A26-30-10-110V-50HZ ABB | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 5

Technical content

"No longer for sale" replaced by A26-30-10 110V 50Hz / 110-120V 60Hz Contactor A26-30-10 110V 50Hz / 110-120V 60Hz Extended Product Type A26-30-10 110V 50Hz / 110-120V 60Hz Product ID 1SBL241001R8410 EAN 3471522062840 Catalog Description A26-30-10 110V 50Hz / 110-120V 60Hz Contactor Long Description A26 contactors are mainly used for controlling 3-phase motors and generally for controlling power circuits up to 690 V AC or 220 V DC. The contactors can also be used for many other applications such as isolation, capacitor switching, lighting. The A... series 1-stack 3-pole contactors are of the block type design. - Main poles and auxiliary contact blocks: 3 main poles, 1 built-in auxiliary contact, front and side-mounted add- on auxiliary contact blocks - Control circuit: AC operated with laminated magnet circuit - Accessories: a wide range of accessories is available. General Information PRODUCT-DETAILS Ordering 1 piece Minimum Order Quantity 85364900 Customs Tariff Number 1SBL231001R8400 Replacement Product ID (NEW) Popular Downloads 1SBC100122C0202_Ch02 Data Sheet, Technical Information FPTC407722P0001 Instructions and Manuals

93.6 mm Product Net Depth / Length 90 mm Product Net Height 0.6 kg Product Net Weight Technical Number of Main Contacts NO Number of Main Contacts NC Number of Auxiliary Contacts NO Number of Auxiliary Contacts NC Auxiliary Circuit 690 V Main Circuit 690 V Rated Operational Voltage Supply Circuit 50 / 60 Hz Rated Frequency (f) acc. to IEC 60947-4-1, Open Contactors q = 40 °C 45 A acc. to IEC 60947-5-1, q = 40 °C 16 A Conventional Free-air Thermal Current (I th (690 V) 40 °C 45 A (690 V) 55 °C 40 A (690 V) 70 °C 32 A Rated Operational Current AC-1 (I e (415 V) 55 °C 26 A (440 V) 55 °C 26 A (500 V) 55 °C 22 A (690 V) 55 °C 17 A (380 / 400 V) 55 °C 26 A (220 / 230 / 240 V) 55 °C 26 Rated Operational Current AC-3 (I e (415 V) 11 kW (440 V) 15 kW (500 V) 15 kW (690 V) 15 kW (380 / 400 V) 11 kW (220 / 230 / 240 V) 6.5 kW Rated Operational Power AC-3 (P e (230 / 240 V) 40 °C, 50 / 60 Hz 11.5 kvar (230 / 240 V) 55 °C, 50 / 60 Hz 11.5 kvar (230 / 240 V) 70 °C, 50 / 60 Hz 9 kvar (400 / 415 V) 40 °C, 50 / 60 Hz 19 kvar (400 / 415 V) 70 °C, 50 / 60 Hz 15 kvar (400 / 415 V) 55 °C, 50 / 60 Hz 19 kvar (440 V) 40 °C, 50 / 60 Hz 20 kvar (440 V) 55 °C, 50 / 60 Hz 20 kvar (440 V) 70 °C, 50 / 60 Hz 16.5 kvar (500 / 550 V), 40 °C, 50 / 60 Hz 23 kvar (500 / 550 V) 55 °C, 50 / 60 Hz 23 kvar (500 / 550 V) 70 °C, 50 / 60 Hz 19 kvar (690 V) 40 °C, 50 / 60 Hz 32 kvar (690 V) 55 °C, 50 / 60 Hz 32 kvar (690 V) 70 °C, 50 / 60 Hz 26 kvar Rated Operational Power AC-6b (P e 8 x Ie AC-3 Rated Breaking Capacity AC-3 10 x Ie AC-3 Rated Making Capacity AC-3 (500 V) 2 A (690 V) 2 A (24 / 127 V) 6 A (220 / 240 V) 4 A (380 / 400 V) 3 A Rated Operational Current AC-15 (I e Auxiliary Circuit - gG Type Fuses 10 A gG Type Fuses 50 A Short-Circuit Protective Devices at 40 °C Ambient Temp, in Free Air, from a Cold State 10 s 210 A at 40 °C Ambient Temp, in Free Air, from a Cold State 15 min 45 A Rated Short-time Withstand Current Low A26-30-10 110V 50Hz / 110-120V 60Hz

at 40 °C Ambient Temp, in Free Air, from a Cold State 1 min 90 A at 40 °C Ambient Temp, in Free Air, from a Cold State 1 s 400 A at 40 °C Ambient Temp, in Free Air, from a Cold State 30 s 110 A Voltage (I cw cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 440 V 420 A cos phi=0.45 (cos phi=0.35 for Ie > 100 A) at 690 V 170 A Maximum Breaking Capacity (AC-1) 600 cycles per hour (AC-2 / AC-4) 300 cycles per hour (AC-3) 1200 cycles per hour Maximum Electrical Switching Frequency (24 V) 6 / 144 A (48 V) 2.8 / 134 A (72 V) 2 / 144 A (125 V) 1.1 / 138 A (250 V) 0.55 / 138 A Rated Operational Current DC-13 (I e acc. to IEC 60947-4-1 and VDE 0110 (Gr. C) 1000 V acc. to UL/CSA 600 V Rated Insulation Voltage i 8 kV Rated Impulse Withstand Voltage (U imp 10 million Mechanical Durability 3600 cycles per hour Maximum Mechanical Switching Frequency

50 Hz 110 V

60 Hz 110 ... 120 V Rated Control Circuit Voltage (U c Average Holding Value 50 / 60 Hz 12 V·A Average Pull-in Value 50 Hz 125 V·A Average Pull-in Value 60 Hz 120 V·A Coil Consumption Between Coil De-energization and NO Contact Opening 4 ... 11 ms Between Coil Energization and NO Contact Closing 8 ... 21 ms Operate Time TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715 TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715 Mounting on DIN Rail 2 x M4 screws placed diagonally Mounting by Screws (not supplied) Flexible with Cable End 0.75 ... 4 mm² Rigid Cable 1.5 ... 6 mm² Connecting Capacity Main Circuit Rigid Cable 1 ... 4 mm² Connecting Capacity Auxiliary Circuit acc. to IEC 60529, IEC 60947-1, EN 60529 Auxiliary Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20 acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP20 Degree of Protection M 4 (+,-) pozidriv 2 screws with cable clamp Connecting Terminals (delivered in open position) Main Poles Screw Terminals Terminal Type Technical UL/CSA (600 V AC) 40 A General Use Rating UL/CSA (200 ... 208 V AC) Three Phase 7-1/2 hp (220 ... 240 V AC) Three Phase 10 hp (440 ... 480 V AC) Three Phase 20 hp (550 ... 600 V AC) Three Phase 25 hp Horsepower Rating UL/CSA Environmental Close to Contactor Fitted with Thermal O/L Relay -25 ... 55 °C Close to Contactor without Thermal O/L Relay (Uc) -40 ... 70 °C Close to Contactor for Storage -60 ... +80 °C Ambient Air Temperature acc. to IEC 60068-2-30 and 60068-2-11 - UTE C 63-100 specification II Climatic Withstand Without Derating 3000 m Maximum Operating Altitude Permissible Closed, Shock Direction: B1 10 g Open, Shock Direction: B1 5 g Shock Direction: A 20 g Resistance to Shock acc. to IEC 60068-2-27 A26-30-10 110V 50Hz / 110-120V 60Hz

Shock Direction: B2 15 g Shock Direction: C1 20 g Shock Direction: C2 20 g Following EU Directive 2011/65/EU RoHS Status Certificates and Declarations (Document Number) BV_2634H07559E0 BV Certificate CB_FR_602227A CB Certificate CCC_2013010304615752 CCC_2004010309133982 CCC Certificate CQC2013010304615752 CQC2004010309133982 CQC Certificate CSA_1033838_LR056745 CSA Certificate 2020980304001609 2020980304001227 Declaration of Conformity - CCC 1SBD250801U1000 Declaration of Conformity - CE 1SBD250818U1000 Declaration of Conformity - UKCA DNV-GL_TAE00000TX DNV Certificate DNV-GL_TAE00000TX DNV GL Certificate EAC_RU C-FR ME77 B03599 EAC Certificate 1SBD250004E1003 Environmental Information FPTC407722P0001 Instructions and Manuals LOVAG_FR97043 LOVAG Certificate LRS_9830011E4 LR Certificate RINA_ELE172319XG001 RINA Certificate RMRS_0507015250 RMRS Certificate 2CMT2021-006277 RoHS Information UL_071301E39231 UL Certificate Container Information 1 piece Package Level 1 Units 101 mm Package Level 1 Width 115 mm Package Level 1 Depth / Length 61 mm Package Level 1 Height 0.6 kg Package Level 1 Gross Weight 3471522062840 Package Level 1 EAN box 24 piece Package Level 2 Units 300 mm Package Level 2 Width 245 mm Package Level 2 Depth / Length 308 mm Package Level 2 Height 14.4 kg Package Level 2 Gross Weight 576 piece Package Level 3 Units Classifications Q Object Classification Code EC000066 - Magnet contactor, AC-switching ETIM 4 EC000066 - Magnet contactor, AC-switching ETIM 5 A26-30-10 110V 50Hz / 110-120V 60Hz

EC000066 - Power contactor, AC switching ETIM 6 EC000066 - Power contactor, AC switching ETIM 7 EC000066 - Power contactor, AC switching ETIM 8 V11.0 : 27371003 eClass 39121529 UNSPSC Low Voltage Products and Systems Control Products Contactors Block Contactors Categories A26-30-10 110V 50Hz / 110-120V 60Hz