Input Power 12 to 35 Vdc/12 to 28 Vac, 200 mA Communication Modbus RTU, BACnet MSTP Output Scaled pulse, open drain Flow Calculation Accuracy ±2% of flow rate within range; 0.5% repeatability Temperature Sensors Meets IEC751 Class B Flow Range 1 to 15 FPS Pressure Up to 400 psi MATERIALS Housing Polycarbonate Flow Sensor PEEK Potting Material Polyurethane Tee Material Bronze ENVIRONMENTAL Fluid Temperature -20 to 126 °C (-4 to 260 °F) Ambient Temperature -20 to 65 °C (-4 to 149 °F) WARRANTY Limited Warranty 1 year Series 380 BTU system provides a low-cost system for metering hot and cold systems. The 380 measures flow and temperature differential to accurately calculate energy. With BACnet, Modbus RS-485, or scaled pulse output, it can interface with many existing control systems. The rugged design incorporates an impeller flow sensor and two temperature probes, one mounted in the flow sensor tee and the other on either the supply or return line, depending on the application. Commissioning can be done in the field via a computer connection or set up at the factory. Setup includes energy measurement units, measurement method, communication protocol, pulse output control, fluid density, and specific heat parameters (requires re-usable programming cable and software, see Ordering Information). SPECIFICATIONS BACnet & Modbus BACnet and Modbus protocols are standard features…easy integration with existing control systems Integrated flow & temperature Integration of flow and temperature sensors with metering components...single solution for BTU metering Easy installation Minimal connections…simplify installation, saving time and cost Two temperature probes Rugged, compact design with two temperature probes Stainless steel impeller 316 stainless steel impeller with tungsten carbide shaft Sensor PEEK sensor tip

  • Energy management
  • Data systems

APPLICATIONS

Flow Monitoring | Tee Meter, BTU System

380 SERIES

Measures Temperature and Flow Rate and Calculates Energy HQ0001783.K 0221

B Overall Height A Overall Length C Tee Length D Hex RTD Fitting 1/8” NPT Length 6.6’ (2m) Ø 0.2 “ (6 mm) Ø 8” 360˚ pivot area case from center of tee PG-7 PG-9 E Width VERIS PART # MANUF. PART # DESCRIPTION MAX. GAL/MIN (GPM) BGR-8380207000-1202* 8380207000-1202 BTU system, hot and cold service, ¾" tee NPT, with pulse, Modbus and BACNet outputs 25 BGR-8380210000-1202* 8380210000-1202 BTU system, hot and cold service, 1” tee NPT, with pulse, Modbus and BACNet outputs 40 BGR-8380212000-1202* 8380212000-1202 BTU system, hot and cold service, 1-¼” tee NPT, with pulse, Modbus and BACNet outputs 70 BGR-8380215000-1202* 8380215000-1202 BTU system, hot and cold service, 1-½” tee NPT, with pulse, Modbus and BACNet outputs 95 BGR-8380220000-1202* 8380220000-1202 BTU system, hot and cold service, 2” tee NPT, with pulse, Modbus and BACNet outputs 150 BGR-8A304-1M ** 8A304-1M Programming Cable with CD for 380 Series n/a TEE/NPT SIZE A B C D E * Requires programming accessory. ** Required to program 380 Series BTU meters (reusable). Standard USB type A to mini-B cable included. Software available from manufacturer’s website, www.badgermeter.com DIMENSIONAL DRAWING

ORDERING INFORMATION

Flow Monitoring | 380 Series HQ0001783.K 0221