Features
- Offers the SLC connectivity via the Velociti protocol.
- Supports 159 FAAST XT devices per loop.
- Provides Very Early Warning Fire Detection, as precise as 0.00046%/ft obscuration.
- Includes five alarm levels and two sensitivity modes to provide application flexibility.
- Has 3-fan speed settings that allow for maximum cover- age area, and provide savings on current consumption.
- Delivers ultrasonic flow sensing for each pipe inlet and chamber airflow monitoring for precise system health information.
- A single device can cover up to 28,800 square feet.
- Combines a dual source optical detection chamber with enhanced algorithms to provide high sensitivity with greater immunity to nuisance conditions.
- Delivers a patented particle separator to remove large, non-fire particulate, ensuring chamber health and extending the life of the field-replaceable filter.
- Converts TCP and Serial modbus for easy integration with building management systems.
- Offers easy configuration via USB interface, no external power needed.
- Supports an onboard Ethernet interface that enables remote monitoring and email notification.
- Displays an LCD user interface that allows for detailed device information and interaction such as the following. - Active faults - Reset of airflow baseline - Test/reset/isolate - Precise airflow monitoring
- Produces configurable air flow fault thresholds. AAD-9400X
12 Clintonville Road, Northford, CT 06472-1610 USA • Tel: (203) 484-7161 • Fax: (203) 484-7118
9021-60838 Rev. A page 2 of 2 www.gamewell-fci.com Figure 1 illustrates the FAAST XT user interface display. Specifications Intelligent FAAST XT Specifications Electrical Specifications External Supply Voltage18-30 VDC Remote Reset Time External monitor must be pulled low for a minimum of 100 ms Power Reset 1 sec. Avg. Operating Current Fan High - 465mA, 11.2W; Fan Med - 340mA, 8.2W; Fan Low - 220mA, 5.3W Alarm Fan High - 493mA, 11.85W; Fan Med - 368mA, 8.85W; Fan Low - 248mA, 6W Relay Contact Ratings 3.0 A @ 30 VDC,
0.5 A @ 125 VAC
Operating Temperature 32°F (0°C) to 100°F (38°C); Factory Tested to 133°F (55°C) Sampled Air Temperature -4°F (-20°C) to 140°F (60°C) Humidity Range 10 to 95% (non-condensing) IP Rating IP30 Coverage Area 28,800 sq.ft. (2,676 sq.m) Air Movement 0-4,000 ft./min. (0-1,219 m/min.) Physical Specifications Height 13.3 in (338 mm) Width 13.1 in (333 mm) Depth 7.5 in (191 mm) Cable Access 4 1-inch (2.54 cm) cable entry holes on top, bottom and back of the unit Wire Gauge 12 AWG (2.05 mm) max. to 24 AWG (0.5 mm) min. Maximum Single Pipe Length 400 ft. (123 m) Total Pipe Length 1050 ft. (320 m) (*all designs must be verified within PipeIQ software) Multiple Pipe Network 262 ft. per pipe Network Outside Pipe Diameter 1.050 inches, IPS (25 mm) Internal Pipe Diameter 0.591 to 0.827 inches (15-21 mm) Sensitivity Range 0.00046%Obs/ft to 6.25% Obs/ft (0.0015% Obs/m to 20.5% Obs/m) Relays 8 Form C, 3 AMP , programma- ble latching or non-latching Diagnostic Specifications Event Log 18,000 events stored Trend Data Log Configurable sampling period (1 minute to 1 day) Service Log 300 custom user entries Network Specifications Communication Network Ethernet monitoring
6 E-mail address alerts,
Network Services DHCP, SMTP, HTTP, MODBUS/ TCP, AutoIP , NetBIOS-NS, Serial MODBUS Ethernet 10/100Mbps, MDI-X Modbus TCP or Serial RS- Email 6 recipients, sel. notification Specifications (Continued) Network Specifications (Continued) Webserver Read Configuration, Live View, Logs Configuration Specifications PipeQ USB or Ethernet Modbus Ethernet or RS-485 Figure 1 - Intelligent FAAST XT User Interface Display The User Interface consists of 5 Alarm levels:
- Alert • Fire 1 and Fire 2, 10 Particulate levels
- Action 1 and Flow and Fault graph
- Action 2
Ordering Information
AAD-9400X System Sensor Intelligent FAAST XT Fire Alarm Aspiration Sensing Technology Accessories CMKT00100 FAAST Information Kit–Includes a Comprehensive Instruction Manual F-A3384-000 Replacement Air Filter Assembly Various† UL®-Approved Pipe and Fittings † Additional accessory information, including part num- bers, can be accessed at systemsensor.com/faast.