code Order code EAN kg pc. 2 5+5=5A 6 CTSM-5-5 2CSM101010R1181 610403 0.300 1 3 5+5+5=5A 6 CTSM-5-5-5 2CSM101020R1181 610502 0.300 1 4 5+5+5+5=5A 6 CTSM-5-5-5-5 2CSM101030R1181 610601 0.300 1 2CSC400119F0201

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments TV Voltage transformers They are used for transforming primary voltages up to 600 V into secondary voltages of…/100 V max. for indirect supply of analogue as well as digital measurement instruments. R3 voltage transformers are used in three-phase distribution systems with neutral. Voltage transformers with self-extinguishing plastic housing, precision class 1 Primary/ Power Order Bbn Price Price Weight Pack secondary details 8012542 1 piece group 1 piece unit voltage V/V VA Type code Order code EAN kg pc. 100/100 3 TV-100/100 2CSG112010R5021 746805 1.000 1 230/100 6 TV-230/100 2CSG112070R5021 610809 1.000 1 380/100 6 TV-380/100 2CSG112090R5021 610908 1.000 1 400/100 6 TV-400/100 2CSG112110R5021 611004 1.000 1 440/100 3 TV-440/100 2CSG112130R5021 747000 1.000 1 500/100 6 TV-500/100 2CSG112150R5021 611103 1.000 1 100/100-√3 1.5 TV-100R3/100 2CSG111020R5021 747604 1.000 1 230/100-√3 1.5 TV-230R3/100 2CSG111080R5021 747901 1.000 1 380/100-√3 1.5 TV-380R3/100 2CSG111100R5021 748007 1.000 1 400/100-√3 1.5 TV-400R3/100 2CSG111120R5021 748106 1.000 1 440/100-√3 1.5 TV-440R3/100 2CSG111140R5021 748205 1.000 1 500/100-√3 1.5 TV-500R3/100 2CSG111160R5021 748304 1.000 1 2CSC400121F0201 Voltage transformers with metallic housing, precision class 0.5 Primary/ Power Order Bbn Price Price Weight Pack secondary details 8012542 1 piece group 1 piece unit voltage V/V VA Type code Order code EAN kg pc. 100/100 10 TV2-100/100 2CSG324010R5021 729808 2.100 1 230/100 10 TV2-230/100 2CSG324070R5021 730101 2.100 1 380/100 10 TV2-380/100 2CSG324090R5021 730200 2.100 1 400/100 10 TV2-400/100 2CSG324110R5021 730309 2.100 1 440/100 10 TV2-440/100 2CSG324130R5021 730408 2.100 1 500/100 10 TV2-500/100 2CSG324150R5021 730507 2.100 1 600/100 10 TV2-600/100 2CSG324170R5021 730606 2.100 1 100/100-√3 5 TV2-100R3/100 2CSG323020R5021 730705 2.100 1 230/100-√3 5 TV2-230R3/100 2CSG323080R5021 731009 2.100 1 380/100-√3 5 TV2-380R3/100 2CSG323100R5021 731108 2.100 1 400/100-√3 5 TV2-400R3/100 2CSG323120R5021 731207 2.100 1 440/100-√3 5 TV2-440R3/100 2CSG323140R5021 731306 2.100 1 500/100-√3 5 TV2-500R3/100 2CSG323160R5021 731405 2.100 1 600/100-√3 5 TV2-600R3/100 2CSG323180R5021 731504 2.100 1 100/100 50 TV4-100/100 2CSG528010R5021 733409 2.400 1 230/100 50 TV4-230/100 2CSG528070R5021 733706 2.400 1 380/100 50 TV4-380/100 2CSG528090R5021 733805 2.400 1 400/100 50 TV4-400/100 2CSG528110R5021 733904 2.400 1 440/100 50 TV4-440/100 2CSG528130R5021 734000 2.400 1 500/100 50 TV4-500/100 2CSG528150R5021 734109 2.400 1 600/100 50 TV4-600/100 2CSG528170R5021 734208 2.400 1 100/100-√3 25 TV4-100R3/100 2CSG527020R5021 734307 2.400 1 230/100-√3 25 TV4-230R3/100 2CSG527080R5021 734604 2.400 1 380/100-√3 25 TV4-380R3/100 2CSG527100R5021 734703 2.400 1 400/100-√3 25 TV4-400R3/100 2CSG527120R5021 734802 2.400 1 440/100-√3 25 TV4-440R3/100 2CSG527140R5021 734901 2.400 1 500/100-√3 25 TV4-500R3/100 2CSG527160R5021 735007 2.400 1 600/100-√3 25 TV4-600R3/100 2CSG527180R5021 735106 2.400 1 2CSC400127F0201

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments CONV 2CSC400120F0201 2CSC400920F0201 Current and voltage converters They produce an output signal in direct current independent from the load that is directly proportional to the input current or voltage signal. Their electronic circuit guarantees high reliability and accuracy of operation, extension of the mea- surement field, resistance to temperature changes and to vibrations, limited power absorption from the circuit to be measured. Thanks to their centralized data acquisition speed, even at high distances, and thanks to the availability of different output types (that can be selected by means of the adjusting minidips) they are appropriate for plants requiring specific attention to production, distribution and use of electric energy. Supply Modules Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit VAC Type code Order code EAN kg pc. Current converters with a.c. supply with inputs 1 and 5 A a.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 3 CONV-I-1-24CA 2CSG313000R5031 740902 0.400 1 110 3 CONV-I-1-110CA 2CSG353000R5031 741107 0.400 1 230 3 CONV-I-1-230CA 2CSG373000R5031 741206 0.400 1 Current converters with a.c. supply with inputs 60 mV d.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 6 CONV-I-2-24CA 2CSG414000R5031 741305 0.800 1 110 6 CONV-I-2-110CA 2CSG454000R5031 741503 0.800 1 230 6 CONV-I-2-230CA 2CSG474000R5031 741602 0.800 1 Current converters with d.c. supply with inputs 1 and 5 A a.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 3 CONV-I-1-24CC 2CSG323000R5031 741701 0.400 1 48 3 CONV-I-1-48CC 2CSG343000R5031 741800 0.400 1 110 3 CONV-I-1-110CC 2CSG363000R5031 741909 0.400 1 Current converters with d.c. supply with inputs 60 mV d.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 6 CONV-I-2-24CC 2CSG424000R5031 742005 0.800 1 48 6 CONV-I-2-48CC 2CSG444000R5031 742104 0.800 1 110 6 CONV-I-2-110CC 2CSG464000R5031 742203 0.800 1 Voltage converters with a.c. supply with inputs 120-300-500 V a.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 3 CONV-V-1-24CA 2CSG111000R5031 739500 0.400 1 110 3 CONV-V-1-110CA 2CSG151000R5031 739708 0.400 1 230 3 CONV-V-1-230CA 2CSG171000R5031 739807 0.400 1 Voltage converters with a.c. supply with inputs 500 V d.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 6 CONV-V-2-24CA 2CSG212000R5031 739906 0.800 1 110 6 CONV-V-2-110CA 2CSG252000R5031 740100 0.800 1 230 6 CONV-V-2-230CA 2CSG272000R5031 740209 0.800 1 Voltage converters with d.c. supply with inputs 120-300-500 V a.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 3 CONV-V-1-24CC 2CSG121000R5031 740308 0.400 1 48 3 CONV-V-1-48CC 2CSG141000R5031 740407 0.400 1 110 3 CONV-V-1-110CC 2CSG161000R5031 740506 0.400 1 Voltage converters with d.c. supply with inputs 500 V d.c. and selectable outputs 1-5-10 V d.c. and 1-5-10-20-4…20 mA d.c. 24 6 CONV-I-2-24CC 2CSG222000R5031 740605 0.800 1 48 6 CONV-I-2-48CC 2CSG242000R5031 740704 0.800 1 110 6 CONV-I-2-110CC 2CSG262000R5031 740803 0.800 1

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments CNV Transducers for angle phase meters They are necessary for the indirect insertion of analogue angle phase meters. They operate with a 230 V or 400 V supply and they are equipped with an electronic programming pushbutton for the selection of the more suitable output out of the eight available outputs (1, 5, 10 V d.c. and 1, 5, 10, 20, 4/20 mA d.c.). They have a galvanic type separation between inputs and outputs. Phase Description Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Transducers for angle phase meters 230/440 VAC supply 1 (2 wires) CNV-C-1 2CSM310000R1131 600206 0.400 1 3 balanced without CNV-C-2 2CSM320000R1131 600305 0.400 1 neutral (3 wires) 2CSC400120F0201 Technical features Separated auxiliary supply [V] a.c. 230/400 Input rated values [V] a.c. 230/400 (5 A) Output rated values (selectable) 1, 5, 10 V d.c. Ohmic load [Ohm] 700 Measurement field 0÷Pn (0÷Qn) Conversion type proportional to phase angle or to cos ϕ Accuracy rating 0.5 Permanent overload 2 In/1.2 Un Instantaneous overload 10 In/2 Un for 1 sec. Operating frequency [Hz] 50/60 Time delay [ms] 300 Alternated residue 1% Self-consumption voltage=1 VA/curr.=0.8 VA/aux. supply=4 VA Input/output galvanic separation input/output insulation, aux. supply 2 kV for 1 min./50 Hz circuit/mass insulation 4 kV for 1 min./50 Hz Operating temperature [°C] 0...55 Dimensions 6 DIN modules Weight [kg] 0.49

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments SNT Rated Order Bbn Price Price Weight Pack current details 8012542 1 piece group 1 piece unit A Type code Order code EAN kg pc. 60 mV shunts 5 SNT 1/5 2CSM100010R1121 047605 1.300 1 6 SNT 1/6 2CSM100020R1121 047704 1.800 1 10 SNT 1/10 2CSM100030R1121 047803 1.800 1 15 SNT 1/15 2CSM100040R1121 047902 1.800 1 20 SNT 1/20 2CSM100050R1121 048008 1.800 1 25 SNT 1/25 2CSM100060R1121 048107 1.800 1 30 SNT 1/30 2CSM100070R1121 048206 1.300 1 40 SNT 1/40 2CSM100080R1121 048305 1.300 1 50 SNT 1/50 2CSM100090R1121 048404 2.200 1 60 SNT 1/60 2CSM100100R1121 048503 2.200 1 80 SNT 1/80 2CSM100110R1121 048602 1.300 1 100 SNT 1/100 2CSM100120R1121 048701 1.300 1 150 SNT 1/150 2CSM100130R1121 048800 1.300 1 200 SNT 1/200 2CSM100140R1121 048909 1.300 1 250 SNT 1/250 2CSM100150R1121 049005 1.900 1 400 SNT 1/400 2CSM100160R1121 049104 1.900 1 500 SNT 1/500 2CSM100170R1121 049203 1.900 1 600 SNT 1/600 2CSM100180R1121 049302 1.900 1 800 SNT 1/800 2CSM100190R1121 049401 2.200 1 1000 SNT 1/1000 2CSM100200R1121 049500 2.000 1 1500 SNT 1/1500 2CSM100210R1121 049609 2.200 1 2000 SNT 1/2000 2CSM100220R1121 049708 2.200 1 2500 SNT 1/2500 2CSM100230R1121 049807 2.200 1 4000 SNT 1/4000 2CSM100240R1121 747109 2.200 1 6000 SNT 1/6000 2CSM100250R1121 747208 2.300 1 Shunts Shunts have 60 mV voltage and must be used with a maximum load of 0.25 Ω in combination with measurement instruments in d.c. For an appropriate operation:

  • both horizontal and vertical mounting are possible (the horizontal position enables a greater heat consumption)
  • the faying surface must be completely used and clean; cover with specific grease after the con- nection
  • screws and bolts must be perfectly tight
  • shunts must be sufficiently ventilated; as they are not insulated, it is a good rule to protect them against accidental contacts. 2CSC400523F0201

pro M compact® Selection tables Measurement devices Accessories for analogue and digital instruments SNT Technical features Voltage [mV] 60 Current rating [A] from 5 to 6000 Accuracy class 0.5 (from 10 to 30 °C) Max. load [Ω] 0.25 Overload for 5 sec. from 10 to 500 A : 1xIn from 600 to 2000 A: 5xIn at 2500A: 2xIn OEPM0070 INSTRUMENT GU

continuous use. TM and TS bell transformers are suitable for driving loads that need discontinuous supply TM-C, TM-S, TM-I are control, isolating and safety transformers. SM, RM, TSM and TSR bells and buzzers are suitable for public and tertiary acoustic signalling. Modular sockets allow the connection of devices, tools or electrical and electronic non modular equipments in civil and industrial electrical switchboards. They are available in Italian, French, German, British, Australian and Argentine standards in grey or coloured versions. Some versions are also equipped with a fuse or a light

Reference standard IEC EN 61558-2-8 Classification Fail safe Non-inherently short-circuit proof Thermal protection integrated in secondary ■ Rated power 10, 15, 30, 40 VA 8, 16, 24 VA Operation Discontinuous Primary circuit voltage ratings 230 V a.c. 230 V a.c. Secondary circuit characteristics Double insulation between primary and secondary windings ■■ Full power on all outputs SELV secondary (no-load output voltage <50 V a.c.) ■■ Dimensions 2 modules [10, 15 VA] 2 modules [8, 16 VA] 3 modules [30, 40 VA] 3 modules [24 VA] Approvals System pro M compact® Selection tables Other functions Transformers selection TM, TS, TS-C, TM-C, TM-S, TM-I Use Secondary voltage Rated power Type Solution 25-63 VA Safety TS-C SELV 50-2500 VA Control and safety TM-S Continuous 12-24 V 50-2500 VA Control TM-C 115-230 V 50-2500 VA Control START Control and isolating TM-I Discontinuous SELV 8-24 VA Non-inherently short-circuit proof bell transformer TS 10-40 VA Fail safe bell transformer TM

IEC EN 61558-2-6 CEI EN 61558-2-2 CEI EN 61558-2-2 CEI EN 61558-2-6 CEI EN 61558-2-2 CEI EN 61558-2-4 Non-inherently short-circuit proof Non-short-circuit proof control transformer /L54706 Non-short-circuit-proof control and safety transformer /L54706 Non-short-circuit-proof control and isolating transformer /L54706 25, 40, 63 VA 50 to 2500 VA 50 to 2500 VA 50 to 2500 VA Continuous Continuous Continuous Continuous ■■ ■ ■■■■ 4 modules [25 VA, 40 VA] See overall dimensions 13/61 See overall dimensions 13/61 See overall dimensions 13/61 5 modules [63 VA] System pro M compact® Selection tables Other functions Transformers selection TM, TS, TS-C, TM-C, TM-S, TM-I Bell transformer TM, TS Transformers for supplying extra low voltage, suitable for loads that require a discontinuous supply, in particular doorbells and chimes. The primary and secondary circuits are perfectly isolated and separated. Reference standard: IEC EN 61558-2-8 Control transformer TM-C, TM-S*, TM-I* Transformer for supplying control circuits, for example commands, signalling, interlocks, etc. Reference standard: CEI EN 61558-2-2 Safety transformer TS-C, TM-S* Isolation transformer for supplying safety extra low voltage circuits (<50 V on no load). Accidental contact with the secondary winding phases can be withstood without any danger. Reference standard: CEI EN 61558-2-6 Isolating transformer TM-I* Transformer in which the primary and secondary windings are electrically separated by a double or reinforced insulation, to protect the circuit supplied by the secondary against hazards due to accidental simultaneous contact with earth and live parts, or grounded parts that may become live in the event of an insulation fault. Reference standard: CEI EN 61558-2-4 * TM-S and TM-I both comply to two standards. /L54706 See page 9/7 for the choice of the protections.

Wiring diagrams and marking information TS-C safety isolating transformers for general use These transformers are non-inherently short-circuit proof. In fact they are equipped with a thermal protective device which automatically restores the power when the transformer is sufficiently cooled down. So even during an overload or a short-circuit they maintain their temperature below the spe- cified limits and they continue functioning after the fault’s removal. They are ideal for supplying permanent power to meters, auxiliary electronic devices (e.g. measu- rement, video-entry phone systems, BUS communication) and circuits with safety extremely-low voltage (SELV) for bathrooms and showers, lighting, fountains, electro-medical devices and suchlike. One important feature of these new devices is that they take up very little space in the 4-module size for the 25 and 40 VA versions and the 5-module size for the 63 VA version. Rated Secondary Order details Bbn Price Price Weight Pack power rated 8012542 1 piece group 1 piece unit (continuous) voltage VA V Type code Order code EAN kg pc. 25 12-24 TS 25/12-24 C 2CSM251043R0811 928508 0.920 1 40 12-24 TS 40/12-24 C 2CSM401043R0811 928607 1.100 1 63 12-24 TS 63/12-24 C 2CSM631043R0811 928706 1.150 1 Technical features TS 25 C TS 40 C TS 63 C Rated frequency [Hz] 50/60 50/60 50/60 Rated power (continuous use) [VA] 25 40 63 Power loss [W] 5 10 16,7 Modules [No.] 4 4 5 Standards IEC/EN 61558-2-6 Approvals IMQ, VDE, GOST System pro M compact® Selection tables Other functions Safety isolating transformers for general use TS-C TS25/12-24 C 3 7 10 14 ~ 50 Hz 230 V

24 V~ 25 VA

12 V~ 25 VA t 40 °Ca TS40/12-24 C 3 7 10 14 ~ 50 Hz 230 V

24 V~ 40 VA

12 V~ 40 VA t 40 °Ca TS63/12-24 C 3 7 10 14 ~ 50 Hz 230 V

24 V~ 63 VA

12 V~ 63 VA t 40 °Ca 2CSC400759F0001 2CSC400759F0001 2CSC400200F0202

pro M compact® Selection tables Other functions TM bell transformers TM TM fail safe bell transformers These transformers, with safety extremely-low voltage secondary (SELV), are suitable for loads that require a discontinuous supply, and in particular doorbells and chimes. Fail safe operation and excellent safety are assured thanks to the perfect isolation and separation between the primary and secondary circuits. Maximum Secondary Order Bbn Price Price Weight Pack rated voltage details 8012542 1 piece group 1 piece unit power /L54706 rating (discontin.) VA V a.c. Type code Order code EAN kg pc. 10 4-8-12 TM10/12 2CSM101021R0801 367109 0.300 6 10 12-24 TM10/24 2CSM101041R0801 367208 0.300 6 15 4-8-12 TM15/12 2CSM151021R0801 367307 0.300 6 15 12-24 TM15/24 2CSM151041R0801 367406 0.300 6 30 4-8-12 TM30/12 2CSM301021R0801 367505 0.450 4 30 12-24 TM30/24 2CSM301041R0801 367604 0.450 4 40 4-8-12 TM40/12 2CSM401021R0801 367703 0.450 4 40 12-24 TM40/24 2CSM401041R0801 367802 0.450 4 /L54706 See diagrams below for the RMS power on each secondary output Technical characteristics Rated primary voltage Un [V] 230 a.c. Rated secondary voltage Un [V] 4, 8, 12, 24 Rated frequency [Hz] 50/60 Rated power (discontinuous) [VA] 10, 15, 30, 40 Power loss [W] 1…4 Modules [No.] 2 (TM10,TM15), 3(TM30,TM40) Cable section (Ø min/max) [mm 2] 1.5 / 10 Tightening torque [Nm] 1 Protection degree IP 20 Reference standards IEC/EN 61558-2-8 Approvals GOST, IMQ (TM10, TM15, TM30) 2CSC400594F02012CSC400595F0201 TM40/24 8 11 2 5 24 V~ ~ 50 Hz 230 V 40 VA 12 V~ 20 VA 12 V~ 20 VA t 40 °C/BaF TM40/12 8 11 2 5 12 V~ ~ 50 Hz 230 V 40 VA 8 V~ 27 VA 4 V~ 13 VA t 40 °C/BaF TM30/12 8 11 2 5 12 V~ ~ 50 Hz 230 V 30 VA 8 V~ 20 VA 4 V~ 10 VA t 40 °C/BaF TM30/24 8 11 2 5 24 V~ ~ 50 Hz 230 V 30 VA 12 V~ 15 VA 12 V~ 15 VA t 40 °C/BaF TM15/24 5 8 1 4 24 V~ ~ 50 Hz 230 V 15 VA 12 V~ 7,5 VA 12 V~ 7,5 VA t 40 °C/BaF TM15/12 5 8 1 4 12 V~ ~ 50 Hz 230 V 15 VA 8 V~ 10 VA 4 V~ 5V A t 40 °C/BaF TM10/12 5 8 1 4 12 V~ ~ 50 Hz 230 V 10 VA 8 V~ 6,66 VA 4 V~ 3,33 VA t 40 °C/BaF TM10/24 5 8 1 4 24 V~ ~ 50 Hz 230 V 10 VA 12 V~ 5V A 12 V~ 5V A t 40 °C/BaF OEPM0080

pro M compact® Selection tables Other functions TS bell transformers TS TS non-inherently short-circuit proof bell transformers These transformers, with safety extremely-low voltage secondary (SELV), are suitable for driving loads that call for a discontinuous supply, and in particular doorbells and chimes. In addition to perfect isolation and separation between the primary and secondary circuits, the TS transformers have a thermal protection device integrated into the secondary that makes them resistant to short circuit currents (non-inherently short-circuit proof). In addition, the TS8/SW series is equipped with a switch for controlling loads connected to the secondary. Maximum Secondary Switch Order Bbn Price Price Weight Pack rated voltage 0-1 details 8012542 1 piece group 1 piece unit power /L54706 rating (discontin.) VA V a.c. Type code Order code EAN kg pc. 8 8 TS8/8 2CSM081301R0811 368007 0.355 6 8 12 TS8/12 2CSM081401R0811 368106 0.355 6 8 24 TS8/24 2CSM081501R0811 368205 0.355 6 8 8 ■ TS8/8 SW 2CSM081302R0811 368304 0.277 6 8 12 ■ TS8/12 SW 2CSM081402R0811 368403 0.277 6 8 4-6-8 ■ TS8/4-6-8 SW 2CSM081012R0811 368601 0.280 6 8 4-8-12 ■ TS8/4-8-12 SW 2CSM081022R0811 368700 0.280 6 16 8 TS16/8 2CSM161301R0811 368809 0.355 6 16 12 TS16/12 2CSM161401R0811 368908 0.355 6 16 24 TS16/24 2CSM161501R0811 369004 0.330 6 16 4-6-8 TS16/4-6-8 2CSM161011R0811 369103 0.333 6 16 4-8-12 TS16/4-8-12 2CSM161021R0811 369202 0.333 6 24 4-8-12 TS24/4-8-12 2CSM241021R0811 369301 0.465 4 24 8-12-24 TS24/8-12-24 2CSM241031R0811 369400 0.465 4 /L54706 See diagrams below for the RMS power on each secondary output 2CSC400597F02012CSC400598F02012CSC400596F0201 Technical characteristics Rated voltage Un primary [V] 230 a.c. Rated voltage Un secondary [V] 4, 8, 12, 24 Rated frequency [Hz] 50/60 Rated power (discontinuous) [VA] 10, 15, 30, 40 Power loss [W] 1…4 Modules [No.] 2 (TS8,TS16), 3(TS24) Cable section (Ø min/max) [mm 2] 1.5 / 10 Tightening torque [Nm] 1 Protection degree IP 20 Reference standards IEC/EN 61558-2-8 Approvals VDE, GOST TS16/4-8-12 1 4~ 50 Hz 230 V

12 V~16 VA

8 V~10,6 VA

4 V~ 5,3 VA

t 40 °C/Ba TS8/4-6-8 SW 1 4~ 50 Hz 230 V

8 V~ 8 VA

6 V~ 6V A

4 V~ 4V A

t 40 °C/Ba TS16/4-6-8 1 4~ 50 Hz 230 V

8 V~16 VA

6 V~12 VA

4 V~ 8V A

t 40 °C/Ba TS8/4-8-12 SW 5 8 4 4 12 V~ ~ 50 Hz 230 V 8V A 8 V~ 5,3 VA 4 V~ 2,7 VA t 40 °C/Ba TS16/24 5 8 1 4~ 50 Hz 230 V

24 V~16 VA

t 40 °C/Ba TS24/4-8-12 2 5~ 50 Hz 230 V

12 V~ 24 VA

8 V~ 16 VA

t 40 °C/Ba TS16/12 5 8 1 4~ 50 Hz 230 V t 40 °C/Ba TS16/8 5 8 1 4~ 50 Hz 230 V t 40 °C/Ba TS24/8-12-24 2 5~ 50 Hz 230 V

24 V~ 24 VA

12 V~ 12 VA

8 V~ 8V A

t 40 °C/Ba TS8/8 SW 5 8 1 4~ 50 Hz 230 V t 40 °C/Ba TS8/12 SW 5 8 1 4~ 50 Hz 230 V

12 V~ 8V A

t 40 °C/Ba TS8/8 5 8 1 4 ~ 8 V ~ 50 Hz 230 V t 40 °C/Ba 8 VA TS8/12 5 8 1 4 ~ 12 V ~ 50 Hz 230 V t 40 °C/Ba 8V A 8V A TS8/24 5 8 1 4 ~ 24 V ~ 50 Hz 230 V t 40 °C/Ba OEPM0080

pro M compact® Other modular functions Control, isolating and safety transformers TM-C TM-S TM-I Selection table of products and secondary protections Primary protection: see page 11/165 TM-C Control TM-S Control/Safety TM-I Control/Isolating Power VA Secondary voltage 12 V 24 V 115 V 230 V 12 V 24 V 24 V 48 V 115 V 230 V

50 Transformer 2CSM207113R0801 2CSM207213R0801 2CSM236893R0801 2CSM204653R0801 /L54707 2CSM204583R0801

Fuse gauge /L54706 4 A 2 A 0.4 A 0.2 A 4 A 2 A 2 A 1 A 0.4 A 0.2 A 100 Transformer 2CSM207103R0801 2CSM236933R0801 2CSM207163R0801 2CSM204643R0801 2CSM201123R0801 Fuse gauge /L54706 8 A 4 A 0.8 A 0.4 A 8 A 4 A 4 A 2 A 0.8 A 0.4 A Breaker type S202 C8 S202 C4 S202 C1 S202 C0,5 S202 C8 S202 C4 S202 C4 S202 C2 S202 C1 S202 C0,5 160 Transformer 2CSM236853R0801 2CSM207203R0801 2CSM202073R0801 2CSM204633R0801 2CSM204533R0801 Breaker type S202 C13 S202 C8 S202 C1.6 S202 C- S202 C13 S202 C8 S202 C8 S202 C4 S202 C1.6 - 200 Transformer 2CSM236823R0801 2CSM236883R0801 2CSM260043R0801 2CSM204513R0801 Fuse gauge /L54706 16 A 8 A 1.6 A 0.8 A 16 A 8 A 1.6 A 0.8 A Breaker type S202 C16 S202 C8 S202 C2 S202 C1 S202 C16 S202 C8 S202 C2 S202 C1 250 Transformer 2CSM207093R0801 2CSM236923R0801 2CSM260063R0801 2CSM204673R0801 2CSM204493R0801 Fuse gauge /L54706 20 A 10 A 2 A 1 A 20 A 10 A 10 A 5 A 2 A 1 A Breaker type S202 C20 S202 C10 S202 C2 S202 C1 S202 C20 S202 C10 S202 C10 S202 C6 S202 C2 S202 C1 320 Transformer 2CSM236843R0801 2CSM236923R0801 2CSM260063R0801 2CSM204673R0801 2CSM204493R0801 Breaker type S202 C25 S202 C13 S202 C3 S202 C1,6 S202 C25 S202 C13 S202 C13 S202 C8 S202 C3 S202 C1,6 400 Transformer 2CSM289703R0801 2CSM207193R0801 2CSM260103R0801 2CSM204613R0801 2CSM201073R0801 Fuse gauge /L54706 32 A 16 A 3.15 A 1.6 A 32 A 16 A 16 A 8 A 3.15 A 1.6 A Breaker type S202 C32 S202 C16 S202 C4 S202 C2 S202 C32 S202 C16 S202 C16 S202 C8 S202 C4 S202 C2 630 Transformer 2CSM236813R0801 2CSM207183R0801 2CSM260053R0801 2CSM204603R0801 2CSM204423R0801 Fuse gauge /L54706 50 A 25 A 5 A 2.5 A 50 A 25 A 25 A 12 A 5 A 2.5 A Breaker type S202 C50 S202 C25 S202 C6 S202 C3 S202 C50 S202 C25 S202 C25 S202 C13 S202 C6 S202 C3 1000 Transformer 2CSM292873R0801 2CSM236913R0801 2CSM260093R0801 2CSM204413R0801 Fuse gauge /L54706 80 A 40 A 8 A 4 A 80 A 40 A 8 A 4 A Breaker type S292 C80 S202 C40 S202 C8 S202 C4 S292 C80 S202 C40 S202 C8 S202 C4 1600 Transformer 2CSM292863R0801 2CSM201813R0801 2CSM260083R0801 2CSM204403R0801 Fuse gauge /L54706 125 A 63 A 16 A 8 A 125 A 63 A 16 A 8 A Breaker type S292 C125 S202 C63 S202 C16 S202 C8 S292 C125 S202 C63 S202 C16 S202 C8 2000 Transformer 2CSM292853R0801 2CSM236903R0801 2CSM260073R0801 2CSM204383R0801 Fuse gauge /L54706 160 A 80 A 16 A 8 A 160 A 80 A 16 A 8 A Breaker type - S292 C80 S202 C20 S202 C10 - S292 C80 S202 C20 S202 C10 2500 Transformer 2CSM236943R0801 2CSM207173R0801 2CSM204663R0801 2CSM204363R0801 Fuse gauge /L54706 200 A 100 A 20 A 10 A 200 A 100 A 20 A 10 A Breaker type - S292 C100 S202 C25 S202 C13 - S292 C100 S202 C25 S202 C13 /L54706 FUSES - Gauge ≤ 6.3 A use aM fuses with high breaking capacity and IEC60127-compliant - Gauge > 6.3 A use gG fuses IEC60269-2 or IEC60269-3-compliant /L54707 TM-S 50/24-48 P complies with IEC EN 61558-2-4 on the secondary circuit at 48 V and with IEC EN 61558-2-6 on the secondary circuit at 24 V

pro M compact® Other modular functions Control, isolating and safety transformers TM-C TM-S TM-I Technical characteristics TM-C TM-S TM-I Primary voltage adjustment outlets ±15 V No Yes Yes Max ambient temperature /L54708 [°C] 40 40 40 Rated frequency [Hz] 50/60 50/60 50/60 Isolation voltage between primary and secondary [kV] 3.5 4.8 4.8 Rated powers [VA] 50-2500 50-2500 50-2500 Primary cable section (Ø max) [mm 2] 6 6 6 Operating temperature [°C] /L54706 /L54706 /L54706 Approvals ENEC (Up to 1000 VA), ENEC (Up to 1000 VA), ENEC (Up to 1000 VA), UR, CSA UR, CSA UR, CSA Standards CEI EN 61558-2-2 CEI EN 61558-2-2 CEI EN 61558-2-2 CEI EN 61558-2-6 CEI EN 61558-2-4 /L54706 See technical details /L54707 TM-S 50/24-48 P complies to CEI EN 61558-2-4 on the 48 V secondary and to CEI EN 61558-2-6 on the

24 V secondary

/L54708 Maximum temperature without any power draw. See technical details for power draw according to temperature. Rated Secondary Order Bbn Price Price Weight Pack power voltages details 8012542 1 piece group 1 piece unit VA V a.c. Type code Order code EAN kg pc. TM-C single phase control transformers, primary 230-400 V 50 12-24 TM-C 50/12-24 2CSM207113R0801 071136 1.1 1 100 12-24 TM-C 100/12-24 2CSM207103R0801 071037 2 1 160 12-24 TM-C 160/12-24 2CSM236853R0801 368533 3 1 200 12-24 TM-C 200/12-24 2CSM236823R0801 368236 3.2 1 250 12-24 TM-C 250/12-24 2CSM207093R0801 070931 3.6 1 320 12-24 TM-C 320/12-24 2CSM236843R0801 368434 4.4 1 400 12-24 TM-C 400/12-24 2CSM289703R0801 897033 5.5 1 630 12-24 TM-C 630/12-24 2CSM236813R0801 368137 7.8 1 1000 12-24 TM-C 1000/12-24 2CSM292873R0801 928737 13.2 1 1600 12-24 TM-C 1600/12-24 2CSM292863R0801 928638 21.2 1 2000 12-24 TM-C 2000/12-24 2CSM292853R0801 928539 25.5 1 2500 12-24 TM-C 2500/12-24 2CSM236943R0801 369431 26.8 1 50 115-230 TM-C 50/115-230 2CSM207213R0801 072133 1.1 1 100 115-230 TM-C 100/115-230 2CSM236933R0801 369332 2 1 160 115-230 TM-C 160/115-230 2CSM207203R0801 072034 3 1 200 115-230 TM-C 200/115-230 2CSM236883R0801 368830 3.2 1 250 115-230 TM-C 250/115-230 2CSM207153R0801 071532 3.6 1 320 115-230 TM-C 320/115-230 2CSM236923R0801 369233 4.4 1 400 115-230 TM-C 400/115-230 2CSM207193R0801 071938 5.5 1 630 115-230 TM-C 630/115-230 2CSM207183R0801 071839 7.8 1 1000 115-230 TM-C 1000/115-230 2CSM236913R0801 369134 13.2 1 1600 115-230 TM-C 1600/115-230 2CSM201813R0801 018131 21.2 1 2000 115-230 TM-C 2000/115-230 2CSM236903R0801 369035 25.5 1 2500 115-230 TM-C 2500/115-230 2CSM207173R0801 071730 26.8 1 2CSC400204F0202 2CSC400203F0202 2CSC400202F0202 2CSC400201F0202

2CSC400204F0202 2CSC400203F0202 2CSC400202F0202 2CSC400201F0202 Rated Secondary Order Bbn Price Price Weight Pack power voltages details 8012542 1 piece group 1 piece unit VA V a.c. Type code Order code EAN kg pc. System pro M compact® Other modular functions Control, isolating and safety transformers TM-C TM-S TM-I 2CSC400166F0902 TM-S, TM-I Label on product: 12-24 V output TM-S 24-48 V output TM-S 115-230 V output TM-I 8 6 4 2 +15 0 -15 230 400

230 V˜ VA

+15 0 -15 230 400

24 V˜ VA

+15 0 -15 230 400

12 V˜ VA

+15 0 -15 230 400

48 V˜ VA

+15 0 -15 230 400 +15 0 -15 230 400

115 V˜ VA

Label on product: 12-24 V output 115-230 V output +15 -15 230 400 8 6 4 2 230 400 8 6 4 2 TM-S single phase control and safety transformers, primary 230-400 V ±15 50 12-24 TM-S 50/12-24 P 2CSM236893R0801 368939 1.1 1 100 12-24 TM-S 100/12-24 P 2CSM207163R0801 071631 2 1 160 12-24 TM-S 160/12-24 P 2CSM202073R0801 020738 3 1 200 12-24 TM-S 200/12-24 P 2CSM260043R0801 600435 3.2 1 250 12-24 TM-S 250/12-24 P 2CSM260113R0801 601135 3.6 1 320 12-24 TM-S 320/12-24 P 2CSM260063R0801 600633 4.4 1 400 12-24 TM-S 400/12-24 P 2CSM260103R0801 601036 5.5 1 630 12-24 TM-S 630/12-24 P 2CSM260053R0801 600534 7.8 1 1000 12-24 TM-S 1000/12-24 P 2CSM260093R0801 600930 13.2 1 1600 12-24 TM-S 1600/12-24 P 2CSM260083R0801 600831 21.2 1 2000 12-24 TM-S 2000/12-24 P 2CSM260073R0801 600732 25.5 1 2500 12-24 TM-S 2500/12-24 P 2CSM204663R0801 046639 26.8 1 50 24-48 TM-S 50/24-48 P 2CSM204653R0801 046530 1.1 1 100 24-48 TM-S 100/24-48 P 2CSM204643R0801 046431 2 1 160 24-48 TM-S 160/24-48 P 2CSM204633R0801 046332 3 1 250 24-48 TM-S 250/24-48 P 2CSM204683R0801 046837 3.2 1 320 24-48 TM-S 320/24-48 P 2CSM204673R0801 046738 3.6 1 400 24-48 TM-S 400/24-48 P 2CSM204613R0801 046134 4.4 1 630 24-48 TM-S 630/24-48 P 2CSM204603R0801 046035 5.5 1 TM-I single phase control and isolating transformers, primary 230-400 V ±15 50 115-230 TM-I 50/115-230 P 2CSM204583R0801 045830 1.1 1 100 115-230 TM-I 100/115-230 P 2CSM201123R0801 011231 2 1 160 115-230 TM-I 160/115-230 P 2CSM204533R0801 045335 3 1 200 115-230 TM-I 200/115-230 P 2CSM204513R0801 045137 3.2 1 250 115-230 TM-I 250/115-230 P 2CSM204503R0801 045038 3.6 1 320 115-230 TM-I 320/115-230 P 2CSM204493R0801 044932 4.4 1 400 115-230 TM-I 400/115-230 P 2CSM201073R0801 010739 5.5 1 630 115-230 TM-I 630/115-230 P 2CSM204423R0801 044239 7.8 1 1000 115-230 TM-I 1000/115-230 P 2CSM204413R0801 044130 13.2 1 1600 115-230 TM-I 1600/115-230 P 2CSM204403R0801 044031 21.2 1 2000 115-230 TM-I 2000/115-230 P 2CSM204383R0801 043836 25.5 1 2500 115-230 TM-I 2500/115-230 P 2CSM204363R0801 043638 26.8 1 Accessories Order Bbn Price Price Weight Pack details 8012542 1 piece group 1 piece unit Type code Order code EAN kg pc. Mounting bracket for DIN rail (up to 160 VA) TM-C-DIN 2CSM201033R0801 010333 0.10 10

pro M compact® Selection tables Other functions Bells and buzzers SM, RM, TSM, TSR Bells and buzzers The range of bells and buzzers includes modular versions for discontinuous use SM1, RM1, TSM and TSR, suitable for acoustic signalling in residential and commercial sectors, and versions for continuous use SM2 and RM2, which are able to operate continuously for up to 12 hours while maintaining the quality and level of the sound. RM2 and SM2 are dedicated to specific applications such as acoustic signalling in the industry, alarms notification, supervision and intensive use (schools, bell is supplied in 12 or 24 V. Rated Use Order Bbn Price Price Weight Pack voltage details 8012542 1 piece group 1 piece unit V AC Type code Order code EAN kg pc. SM electro-mechanical modular bells 8/12 Discontinuous SM1-12 2CSM111000R0821 886204 0.076 12 230 Discontinuous SM1-230 2CSM131000R0821 886303 0.076 12 12 Continuous SM2-12 2CSM112000R0821 886600 0.076 12 24 Continuous SM2-24 2CSM122000R0821 886709 0.076 12 230 Continuous SM2-230 2CSM132000R0821 886808 0.076 12 RM electro-mechanical modular buzzers 8/12 Discontinuous RM1-12 2CSM211000R0821 886419 0.076 12 230 Discontinuous RM1-230 2CSM231000R0821 886518 0.076 12 12 Continuous RM2-12 2CSM212000R0821 886907 0.076 12 24 Continuous RM2-24 2CSM222000R0821 887003 0.076 12 230 Continuous RM2-230 2CSM232000R0821 887102 0.076 12 TSM modular electronic bell (two-tones) + transformer included 230 Discontinuous TSM 2CSM100000R0841 007005 0.300 6 TSR bell + buzzer + transformer included 230 Discontinuous TSR 2CSM100000R0831 369608 0.300 1 2CSC400543F0001 2CSC400518F0001 Technical characteristics SM1-12, RM1-12 SM1-230, RM1-230 SM2-12, RM2-12 SM2-24, RM2-24 SM2-230, RM2-230 TSM, TSR Rated Voltage Un [V c.a.] 8-12 230 12 24 230 230 Rated frequency [Hz] 50 50 50 50 50 50 Power consumption [VA] 2,5-6,5 4,5 4,5 4,5 4,5 5,5 Sound level at 1 meter SM: [dB] 82 82 82 82 82 80 RM: [dB] 80 80 80 80 80 70 Max permanent TSM: 1 min working time 15 min 15 min 12 h /L54706 12 h /L54706 12 h /L54706 TSR: 5 min Max cable cross-section [mm2] 10 10 10 10 10 10 Mounting position vertical only Protection degree IP20-IP40, switchboard mounting Modules [No.] 1 1 1 1 1 2 /L54706 Continuative work for more than 12 hours could affect the sound level 5 6 7 8TSM 1234 230V N L 5 6 7 8TSR 1234 230V N L 24V 24V SM RM N L 2CSC400407F0001 2CSC400261F0001

pro M compact® Selection tables Other functions Primary switch mode power supplies CP-D Primary switch mode power supplies Rated output Pack. Price Weight Rated input voltage / unit 1 piece 1 piece Type voltage current Order code pieces kg/lb CP-D 12/0.83 100-240 V AC 12 V DC / 0.83 A 1SVR 427 041 R1000 1 0.06/0.13 CP-D 12/2.1 100-240 V AC 12 V DC / 2.1 A 1SVR 427 043 R1200 1 0.19/0.41 CP-D 24/0.42 100-240 V AC 24 V DC / 0.42 A 1SVR 427 041 R0000 1 0.06/0.13 CP-D 24/1.3 100-240 V AC 24 V DC / 1.3 A 1SVR 427 043 R0100 1 0.19/0.41 CP-D 24/2.5 100-240 V AC 24 V DC / 2.5 A 1SVR 427 044 R0200 1 0.25/0.55 CP-D 24/4.2 100-240 V AC 24 V DC / 4.2 A 1SVR 427 045 R0400 1 0.32/0.71 - Output voltages 12 V, 24 V - Adjustable output voltages (devices > 10 W) - Power range 10 W, 30 W, 60 W, 100 W - Wide range input 100-240 V AC (90-264 V AC, 120-370 V DC) - High efficiency of up to 89 % - Low power dissipation and low heating - Free convection cooling (no forced cooling with ventilators) - Ambient temperature range during operation -10...+70 °C - Open-circuit, overload and short-circuit stable - Integrated input fuse - U/I characteristic (fold-forward behaviour at overload – no switch-off) - LEDs for status indication - Light-grey enclosure in RAL 7035 CP-D 24/4.2 CP-D 12/0.83, CP-D 24/0.42 CP-D 12/2.1 CP-D 24/1.3 CP-D 24/2.5 2CDC271029Fb07 2CDC271028Fb07 2CDC271025Fb07 2CDC271024Fb07

pro M compact® Selection tables Other functions Modular sockets selection table M1170, M1173, M1174, M1175, M1176, M1363, M2071 Model selection RAL 7035 RAL 6029 RAL 3000 RAL 7012 German Schuko Strandard M1175 2CSM210000R0721 2CSM220000R0721 2CSM230000R0721 2CSM240000R0721 M1175-L Indicator light 2CSM212000R0721 2CSM222000R0721 2CSM232000R0721 2CSM242000R0721 M1175-FL Indicator light Fuse 6.3 A aM 2CSM214000R0721 2CSM224000R0721 2CSM234000R0721 2CSM244000R0721 M1175-C Cover IP30 2CSM211000R0721 2CSM221000R0721 2CSM231000R0721 2CSM241000R0721 Italian P30 standard M1173 2CSM110000R0701 2CSM120000R0701 2CSM130000R0701 2CSM140000R0701 M1173-L Indicator light 2CSM112000R0701 2CSM122000R0701 2CSM132000R0701 2CSM142000R0701 Series selection For further information about sockets selection by country please see page 11/176 M1175 M1173 M1170 M1174 M1363 M1176 M2071 EU 10A ■■■■ Schuko 10 A / 16 A ■■■ Italian 10 A ■■ Italian 16 A ■ French 10 A / 16 A Pluggable but not earthed Pluggable but not earthed Pluggable but not earthed ■ British 13 A ■ Australian 10 A / 15 A ■ Argentine 10 A ■

pro M compact® Selection tables Other functions Modular sockets selection table M1170, M1173, M1174, M1175, M1363, M1176, M2071 RAL 7035 RAL 6029 RAL 3000 RAL 7012 Italian dual standard M1170 2CSM210000R0701 2CSM220000R0701 2CSM230000R0701 2CSM240000R0701 French Standard M1174 2CSM110000R0711 British Standard Available in the second half of 2011 M1363 2CSM259343R0721 M1363-L Indicator light 2CSM258163R0721 Australian Standard Available in the second half of 2011 M1176-L10 10 A Indicator light 2CSM256983R0721 M1176-L15 15 A Indicator light 2CSM259473R0721 Argentine Standard Available in the second half of 2011 M2071-L10 10 A Indicator light 2CSM257783R0721

Modular sockets allow the connection of devices, tools or electrical and electronic non modular equipments in civil and industrial electrical switchboards. The range is composed by standard versions as well as upgraded versions with additional features as light indicator, protection fuse, cover and coloration. In addition to the grey-coloured (RAL 7035) version there are three other colours which are useful to indicate specific socket uses: - green (RAL 6029), for example to indicate a dedicated upstream protection device; - red (RAL 3000), for example to indicate an UPS group that allows the socket to be used if the main power supply fails; - black (RAL 7012), to match with industrial and automation devices. Color Description Bbn Weight Pack unit 8012542 1 piece Type Order code EAN kg German Shuko standard modular sockets The M1175 series (VDE certified) takes Schuko standard plugs up to 16 A. Also available with cover, M1175-C. grey M1175 2CSM210000R0721 027850 0,120 4 green M1175-G 2CSM220000R0721 027959 0,120 4 red M1175-R 2CSM230000R0721 028055 0,120 4 black M1175-B 2CSM240000R0721 028154 0,120 4 grey with cover M1175-C 2CSM211000R0721 029052 0,140 4 green with cover M1175-C-G 2CSM221000R0721 029151 0,140 4 red with cover M1175-C-R 2CSM231000R0721 029250 0,140 4 black with cover M1175-C-B 2CSM241000R0721 029359 0,140 4 German Shuko standard modular sockets with integrated indicator light and fuse grey with light M1175-L 2CSM212000R0721 028253 0,140 4 green with light M1175-L-G 2CSM222000R0721 028352 0,140 4 red with light M1175-L-R 2CSM232000R0721 028451 0,140 4 black with light M1175-L-B 2CSM242000R0721 028550 0,140 4 grey with light and fuse M1175-FL 2CSM214000R0721 028659 0,160 4 green with light and fuse M1175-FL-G 2CSM224000R0721 028758 0,160 4 red with light and fuse M1175-FL-R 2CSM234000R0721 028857 0,160 4 black with light and fuse M1175-FL-B 2CSM244000R0721 028956 0,160 4 Indicator light detailFuse detail System pro M compact® Selection tables Other functions Modular sockets M1175 2CSC400759F00012CSC400759F00012CSC400759F00012CSC400759F0001

2CSC400759F00012CSC400759F00012CSC400759F00012CSC400759F00012CSC400759F00012CSC400759F0001 2CSC400759F0001 System pro M compact® Selection tables Other functions Modular sockets M1170, M1173, M1174, M1176, M1363, M2071 Italian P30 standard modular sockets The M1173 series (IMQ certified) takes Italian standard 10 A plugs and Schuko plugs up to 16 A grey M1173 2CSM110000R0701 004103 0,120 4 green M1173-G 2CSM120000R0701 026754 0,120 4 red M1173-R 2CSM130000R0701 026853 0,120 4 black M1173-B 2CSM140000R0701 026952 0,120 4 Italian P30 standard modular sockets with integrated indicator light grey with light M1173-L 2CSM112000R0701 027058 0,140 4 green with light M1173-L-G 2CSM122000R0701 027157 0,140 4 red with light M1173-L-R 2CSM132000R0701 027256 0,140 4 black with light M1173-L-B 2CSM142000R0701 027355 0,140 4 Italian dual standard modular sockets The M1170 series takes Italian standard P11/P17 plugs and Schuko plugs up to 16 A grey M1170 2CSM210000R0701 027454 0,120 4 green M1170-G 2CSM220000R0701 027553 0,120 4 red M1170-R 2CSM230000R0701 027652 0,120 4 black M1170-B 2CSM240000R0701 027751 0,120 4 French standard modular sockets The M1174 series (LCIE and CEBEC certified) takes French standard plugs up to 16 A grey M1174 2CSM110000R0711 006602 0,140 4 British standard modular sockets. Available in the second half of 2011. The M1163 series takes British standard BS1363 plugs up to 13 A grey M1363 2CSM259343R0721 593430 0,140 4 grey with light M1363-L 2CSM258163R0721 581635 0,140 4 Australian/New Zealand standard modular sockets. Available in the second half of 2011. The M1176 series takes Australian/New Zealand standard AS/NZS 3112 plugs up to 10 A and 15 A grey with light 10A M1176-L10 2CSM256983R0721 569831 0,110 4 grey with light 15A M1176-L15 2CSM259473R0721 594734 0,110 4 Argentine standard modular sockets. Available in the second half of 2011. The M2071 series takes Argentine standard IRAM 2071 plugs up to 10 A grey with light 10A M2071-L10 2CSM257783R0721 577836 0,110 4

Technical specifications Rated voltage Un [V] 250 a.c. Rated current In [A] 16 (M1170, M1173, M1174, M1175), 13 (M1363), 10 (M1176-L10, M2071-L10), 15 (M1176-L15) Rated frequency [Hz] 50/60 Power loss [W] 0,6 Modules [No.] 2.5, 3 for M1363 Safety shutters yes, on entire range Terminal type positive safety Cable section (ø min./max.) [mm 2] 2.5 / 16 Tightening torque [Nm] 1.2 Temperature storage [°C] -40 … +70 operating [°C] -25 … +35 Protection degree IP20 / IP30 versions with cover M1175 M1173 M1170 M1174 M1363 M1176 M2071 Reference standards DIN VDE 0620-1 CEI 23-50 NF C 61 303 BS1363 AS NZS 3112 IRAM 2071 Approvals VDE, GOST IMQ, GOST GOST LCIE, BSI RCM IRAM CEBEC, GOST Indicator light technical specifications Type fluorescent torpedo-shaped lamp Function Indication of power supply presence (M1363, M1173, M1175) Indication of plug inserted + power supply presence (M1176, M2071) Light colour green Power consumption [W] 0.25 Fuse technical specifications Type 5 x 20 mm up to 6.3 A aM Function phase protection Breaking capacity [A] 1500 Reference standard IEC EN 60127 System pro M compact® Selection tables Other functions Modular sockets M1170, M1173, M1174, M1175, M1176, M1363, M2071

[0&%% 0&%% 0'% 0'% 0&%% 0&%% [0&%% 0&%% 0&%% 0/%% 0/%% 0'% System pro M compact® Selection tables Other functions MA1-8001 DIN rail adapter MA1-8001 MA1-8001 DIN rail adapter Through an appropriate kit, this product born with the Modular Range of Pilot devices is the perfect case for alongside Ø 22 mm pilot devices with “System pro M compact” products. The Ø 22 mm pilot devices can now find a greater use even within distribution or automation switch- boards with modular panels maintaining an high aesthetic level. The MA1-8001 offers a lot of advantages: - Fast and easy mounting - Simple wiring - Simple maintenance - Less depth of operators - Perfect harmony alongside the “System pro M compact” products Using MA1-8001 it’s possible to put together “System pro M compact” products with LED pilot light, potentiometer, key selectors , toggle switches, selector switches, push- buttons, mushroom buttons and emergency stop, illuminated or not. For detailed description of the industrial devices that can be installed using this kit, see technical catalogue 1SFC151003C0201 Description Order Bbn Price Price Weight Pack details 7320500 1 piece group 1 piece unit Type code Order code EAN kg pc. DIN rail adapter KIT (2 modules) /L54706/L54707 MA1-8001 1SFA611920R8001 357880 0.023 1 DIN rail adapter (2 modules) /L54706 MA1-8131 1SFA611920R8131 357702 0.020 10 /L54706 Can be used only with Modular range pilot devices units; it cannot be used with the old CBK range or Compact range products. /L54707 KIT includes one Din rail adapter, one empty block and 2 pins Technical notes – To assemble the new housing with push-buttons, selector switch and indicator lamps, contact blocks and lamp blocks for DIN rails must be used. – The MCBH-00 holder is not necessary, because the housing hooks directly to contact blocks. – To line up with “System pro M compact” products, a maximum of 3 blocks must be used. – In the configuration with 3 contacts, it is advisable to use securing pins to make the blocks more solid. – In making up actuators or indicator lamps that use a single contact, one or two MDB-2 empty blocks must be used. Assembly instruction After hooking the contact and/ or lamp blocks on the DIN rail, inserting the securing pins (if necessary) and wiring the terminals:

1 Insert the push-button,

selector or pilot light where desired 2 tighten the locking nut using the specific tool 3 hook the housing to the empty and/or contact blocks fixed on the DIN rail 1SFC151346F00011SFC151347F0001 1SFC151006M0201

Smissline and Unifix

SMISSLINE – Pluggable System Keeps downtime to a minimum SMISSLINE protection devices are simply snapped into a plug-in socket system. The arduous task of power supply and connection is done. In addition to savings in time and money, another advantage of the system is the quick and easy exchangeability of the devices. If the corresponding spare capacity is planned, subsequent expansion consists merely of plugging in and connecting additional devices. Customer Benefits with SMISSLINE Reliability and Availability Fast and easy handling with pluggable devices Plug-in technology provides 24-hour service, 365 days a year Freedom in concept and design Mix of devices, various power supply options Flexible architecture without risk of damage to life and property Upgradeability Easy integration of new devices Upgrade without changing the existing installation For order codes and technical details please check the SMISSLINE catalogue 2CCC451028C0204 or go to ABB Homepage. System pro M compact® Selection tables Plug-in systems with Smissline and Unifix SMISSLINE 5 8 2CCC451256F0001

1 Supply terminal

2 Incoming terminal block with a max. current rating of

160 A 50 mm

2 (2 x 25 mm2) + 2 x 10 mm2 (LA, LB)

3 Cover for incoming terminal block

4 Supply cable

5 Surge arrester OVR404

6 RCBO FS401

7 Residual-current circuit breaker F404

8 Miniature circuit breaker S401 M

9 Signal contact

10 Plug contacts

11 DIN adapter

12 Spare way cover

13 Device latch

14 Busbar L3 or DC +, –

15 Busbar L2 or DC +, –

16 Busbar L1 or DC +, –

17 Busbar N

18 Sockets, 8-module and 6-module

19 Auxiliary busbar LA

20 Auxiliary busbar LB

21 Busbar N, external

22 Busbar PE, external

23 Additional socket

24 Output circuits

pro M compact® Selection tables Plug-in systems with Smissline and Unifix UNIFIX UNIFIX – Rapid Wiring System Keeps downtime to a minimum UNIFIX makes bench pre-cabling possible, with installation in the switchboard only carried out at a later time, without any limit to the types or combination of apparatus you may need to install… and this becomes even easier, thanks to the rigid coupled connectors, standardized for the different types of apparatus. Unifix H allows modular and moulded-case circuit-breakers up to 250A to be mounted on an ap- paratus frame, which can be connected directly to the rear busbar system. This means many fewer conductors circulating inside the switchboard with considerable advantages in terms of space taken up, connections needed to be checked, and cabling times, with consequent cost savings. Unifix L means traditional wire cabling on the supply side of the circuit-breakers can be replaced. It is thanks to the characteristics of its connections that cabling can be done rapidly and without any possibility of error, obtaining a more essential switchboard without conductors and cabling ducts around. Flexibility is its strong point: several independent circuits can be realized on the same DIN rail, and circuit-breakers of different types, with different polarity and characteristics can be mounted. Customer Benefits with UNIFIX Wiring Time The use of Unifix reduces considerably wiring time. Use of Standard Devices Unifix can be applied to all standard versions of ABB Sace modular devices, Tmax T1 - T2 - T3 - XT1 - XT3 moulded-case circuit breakers Flexible Unifix has variable modular capacity, it is possible to place both circuit-breakers with different polarities side by side on the same line and auxiliary elements. Reduce Space Space taken up by Unifix is extremely low For order codes and technical details please check the Distribution Switchgear Catalogue 1STC008001D0201, pages 3/15-16, 4/15-16, 5/36-37, or go to ABB Homepage. Unifix H 2CSC400220F0202 2CSC400220F0202 2CSC400221F0202 Unifix L

MCBs internal resistance, power loss and max. permissible earth-fault loop impedance .. 11/65 RCDs Electronic residual current devices SPDs Installation rules for SPDs: choice of associated MDRCs Protection devices Command devices Measurement devices Other functions Technical detailsSystem pro M compact®

pro M compact® MCBs /L54706 The indicated tripping values of electromagnetic tripping devices apply to a frequency range of 16 2/3...60 Hz. In the case of diverging frequencies or direct current, see paragraph “Variation of tripping threshold of MCBs, according to network frequency” (page 6/7) Tripping characteristics Thermal release /L54707 Electromagnetic release /L54706 Acc. to Tripping characteristic Current: Tripping time Currents: Tripping time and rated current conventional conventional hold trip non-tripping c. tripping c. current at least at surges IEC/EN 60898-1 B 6 to 63 A 1.13 · I n > 1 h 3 · I n > 0.1 s 1.45 · I n < 1 h 5 · I n < 0.1 s C 0.5 to 63 A 1.13 · I n > 1 h 5 · I n > 0.1 s 1.45 · I n < 1 h 10 · I n < 0.1 s D 0.5 to 63 A 1.13 · I n > 1 h 10 · I n > 0.1 s 1.45 · I n < 1 h 20 · I n < 0.1 s IEC/EN 60947-2 K 0.5 to 63 A 1.05 · I n > 1 h 1.2 · I n < 1 h not applicable 1.05 · I n > 2 h 10 · I n > 0.2 s 1.2 · I n < 1 h /L54708 14 · I n < 0.2 s IEC/EN 60947-2 Z 0.5 to 63 A 1.05 · I n > 1 h 1.2 · I n < 1 h not applicable 1.05 · I n > 2 h 2 · I n > 0.2 s 1.2 · I n < 1 h /L54708 3 · I n < 0.2 s /L54707 The thermal releases are calibrated to a nominal reference ambient temperature; for Z and K, the value is 20 °C, for B and C = 30 °C. In the case of higher ambient temperatures, the current values fall by ca. 6 % for each 10 K temperature rise. /L54708 As from operating temperature (after I1 > 1 h or, as applicable, 2 h). Tripping behavior S 700 Tripping Rated Delayed thermal release Short-time delayed selective tripping device charakteristic current Conventional non- Conventional Tripping time Delayed Short-time Tripping time tripping current ➀ tripping current ➀ tripping delayed tripping I Int I It t I Itv I Itk t E 1.05 x l n /L50871 2 h 5 x l n 0.05 s < t < 5 s (l n /L50872 32 A) 10 to 100 A 0.05 s < t < 10 s (ln > 32 A) 1.2 x l n < 2 h 6.25 x l n 0.01 s < t < 0.3 s K 16 to 50 A 1,05 x l n /L50871 2 h 10 x l n 0.05 s < t < 5 s (l n /L50872 32 A) 0.05 s < t < 10 s (ln > 32 A) 1,2 x l n < 2 h 14 x l n 0.01 s < t < 0.3 s 63 to 100 A 1,05 x l n /L50871 2 h 8 x l n 0.05 s < t < 10 s 1,2 x l n < 2 h 12 x l n 0.01 s < t < 0.3 s ➀ The thermal trip values refer to a reference temperature of 20 °C. For higher ambient temperatures the current rating will be reduced by 3 % per 10 °C decrease.

Characteristic B Characteristic C IEC-EN60898 Seconds Multiples of rated current Minutes Tripping curve from cold state Seconds Multiples of rated current Minutes Tripping curve from cold state a thermal trip b electromagnetic trip Technical details Tripping characteristics System pro M compact® MCBs

Characteristic D Characteristic K IEC-EN60947-2 a thermal trip b electromagnetic trip Seconds Multiples of rated current Minutes Tripping curve from cold state Technical details Tripping characteristics System pro M compact® MCBs

Multiples of rated current Minutes Tripping curve from cold state Technical details Tripping characteristics System pro M compact® MCBs Characteristic S 700 E E

Characteristic S 700 K - K 16 to K 50 Characteristic S 700 K - K 63 to K 100 a thermal trip b electromagnetic trip Technical details Tripping characteristics System pro M compact® MCBs KK

Limitation of specific let-through energy I System pro M compact® MCBs Limitation of specific let-through energy Tripping of an installation circuit by circuit-breaker when there is a short-circuit requires a certain amount of time depending on the characteristics of the circuit-breaker and the entity of the short-circuit current. During this period of time, some or all of the short-circuit current flows into the installation; the parameter I2t defines the “specific let-through energy”, ie. the specific energy that the breaker allows through when there is a short-circuit current Icc during the tripping time t. In this way, we can determine the capacity of a circuit-breaker to limit, ie. break high currents up to the rated breaking power of the device, by reducing the peak value of the above-mentioned currents to a value which is considerably lower than the estimated current. This can be achieved using mechanisms which open very rapidly and have the following advanta- ges: - they limit the thermal and dynamic effects both on the circuit-breaker and on the protected circuit; - they reduce the dimensions of the current-limiting circuit-breaker without reducing breaking capacity; - they considerably reduce ionized gases and sparklers emitted during the short-circuit and therefore they avoid the danger of ignition and fires. Irms = perspective simmetrical short-circuit current Oscillogram of short-circuit breaks on two circuit-breakers: 1 = traditional non-current limiting circuit-breaker 2 = current limiting circuit- breaker uB = arc voltage (red) uM = rest voltage (blue) KM t t t t = 0 tv U iK uMuB Non-current limiting circuit-breaker Short-circuit current red = effective short-circuit current squared blue = estimated short-circuit current squared (shun- ted circuit-breaker) iK M = maximum values of symmetrical component of short-circuit current squared shaded in red = specific let-through energy in two cases U tv KM i iK uM uB t = 0 Current limiting circuit-breaker Limiting of let-through energy Main selective circuit breakers like S 700 support downstream mcbs in clearing short-circuit currents. They additionally reduce let-through energies without tripping. This increases the operational availability of the electrical supply and reduces drawbacks to the feeding grid and the installed equipment.

Max. withstanding specific let-through energy of cables Section mm2 PVC EPR HEPR 50 33,062,500 39,062,500 51,122,500 35 16,200,625 19,140,625 25,050,025 25 8,265,625 9,765,625 12,780,625 16 3,385,600 4,000,000 5,234,944 10 1,322,500 1,562,500 2,044,900 6 476,100 562,500 736,164 4 211,600 250,000 327,184 2.5 82,656 97,656 127,806 1.5 29,756 35,156 46,010 The selection of the cables depends both from the breakers’ specific let-through energy and from carrying capacity and voltage drop of the line. Data of the previous table are referred to the following cables: PVC EPR HEPR FM9 H07RN-F N07G9-K FM9OZ1 FTG10OM1 N07V-K RG7OR FROR FG7OM1 FG7OR Designation Cable’s reference to the standards harmonized H national cable recognized by CENELC A Rated voltage Uo/U 100/100 ≤ Uo/U < 300/300 01 300/300 V 03 300/500 V 05 450/750 V 07 750/1000 V 1 Insulating materials and non-metallic sheath ethylene-vinylacetate G mineral M polyvinyl chloride V Conductor’s shape flexible conductor of a cable for fixed installation K Some cables on the market are identified with different names according with the designation UNEL 35011. Technical details Limitation of specific let-through energy I System pro M compact® MCBs

S 200-S 200 M-S 200 P , characteristics D-K 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 103 104 105 106 1000.1 1

40 A 20/32 A

1.6 A S 200 S 200 M 10 A S 200 P 50/63 A Irms [kA] I2t [A2s] Technical details Limitation of specific let-through energy I System pro M compact® MCBs I2t diagrams - Specific let-through energy value I2t The I2t curves give the values of the specific let-through energy expressed in A2s (A=amps; s=seconds) in relation to the perspective short-circuit current (Irms) in kA. HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 103 104 105 100100.1 1 20/25 A 13/16 A 10 A 6 A 4 A 3 A 2 A 1 A 1.6 A S 200 DS 200 S 200 M DS 200 M S 200 P 50/60 A 32/40 A Irms [kA] I2t [A2s] S 200-S 200 M-S 200 P , characteristics B and C DS 200-DS 200 M, characteristics B and C 230/400 V let-through energy For further information about the selection of the cable, please look at the table in page 10/3 2CSC400402F02022CSC400403F0202

Limitation of specific let-through energy I System pro M compact® MCBs S 200 P , characteristic Z 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 103 104 105 106 100100,1 1 50/63 A 32/40 A 20/25 A 13/16 A 10 A 6 A 4 A 3 A 2 A 1 A 1,6 A S 200 P Irms [kA] I2t [A2s] For further information about the selection of the cable, please look at the table in page 10/3 SN201 L-SN201-SN201 M, characteristics B

230 V let-through energy

46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 Specific let-through energy I2t (A2s) 103 104 102 Perspective short-circuit current (kA) SN201 SN201M 105 SN201L 4 A 2 A 10 A 6 A 20 A 16 A 32 A 25 A 40 A 2CSC400404F02022CSC400405F0202

Limitation of specific let-through energy I System pro M compact® MCBs SN201, characteristics D 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 Specific let-through energy I2t (A2s) 103 104 102 Perspective short-circuit current (kA) SN201 105 10 A 6 A 20 A 16 A 32 A 25 A 40 A SN201 L-SN201-SN201 M, characteristics C 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 Specific let-through energy I2t (A2s) 103 104 102 Perspective short-circuit current (kA) SN201 SN201M 105 SN201L 4 A 2 A 10 A 6 A 20 A 16 A 32 A 25 A 40 A 2CSC400406F02022CSC400407F0202

Limitation of specific let-through energy I System pro M compact® MCBs S 280 80-100 A, characteristic B 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 10-3 10-2 10-1 11 0 100 A 80 A Irms [kA] I2t [A2s] S 280 80-100 A, characteristic C 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 10-3 10-2 10-1 11 0 100 A 80 A Irms [kA] I2t [A2s] For further information about the selection of the cable, please look at the table in page 10/3 2CSC400408F02022CSC400409F0202

Limitation of specific let-through energy I System pro M compact® MCBs S 280 characteristics K, Z 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 I2t (A2s) Irms (kA) 104103 103 104 105 106 107 1.5.104 C 100/125 A C 80 A D, K 100/125 A D, K 80 A For further information about the selection of the cable, please look at the table in page 10/3 S 290 characteristics C, D, K 230/400 V let-through energy S 290 characteristics B 230/400 V let-through energy HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 I2t (A2s) Icc (kA) 101 101 102 103 104 105 K63 K50 K40 K32 K25 K16 K10 HEPR PVC EPR EPR PVC 46.010 82.656 97.656 35.156 29.756 HEPR127.806 2.5 mm21.5 mm2 I2t (A2s) Icc (kA) 101 101 102 103 104 105 Z63 Z40 Z16 Z10 HEPR PVC EPR PVC HEPREPR 46.010 82.656 97.656 35.156 29.756 127.806 2.5 mm 21.5 mm 2 I2t (A2s) Irms (kA) 101100 101 102 103 104 105 AB 100/125 B 80 A 2CSC400410F0202OEPM0098

Limitation of specific let-through energy I System pro M compact® MCBs 2CDC 022 160 F0103 let-through i2t / A2s p prospective short-circuit current Icc / kA p 2CDC 022 162 F0103 let-through i2t / A2s p prospective short-circuit current Icc / kA p S 700 characteristic K let-through energy

let-through peak current (Ipeak) Technical details Limitation of specific let-through peak current I peak System pro M compact MCBs 2CDC 022 164 F0103 peak current ipeak p prospective short-circuit current Icc / kA p SK 0276 Z 02 peak current ipeak p prospective short-circuit current Icc / kA p S 700 characteristic K let-through peak current (Ipeak)

S800 S characteristics B, C, K and D

230 VAC/50 Hz

60˚ Sine-shaped half-wave 105 104 21 0 50 100 A 40 A 25 A 16 A 10 A

63 A160 A

60˚ Sine-shaped half-wave Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] Technical details Limitation of specific let-through energy I System pro M compact® MCBs Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] /L54706 Min. pre-arching I2t, e.g. NH80 A gL/gG /L54707 Max. let-through I2t, e.g. S801S-C20 2CCC413024Z00012CCC413025Z0001

S800 S characteristics B, C, K and D

400 V let-through energy

400 VAC/50 Hz

60˚ Sine-shaped half-wave 105 104 21 0 50 100 A 40 A 25 A 16 A 10 A 60˚ Sine-shaped half-wave Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] /L54706 Min. pre-arching I2t, e.g. NH80 A gL/gG /L54707 Max. let-through I2t, e.g. S801S-C20 Technical details Limitation of specific let-through energy I System pro M compact® MCBs 2CCC413024Z00012CCC413025Z0001

100 A 100 A

60˚ 125 A 50 A 32 A 20 A 13 A 80 A Sine-shaped half-wave 105 104 21 0 100 A 40 A 25 A 16 A 10 A 63 A 160 A 125 A 100 A 80 A 63 A 200 A 60˚ Sine-shaped half-wave S800 N characteristics B, C and D Limitation of specific let-through energy I System pro M compact® MCBs Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] /L54706 Min. pre-arching I2t, e.g. NH80 A gL/gG /L54707 Max. let-through I2t, e.g. S801S-C20 2CCC413028Z00022CCC413029Z0002

60˚ 125 A 50 A 32 A 20 A 13 A 80 A Sine-shaped half-wave 105 104 21 0 100 A 40 A 25 A 16 A 10 A 63 A 160 A 125 A 100 A 80 A 63 A 200 A 60˚ Sine-shaped half-wave S800 N characteristics B, C and D Limitation of specific let-through energy I System pro M compact® MCBs Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] Let-through energy I2t [A2s] Prospective short current circuit Icc [kA] /L54706 Min. pre-arching I2t, e.g. NH80 A gL/gG /L54707 Max. let-through I2t, e.g. S801S-C20 2CCC413028Z00022CCC413029Z0002

/MT72/MT69/MT80/MT82 /MT80/MT86/MT67 /MT69/MT80/MT82 /MT69/MT80/MT82 /MT80/MT86/MT67 /MT52/MT54/MT46/MT48/MT49/MT48 /MT56/MT50/MT46/MT54/MT53/MT54 /MT57/MT55/MT46/MT54/MT53/MT54 /MT51/MT53/MT46/MT49/MT53/MT54 /MT50/MT57/MT46/MT55/MT53/MT54 /MT72/MT69/MT80/MT82/MT49/MT50/MT55/MT46/MT56/MT48/MT54 /MT50/MT46/MT53/MT32/MT109/MT109/MT50/MT49/MT46/MT53/MT32/MT109/MT109/MT50 /MT83/MT112/MT101/MT99/MT105/MT102/MT105/MT99/MT32/MT108/MT101/MT116/MT45/MT116/MT104/MT114/MT111/MT117/MT103/MT104/MT32/MT101/MT110/MT101/MT114/MT103/MT121/MT32/MT73/MT50/MT116/MT32/MT32/MT40/MT65/MT50/MT115/MT41 /MT49/MT48/MT51 /MT49/MT48/MT52 /MT49/MT48/MT50 /MT80/MT101/MT114/MT115/MT112/MT101/MT99/MT116/MT105/MT118/MT101/MT32/MT115/MT104/MT111/MT114/MT116/MT45/MT99/MT105/MT114/MT99/MT117/MT105/MT116/MT32/MT99/MT117/MT114/MT114/MT101/MT110/MT116/MT32/MT40/MT107/MT65/MT41 /MT48/MT46/MT53 /MT49/MT46/MT53 /MT50/MT46/MT53 /MT51/MT46/MT53 /MT52/MT46/MT53 /MT53/MT46/MT53 /MT54/MT46/MT53 /MT55/MT46/MT53 /MT56/MT46/MT53 /MT57/MT46/MT53 /MT49/MT48/MT46/MT53 /MT49/MT48/MT53 /MT68/MT83/MT50/MT48/MT49/MT32/MT76/MT68/MT83/MT50/MT48/MT49 /MT68/MT83/MT50/MT48/MT50/MT67 /MT68/MT83/MT50/MT48/MT49/MT32/MT77 /MT68/MT83/MT50/MT48/MT50/MT67/MT32/MT77 /MT52/MT32/MT65 /MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT49/MT54/MT32/MT65 /MT51/MT50/MT32/MT65 /MT50/MT53/MT32/MT65 /MT52/MT48/MT32/MT65 /MT49/MT48/MT32/MT65 DS201 L - DS201 - DS201 M DS202C - DS202C M, characteristics B and C Limitation of specific let-through energy I System pro M compact® MCBs 2CSC400412F0202

pro M compact® MCBs Limitation curves - Peak current values The Ip curves give the values of the peak current, expressed in kA, in relation to the perspective symmetrical short-circuit current (kA). S 200-S 200 P , characteristics B-C DS 200-DS 200 M, characteristics B-C S 200-S 200 P , characteristics K-D Ip [kA] 0.2 0.5 100 Irms [kA] 0.2 0.5 1 2 5 10 20 50 100 50 63 A 32 40 A 20 25 A 13 16 A 8 10 A 6 A 0,5 1 A 3 A 2 A 1,6 A 4 A S 200 DS 200 S 200 M DS 200 M S 200 P Ip [kA] 0.2 0.5 100 Irms [kA] 0.2 0.5 1 2 5 10 20 50 100 50 63 A 32 40 A 20 25 A 13 16 A 8 10 A 6 A 0,5 1 A 3 A 2 A 1,6 A 4 A S 200 S 200 M S 200 P 2CSC400413F02022CSC400414F0202

pro M compact® MCBs S 200 P , characteristic Z Ip [kA] 0.2 0.5 100 Irms [kA] 0.2 0.5 1 2 5 10 20 50 100 50 63 A 32 40 A 20 25 A 13 16 A 8 10 A 6 A 0,5 1 A 3 A 2 A 1,6 A 4 A S 200 P SN 201 L, SN 201, SN 201 M, characteristic B 230 V Ip [A] 10000 100 Irms [kA] 1000 200 2000 500 5000 345 789 1 0 6 40 A 25 A 16 A 10 A 6 A SN201 SN201 MSN201 L 32 A 20 A 2CSC400415F02022CSC400416F0202

pro M compact® MCBs SN 201, characteristic D 230 V SN 201 L, SN 201, SN 201 M, characteristic C 230 V Ip [A] 10000 100 Irms [kA] 1000 200 2000 500 5000 345 789 1 0 6 40 A 25 A 16 A 10 A 6 A 4 A 2 A SN201 SN201 MSN201 L 32 A 20 A Ip [A] 10000 100 Irms [kA] 1000 200 2000 500 5000 345 789 1 0 6 40 A 25 A 16 A 10 A SN201 32 A 20 A 6 A 2CSC400417F02022CSC400418F0202

pro M compact® MCBs S 280 80-100 A, characteristic C Ip [kA] 0.2 0.5 100 Irms [kA] 0.2 0.5 1 2 5 10 20 50 100 80 A 100 A S 280 80-100 A, characteristic B Ip [kA] 0.2 0.5 100 Irms [kA] 0.2 0.5 1 2 5 10 20 50 100 80 A 100 A 2CSC400419F02022CSC400420F0202

S 800 S characteristics B, C, K and D 6!#(Z 6!#(Z Ip [kA] Irms [kA] Ip [kA] Irms [kA] Technical details Peak current Ip System pro M compact® MCBs 2CCC413032Z00012CCC413033Z0001

6!#(Z 6!#(Z S 800 N characteristics B, C and DIp [kA] Irms [kA] Ip [kA] Irms [kA] Technical details Peak current Ip System pro M compact® MCBs 2CCC413036Z00012CCC413037Z0001

DS202C - DS202C M characteristics B and C 230 V /MT73/MT112/MT32/MT91/MT107/MT65/MT93 /MT49/MT48 /MT48 /MT50/MT48 /MT53/MT48 /MT48/MT46/MT50 /MT48/MT46/MT53 /MT49/MT48/MT48 /MT48 /MT73/MT114/MT109/MT115/MT32/MT91/MT107/MT65/MT93 /MT48/MT46/MT50 /MT48/MT46/MT53 /MT49 /MT50 /MT53 /MT49/MT48 /MT50/MT48 /MT53/MT48 /MT49/MT48/MT48 /MT49 /MT50 /MT53 /MT49/MT48/MT32/MT65 /MT54/MT32/MT65 /MT52/MT32/MT65 /MT49/MT54/MT32/MT65 /MT50/MT48/MT32/MT65 /MT50/MT53/MT32/MT65 /MT51/MT50/MT32/MT65 /MT52/MT48/MT32/MT65 /MT68/MT83/MT50/MT48/MT49/MT32/MT76 /MT68/MT83/MT50/MT48/MT49 /MT68/MT83/MT50/MT48/MT50/MT67 /MT68/MT83/MT50/MT48/MT49/MT32/MT77 /MT68/MT83/MT50/MT48/MT50/MT67/MT32/MT77 Technical details Peak current Ip System pro M compact® MCBs 2CSC400421F0202

pro M compact® MCBs Back-up protection The tables given provide the value (in kA, referring to the breaking capacity according to the IEC 60947-2 Standard) for which the back-up protection among the combination of selected circuit- breakers is verified. The tables cover the possible combinations between ABB SACE Tmax series of moulded-case circuit-breakers and those between the above-mentioned circuit-breakers and the ABB series of modular circuit-breakers. The values indicated in the tables refer to the voltage: – Vn of 230/240 V AC for coordination with modular SN 201 circuit-breakers – Vn of 400/415 V AC for all the other coordinations. Selective protection The tables given provide the value (in kA, referring to the breaking capacity according to the IEC 60947-2 Standard) for which the selective protection is verified among the combination of selected circuit-breakers. The tables cover the possible combinations between ABB SACE Tmax series of moulded-case circuit-breakers, and the ABB series of modular circuit-breakers. The values in the table represent the maximum value obtainable of discrimination between supply side circuit-breaker and load side circuit-breaker referring to the voltage: – Vn of 230/240 V AC for the SN 201 circuit-breakers and Vn of 400/415 V AC for the supply side circuit-breakers in the coordination between MCB with the modular SN 201 circuit-breakers (see picture). – Vn of 400/415 V AC for all the other coordinations. General prescriptions – Function I of the electronic releases of the supply side circuit-breakers must be excluded (I 3 in OFF); – The magnetic trip of thermomagnetic (TM) or magnetic only (M) circuit-breakers placed on the supply side must be 10 x In and regulated to the maximum threshold; – It is of prime importance to check that the settings made by the user for the electronic and ther- momagnetic relays of circuit-breakers placed both on the load and supply side do not create intersections on the time-current curves. Note The following tables give the breaking capacities at 415 V AC for circuit-breakers SACE Tmax. Tmax @ 415 V AC Version Icu [kA] B 16 C 25 N 36 S 50 H 70 L (T2) 85 L (T4, T5) 120 V 200 L3 N L3 N L2L1 400 V 400 V 230 V 400 V Caption MCB = miniature circuit-breakers (SN 201, S 2, S 800) MCCB = moulded-case circuit-breakers (Tmax) For moulded-case or air circuit-breakers: TM = thermomagnetic release – TMD (Tmax) – TMA (Tmax) M = magnetic only release – MF (Tmax) – MA (Tmax) EL = electronic release – PR221DS - PR222DS (Tmax) For miniature circuit-breakers: B = trip characteristic (Im=3...5In) C = trip characteristic (Im=5...10In) D = trip characteristic (Im=10...20In) K = trip characteristic (Im=8...14In) Z = trip characteristic (Im=2...3In) For solutions not shown in these tables, please consult the website: http://bol.it.abb.com or contact ABB SACE

Coordination tables: back-up System pro M compact MCBs MCB -MCB @240 V Supply s. S200 S200M S200P S200P S280 S290 S800S 25gL 40gL 50gL 63gL 80gL 100gL Load s. Char. B-C B-C B-C B-C B-C C-D B-C- D-K Icu [kA] 20 25 40 25 20 25 50 In[A] 0,5…630,5…63 0,5…25 32…63 80…100 80…125 10…125 SN201 L/DS201 L B,C 6 2...40 20 25 40 25 15 15 50 35 25 20 15 10 10 SN201/DS201/DS202C B,C,D 10 2...40 20 25 40 25 15 15 50 35 25 20 15 10 10 SN201 M/DS201 M/ DS202C M B,C 10 2...40 20 25 40 25 15 15 50 35 25 20 15 10 10 S200 B,C,K,Z 20 0,5…63 25 40 25 50 S200 M B,C,D 25 0,5…63 40 50 S200 P B,C 40 0,5…25 50 D,K,Z 25 32…63 50 S290 C,D,K 25 80…125 S800 B,C 100 10…125 MCCB @ 415 V - MCB/RCBO @ 240 V Supply S.1 T1 T1 T1 T2 T3 T2 T3 T2 T2 Version B C N S H L Load S. Char. I n [A] I cu [kA] 16 25 36 50 70 85 SN201 L DS201 L B, C 2..25 16 16 16 20 20 20 32, 40 10 10 10 16 16 16 16 SN201 DS201 DS202C B, C, D, K 2..25 10 16 16 16 25 25 32, 40 16 16 16 16 SN201 M DS201 M DS202C M B, C 2..25 10 16 16 16 25 25 32, 40 16 16 16 16

1 Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral)

Coordination tables: back-up System pro M compact MCBs MCB - MCB @ 415 V Supply S. S200 S200M S200P S280 S290 S800N S800S Char. B-C B-C B-C B-C C B-C-D B-C-D-K Load S. I cu [kA] 10 15 25 15 6 15 36 50 S200 B,C,K,Z 10 0.5..63 15 25 15 15 36 50 S200M B,C 15 0.5..63 25 36 50 S200P B,C, D,K,Z 25 0.5..25 36 50 15 32..63 36 50 S280 B,C 6 80, 100 S290 C,D 15 80..125 S800N B,C,D 36 10..125 S800S B,C,D,K 50 10..125 MCCB - MCB @ 415 V Supply S. T1 T1 T1 T2 T3 T4 T2 T3 T4 T2 T4 T2 T4 T4 Version B C N S H L L V Load S. Char. I n [A] I cu [kA] 16 25 36 50 70 85 120 200 S200P B,C, D,K,Z 0.5..10 25 30 36 36 36 50 40 40 70 40 85 40 40 13..25 30 36 30 36 50 30 40 60 40 60 40 40 32..63 15 16 25 30 36 25 36 50 25 40 60 40 60 40 40 S280 B,C 80, 100 6 16 16 16 36 16 30 36 16 30 36 30 36 30 30 S290 C,D 80..125 20 (15*) 16 25 30 36 30 30 50 30 30 70 30 85 30 30 S800N B,C,D 10..125 36 70 70 85 120 200 S800S B,C,D,K 10..125 50 70 70 85 120 200 * only for D characteristic Fuse 125 A gG, gL - RCBO @ 230V Supply S. Fuse 125 A gG, gLLoad S. Char. In [A] [kA] DS 271 B,C 6-40 10 15

Fuse gG, gL - MCB S 200, S 200 M 240 V Supply s. Fuse gG, gL Characteristic Load s. In [A] S200 S200 M B 66 3 10...20 100 25...32 100 40 125 50...63 160 S200 S200 M C 3...4 20 64 0 86 3 10...20 100 25...32 100 40 125 50...63 160 S200 K 32 0 42 5 6...10 63 16...20 80 25...32 100 40 125 50...63 160 S200 Z 3...4 20 63 5 84 0 10...16 63 20...25 80 32...40 100 50...63 125 This table shows coordination between an MCB and the upstream fuse maximum current value. Combination of the two protec- tions allows the breaking capacity to be elevated up to that of the combined fuse. I.e. downstream MCB breaker S 202 C16, upstream fuse with In up to 100 A (breaking capacity: 100 kA). MCB breaker pro- tection up to 100 kA. Technical details Coordination tables: back-up System pro M compact MCBs

Coordination tables: selectivity System pro M compact MCBs Selective protection Selectivity between SN 201 and S 200 upstream and downstream modular circuit-breakers In the case, selectivity is amperometric and so the selectivity limit is given simply by the magnetic threshold of the upstream breaker, which is fixed. The selectivity value is obtained if a minimum ratio of 1.6 (In upstream/In downstream > 1.6) is observed between the rated currents of the two breakers. Example Upstream circuit-breaker S 200 P , curve D 50 A Downstream circuit-breaker SN 201 L, curve B 10 A Selectivity limit 10 In=500 A Supply S.2 S290 S800 N-S Load S.1 Char. C D B Icu [kA] 15 36-50 In [A] 80 100 125 80 100 25 32 40 50 63 80 100 125 SN201 L B, C 6 2 T T T T T 0.433 0.6 1.3 4 T T T 45 T T T T 0.45 0.8 1.5 2.5 4 T 10 4 4.5 5 5 5 0.5 1.1 1.4 2 3 SN201 B, C, D 10 2 6 8 9 7 8 0.43 3 0.6 1.3 4 9 T T 10 4 4.5 5 5 5 0.5 1.1 1.4 2 3 SN201 M B, C 10 2 6 8 9 7 8 0.43 3 0.6 1.3 4 9 T T 10 4 4.5 5 5 5 0.5 1.1 1.4 2 3

1 Load side circuit-breaker 1P+N (230/240 V)

2 For networks with 230/240 V AC two-pole circuit-breaker (phase + neutral)

for networks at 400/415 V AC four-pole circuit-breaker (load side circuit branched between one phase and the neutral)

3 Only for curve B

MCB - SN201 @ 230/240 V

25 32 40 50 63 80 100 125 25 32 40 50 63 80 100 125 1.4 2.1 1.7 2.7 4 5 1.4 2.1 1.7 2.7 4 5 1.4 2.1 1.7 2.7 4 5 Technical details Coordination tables: selectivity System pro M compact MCBs

Fuse - SN201 @ 230/240 V Im Icu [kA] In [A] 25 32 40 50 63 80 100 125 SN201 L B-C 6 2 1.5 2.5 T T T T T T 6 4 1 2 4.5 T T T T T 6 6 1 1.5 4 4.5 T T T T 6 10 1.2 3.5 4 T T T T 6 16 1 3 3.5 5 T T T 6 20 1 3 3.5 5 T T T 6 25 1 2 3 4.5 T T T 6 32 1 2 3 4.5 5 T T 6 40 1.5 2.5 4 5 T T SN201 B-C-D 10 2 1.5 2.5 5 T T T T T 10 4 1 2 4.5 5 T T T T 10 6 1 1.5 4 4.5 7 T T T 10 10 1.2 3.5 4 6 T T T 10 16 1 3 3.5 5 T T T 10 20 1 3 3.5 5 8 T T 10 25 1 2 3 4.5 6.5 T T 10 32 1 2 3 4.5 5 8 T 10 40 1.5 2.5 4 5 6.5 T SN201 M B-C 10 2 1.5 2.5 5 7 T T T T 10 4 1 2 4.5 5 8 T T T 10 6 1 1.5 4 4.5 7 T T T 10 10 1.2 3.5 4 6 T T T 10 16 1 3 3.5 5 9 T T 10 20 1 3 3.5 5 8 T T 10 25 1 2 3 4.5 6.5 9 T 10 32 1 2 3 4.5 5 8 T 10 40 1.5 2.5 4 5 6.5 9 Technical details Coordination tables: selectivity System pro M compact MCBs

MCB S700 - SN201 @ 230/240 V Im EEEEEEEE Icu [kA] 25 25 25 25 25 25 25 25 In [A] 20 25 35 40 50 63 80 100 SN201 L B-C

62 T T T T T T T T

64 T T T T T T T T

66 T T T T T T T T

Coordination tables: selectivity System pro M compact MCBs

Coordination tables: selectivity System pro M compact MCBs MCCB @ 415 V 4P - SN201/DS201/DS202C @ 240 V Supply side circuit-breaker 4P (load side circuit branched between one phase and the neutral) Load side circuit-breaker 1P+N (230/240 V)

1 Value valid for magnetic only supply side circuit-breaker

2 Neutral at 50%

Supply S. T1 Version B, C, N Release TMD Iu [A] 160 Load S. Char. I cu [kA] I n [A] 16 20 25 32 40 50 63 80 100 125 160 2 160 16 20 25 32 40 50 SN201 L DS201 L B, C ≤4 T T T T T T T T T T T T T T T T T T B, C 6 T T T T T T T T T T T T T T T T T T B, C 10 3 3 3 4.5 T T T T T T 31 333 4 . 5 B, C 16 3 4.5 5 T T T T T 31 3 4.5 B, C 20 3 5 T T T T T 31 3 B, C 25 5 T T T T T 31 B, C 32 T T T T T 31 B, C 40 T T T T SN201 DS201 DS202C B, C, D, K ≤4 T T T T T T T T T T T T T T T T T T B , C , D , K 6 666666 T T T T T T T T T T T T B, C, D, K 8 3 3 3 4.5 7.5 8.5 T T T T 31 333 4 . 5 B, C, D, K 10 3 3 3 4.5 7.5 8.5 T T T T 31 333 4 . 5 B, C, D, K 13 3 4.5 5 7.5 T T T T 31 3 4.5 B, C, D, K 16 3 4.5 5 7.5 T T T T 31 3 4.5 B, C, D, K 20 3 5 6 T T T T 31 3 B, C, D, K 25 5 6 T T T T 31 B, C, D, K 32 6 7.5 T T T 31 B, C, D, K 40 7.5 T T T SN201 M DS201 M DS202C M B, C ≤4 T T T T T T T T T T T T T T T T T T B, C 6 6 6 6 6 6 6 12 T T T T T T T T T T T B, C 10 3 3 3 4.5 7.5 8.5 T T T T 31 333 4 . 5 B, C 13 3 4.5 5 7.5 T T T T 31 3 4.5 B, C 16 3 4.5 5 7.5 T T T T 31 3 4.5 B, C 20 3 5 6 T T T T 31 3 B, C 25 5 6 T T T T 31 B, C 32 6 7.5 T T T 31 B, C 40 7.5 T T T

Coordination tables: selectivity System pro M compact MCBs T2 T3 N, S, H, L N, S TMD, MA EL TMD, MA 160 250 63 80 100 125 2 125 160 2 160 10 25 63 100 160 63 80 100 125 2 125 160 2 160 200 2 200 250 2 250 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T

5 T T T T T T T T T 5 T T T T T T T T T T

T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 8.5 T T T T T T T T T 7.5 8.5 T T T T T T T T T 7.5 8.5 T T T T T T T T T 7.5 8.5 T T T T T T T T T 5 7.5 T 7.5 T T T T T T 5 7.5 T 7.5 T T T T T T T 5 7.5 T 7.5 T T T T T T 5 7.5 T 7.5 T T T T T T T

56 T 6 T T T T T T 56 T 6 T T T T T T T

6 7.5 6 T T T T T T 6 7.5 6 T T T T T T T 61 7.5 6 T T T T T 61 7.5 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 8.5 T T T T T T T T T 7.5 8.5 T T T T T T T T T 5 7.5 T 7.5 T T T T T T 5 7.5 T 7.5 T T T T T T T 5 7.5 T 7.5 T T T T T T 5 7.5 T 7.5 T T T T T T T 6 7.5 6 T T T T T T 6 7.5 6 T T T T T T T 61 7.5 6 T T T T T 61 7.5 T T T T T T T

MCB S290 - S200 @ 400/415 V 400/415 V Supply s. S290 Char. D Icu [kA] 15 Load s. In [A] 80 100 S200 C 10 ≤ 2 T T

3 T T

4 T T

8 T T

13 4.5 7 16 4.5 7 20 3.5 5 25 3.5 5 32 4.5 D 10 ≤ 2 T T

6 T T

400/415 V Supply s. S290 Char. D Icu [kA] 15 Load s. In [A] 80 100 S200 K 10 ≤ 2 T T Z 10 ≤ 2 T T 16 4.5 7 20 3.5 5 25 3.5 5 32 3 4.5 40 3 4.5 50 3 Technical details Coordination tables: selectivity System pro M compact MCBs

400/415 V Supply s. S290 Char. D Icu [kA] 15 Load s. In [A] 80 100 S200 M C 15 ≤ 2 T T B-C 15 6 10.5 T 8 10.5 T 10 5 8 13 4.5 7 16 4.5 7 20 3.5 5 25 3.5 5 32 4.5 D 15 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 16 3 5 20 3 5 25 4 K 15 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 16 3 5 20 3 5 25 4 MCB S290 - S200 M @ 400/415 V Technical details Coordination tables: selectivity System pro M compact MCBs 400/415 V Supply s. S290 Char. D Icu [kA] 15 Load s. In [A] 80 100 S200 P B-C 25 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 13 4.5 7 16 4.5 7 20 3.5 5 25 3.5 5 15 32 4.5 D 25 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 13 3 5 16 3 5 20 3 5 25 4 15 32 MCB S290 - S200 P @ 400/415 V 400/415 V Supply s. S290 Char. D Icu [kA] 15 Load s. In [A] 80 100 S200 P K 25 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 13 3 5 16 3 5 20 3 5 25 4 15 32 Z 25 ≤ 2 T T 6 10.5 T 8 10.5 T 10 5 8 16 4.5 7 20 3.5 5 25 3.5 5 15 32 3 4.5 40 3 4.5 50 3

pro M compact® MCBsTechnical details Coordination tables: selectivity E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.1 T T T T T 2 0.3 0.5 0.7 2.1 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 0.8 4.5 T T T T T T 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 10

0.5 T T TTTTTT

1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 10 0 . 5 TTTTTTTT

1 TTTTTTTT

1.6 0.6 T T T T T T T 2 0 . 5 1TTTTTT 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 10 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 10 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 Char. Char. Char. Char. Char. Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800S - S200 @ 230/400 V

pro M compact® MCBsTechnical details Coordination tables: selectivity E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 C 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT

2 TTTTTTTT

3 0.7 2.2 4.4 T T T T T 4 0.7 1.3 2.2 4.4 T T T T 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200 B 10 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 Char. Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA

Coordination tables: selectivity System pro M compact MCBs E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1.6 0.6 T T T T T T T 2 0 . 5 1TTTTTT 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800S C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M B 15 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800S B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M B 15 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 Char. Char. Char. Char. Char. Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800S - S200 M @ 230/400 V

Coordination tables: selectivity System pro M compact MCBs E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 3 0.7 2.2 4.4 T T T T T 6 0.5 1 1.2 2 2.8 9.9 T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800S D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200M B 15 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 Char. Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA

Coordination tables: selectivity System pro M compact MCBs E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K 25 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT

0.75 T T T T T T T T

1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.1 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800S B L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 25 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S C L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 25 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 25 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S B L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 25 0 . 5 T TT T T T T T 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.2 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800S C L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K 25 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 Char. Char. Char. Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800S - S200 P @ 230/400 V

Coordination tables: selectivity System pro M compact MCBs E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P K 25 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800S D L. Icu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P B 25 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800S D L. I cu [kA] 50 In [A] 25 32 40 50 63 80 100 125 S200P C 25 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 3 0.7 2.2 4.4 T T T T T 6 0.5 1 1.2 2 2.8 9.9 22 T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 Char. Char. Char. E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800N - S200 @ 230/400 V E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 B 10 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 C 10 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.2 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 4 0.4 0.4 0.7 1 1.7 3 T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 B 10 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 C 10 0 . 5 TTTTTTTT 1.6 0.6 T T T T T T T 2 0 . 5 1TTTTTT 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 Technical details Coordination tables: selectivity System pro M compact MCBs

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 B 10 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 C 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 3 0.7 2.2 4.4 T T T T T 4 0.7 1.3 2.2 4.4 T T T T 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 D 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200 K 10 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 T T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 Technical details Coordination tables: selectivity System pro M compact MCBs

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800N - S200M @ 230/400 V E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M B 15 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M B 15 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1.6 0.6 T T T T T T T 2 0 . 5 1TTTTTT 32 0.5 0.6 0.8 1 1.4 40 0.6 0.8 1 1.4 50 0.7 0.9 1.3 63 0.9 1.2 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 2 . 1 TTTTTTT 1.6 0.8 2.3 T T T T T T 2 0.4 0.7 2.3 T T T T T 13 0.7 1 1.4 2 16 1 1.4 2 20 1 1.4 25 1.4 Technical details Coordination tables: selectivity System pro M compact MCBs

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M B 15 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M C 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 3 0.7 2.2 4.4 T T T T T 6 0.5 1 1.2 2 2.8 T T T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M D 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200M K 15 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 Technical details Coordination tables: selectivity System pro M compact MCBs

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA S800N - S200P @ 230/400 V E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P B 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P C 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. B L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P K 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.1 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P B 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P C 0 . 5 TTTTTTTT 1 3 . 3 TTTTTTT 1.6 0.6 1.3 T T T T T T 2 0.4 0.7 1.3 T T T T T 8 0.4 0.6 0.7 1 1.4 10 0.4 0.6 0.7 1 1.4 13 0.5 0.7 0.9 1.3 16 0.7 0.9 1.3 20 0.9 1.3 25 0.9 1.3 32 0.8 1.1 40 0.8 1.1 50 1 63 0.9 E. S800N Char. C L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P K 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT 1 0 . 8 5TTTTTT 1.6 0.5 1 2.3 T T T T T 2 0.3 0.5 0.7 2.3 T T T T 6 0.6 0.8 1.2 2 3.6 8 0.7 0.9 1.3 2 10 0.9 1.3 2 13 1 1.5 16 1.5 Technical details Coordination tables: selectivity System pro M compact MCBs

E. = feed side L. = load side T = Total selectivity up to breaking capacity of the switch on load side Selectivity limit values indicated in kA E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P B 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P C 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 3 0.7 2.2 4.4 T T T T T 6 0.5 1 1.2 2 2.8 9.9 22 T 40 1.1 1.9 2.4 3.7 50 1.5 1.9 2.3 63 1.7 2.3 E. S800N Char. D L. Icu [kA] 36 In [A] 25 32 40 50 63 80 100 125 S200P K 0 . 2 TTTTTTTT 0 . 3 TTTTTTTT 0 . 5 TTTTTTTT 1 . 6 TTTTTTTT 2 2 . 3 TTTTTTT 3 0.7 1.3 4.4 T T T T T 4 0.7 1 2.2 4.4 7.7 T T T 25 1.1 1.8 2.2 3.2 32 1.7 2 2.9 40 1.9 2.6 50 2.2 Technical details Coordination tables: selectivity System pro M compact MCBs

Coordination tables: selectivity System pro M compact MCBs Functional diagram of selective main circuit breakers S 700 2CDC 022 453 F0103 Back-up protection Selective main circuit breakers of the S 700 series are capable of switching off short-circuit currents of up to 25 kA automatically in networks with a rated voltage of 230/400 V. Back-up protection is necessary only when the prospective short-circuit current may exceed 25 kA prosp. at the installation point. Further information on back-up protection on request. Short circuit discrimination When ABB miniature circuit-breaker are used in combination with the S 700, higher short- circuit currents can be disconnected than are indicated as permissible rated switching capacity of device. Considering the values given in the table, the S 700 operates selectively with respect to the combination with the final device. If other mcbs are used selectivity for 6 kA and 10 kA devices is available up to the rated switching capacity of the final device. MCB Supply side S 700 fuse Char. E/K gG Icu [kA] 25 Load side In [A] 16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 S 200 C 3 1 0 1 0 1 0 1 0 1 0 1 0 1 0 88 0 . 3 0 . 7 1 . 2 4 . 6 6666 4 1 0 1 0 1 0 1 0 1 0 1 0 1 0 88 0 . 3 0 . 6 0 . 9 2 . 8 6666 B, C 13 10 10 10 10 10 10 10 8 8 0.7 1.5 2.5 3.5 5 6 16 10 10 10 10 10 10 8 8 1.3 2 2.9 4.1 6 20 10 10 10 10 10 8 8 1.8 2.6 3.5 5 25 10 10 10 10 8 8 1.8 2.6 3.5 5 32 10 10 10 8 8 2.2 3 4 40 10 10 8 8 2.5 4 50/63 8 8 3.5 S 200 M C 3 15 15 15 15 15 15 15 10 10 0.3 0.7 1.2 4.6 10 10 10 10 4 15 15 15 15 15 15 15 10 10 0.3 0.6 0.9 2.8 10 10 10 10 B, C 16 15 15 15 15 15 15 10 10 1.3 2 2.9 4.2 6 20 15 15 15 15 15 10 10 1.9 2.7 3.8 5.6 25 15 15 15 15 10 10 1.9 2.6 3.6 5.4 32 15 15 15 10 10 2.4 3.2 4.2 40 15 15 10 10 3.2 4.2 50/63 10 10 3.8 Limited overload selectivity

Coordination tables: selectivity System pro M compact MCBs MCB Supply side S 700 fuse Char. E/K gG Icu [kA] 25 Load side In [A] 16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 S 200 S 200 M K6 /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 0.3 1.2 4 >15 >15 >15 >15 >15 3 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 . 3 0 . 7 1 . 2 4 . 6 6666 4 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 . 3 0 . 6 0 . 9 2 . 8 6666 6 1 01 01 01 01 01 01 01 01 0 0 . 7 1 . 7 3 5 . 9 6 6 8 1 01 01 01 01 01 01 01 01 0 1 . 3 2 . 2 3 . 6 6 6 10 10 10 10 10 10 10 10 10 10 1.7 2.5 4 6 16 10 10 10 10 10 10 10 10 2.2 3.1 4.6 20 10 10 10 10 10 10 10 3.1 4.6 25 10 10 10 10 10 10 2.6 3.5 32 10 10 10 10 10 3.5 40 10 10 10 10 50/63 10 10 S 200 S 200 M Z6 /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 0.5 2 >15 >15 >15 >15 >15 >15 3 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 . 3 0 . 7 1 . 8 66666 4 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 . 3 0 . 6 1 . 3 76666 6 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 0 . 2 0 . 5 0 . 9 2 . 7 6666 10 10 10 10 10 10 10 10 10 10 0.4 0.6 1.3 2.4 4 6 6 16 10 10 10 10 10 10 10 10 0.5 1.1 1.7 3 4.5 6 25 10 10 10 10 10 10 1.4 2 3 4 32 10 10 10 10 10 1.4 2 3 4 40 10 10 10 10 2 3 4 50/63 10 10 2.2 3.5 Limited overload selectivity S 200 M S 200 M

Coordination tables: selectivity System pro M compact MCBs MCB Supply side S 700 fuse Char. E/K gG Icu [kA] 25 Load side In [A] 16 20 25 35 40 50 63 80 100 16 20 25 35 50 63 80 100 S 200 P B 6 16 25 25 25 25 25 25 25 25 1 1.6 2.4 3.5 5.3 20 25 25 25 25 25 25 25 1 1.6 2.2 3.3 4.7 25 25 25 25 25 25 25 1.5 2 3 4 32 25 25 25 25 25 1.3 2 2.8 3.6 40 25 25 25 25 1.9 2.7 3.4 50/63 10 10 2.7 3.4 S 200 P C 6 3 2 52 52 52 52 52 52 52 52 5 0 . 3 0 . 8 1 . 5 6 1 01 01 01 0 4 2 52 52 52 52 52 52 52 52 5 0 . 3 0 . 6 1 3 . 3 6 1 01 01 0 6 2 52 52 52 52 52 52 52 52 5 0 . 6 1 . 3 3 5 . 5 1 01 0 8 2 52 52 52 52 52 52 52 52 5 1 . 1 2 . 9 3 . 5 6 1 0 10 25 25 25 25 25 25 25 25 25 1 1.7 2.5 4 6 13 25 25 25 25 25 25 25 25 25 1.8 2.2 3 5.5 16 25 25 25 25 25 25 25 25 1.6 2 3 5 20 25 25 25 25 25 25 25 1.6 2.8 3.6 25 25 25 25 25 25 25 2.4 3.5 32 25 25 25 25 25 3.1 40 25 25 25 25 50/63 10 10 S 200 P K 6 /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 0.3 1 >15 >15 >15 >15 >15 >15 3 1 51 51 51 51 51 51 51 51 5 0 . 3 0 . 8 1 . 5 6 6 6 1 01 0 4 1 51 51 51 51 51 51 51 51 5 0 . 3 0 . 6 1 3 . 3 6 6 6 1 0 6 1 51 51 51 51 51 51 51 51 5 0 . 6 1 . 3 3 5 . 5 6 9 . 5 8 1 51 51 51 51 51 51 51 51 5 1 . 1 2 . 5 3 . 5 6 6 10 25 25 25 25 25 25 25 25 25 1 1.7 2.5 4 6 13 25 25 25 25 25 25 25 25 25 1.6 2.2 3 5.5 16 25 25 25 25 25 25 25 25 1.5 2 3 5 20 25 25 25 25 25 25 25 1.6 2.6 3.6 25 15 15 15 15 15 15 2.4 3.3 32 15 15 15 15 15 3.1 40 15 15 15 15 50/63 10 10 S 200 P Z 6 /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 0.3 1 >15 >15 >15 >15 >15 >15 3 15 15 15 15 15 15 15 15 15 0.3 0.6 1.8 10 10 10 10 10 4 1 51 51 51 51 51 51 51 51 5 0 . 3 0 . 6 0 . 6 1 . 3 6 1 01 01 0 6 1 51 51 51 51 51 51 51 51 5 0 . 8 2 . 6 6 1 01 0 8 1 51 51 51 51 51 51 51 51 5 1 . 7 3 . 4 7 1 0 10 25 25 25 25 25 25 25 25 25 1.3 2.2 3.7 6 16 25 25 25 25 25 25 25 25 1.7 2.8 4.1 20 25 25 25 25 25 25 25 2.1 3.1 25 15 15 15 15 15 15 2.6 32 15 15 15 15 15 40 15 15 15 15 50/63 10 10 Limited overload selectivity S 200 P S 200 P

Coordination tables: selectivity System pro M compact MCBs Upstream fuse 63 A gG fuse 80 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 C /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 3 1 01 01 01 0 1 01 01 01 0 8 4 1 01 01 01 0 1 01 01 01 0 8 B , C 6 1 01 01 01 0 1 01 01 01 0 8 C 8 7.5 7 7 6 10 10 10 8 8 B, C 10 7.5 7 7 6 10 10 10 8 6 13 6 6 6 6 10 10 9 7.5 6 16 6 6 6 6 10 10 9 7.5 6 2 0 6655 98866 32 4.5 4.5 6 6 6 40 4 6 6 50 4.5 S 700 S 200 Upstream fuse 100 A gG fuse /L50871 125 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 C 3 1 01 01 01 0 8 8 1 01 01 01 0 8 8 4 1 01 01 01 0 8 8 1 01 01 01 0 8 8 B , C 6 1 01 01 01 0 8 8 1 01 01 01 0 8 8 C 8 10 10 10 10 8 8 10 10 10 10 8 8 B, C 10 10 10 10 10 8 8 10 10 10 10 8 8 13 10 10 10 10 8 8 10 10 10 10 8 8 16 10 10 10 10 8 8 10 10 10 10 8 8 20 10 10 10 10 8 8 10 10 10 10 8 8 25 10 10 10 8 8 10 10 10 8 8 32 10 10 8 7.5 10 10 8 8 40 10 8 7 10 8 8 5 0 76 88 63 5 8 Limit of selectivity For the coordination of MCB, S 700 and upstream fuses the following selectivity limits can be assumed: Values for < 6 A and 8 A are only valid for C characteristic.

Coordination tables: selectivity System pro M compact MCBs Upstream fuse 100 A gG fuse /L50871 125 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 M C 3 1 51 51 51 51 01 01 51 51 51 51 01 0 4 1 51 51 51 51 01 01 51 51 51 51 01 0 B , C 6 1 51 51 51 51 01 01 51 51 51 51 01 0 C 8 15 15 15 15 10 10 15 15 15 15 10 10 B, C 10 15 15 15 15 10 10 15 15 15 15 10 10 13 15 12.5 12.5 12.5 10 10 15 15 15 15 10 10 16 15 12.5 12.5 12.5 10 10 15 15 15 15 10 10 20 12.5 10 12.5 10 10 10 15 15 15 15 10 10 25 10 10 10 10 9 15 15 15 10 10 32 10 10 10 7.5 15 15 10 10 40 10 9 7 15 10 10 50 7 6 10 10 63 5 10 Upstream fuse 63 A gG fuse 80 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 M C /L50872 2 >15 >15 >15 >15 >15 >15 >15 >15 >15 3 1 51 51 51 5 1 51 51 51 51 0 4 1 51 51 51 5 1 51 51 51 51 0 B , C 6 1 51 51 51 5 1 51 51 51 51 0 C 8 7.5 7 7 6 12.5 10 10 10 6 B, C 10 7.5 7 7 6 12.5 10 10 10 6 13 6 6 6 5 10 10 9 7.5 6 16 6 6 6 5 10 10 9 7.5 6 2 0 6655 98866 32 4.5 4.5 6 6 6 40 4 6 6 50 4.5 Values for < 6 A and 8 A are only valid for C characteristic.

Coordination tables: selectivity System pro M compact MCBs Upstream fuse 100 A gG fuse 125 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 P C 3 2 52 52 52 52 52 52 52 52 52 52 52 5 4 2 52 52 52 52 52 52 52 52 52 52 52 5 B , C 6 2 52 52 52 52 52 52 52 52 52 52 52 5 C 8 20 17 15 15 13 10 25 25 25 25 15 15 B, C 10 20 17 15 15 13 10 25 25 25 25 25 25 13 19 17 15 12.5 10 10 25 25 25 25 25 25 16 19 17 15 12.5 10 10 25 25 25 25 25 25 20 17 17 15 10 10 10 25 25 25 25 25 25 25 15 15 10 10 9 25 22 20 20 20 32 15 10 10 9 20 20 15 20 40 10 9 9 15 15 15 50 7 7 10 10 63 6 10 Upstream fuse 63 A gG fuse 80 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 P C /L50872 2 >25 >25 >15 >15 >25 >25 >25 >25 >25 3 1 51 51 51 5 2 52 51 51 51 5 4 1 51 51 51 5 2 52 51 51 51 5 B , C 6 1 51 51 51 5 2 52 51 51 51 5 C 8 7.5 7 7 6 12.5 10 12.5 10 10 B, C 10 7.5 7 7 6 12.5 10 12.5 10 6 1 3 6665 1 0 1 0 1 0 86 1 6 6665 1 0 1 0 1 0 86 2 0 6655 98876 32 4.5 4.5 6 6 6 40 4 6 6 50 4.5 Values for < 6 A and 8 A are only valid for C characteristic. Upstream fuse 160 A gG fuse /L50871 200 A gG Supply side S 700 S 700 Char. E/K E/K Icu [kA] 25 25 Load side In [A] 35 40 50 63 80 100 35 40 50 63 80 100 S 200 P C 3 2 52 52 52 52 52 52 52 52 52 52 52 5 4 2 52 52 52 52 52 52 52 52 52 52 52 5 B , C 6 2 52 52 52 52 52 52 52 52 52 52 52 5 C 8 25 25 25 25 15 15 25 25 25 25 15 15 B, C 10 25 25 25 25 25 25 25 25 25 25 25 25 13 25 25 25 25 25 25 25 25 25 25 25 25 16 25 25 25 25 25 25 25 25 25 25 25 25 20 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 25 32 25 25 25 25 25 25 25 25 40 25 25 25 25 25 25 50 15 10 25 10 63 10 10

Coordination tables: selectivity System pro M compact MCBs Supply S. T2 T1 - T2 T1 - T2 - T3 Version B, C, N, S, H, L Char. Icu [kA] Release TM 10 15 25 In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 Load S. B --- ≤2 --- 3 --- 4 S200 S200M S200P 10 3 1 3 3 3 4.5 7.5 8.5 17 T T S200 S200M S200P 13 3 1 3 3 4.5 7.5 7.5 12 20 T S200 S200M S200P 16 3 1 3 4.5 5 7.5 12 20 T S200 S200M S200P 20 3 1 356 1 0 1 5 T S200 S200M S200P 25 3 1 5 6 10 15 T S200 S200M-S200P - 32 3 1 6 7.5 12 T S200 S200M-S200P - 40 5.5 1 7.5 12 T S200 S200M-S200P - 50 3 1 52 7.5 10.5 S200 S200M-S200P - 63 5 2 63 10.5 --- 8 0 --- 1 0 0 --- 1 2 5

1 Value valid only for T2 magnetic only supply side circuit-breaker

2 Value valid only for T2-T3 magnetic only supply side circuit-breaker

3 Value valid only for T3 magnetic only supply side circuit-breaker

4 Value valid only for T4 magnetic only supply side circuit-breaker

Supply S. T2 T1 - T2 T1 - T2 - T3 Version B, C, N, S, H, L Char. Icu [kA] Release TM 10 15 25 In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 Load S. C S200 S200M S200P ≤2 T T T T T T T T T T T T S200 S200M S200P 3 T T T T T T T T T T T T S200 S200M S200P 4 T T T T T T T T T T T T S200 S200M S200P 10 3 1 3 3 3 4.5 7.5 8.5 17 T T S200 S200M S200P 13 3 1 3 3 4.5 7.5 7.5 12 20 T S200 S200M S200P 16 3 1 3 4.5 5 7.5 12 20 T S200 S200M S200P 20 3 1 356 1 0 1 5 T S200 S200M S200P 25 3 1 5 6 10 15 T S200 S200M-S200P - 32 3 1 6 7.5 12 T S200 S200M-S200P - 40 5.5 1 7.5 12 T S200 S200M-S200P - 50 3 1 52 7.5 10.5 S200 S200M-S200P - 63 5 2 63 10.5 - S290 - 80 43 - S290 - 100 4 3 - S290 - 125

5 Value valid only for T4 In 160 magnetic only supply side circuit-breaker

MCCB - S2.. B @ 415 V MCCB - S2.. C @ 415 V

B, C, N, S, H, L, V TM EL 200 250 20 25 32 50 80 100 125 160 200 250 320÷500 10 25 63 100 160 100, 160 250, 320 320÷630 T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 55 4 5 6.5 9 T T T T T T T T T T T T T T T 54 5 6.5 8 T T T T T T T T T T T T T T T 34 5 6.5 8 T T T T T T T T T T T T T T 5 7.5 T T T T T T T T T T T T T T 5 7.5 T T T T T T T T T T T T T T 54 7.5 T T T T T T T T T T T T T T 6.5 T T T T T T T T T T T T T 54 T T T T T T 10.5 10.5 T T T T T T4 T4 T T T T 10.5 T T T T3 T4 T5 T2 T4 T5 B, C, N, S, H, L, V TM EL 200 250 20 25 32 50 80 100 125 160 200 250 320÷500 10 25 63 100 160 100, 160 250, 320 320÷630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 55 4 5 6.5 9 T T T T T T T T T T T T T T T 54 5 6.5 8 T T T T T T T T T T T T T T T 34 5 6.5 8 T T T T T T T T T T T T T T 5 7.5 T T T T T T T T T T T T T T 5 7.5 T T T T T T T T T T T T T T 54 7.5 T T T T T T T T T T T T T T 6.5 T T T T T T T T T T T T T 54 T T T T T T 10.5 10.5 T T T T T T T T T T T 10.5 T T T 10 15 5 11 T T 4 T T T 7.53 15 5 4 8 T T 41 2 4 T T 7.53 84 12 T 4 T T Technical details Coordination tables: selectivity System pro M compact MCBs

Coordination tables: selectivity System pro M compact MCBs Supply S. T2 T1 - T2 T1 - T2 - T3 Version B, C, N, S, H, L Char. Icu [kA] Release TM 10 15 25 In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 Load S. D S200 S200M S200P ≤2 T T T T T T T T T T T T S200 S200M S200P 3 T T T T T T T T T T T T S200 S200M S200P 4 T T T T T T T T T T T T S200 S200M S200P 10 3 1 3 3 3 3 5 8.5 17 T T S200 - S200P 13 2 1 2 2 3 5 8 13.5 T S200 S200M S200P 16 2 1 2 2 3 5 8 13.5 T S200 S200M S200P 20 2 1 2 3 4.5 6.5 11 T S200 S200M S200P 25 2 1 2.5 4 6 9.5 T S200 S200M-S200P - 32 4 6 9.5 T S200 S200M-S200P -4 0 3 1 58 T S200 S200M-S200P -5 0 2 1 32 5 9.5 S200 S200M-S200P -6 3 3 2 53 9.5 - S290 - 80 43 - S290 - 100 43 - - - 125 Supply S. T2 T1 - T2 T1 - T2 - T3 Version B, C, N, S, H, L Char. Icu [kA] Release TM 10 15 25 In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 Load S. K S200 S200M S200P ≤2 T T T T T T T T T T T T S200 S200M S200P 3 T T T T T T T T T T T T S200 S200M S200P 4 T T T T T T T T T T T T S200 S200M S200P 10 3 1 3 3 3 3 6 8.5 17 T T - - S200P 13 2 1 3 3 5 7.5 10 13.5 T S200 S200M S200P 16 2 1 3 3 4.5 7.5 10 13.5 T S200 S200M S200P 20 2 1 3 3.5 5.5 6.5 11 T S200 S200M S200P 25 2 1 3.5 5.5 6 9.5 T S200 S200M-S200P - 32 4.5 6 9.5 T S200 S200M-S200P -4 0 3 1 58 T S200 S200M-S200P -5 0 2 1 32 6 9.5 S200 S200M-S200P -6 3 3 2 5.53 9.5 - S290 - 80 43 - S290 - 100 43 --- 1 2 5 MCCB - S2.. D @ 415 V MCCB - S2.. K @ 415 V

B, C, N, S, H, L, V TM EL 200 250 20 25 32 50 80 100 125 160 200 250 320÷500 10 25 63 100 160 100, 160 250, 320 320÷630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 55 4 559 T T T T T T T T T T T T T T T 54 4 5.5 T T T T T T T T T T T T T T 4 5.5 T T T T T T T T T T T T T T 44 5 T T T T T T T T T T T T T T 44 4.5 T T T T T T T T T T T T T T 4.54 T T T T T T T T T T T T T T 4.54 T T T T T T T T T T T T T T T T T T T 9.5 9.5 T T T T T T T T T T 9.5 T T T 10 15 5 11 T T 4 T T T 7.53 15 8 T T 41 2 5 T T T3 T4 T5 T2 T4 T5 B, C, N, S, H, L, V TM EL 200 250 20 25 32 50 80 100 125 160 200 250 320÷500 10 25 63 100 160 100, 160 250, 320 320÷630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 54 559 T T T T T T T T T T T T T T T 54 558 T T T T T T T T T T T T T T T 54 58 T T T T T T T T T T T T T T 56 T T T T T T T T T T T T T T 54 64 T T T T T T T T T T T T T T 54 64 T T T T T T T T T T T T T T 5.54 T T T T T T T T T T T T T 54 T T T T T T 9.5 9.5 T T T T T T T T T T T 9.5 T T T 10 15 5 11 T T 4 T T T 7.53 15 5 4 8 T T 41 2 5 T T Technical details Coordination tables: selectivity System pro M compact MCBs 4 4

Coordination tables: selectivity System pro M compact MCBs MCCB - S 290 @ 415 V 400V Supply s. T2 Version N-S-H-L Relay TM-M EL Iu [A] 160 160 Load S. Char. Icu [kA] In [A] 160 160 S 290 C-D 20* 80 4 100 4 C 20* 125 4 * 15 kA for D characteristic. 400V Supply s. T3 Version N-S Relay TM-M Iu [A] 250 Load S. Char. Icu [kA] In [A] 160 200 250 S 290 C-D 20* 80 4 10 15 100 4 7.5 15 125 7.5 * 15 kA for D characteristic. ** Value valid with supply side magnetic only circuit-breaker. Supply S. T2 T1 - T2 T1 - T2 - T3 Version B, C, N, S, H, L Char. Icu [kA] Release TM 10 15 25 In [A] 12.5 16 20 25 32 40 50 63 80 100 125 160 Load S. Z S200 - S200P ≤2 T T T T T T T T T T T T S200 - S200P 3 T T T T T T T T T T T T S200 - S200P 4 T T T T T T T T T T T T S200 - S200P 10 3 1 3 3 3 4.5 8 8.5 17 T T - - S200P 13 3 1 3 3 4.5 7.5 7.5 12 20 T S200 - S200P 16 3 1 3 4.5 5 7.5 12 20 T S200 - S200P 20 3 1 356 1 0 1 5 T S200 - S200P 25 3 1 5 6 10 15 T S200 S200P - 32 3 1 6 7.5 12 T S200 S200P - 40 5.5 1 7.5 12 T S200 S200P - 50 4 1 52 7.5 10.5 S200 S200P - 63 5 2 63 10.5 --- 8 0 --- 1 0 0 --- 1 2 5 MCCB - S2.. Z @ 415 V

B, C, N, S, H, L, V TM EL 200 250 20 25 32 50 80 100 125 160 200 250 320÷500 10 25 63 100 160 100, 160 250, 320 320÷630 T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 7.5 7.5 4 7.5 7.5 T T T T T T T T T T T T T T T T 55 4 5 6.5 9 T T T T T T T T T T T T T T T 54 5 6.5 8 T T T T T T T T T T T T T T T 54 4.5 6.5 8 T T T T T T T T T T T T T T 5 6.5 T T T T T T T T T T T T T T 5 6.5 T T T T T T T T T T T T T T 54 6.5 T T T T T T T T T T T T T T 5 T T T T T T T T T T T T T 3.54 T T T T T T 10.5 10.5 T T T T T T T T T T T 10.5 T T T Technical details Coordination tables: selectivity System pro M compact MCBs MCCB - S800 @ 415 V Supply S. T1 T1 - T3 T1 T3 Version B, C, N, S, H, L, V Release TM Load S. Char. I cu [kA] I n [A] 16 20 25 32 40 50 63 80 100 125 160 160 200 250 S800N B C D 10 4.5 4.5 4.5 4.5 8 10 20 1 251 T T T T 13 4.5 4.5 4.5 7.5 10 15 25 1 T T T T 16 4.5 4.5 7.5 10 15 25 1 T T T T 20 4.5 7.5 10 15 25 1 T T T T 25 6 10 15 20 1 T T T T 32 7.5 10 20 1 T T T T 40 10 20 1 T T T T 50 15 T T T T

63 T T T T

80 T T T

100 T T

B C D K 10 4.5 4.5 4.5 4.5 8 10 20 1 251 361 361 361 T 13 4.5 4.5 4.5 7.5 10 15 25 1 361 361 361 T 16 4.5 4.5 7.5 10 15 25 1 361 361 361 T 20 4.5 7.5 10 15 25 1 361 361 361 T 25 6 10 15 20 1 361 361 361 T 32 7.5 10 20 1 361 361 361 T 40 10 20 1 361 361 361 T 50 15 36 1 361 361 T 63 361 361 361 T 80 361 361 T 100 361 T 125 T 1 Select the lowest value between what is indicated and the breaking capacity of the supply side circuit-breaker

Coordination tables: selectivity System pro M compact MCBs MCCB-S800 @ 415 V Supply S. T4 T4 - T5 Version N, S, H, L, V Release TM EL Load S. Char. I cu [kA] I n [A] 20 25 32 50 80 100 125 160 200÷250 100÷630 S800N/S B 36-50 10 6.5 6.5 1 6.5 6.5 11 T T T T T 13 6.5 5 1 6.5 6.5 11 T T T T T 16 5 1 6.5 6.5 11 T T T T T 20 4 1 6.5 6.5 11 T T T T T 25 6.5 11 T T T T T 32 6.5 8 T T T T T 40 5 1 6.5 T T T T T 50 5 1 7.5 T T T T 63 5 1 7 T T T 10 6.5 6.5 1 6.5 6.5 11 T T T T T 13 6.5 5 1 6.5 6.5 11 T T T T T 16 5 1 6.5 6.5 11 T T T T T 20 4 1 6.5 6.5 11 T T T T T 25 4 1 6.5 11 T T T T T 32 6.5 8 T T T T T 40 5 1 6.5 T T T T T 50 4 1 51 7.5 T T T T 63 4 1 6.51 7 T T T 80 4 1 51 6.51 6.5 T T 100 4 1 51 51 6.5 T 125 4 1 41 51 T D 36-50 10 6.5 6.5 1 6.5 6.5 11 T T T T T 13 5 1 6.5 11 T T T T T 16 6.5 11 T T T T T 20 6.5 1 11 T T T T T 25 6.5 1 11 T T T T T 32 8 1 T T T T T 40 6.5 1 T T T T T 50 7.5 1 T T T T 63 7 1 T T T 80 51 T T 100 51 T 125 T K 36-50 10 6.5 1 6.5 6.5 11 T T T T T 13 5 1 5 6.5 11 T T T T T 16 5 1 6.5 11 T T T T T 20 4 1 6.5 11 T T T T T 25 6.5 1 111 T T T T T 32 5 1 81 T T T T T 40 6.5 1 T T T T T 50 5 1 7.51 T T T T 63 4 1 6.51 71 T T T 80 5 1 6.51 71 T T 100 5 1 6.51 71 T 125 51 6.51 T 1 Value valid only for magnetic only supply side circuit-breaker (with In = 50 A, please consider MA52 circuit-breakers)

2 For T4 In = 100 A, value valid only for magnetic only supply side circuit-breaker

3 For T4 In = 160 A, value valid only for magnetic only supply side circuit-breaker

MCBs internal resistance, power loss and max. permissible earth-fault loop impedance System pro M compact MCBs Internal resistance and power loss of the miniature circuit-breakers Internal resistance per pole in mΩ, power loss per pole in W Type Rated current Device series B, C, D * In A m Ω W SN201 L 2 520 2.1 SN201 4 147.5 2.4 SN201 M 6 64 2.3 10 19 1.9 16 14 3.6 20 12 4.8 25 7,1 4.4 32 6,5 6.7 40 4,7 7.5 * Total power loss Type Rated Device series current B, C, D /L54706 K Z In A m Ω W m Ω W m Ω W S 200 and 0.5 5500 1.4 6340 1.6 10100 2.5 1 1440 1.4 1550 1.6 2270 2.3 S 200 M 1.6 630 1.6 695 1.8 1100 2.8 2 460 1.8 460 1.9 619 2.5 3 150 1.3 165 1.5 202 1.8 4 110 1.8 120 2.0 149 2.4 6 55 2.0 52 1.9 104 3.7 8 15 1.0 38 2.5 53.9 3.45 13 13.3 2.3 12.6 2.1 – – /L54706 Current intensities 0.5 – 4 apply exclusively to C-type trip characteristics. Internal resistances are subject to application-specific and environment-specific conditions and are therefore to be considered as typical values. Type Rated Type current Ri Pvmax Ri Pvmax A m Ω W m Ω W S 700-E 10 38.0 4.9 S 700-K 16 15.5 5.2 10.5 3.1 20 12.5 6.5 7.5 3.8 25 7.4 6.5 5.7 3.9 32 5.3 7.2 35 4.0 7.6 4.7 7.8 40 4.0 8.0 3.8 6.8 50 2.9 9.5 3.0 10.0 63 2.0 9.9 2.0 9.6 80 1.5 13.5 1.3 10.1 100 1.0 14.4 1.1 12.3

PDF text was truncated. Refer to the original document for complete details.