6811499 TURCK | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 8

Technical content

Edition • 2023-07-21T16:02:47+02:00 BL compact™ multiprotocol fieldbus station for Industrial Ether- net

4 IO-Link Channels

Nominal system voltage 24 VDC System power supply Via auxiliary power Voltage supply connection 2 x M12, 5-pin Admissible range Vi 20…30 VDC Nominal current Vi 165 mA Max. current Vi 1 A Admissible range Vo 20…30 VDC Nominal current Vo 80 mA Max. current Vo 4 A Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus address range 1…92 0 (192.168.1.254) 93 (BOOTP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *recommended for PROFINET 97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Fieldbus connection technology 2 × M12 4-pole, D-coded Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11499 ■ On-machine Compact fieldbus I/O block ■ EtherNet/IP™, Modbus® TCP, or PROFINET slave ■ Integrated Ethernet Switch ■ 10 Mbps / 100 Mbps supported ■ Two 4-pole M12, D-coded, connectors for fieldbus connection ■ 2 rotary switches for node address ■ IP67, IP69K ■ M12 I/O connectors ■ LEDs indicating status and diagnostics ■ Electronics galvanically separated from the field level via optocouplers

Edition • 2023-07-21T16:02:47+02:00 Modbus TCP Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 10 register Input register start address 0 (0x0000 hex) Output Data Size max. 8 register Output register start address 2048 (0x0800 hex) Ethernet/IP Addressing acc. to EtherNet/IP specification Device Level Ring (DLR) supported Class 1 connections (CIP) 6 Input Assembly Instance 103 Input Data Size 13 INT Output Assembly Instance 104 Output Data Size 8 INT Configuration Assembly Instance 106 Configuration Size 0 Comm Format Data - INT PROFINET Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Input Data Size max. 16 BYTE Output Data Size max. 16 BYTE Digital inputs from 4IOL Input type PNP Low level signal voltage < 5 V High level signal voltage > 11 V Low level signal current < 1.5 mA DI / < 5mA SIO Digital outputs from 4IOL Output type PNP Sensor supply (VSENS) 24 VDC Output current per channel 0.5 A Output voltage 24 VDC Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive > 48 ò Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes Technology Signal type IO-Link Electrical isolation isolation of electronics and field level via optocou- plers

Edition • 2023-07-21T16:02:47+02:00 Dimensions 113 x 71 x 32.5 mm Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque Weight 390 ± 20 g Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Protection class IP67 IP69K Ambient temperature -40…+70 °C Storage temperature -40…+85 °C Relative humidity 15 to 95% (non-condensing) Vibration test Acc. to IEC 61131-2 - up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility Acc. to IEC 61131-2 MTTF 136 years MTTF note acc. to SN 29500 (Ed. 99) 20 °C Approvals and certificates CE, cULus, Class I Div.2

Edition • 2023-07-21T16:02:47+02:00 Pinning and wiring diagram Ethernet Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218 Pin assignment (M12, D-coded) I/O Channels Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment Auxiliary Power Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no. U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment

Edition • 2023-07-21T16:02:47+02:00 Station LED status LED Color Status Description IOs OFF No power RED ON Low power or station error RED FLASHING (1 Hz) I/O module configuration error RED FLASHING (4 Hz) No I/O module bus communication GREEN ON Station ok GREEN FLASHING Force mode active BUS OFF Power Off GREEN ON Connected to Master GREEN FLASHING Ready GREEN FLASHING 3x (1Hz) ARGEE Running RED ON Error RED FLASHING WINK YELLOW ON DHCP/BOOTP Search OFF No Link GREEN ON Link GREEN FLASHING Traffic LNK/ACT YELLOW ON 100 Mbit Linked I/O LED status LED Color Status Description D * OFF No diagnostics active RED ON Station error/ module bus communication failure RED FLASHING (0.5Hz) Diagnostics active OFF Channel Status x = “0“ (OFF), no diagnostics active GREEN Flashing IO-Link communication, Process data valid RED ON No IO-Link communication IO-Link Mode channels 10...13 Flashing Process Data Invalid OFF Channel Status x = “0” (OFF)DI Mode 10...13 GREEN ON Channel Status x = “1” (ON) OFF Channel Status x = “0” (OFF)XSG 14...17 GREEN ON Channel Status x = “1” (ON) * D LED also indicates gateway diagnostics

Edition • 2023-07-21T16:02:47+02:00 Process Data Mapping of Each Protocol EtherNet/IP™ I/O & Diagnostics Data Mapping INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 DI 17 DI 16 DI 15 DI 14 DI 13 DI 12 DI 11 DI 10Digital

1 OCDO 17 OCDO 16 OCDO 15 OCDO 14 DVS 13 DVS 12 DVS 11 DVS 10

IOL Data 2…15 IO-Link Read Data (depends on parameter settings)

16 Module number reporting diagnostic dataDiagnostics

17 Replace Sta-

  • Diagnostics Active - - - - -

18 IOL 10 EVT2 IOL 10 EVT1 IOL 10 PDINV IOL 10 HWER IOL 10 DSER IOL 10 CFGER - OCDO 14

19 IOL 10 GEN-

IOL 10 OVL IOL 10 VHIGH IOL 10 VLOW IOL 10 ULVE IOL 10 LLVU IOL 10 OTMP IOL 10 PRMER

20 IOL 11 EVT2 IOL 11 EVT1 IOL 11 PDINV IOL 11 HWER IOL 11 DSER IOL 11 CFGER - OCDO 15

21 IOL 11 GEN-

IOL 11 OVL IOL 11 VHIGH IOL 11 VLOW IOL 11 ULVE IOL 11 LLVU IOL 11 OTMP IOL 11 PRMER

22 IOL 12 EVT2 IOL 12 EVT1 IOL 12 PDINV IOL 12 HWER IOL 12 DSER IOL 12 CFGER - OCDO 16

23 IOL 12 GEN-

IOL 12 OVL IOL 12 VHIGH IOL 12 VLOW IOL 12 ULVE IOL 12 LLVU IOL 12 OTMP IOL 12 PRMER

24 IOL 13 EVT2 IOL 13 EVT1 IOL 13 PDINV IOL 13 HWER IOL 13 DSER IOL 13 CFGER - OCDO 17

Slot 1 (ref. Byte 16)

25 IOL 13 GEN-

IOL 13 OVL IOL 13 VHIGH IOL 13 VLOW IOL 13 ULVE IOL 13 LLVU IOL 13 OTMP IOL 13 PRMER OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 DO 17 DO 16 DO 15 DO 14 - - - -Digital

IOL Data 2…15 IO-Link Write Data (depends on parameter settings) Legend GENER Common error EVT1 Maintenance events VHIGH Overvoltage HWER Hardware error ULVE Upper limit value exceeded CFGER Wrong or missing device OTMP Overtemperature DVS Data Valid Signal EVT2 Out of specification error OC Over Current PDINV Process input data invalid DIAG Diagnostics DSER Data storage error DO Digital Output OVL Overload DI Digital Input VLOW Undervoltage COM Communication Lost Bit LLVU Lower limit value underrun CFG Connfiguration Error PRMER Parameterization error Modbus® TCP Register Mapping REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 0x0000 OCDO OCDO OCDO OCDO DVS 13 DVS 12 DVS 11 DVS 10 DI 17 DI 16 DI 15 DI 14 DI 13 DI 12 DI 11 DI 10Inputs (RO) 0x0001… 0x0007 IO-Link Read Data (depends on parameter settings) Status (RO) 0x000C - FCE - - CFG COM VI low VI high VO low VO high OCVI - - - - DIAG DIAG 0x0800 - - - - - - - - DO 17 DO 16 DO 15 DO 14 - -Outputs (RW) 0x0801… 0x0807 IO-Link Write Data (depends on parameter settings) 0xA000 IOL 10 GEN- ER IOL 10 OVL IOL 10 VHIGH IOL 10 VLOW IOL 10 ULVE IOL 10 LLVU IOL 10 OTMP IOL 10 PRMER IOL 10 EVT2 IOL 10 EVT1 IOL 10 PDINV IOL 10 HWER IOL 10 DSER IOL 10 CFGER - OC DO 14 01A001 IOL 11 GEN- ER IOL 11 OVL IOL 11 VHIGH IOL 11 VLOW IOL 11 ULVE IOL 11 LLVU IOL 11 OTMP IOL 11 PRMER IOL 11 EVT2 IOL 11 EVT1 IOL 11 PDINV IOL 11 HWER IOL 11 DSER IOL 11 CFGER - OC DO 15 01A002 IOL 12 GEN- ER IOL 12 OVL IOL 12 VHIGH IOL 12 VLOW IOL 12 ULVE IOL 12 LLVU IOL 12 OTMP IOL 12 PRMER IOL 12 EVT2 IOL 12 EVT1 IOL 12 PDINV IOL 12 HWER IOL 12 DSER IOL 12 CFGER - OC DO 16 I/O Diag. (RO) 01A003 IOL 13 GEN- ER IOL 13 OVL IOL 13 VHIGH IOL 13 VLOW IOL 13 ULVE IOL 13 LLVU IOL 13 OTMP IOL 13 PRMER IOL 13 EVT2 IOL 13 EVT1 IOL 13 PDINV IOL 13 HWER IOL 13 DSER IOL 13 CFGER - OC DO 17 PROFINET® Process Data Inputs 0 DI 17 DI 16 DI 15 DI 14 DI 13 DI 12 DI 11 DI 10

Edition • 2023-07-21T16:02:47+02:00 2…15 IO-Link Read Data (depends on parameter settings)

0 DO 17 DO 16 DO 15 DO 14 - - - -

2…15 IO-Link Write Data (depends on parameter settings)

Edition • 2023-07-21T16:02:47+02:00 Accessories Type code Ident-No. Dimension drawing LOCK-EURO-C A0885 Locking guard for straight eurofast™ C-body connectors (RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa- tions LOCK-EURO-C (10/BAG) A0886 Locking guard for straight eurofast™ C-body connectors (RKC, RKCV, RSC, RSCV) in a Class I, Division 2 installa- tions