84134000 SENSATA | Alldatasheet

Document overview

  • Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
  • PDF pages: 7

Technical content

Features

  • Current ratings from 10 to 125 Amps
  • Output voltage 24-280 VAC and 48-660 VAC
  • Available with or without IP20 touch-safe cover
  • LED Input Status Indicator
  • UL, CSA and TUV Approved, CE Compliant to EN60950-1
  • Improved SEMS screw and washer
  • Redesigned housing with anti-rotation barriers
  • EMC Compliant to level 3 Control Voltage 10 A 25 A 50 A 75 A 100 A 125 A 3-32 VDC 84134000 84134010 84134020 84134030 84134040 84134080 18-36 VAC 84134002 84134012 84134022 84134032 84134042 84134082 90-280 VAC 84134001 84134011 84134021 84134031 84134041 84134081 Output (1) Description 280 VAC 660 VAC Operating Voltage (47-440 Hz) [Vrms] 24-280 48-600 Transient Voltage [Vpk] (2) 600 1200 Maximum Off-State Leakage Current @ Rated Voltage [mArms] 0.1 0.25 Minimum Off-State dv/dt @ Maximum Rated Voltage [V/μsec] 500 500

www.sensata.comCopyright © 2024 Sensata Technologies, Inc. Input (1) Description 8413xxx0 8413xxx2 8413xxx1 Control Voltage Range 3-32 VDC (4) 18-36 VAC 90-280 VAC (5) Maximum Reverse Voltage -32 VDC - - Minimum Turn-On Voltage 3 VDC (4) 18 VAC 90 VAC Must Turn-Off Voltage 1 VDC 4 VAC 10 VAC Minimum Input Current (for on-state) [mA] 10 13 6 Maximum Input Current [mA] 15 15 10 Nominal Input Impedance [Ohm] Current Regulated Maximum Turn-On Time [µsec] 1/2 Cycle (6) 20 20 Maximum Turn-Off Time [µsec] 1/2 Cycle 30 30 General (1) Description Parameters Dielectric Strength, Input/Output/Base (50/60 Hz) 4000 Vrms Minimum Insulation Resistance (@ 500 VDC) 109 Ohms Maximum Capacitance, Input/Output 8 pF Ambient Operating Temperature Range (7) -40 to 80 °C Ambient Storage Temperature Range -40 to 125 °C Weight (typical) 2.53 oz (72 g) Housing Material UL94 V-0 Baseplate Material Aluminum Input Terminal Screw Torque Range (lb-in/Nm) 13-15 /1.5-1.7 Load Terminal Screw Torque Range (lb-in/Nm) 18-20 / 2-2.2 SSR Mounting Screw Torque Range (lb-in/Nm) 18-20 / 2-2.2 Humidity per IEC60068-2-78 93% non-condensing LED Input Status Indicator Green MTBF (Mean Time Between Failures) at 40°C ambient temperature (8) 11,641,553 hours (1,328 years) MTBF (Mean Time Between Failures) at 60°C ambient temperature (8) 7,210,376 hours (823 years) Output (1) Description 10 A 25 A 50 A 75 A 100 A 125 A Maximum Load Current [Arms] (3) 10 25 50 75 100 125 Minimum Load Current [mArms] 50 50 100 100 100 100 Maximum 1 Cycle Surge Current (50/60 Hz) [Apk] 150/175 275/300 710/750 1050/1100 1120/1200 1600/1700 1 Second surge current (Apk. Ta=25°C) 50/60 Hz 50 85 150 225 300 375 Maximum 1/2 Cycle I² t for Fusing (50/60Hz) [A² sec] 110/120 380/370 2520/2320 5500/5000 6270/6000 12800/12050 Minimum Heat Sink for Rated Current @ 40°C [°C/W] 5 2 1 0.7 0.5 0.5

www.sensata.comCopyright © 2024 Sensata Technologies, Inc. MECHANICAL SPECIFICATIONS (1) Tolerance: ±0.02 in / 0.5 mm All dimensions are in: inches [millimeters] EQUIVALENT CIRCUIT BLOCK DIAGRAMS

www.sensata.comCopyright © 2024 Sensata Technologies, Inc. SURGE CURRENT INFORMATION WIRING DIAGRAM --- Single Pulse (10)

www.sensata.comCopyright © 2024 Sensata Technologies, Inc. ACCESSORIES THERMAL DERATE INFORMATION

www.sensata.comCopyright © 2024 Sensata Technologies, Inc. ORDERING OPTIONS Example : 84134010H Series 8413 Touch Safe Cover 4 : Not included (IP00) 7 : Included (IP20) Operating Voltage 0 : 24-280 VAC/Zero Voltage Turn-On 1 : 48-660 VAC/Zero Voltage Turn-On 2 : 24-280 VAC/Instantaneous Turn-On 3 : 48-660 VAC/Instantaneous Turn-On Rated Load Current 0 : 10 Amps 1 : 25 Amps 2 : 50 Amps 3 : 75 Amps 4 : 100 Amps 8 : 125 Amps Control Voltage 0 : 3-32 VDC 1 : 90-280 VAC 2 : 18-36 VAC Thermal Pad Blank : Not Included H : Included 8413 4 0 1 0 H Not all part number combinations are available. Contact Technical Support for information on the availability of a specific part number. GENERAL NOTES (1) All parameters at 25°C unless otherwise specified. (2) Output will self trigger between 450-600 Vpk / 900-1200 Vpk for 280 VAC/660 VAC models not suitable for capacitive loads. (3) Heat sinking required, see derating curves. (4) 14-32 VDC for 48-660 VAC models. (5) For ambient temperatures above 40°C the maximum control voltage must not exceed 250 VAC. (6) Turn-on time for Instantaneous turn-on versions is 0.1 msec. (7) AC models operating range is -20 to 80°C. (8) All parameters at 50% power rating and 100% duty cycle (contact Crydom tech support for detailed report). (9) Load can be wired to either SSR output terminal 1 or 2. (10) For single surge pulse Tc=25°C; Tj=125°C. For AC Output SSRs, AC Rms value of surge current equals the peak value divided by √2 (1.414). For additional information or specific questions, contact Technical Support. Required for valid part number For options only and not required for valid part number

+1 (877) 502 5500 sales.crydom@sensata.com Europe, Middle East & Africa +44 (1202) 416170 ssr-info.eu@sensata.com Asia Pacific sales.isasia@list.sensata.com China +86 (21) 2306 1500 Japan +81 (45) 277 7117 Korea +82 (31) 601 2004 India +91 (80) 67920890 Rest of Asia +886 (2) 27602006 ext 2808 www.sensata.com CONTACT USCopyright © 2024 Sensata Technologies, Inc. Datasheets provided by Sensata Technologies, Inc., its subsidiaries and/or affiliates (“Sensata”) are solely intended to assist third parties (“Buyers”) who are developing systems that incorporate Sensata products (also referred to herein as “components”). Buyer understands and agrees that Buyer remains responsible for using its independent analysis, valuation, and judgment in designing Buyer’s systems and products. Sensata datasheets have been created using standard laboratory conditions and engineering practices. Sensata has not conducted any testing other than that specifically described in the published documentation for a particular datasheet. Sensata may make corrections, enhancements, improvements, and other changes to its datasheets or components without notice. Buyers are authorized to use Sensata datasheets with the Sensata component(s) identified in each particular datasheet. HOWEVER, NO OTHER LICENSE, EXPRESS OR IMPLIED, BY ESTOPPEL OR OTHERWISE TO ANY OTHER SENSATA INTELLECTUAL PROPERTY RIGHT, AND NO LICENSE TO ANY THIRD PARTY TECHNOLOGY OR INTELLECTUAL PROPERTY RIGHT, IS GRANTED HEREIN. SENSATA DATASHEETS ARE PROVIDED “AS IS”. SENSATA MAKES NO WARRANTIES OR REPRESENTATIONS WITH REGARD TO THE DATASHEETS OR USE OF THE DATASHEETS, EXPRESS, IMPLIED, OR STATUTORY , INCLUDING ACCURACY OR COMPLETENESS. SENSATA DISCLAIMS ANY WARRANTY OF TITLE AND ANY IMPLIED WARRANTIES OF MERCHANTABILITY , FITNESS FOR A PARTICULAR PURPOSE, QUIET ENJOYMENT, QUIET POSSESSION, AND NON-INFRINGEMENT OF ANY THIRD PARTY INTELLECTUAL PROPERTY RIGHTS WITH REGARD TO SENSATA DATASHEETS OR USE THEREOF. All products are sold subject to Sensata’s terms and conditions of sale supplied at www.sensata.com. SENSATA ASSUMES NO LIABILITY FOR APPLICATIONS ASSISTANCE OR THE DESIGN OF BUYERS’ PRODUCTS. BUYER ACKNOWLEDGES AND AGREES THAT IT IS SOLELY RESPONSIBLE FOR COMPLIANCE WITH ALL LEGAL, REGULATORY , AND SAFETY-RELATED REQUIREMENTS CONCERNING ITS PRODUCTS, AND ANY USE OF SENSATA COMPONENTS IN ITS APPLICATIONS, NOTWITHSTANDING ANY APPLICATIONS-RELATED INFORMATION OR SUPPORT THAT MAY BE PROVIDED BY SENSATA. Mailing Address: Sensata Technologies, Inc., 529 Pleasant Street, Attleboro, MA 02703, USA Rev:07/09/24 ECN 20395 FDE-07-01 Rev. B WARNINGS RISK OF MATERIAL DAMAGE AND HOT ENCLOSURE

  • The product’s side panels may be hot, allow the product to cool before touching
  • Follow proper mounting instructions including torque values
  • Do not allow liquids or foreign objects to enter this product Failure to follow these instructions can result in serious injury, or equipment damage. HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power before installing or working with this equipment
  • Verify all connections and replace all covers before turning on power Failure to follow these instructions will result in death or serious injury. AGENCY APPROVALS & CERTIFICATIONS Certified according to EN 62314:2006 IEC 61000-4-2 Electrostatic Discharge Level 3 IEC 61000-4-4 Electrically Fast Transients Level 3