MODEL: ANR ANR SPECIFICATIONS ES-2116 Rev.2 Page 1/4 http://www.m-system.co.jp/ Limit Alarms (potentiometer adj.) A-UNIT ANGLE SENSOR ALARM Functions & Features

  • Providing SPDT relay outputs at preset voltage level provided from Angle Sensor (model: NRA)
  • Dual (Hi/Lo) trip
  • Energized or de-energized coil at a tripped condition selectable
  • 50 % zero/span adjustments
  • Hysteresis (deadband) adjustable
  • Enclosed relays
  • Relays can be powered 110 V DC
  • High-density mounting Typical Applications
  • Annunciator
  • Various alarm applications (1.97) 136 (5.35) (3.15) mm (inch) MODEL: ANR-[1]1[2][3]-[4]

ORDERING INFORMATION

  • Code number: ANR-[1]1[2][3]-[4] Specify a code from below for each of [1] through [4]. (e.g. ANR-1111-B) [1] ACTION 1: Direct (output increases with input increase) 2: Reverse (output increases with input decrease) [2] SETPOINT 1 OUTPUT 1: Hi (coil energized at alarm) 2: Hi (coil de-energized at alarm) 3: Lo (coil energized at alarm) 4: Lo (coil de-energized at alarm) [3] SETPOINT 2 OUTPUT 1: Hi (coil energized at alarm) 2: Hi (coil de-energized at alarm) 3: Lo (coil energized at alarm) 4: Lo (coil de-energized at alarm) [4] POWER INPUT AC Power B: 100 V AC C: 110 V AC D: 115 V AC F: 120 V AC G: 200 V AC H: 220 V AC J: 240 V AC DC Power S: 12 V DC R: 24 V DC V: 48 V DC P: 110 V DC

RELATED PRODUCTS

  • Brushless angle sensor (model: NRA) GENERAL SPECIFICATIONS Construction: Plug-in Connection: M3.5 screw terminals Housing material: Flame-resistant resin (black) Isolation: Input to output 1 to output 2 to power Zero adjustment: 0 – 50 % of linearity-assured range of the angle sensor (front) Span adjustment: 50 – 100 % of linearity-assured range of the angle sensor (front) Setpoint adjustments: 270°-turn screwdriver adjustments (front); 0 – 100 % independently Hysteresis (deadband) adjustments: 1 – 100 % (front) LEDs: LED turns on at a tripped condition; red for output 1, green for output 2 (located behind the front cover) Power ON timer: Relays de-energized for approx. 2 seconds after power is turned on. INPUT SPECIFICATIONS Input: 2 – 3 V DC (output from Angle Sensor) Excitation: 5 V DC ±2 %

MODEL: ANR ANR SPECIFICATIONS ES-2116 Rev.2 Page 2/4 http://www.m-system.co.jp/ OUTPUT SPECIFICATIONS ■ Relay Contact: 100 V AC @ 1 A (cos ø = 1)

120 V AC @ 1 A (cos ø = 1)

240 V AC @ 0.5 A (cos ø = 1)

30 V DC @ 1 A (resistive load)

Maximum switching voltage: 380 V AC or 125 V DC Maximum switching power: 120 VA or 30 W Minimum load: 5 V DC @ 10 mA Mechanical life: 5 x 107 cycles For maximum relay life with inductive loads, external protection is recommended. Output Code: 1 & 4: Terminals 1 – 2, 9 – 10 turn ON Alarm Trip Operation Terminal No. in parentheses Trip Operation in Power Failure

  • Output Code: 2 & 3 : Terminals 1 – 3, 9 – 11 turn ON 0 50 100 ▲ Input (%) Output 2 Setpoint Output 1 Setpoint Output 1 (9-10)ON Output 2 (1-2)ON (1-3)ON (9-11)ON INSTALLATION Power input
  • AC: Operational voltage range: rating ±10 %, 50/60 ±2 Hz, approx. 2 VA
  • DC: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.) approx. 2 W (80 mA at 24 V) Operating temperature: -5 to +60°C (23 to 140°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span Trip point repeatability: ±0.5 % Temp. coefficient: ±0.05 %/°C (±0.03 %/°F) Response time: Approx. 0.5 sec. (0 – 100 % at 90 % setpoint) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @1 minute (input to output 1 to output 2 to power to ground)

MODEL: ANR ANR SPECIFICATIONS ES-2116 Rev.2 Page 3/4 http://www.m-system.co.jp/ EXTERNAL VIEW Front Cover (open) No.1 LED No.1 Hysteresis (Deadband) Adj. No.2 Hysteresis (Deadband) Adj. No.2 LED No.1 Setpoint Adj. No.2 Setpoint Adj. Zero Adj. Span Adj. Input Monitor EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 5678 2111 10 80 (3.15) 80 (3.15) (.79) 40 (1 .57) 50 (1 .97) 7 .8 (.31) CLAMP (top & bottom) DIN RAIL 35mm wide2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 11 –M3.5 SCREW

  • When mounting, no extra space is needed between units. SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM Low Drift Amplifier Inductive Load (Coil) LOAD Diode, Varistor or CR Circuit Inductive Load (Coil) Varistor or Spark Quenching Circuit U LOAD ■ Relay Protection
  • AC Powered
  • DC Powered Base Socket *Relay status for output codes “1” & “4”, at power OFF. U(+) V(–) POWER Ry Ry SETPOINT MONITOR HYSTERESIS (DEADBAND) SETPOINT HYSTERESIS (DEADBAND) H L C EXC INP COM red yellow white SETPOINT 1 OUTPUT H L C SETPOINT 2 OUTPUT SZ ANGLE SENSOR Comparator Comparator Exc. Volt. Generator

MODEL: ANR ANR SPECIFICATIONS ES-2116 Rev.2 Page 4/4 http://www.m-system.co.jp/ Specifications are subject to change without notice.