Description:
- Bussmann® series Indicating and non- indicating E-Rated, current-limiting, medium voltage fuses for potential, small power and control transformers.
Contents
- Low amp, current-limiting E-Rated PT medium voltage fuses are general purpose fuses defined by their melting time-current characteristic that permit their electrical interchangeability with other fuses of the same E Rating.
- E-Rated general purpose fuses must have a current responsive element that will melt in 300 seconds at an RMS current within the range of 200% to 240% of the fuse’s nameplate current rating, fuse refill, or link per ANSI C37 .46 for fuses rated 100E or less.
- PT fuses are physically dimensioned for easy installation in existing hardware.
- Space saving size eases design considerations for new installations.
- Current-limiting fuses provide positive interruption even on low fault currents. The fuse limits the magnitude of electromechanical stresses in the protected apparatus.
- These fuses are in a self-contained, non- venting package for installation indoors or outdoors in an enclosure.
- Available in indicating and non-indicating versions.
- Open fuse indicator speeds troubleshooting by providing a positive visual indication of fuse operation. T ypical applications:
- Primary protection of:
- Medium voltage potential transformers
- Small medium voltage service transformers
- Small medium voltage control transformers. PT Medium voltage fuses for potential and small power transformers
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries E-Rated PT medium voltage fuses Catalog symbols (by maximum voltage rating):
- 2.475kV
- 2NCLPT -_
- 3.6kV
- 3.6ABCNA_
- 3.6ABWNA_
- 3.6CAV_
- 5.5kV
- JCW-_
- 5CLPT -_E
- 5NCLPT -_E
- 5NCLPT -_E-A
- 5.5ABWNA_E
- 5.5AMWNA_E
- 5.5CAV_E
- 5.5CAVH_E
- 7 .2kV
- 7 .2ABWNA_
- 7 .2ABCNA_
- 7 .2AMWNA_E
- 7 .2CAV_
- 8.3kV
- 8CLPT -_E-A
- 8CLPT -_E-B
- 8NCLPT -_E
- 8NCLPT -_E-A
- 8NCLPT -_E-B
- 12kV
- 12ABCNA_
- 12CAV_
- 15.5kV
- 15CLPT -_E
- 15NCLPT -_E-A
- 15NCLPT -_E-B
- 15.5CAV_E
- 15.5CAVH_E
- 17 .5kV
- 17 .5ABGNA_
- 17 .5CAV_
- 24kV
- 24ABGNA_
- 24CAV_
- 25.5kV
- 25CLPT -_E
- 36kV
- 36ABGNA_
- 36CAV_
- 38kV
- 38CAV_E
- 38CAVH_E
- 38CLPT -_E Ratings*:
- Volts
- 2.4kV to 38kV
- Amps
- 0.25 to 15A
- Interrupting ratings
- 25 to 80kA RMS Sym * See catalog number tables for voltages, ampacities and interrupting ratings by catalog number. Agency information:
- Those PT fuses conforming to the requirements for E-Rating meet the performance characteristics of ANSI C37 .46
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 2.475kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 0.25 — 2NCLPT -.25E (63) 1A1837 0.5 — 2NCLPT -.5E (63) 1 — 2NCLPT -1E (40) 2 — 2NCLPT -2E (40) 5 — 2NCLPT -5E (25) Dimensions (see catalog number tables for values) A B C Recommended fuseclip and fuse block: Description Cat. No. Open fuseclip for 0.8 (20mm) dia. fuses 1A1837 Single-pole open fuse block with #10-32 phil-slot screw terminals rated 2500V, 5A maximum and 63kA withstand rating PTFB-2500-JCD
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 2.47kV time-current curves — minimum melting for 2NCLPT -_E Time in seconds Current in apps 2NCLPT-_E 1/4A 1/2A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 2.47kV time-current curves — total clearing for 2NCLPT -_E 1/4A 1/2A Time in seconds Current in apps 2NCLPT-_E
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 2.47kV peak let-through curves for 2NCLPT -_E Peak instantaneous let-through current in kilo-amperes Available current in apps 2NCLPT-_E 1/4A 1A & 2A 1/2A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 3.6kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 2 8.7 (221) 1.6 (41) 7 .6 (193) — 3.6CAV2 (50) 1A1837 A3354705 10 — 3.6ABCNA10 (50) Dimensions (see catalog number tables for values) Recommended fuseclips: Description Cat. No. Open fuseclip for 1.0 (25.4mm) dia. fuses A3354705 A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 3.6kV Time-current curves — minimum melting for 3.6CAV_, 3.6ABC_ and 3.6ABW_ 3.6ABC_, 3.6ABW_, 3.6CAV_ 6.3A (ABC/ABW) 10A (ABC/ABW) 3.15A (ABC/ABW) 2A (CAV) Time in seconds RMS symmetrical prospective current in amperes
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 3.6kV Peak let-through curves for 3.6ABC_ and 3.6ABW_
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 1 5.6 (142) 1 (25) 4.4 (1 12) — 5.5ABWNA1E (50) A3354705 2 5.6 (142) 1 (25) 4.4 (1 12) — 5.5ABWNA2E (50) A3354705 2 7 .4 (188) 1.6 (41) 6.2 (157) 5.5CAVH2E (63) JCW-2E (40) 1A0835 3 5.6 (142) 1 (25) 4.4 (1 12) — 5.5ABWNA3E (50) A3354705 3 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT -3E (80) — 1A0835 3 7 .4 (188) 1.6 (41) 6.2 (157) JCW-3E (40) 1A0835 4 7 .3 (185) 1.6 (41) 5.9 (150) — JCW-4E (40) 1A0835 5 9.5 (241) 1.6 (41) 8.1 (206) 5CLPT -5E (80) — 1A0835 5 5.6 (142) 1 (25) 4.4 (1 12) — 5.5ABWNA5E (50) A3354705 5 7 .3 (185) 1.6 (41) 5.9 (150) — JCW-5E (40) 1A0835 † Does not comply with ANSI C37.46 for “E” rating. CLPT T ype mountings and hardware 5.5kV maximum (4.8kV nominal)* Amp rating Fuse mounting type BIL (kV) Catalog number Mounting (including live parts, end fittings)* Live parts (including end fittings)*** End fittings (disconnect only)Porcelain insulator Glass-polyester insulator CLPT and NCLPT -A Mounting 0.5–10 Non-disconnect 60 5CLPT -PNM-A 5CLPT -GNM-A CLPT -NL — Disconnect† 60 5CLPT -PDM-A 5CLPT -GDM-A CLPT -DL CLPT -DF * Refers to 5CLPT and 5NCLPT-A fuses only. See page 70 for dimensions and diagrams of typical mounting. * End fittings supplied only when required. † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries Dimensions (see catalog number tables for values) Indicator A B C Recommended fuseclips: Description Cat. No. Open fuseclip for 0.8 (20mm) dia. fuses 1A1837 Open fuseclip for 1.0 (25.4mm) dia. fuses A3354705
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — minimum melting for 5NCLPT -_-A 5NCLPT-_E-A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — total clearing for 5NCLPT -_-A 5NCLPT-_E-A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV peak let-through curves for 5NCLPT -_-A 5NCLPT-_E-A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — minimum melting for 5NCLPT_ 5NCLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — total clearing for 5NCLPT_ 5NCLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV peak let-through curves for 5NCLPT_ 5NCLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — minimum melting for 5CLPT_ 0.5A 1.5A 10A 5CLPT-_E 0.5, 1 and 1.5 A fuse melt times in the dotted line region may not be assured due to manufacturing variations. The dotted lines show nominal operation. Some individual fuses may not open until current at 10-second mark is applied.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV Time-current curves — total clearing for 5CLPT_ 5CLPT-_E 0.5A 1.5A 10A Times in seconds
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV peak let-through curves for 5CLPT_ 5CLPT-_E 10A 0.5A 1A & 1.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — minimum melting for 5.5CAV_ and 5.5CAVH_ 5.5CAV_, 5.5CAVH_ 15A (CAV) 0.5A (CAVH) 1A (CAVH) 2A (CAVH)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — total clearing for 5.5CAV_ 5.5CAV_ 15A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV peak let-through curves for 5.5CAVH_ 5.5CAVH_ 2A (CAVH) 1A (CAVH) 0.5A (CAVH)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — minimum melting for 5.5ABW_ and 5.5AMW_ 5.5ABW_, 5.5AMW_ 0.5A (AMW) 5A (AMW) 4A (AMW) 3A (AMW) 2A (AMW) 1A (AMW) 0.5A (ABW) 3A (ABW) 2A (ABW) 1A (ABW) 5A (ABW)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV time-current curves — total clearing for 5.5ABW_ and 5.5AMW_ 5.5ABW_, 5.5AMW_ 0.5A (AMW) 4A (AMW) 3A (AMW) 2A (AMW) 1A (AMW) 5A (AMW) 0.5A (ABW) 3A (ABW) 2A (ABW) 1A (ABW) 5A (ABW)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 5.5kV peak let-through curves for 5.5ABW_ and 5.5AMW_ 5.5ABW_, 5.5AMW_ 5A (AMW) 3A (AMW) 2A (AMW) 1A (AMW) 0.5A (AMW) 4A (AMW) 5A (ABW) 3A (ABW) 2A (ABW) 1A (ABW) 0.5A (ABW)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 7 .2kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 2 8.7 (221) 1.6 (41) 7 .5 (190) — 7 .2CAV2 (63) 1A0835 4 8.7 (221) 1.6 (41) 7 .5 (190) — 7 .2CAV4 (63) 1A0835 5 5.6 (142) 0.8 (20) 4.8 (122) — 7 .2AMWNA5E (50) 1A1837 6 8.7 (221) 1.6 (41) 7 .5 (190) — 7 .2CAV6 (63) 1A0835 10 8.7 (221) 1.6 (41) 7 .5 (190) — 7 .2CAV10 (63) 1A0835 Dimensions (see catalog number tables for values) Recommended fuseclips Description Cat. No. Open fuseclip for 0.8 (20mm) dia. fuses 1A1837 Open fuseclip for 1.0 (25.4mm) dia. fuses A3354705 A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 7 .2kV time-current curves — minimum melting for 7 .2ABW_ and 7 .2CAV_ 7.2ABW_, 7.2CAV_ 10A (CAV) 2A (CAV) 6A (CAV) 4A (CAV) 3.15A (ABW) 6.3A (ABW)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 7 .2kV peak let-through curves for 7 .2ABW_
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 1 5 (127) 1.1 (28) 4 (102) — 8NCLPT -1E (50) A3354705 1 9.5 (241) 1.6 (41) 8.1 (206) — 8NCLPT -1E-A (50) 1A0835 2 8 (203) 0.8 (20) 7 .2 (183) — 8NCLPT -2E (25) 1A1837 4 8 (203) 0.8 (20) 7 .2 (183) — 8NCLPT -4E (25) 1A1837 5 5 (127) 1.1 (28) 4 (102) — 8NCLPT -5E (50) A3354705 † Does not comply with ANSI C37 .46 for “E” rating. CLPT type mountings and hardware 8.3kV maximum (7 .2kV nominal)* Amp rating Fuse mounting type BIL (kV) Catalog number Mounting (including live parts, end fittings)* Live parts (including end fittings)*** End fittings (disconnect only)Porcelain insulator Glass-polyester insulator 0.5–2 Non-disconnect 75 8CLPT -PNM-A 8CLPT -GNM-A CLPT -NL — Disconnect† 75 8CLPT -PDM-A 8CLPT -GDM-A CLPT -DL CLPT -DF 3–10 Non-disconnect 75 8CLPT -PNM-B 8CLPT -GNM-B CLPT -NL — Disconnect† 75 8CLPT -PDM-B 8CLPT -GDM-B CLPT -DL CLPT -DF * Refers to 8CLPT and 8NCLPT -A or -B fuses only. See page 70 for dimensions and diagrams of typical mounting. * End fittings supplied only when required. † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. Dimensions (see catalog number tables for values) Indicator A B C Recommended fuseclips: Description Cat. No. Open fuseclip for 0.8 (20mm) dia. fuses 1A1837 Open fuseclip for 1.0 (25.4mm) dia. fuses A3354705
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — minimum melting for 8NCLPT_ 8NCLPT-_E Curve 59887102 July 2002 Reference # 628852, 598871 Curve 56357206 July 2002
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — total clearing for 8NCLPT_ 8NCLPT-_E Curve 59887104 July 2002 Reference # 598871 Curve 59883706 July 2002
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV peak let-through curves for 8NCLPT_ 8NCLPT-_E Curve 63933703 July 2001 Reference # 639337 Curve 63933704 July 2001 Reference # 639337 2A4A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — minimum melting for 8CLPT_ 8CLPT-_E 10A 0.5A
0.5 A fuse melt time in the dotted line region may not be
assured due to manufacturing variations. The dotted lines show nominal operation. Some individual fuses may not open until current at 10-second mark is applied.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — total clearing for 8CLPT_ 8CLPT-_E 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV peak let-through curves for 8CLPT_ 8CLPT-_E 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — minimum melting for 8NCLPT -_E-A/B 8NCLPT-_E-A/B 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV time-current curves — total clearing for 8NCLPT -_E--A/B 8NCLPT-_E-A/B 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 8.3kV peak let-through curves for 8NCLPT -_E-A/B 8NCLPT-_E-A/B 1A & 2A 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 12kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 2 8.7 (221) 1.6 (41) 7 .5 (190) — 12CAV2 (40) 1A0835 3.15 7 .7 (195) 1 (25) 6.5 (165) — 12ABCNA3.15 (45) A3354705 Dimensions (see catalog number tables for values) Recommended fuseclips: Description Cat. No. Open fuseclip for 1.0 (25.4mm) dia. fuses A3354705 A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 12kV time-current curves — minimum melting for 12ABC_ and 12CAV_ 12ABC_, 12CAV_ 2A (CAV) 3.15A (ABC)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 12kV peak let-through curves for 12ABC_
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 1A0835 1 12.9 (328) 1.6 (41) 1 1.5 (292) 15.5CAVH1E (80) 15NCLPT -1E-A (63) 2 12.9 (328) 1.6 (41) 1 1.5 (292) 15.5CAVH2E (80) 15NCLPT -2E-A (63) 5 17 .6 (447) 1.6 (41) 16.1 (409) 15CLPT -5E-B (80) 15NCLPT -5E-B (63) 10 17 .6 (447) 1.6 (41) 16.1 (409) 15CLPT -10E-B (50) 15NCLPT -10E-B (63) CLPT T ype mountings and hardware 15.5kV maximum (14.4kV nominal) Amp rating Fuse mounting type* BIL (kV) Catalog number Mounting (Including live parts, end fittings) Live parts (including end fittings) End fittings (disconnect only)Porcelain insulator Glass-polyester insulator 0.5–2 Non- disconnect 95 15CLPT -PNM-A 15CLPT -GNM-A CLPT -NL — Disconnect† 95 15CLPT -PDM-A 15CLPT -GDM-A CLPT -DL CLPT -DF 3–10 Non- disconnect 95 15CLPT -PNM-B 15CLPT -GNM-B CLPT -NL CLPT -DF Disconnect† 95 15CLPT -PDM-B 15CLPT -GDM-B CLPT -DL — * See page 70 for dimensions and diagrams of typical mounting. ** End fittings supplied only when required. † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. Dimensions (see catalog number tables for values) Indicator A B C Recommended fuseclips: Description Cat. No.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV time-current curves — minimum melting for 15CLPT_ 15CLPT-_E 10A 0.5A 1.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV time-current curves — total clearing for 15CLPT_ 15CLPT-_E 10A 0.5A 1.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV peak let-through curves for 15CLPT_ 15CLPT-_E 10A 1A & 1.5A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV time-current curves — minimum melting for 15NCLPT_ 15NCLPT-_E 10A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV Time-current curves — total clearing for 15NCLPT_ 15NCLPT-_E 0.5A 10A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV Peak let-through curves for 15NCLPT_ 15NCLPT-_E 10A 1A & 2A 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV time-current curves — minimum melting for 15.5CAV_ and 15.5CAVH_ 15.5CAV_, 15.5CAVH_ 7A (CAV) 0.5A (CAVH) 2A (CAVH) 1A (CAVH) 3A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV time-current curves — total clearing for 15.5CAVH_ 15.5CAV_, 15.5CAVH_ 7A (CAV) 0.5A (CAVH) 2A (CAVH) 1A (CAVH) 3A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 15.5kV peak let-through curves for 15.5CAVH_ 15.5CAVH_ 0.5A (CAVH) 2A (CAVH) 1A (CAVH)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 17 .5kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating — 17 .5CAV2 (40) 1A0835 4 — 17 .5CAV4 (40) 6 — 17 .5CAV6 (40) 10 — 17 .5CAV10 (40) Dimensions (see catalog number tables for values) Recommended fuseclips: Description Cat. No. A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 17 .5kV time-current curves — minimum melting for 17 .5CAV_ 7.5CAV_ 2A (CAV) 6A (CAV) 4A (CAV) 10A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 24kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating — 24CAV2 (40) 1A08353 — 24CAV3 (40) 4 — 24CAV4 (40) Dimensions (see catalog number tables for values) Recommended fuseclips: Description Cat. No. A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 24kV time-current curves — minimum melting for 24CAV_ 24CAV_ 2A (CAV) 3A (CAV) 4A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 25.5kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating † Does not comply with ANSI C37 .46 for “E” rating. CLPT T ype Mountings and Hardware 25.5kV Maximum (23kV Nominal) Amp rating Fuse mounting type* BIL (kV) Catalog number Mounting (including live parts, end fittings) Live parts (including end fittings) End fittings (disconnect only)Porcelain insulator Glass-polyester insulator 0.5–1 Non-disconnect 150 25CLPT -PNM-A — 25CLPT -NL — Disconnect 150 25CLPT -PDM-A — 25CLPT -DL CLPT -DF * See page 70 for dimensions and diagrams of typical mounting. ** End fittings supplied only when required. † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. Dimensions (see catalog number tables for values) Indicator A B C Recommended fuseclips: Description Cat. No.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 25.5kV time-current curves — minimum melting for 25CLPT_ 25CLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 25.5kV time-current curves — total clearing for 25CLPT_ 25CLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 25.5kV Peak let-through curves for 25CLPT_ 25CLPT-_E 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 36kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (Interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 2 17 .3 (439) 1.6 (41) 16.1 (410) — 36CAV2 (40) 1A08354 — 36CAV4 (40) Dimensions (see catalog number tables for values) Recommended fuseclips: Description Cat. No. A B C
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 36kV Time-current curves — minimum melting for 36CAV_ 36CAV_ 4A (CAV) 2A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV maximum system voltage Amp rating Dimensions - in (mm) Catalog No. (interrupting rating - kA) Recommended fuseclipLength A Diameter B Clip centers C Indicating Non-indicating 1A0835 1 17 .3 (439) 1.6 (41) 16.1 (409) 38CAVH1E (38) — 2 17 .3 (439) 1.6 (41) 16.1 (409) 38CAVH2E (38) — 4 17 .3 (439) 1.6 (41) 16.1 (409) — 38CAV4E (38) † Does not comply with ANSI C37 .46 for “E” rating. CLPT T ype Mountings and Hardware 38kV Maximum (34.5kV Nominal) Amp rating Fuse mounting type Catalog number Mounting (including Live Parts, End Fittings)* Live Parts (including end fittings)* End fittings (disconnect only)Porcelain insulator Glass-polyester insulator
0.5 Disconnect† Not applicable Not applicable 25CLPT -NL CLPT -DF
Non-disconnect Not applicable Not applicable 25CLPT -DL — * End fittings supplied only when required. † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized. Dimensions (see catalog number tables for values) Indicator A B C Recommended fuseclip: Description Cat. No.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV time-current curves — minimum melting for 38CAV_ and 38CAVH 38CAV_, 38CAVH_ 1A (CAVH) 0.5A (CAVH) 2A (CAVH) 4A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV time-current curves — total clearing for 38CAV_ and 38CAVH 38CAV_, 38CAVH_ 1A (CAVH) 0.5A (CAVH) 2A (CAVH) 4A (CAV)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV peak let-through curves for 38CAVH 38CAVH_ 1A (CAVH) 0.5A (CAVH) 2A (CAVH)
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV time-current curves — minimum melting for 38CLPT_ 38CLPT_ 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV time-current curves — total clearing for 38CLPT_ 38CLPT_ 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries 38kV peak let-through curves for 38CLPT_ 38CLPT_ 0.5A
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries PT fuse mountings - in (mm) Catalog number Hole centers A Hole centers B Overall length C Hole Inset D Hole centers E Contact height F Overall height G BIL kV 5.5kV Disconnect† 5.5kV Non-disconnect 8.3kV Disconnect† 8.3kV Non-disconnect 15.5kV Disconnect† 15.5kV Non-disconnect 25.5kV Disconnect† 25.5kV Non-disconnect † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
PT medium voltage fuses for potential and small power transformers Eaton.com/bussmannseries D D E E A C B G F D D E E A B C G F Disconnect mountings† Non-disconnect mountings † Disconnect mountings provide a means for fuse extraction only. Do not use a disconnect mounting for load switching or fuse removal while energized.
PT medium voltage fuses for potential and small power transformers Technical Data 6002 Effective March 2016 The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications. Eaton and Bussmann are valuable trademarks of Eaton in the US and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton. Eaton
1000 Eaton Boulevard
Cleveland, OH 44122 United States Eaton.com Bussmann Division 1 14 Old State Road Ellisville, MO 63021 United States Eaton.com/bussmannseries © 2016 Eaton All Rights Reserved Printed in USA Publication No. 6002 – BU-SB15149 March 2016 For Eaton’s Bussmann series product information, call 1-855-287-7626 or visit: Eaton.com/bussmannseries Follow us on social media to get the latest product and support information.