Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-... Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com06.09.04 1

Description

Single, two, three and four pole magnetic and hydraulic-magnetic circuit breakers with trip-free-mechanism and toggle or rocker actuation. A choice of fast m agnetic only or hydraulically delayed switching characteristics (S ty pe MO or HM CBE to EN 60934) ensures suitability for a wide range of applications. Industry standard dimensions and panel mounting. Low temperature sensitivity at rated load. Approved to CBE standard EN 60934 (IEC 60934). Communications systems, process control and transportation. 8350 Voltage rating 3 AC 415 V; AC 240 V 50/60 Hz DC 80 V Current rating range 0.1...70 A multi pole 0.1...100 A single and double pole Auxiliary circuit 6 A, AC 240 V / DC 28 V

1 A, DC 65 V

0.5 A, DC 80 V

Typical life 10,000 operations at I N Insulation co-ordination rated impulse pollution (IEC 60664 and 60664A) withstand voltage degree 2.5 kV 2 reinforced insulation in operating area Dielectric strength AC 3750 V Insulation resistance > 100 M Ω (DC 500 V) Degree of protection operating area IP40 (IEC 60529/DIN 40050) terminal area IP00 Vibration 10 g (55-500 Hz) ± 0,76 mm (10-55Hz) to IEC 60068-2-6, test C 10 frequency cycles/axis per Method 204C, test Condition A. Instantaneous curves tested at 90 % of rated current. Shock 100 g (6 ms) to IEC 60068-2-27, test Ea per Method 213, Cond. I. Instantaneous curves tested at 90 % of rated current. Corrosion 96 hours at 5% salt mist, to IEC 600-9-2-11, test Ka Method 101, Condition A Humidity 24 hours at 55% RH, to IEC 60068-2-78, test Cab Method 106D Mass approx. 65...100 g per pole (depending on version) Current rating (A) Internal resistance ( Ω) per pole 11 . 1 5 0.034 10 < 0.02 15 < 0.02 20 < 0.02 25 < 0.02 30 < 0.02 40 < 0.02 50 < 0.02 60 < 0.02 80 < 0.02 100 < 0.02 Standard current ratings and typical internal resistance values

Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com 06.09.042 Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-...

Ordering information

Type No. 8350 circuit breaker Mounting A flange rectangular aperture (M3 or 6-32) G flange mounting flush, rocker (without rockerguard), max. 3 poles N flange mounting flush, rocker (with rockerguard), max. 3 poles Configuration A metric M3, no interphase barriers B metric M3, with interphase barriers C imperial 6-32, no interphase barriers D imperial 6-32, with interphase barriers Number of poles 1 1pole (handle/rocker) 2 2poles (handle/rocker) 3 3poles (handle/rocker) up to 70 A 4 4poles (handle) up to 70 A Colour of front face B black standard Terminal design A stud terminal M5, max. 50 A A stud terminal 10-32, max. 50 A M stud terminal M6, max. 100 A M stud terminal 1/4-20, max. 100 A V clip terminals 1/4, max. 50 A W push-in-stud 2 screw 10-32 with washer and saddle clamp, max. 50 A 7 0.25 Inch double quick connect, max. 25 A 8 clip terminals 7/16”, max. 50 A Actuator configuration A 1 handle standard, one per pole B reduced number of handles standard E dual color rocker, Indicate ON (legend vertical) G dual color rocker, Indicate OFF (legend vertical) J dual color rocker, push-to-reset, Indicate OFF (legend vertical) T single color rocker, (legend vertical) V single color rocker, push-to-reset (legend vertical)

1 Mid-trip, handle standard, one per pole

2 Mid-trip, handle standard and Alarm Switch,

AD long delay, AC/DC BD medium, AC/DC CD short, AC/DC OP instantaneous Actuator colour and marking details A green I-0 ON-OFF K white I-0 ON-OFF L black I-0 ON-OFF V blue I-0 ON-OFF W gray I-0 ON-OFF X yellow I-0 ON-OFF Y red I-0 ON-OFF Z orange I-0 ON-OFF Illumination voltage range 0 without illumination Auxiliary contacts Auxiliary switch available on Series Trip and Switch only circuits. On multiple units, only one auxiliary switch is normally supplied mounted in extreme right pole. A without auxiliary contacts Internal circuit B series trip, current Remote trip 0 without remote trip 8350 - A A 3 B - A A BS - 3 0 A B 0 . - ... 8350 - A A 3 B - A A BS - 3 0 A B 0 A - ... Frequency A AC 50/60 Hz D DC M AC + DC Current rating 0.1...100 A Approvals A without E UL1077, CSA, TÜV 8350 - A A 3 B - A A BS - 3 0 A B 0 A - 1A - .... ordering example

Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-... Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com06.09.04 3 Internal connection diagrams I > B - Series trip with auxiliary contact C NC NOline 1 load Actuator configuration 4-pole 3-pole OFF O OFF O 1-pole 36.53 1.438 19.18 max .755 max 52.37 2.062 6-32 (M3) threaded x 4.95 / .195 deep (2 plc’s / pole) typical optional “ON-OFF , I-O” legend 2-pole 19.05 .750 OFF O OFF O 38.48 max 1.515 max multi-pole units are assembled at factory with common handle tie. 38.48 max 1.515 max OFF O 19.05 .750 57.53 max 2.265 max 19.05 .750 76.58 max 3.015 max OFF O OFF O OFF O 57.53 max 2.265 max OFF O OFF O OFF O OFF O OFF O OFF O 76.58 max 3.015 max Configuration A Configuration B This is a metric design and millimeter dimensions take precedence ( mm )inch Lists UL Recognized, CSA and TÜV Certified configurations and performance capabilities as a Component Supplementary Protector voltage current rating interrupting capacity (A) Circ. max frequency phase full load general Conf. rating (A) purpose UL TÜV (A) CSA 65 DC – – 71.0-100 5000 – 80 DC – 0.02-70.0 – 7500 – 80 DC – 0.10-70.0 – 7500 – 125/250 50/60 Hz 1Ø 0.02-100 – 5000 – 125/250 50/60 Hz 1Ø 0.02-50 – 3000 – 250 50/60 Hz 1+3Ø 0.10-30.0 – 5000 3000 Series 250 50/60 Hz 1+3Ø 31.0-50.0 – 5000 2000 250 50/60 Hz 1+3Ø 51.0-70.0 – 5000 1000 250 50/60 Hz 1+3Ø 0.02-70.0 – 5000 – 277 50/60 Hz 1Ø 0.02-50.0 – 5000 – 400Y(5) 50/60 Hz 3Ø 0.10-50.0 – – 2000 415Y(5) 50/60 Hz 3Ø 0.10-30.0 – – 2000 480Y(4) 50/60 Hz 1+3Ø 0.02-30.0 31.0-50.0 5000 – 80 DC – 0.02-50.0 – 7500 – 80 DC – 0.10-50.0 – 7500 2500 250 50/60 Hz 1+3Ø 0.10-30.0 – 5000 3000 250 50/60 Hz 1+3Ø 31.0-50.0 – 5000 2000 Shunt 250 50/60 Hz 3Ø 0.02-50.0 – 5000 – 277 50/60 Hz 1Ø 0.02-50.0 – 5000 – 400Y(5) 50/60 Hz 3Ø 0.10-50.0 – – 2000 415Y(5) 50/60 Hz 3Ø 0.10-30.0 – – 2000 480Y(4) 50/60 Hz 1+3Ø 0.02-30.0 31.0-50.0 5000 – Lists UL Recognized configurations and performance capabilities as a manual across the line starter Circuit voltage current Horsepower Configuration max frequency phase rating ratings rating (A) max. Series 277 (1) 50/60 Hz 1Ø 0.02-20.0 3 HP Shunt Switch 480Y (2) 3 Ø 0.02-20.0 5 HP Series 250 (1) 50/60 Hz 1Ø 0.02-20.0 3 HP Shunt Switch 3 Ø 0.02-20.0 5 HP Series 120 (1) 50/60 Hz 1Ø 0.02-50.0 3 HP Shunt Switch 3 Ø 0.02-50.0 7 1/2 HP Lists UL Listed (489), CSA Certified (C22.2No.5.1-M) configurations and performance capabilities as a Molded Case Circuit Breaker Circuit voltage current Interrupt Configuration max frequency phase rating Capacity rating (A) (A) 80 DC – 0.10-100 10,000 125 DC – 0.10-50.0 5,000 Series 120 50/60 Hz 1Ø 0.10-70.0 10,000 240 50/60 Hz 1Ø 0.10-20.0 5,000 120/240 50/60 Hz 1Ø 0.10-50.0 5,000 Lists UL Recognized, CSA Certified configurations and performance capabilities as Protectors, Supplementary for Marine Electrical and Fuel Systems. Ignition Protection per UL Standard 1500. UL Classified Small Craft Electrical Devices, Marine in accordance with ISO 8846 as Marine Supplementary Protectors Circuit voltage current rating Interrupt Configu- max frequency phase full load General Capacity ration rating (A) purpose (A) (A) 65 DC – – 71.0-100 1500 (1) Series 80 DC – 0.02-70.0 – 1500 (1) 125/250 50/60 Hz 1Ø 0.02-100 – 1500 (1) 250 50/60 Hz 1Ø 0.02-70.0 – 1500 (1) Interrupting capacity

57.91 2-pole 52.37 36.7810.97 ø3.96 .156 dia 2.062 1.448.432 OFF O OFF O 36.53 1.438 19.18 max .755 max 52.37 2.062 6-32 (M3) threaded x 4.95 / .195 deep (2 plc’s / pole) typical optional “ON-OFF , I-O” legend 63.5 49.28 2.50 1.94 typical terminal barrier 10.31 .406 3.81 typ. 1.85 .150 typ. 62.87 2.475 30° 60° 13.72 .540 3.42 .135 (short handle) ±0.51 ±0.02 typ. typ. ±1.52 ±0.06 typ. typ. OFF O typical terminal barrier 10-32 threaded stud terminals in series trip circuit configuration shown Panel cut-out (2 plc’s / pole) 19.05 .750 19.30 .760 38.61 1.52 2.28 77.22 3.040 typ. typ. typ. typ. Mounting -A Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com 06.09.044 Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-... Terminal design / Dimensions Description Code Terminal Dimensional detail 15.88 .625 4.19 .165 10-32 STUD A STUD A 1/4-20 STUD M STUD M 10-32 SCREW SCREW .250 DOUBLE Q.C. 1/4” CLIP TERMINALS V 7/16” CLIP TERMINALS PUSH-IN STUD W Auxiliary / Alarm switch terminal detail .215 .630 5.46 17.15 .675 5.97 .235 .669 6.71 .265 3.81 .150 10.16 .40020.83 .821 6.35 .250 4.39 .173 8.13 .320 10.18 .566 .401 14.38 16.36 .901 .644 22.89 24.38 .960 14.17 .558 ø7.90 .311 dia. mating hole centre of push-in stud contact area 7.29 .287 2.80 .110ø1.29 .051 dia. TAB (Q.C.) .110 Dimensions This is a metric design and millimeter dimensions take precedence ( mm )inch 63.5 2.50 49.28 1.94 Panel cut-out screw type terminals in series trip circuit configuration shown 31.62 1.245 63.85 (screw type) 7.87 .310 2.514 1.85 28.58 1.125 63.5 2.50 3.048 .120 10.67 .420 54.86 2.16 31.62 1.245 63.85 (screw type) 10.97 .432 2.514 28.58 1.125 49.28 1.94 LINE LOAD LINE LOAD 6-32 (M3) threaded x 4.95 / .195 deep (2 plc’s / pole) Optional “rocker guard” shown in dashed lines 42.16 1.66 19.18 max .755 OFF O I ON OFF O ON I 5.28 .205 (2 plc’s / pole) 42.16 5.08 ø3.96 .156 dia 1.26 1.66 .20019.05 .750 +.006 +0.13 +.010 +0.25 Mounting -G, -N

Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-... Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com06.09.04 5 … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.25 Curve AS (long delay) for DCCurve AS (long delay) for AC 50/60 Hz … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.25 … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Curve CS (short delay) for DCTrip time in seconds Curve CS (short delay) for AC 50/60 Hz … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Curve OP (instantaneous) for AC 50/60 HzTrip time in seconds Other characteristic curves to special order (e. g. with impulse delay for inrush peaks). N.B. All curves will only be maintained if the escutcheon is mounted on a vertical surface. Trip time in seconds … times rated current 10000 1000 12 4 6 8 1 2 100 0.1 0.01 0.001 30 5 7 9 10 11 Curve OP (instantaneous) for DC 1.5 1.5 1.5 1.25… times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.25 … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.25 Curve BS (medium delay) for DCCurve BS (medium delay) for AC 50/60 Hz … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.25 Typical time/current characteristics

Germany (0 91 87) 10-0 - USA (847) 827-7600 - UK (01296) 420336 - www.e-t-a.com 06.09.046 Magnetic and Hydraulic-Magnetic Circuit Breaker 8350-... Curve AD (long delay) for AC 50/60 Hz, DC … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 Curve CD (short delay) for AC 50/60 Hz, DC Other characteristic curves to special order (e. g. with impulse delay for inrush peaks). N.B. All curves will only be maintained if the escutcheon is mounted on a vertical surface. … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.35 Curve BD (medium delay) for AC 50/60 Hz, DC … times rated current 0.1 0.01 0.001 10000 1000 12 4 6 8 1 2 100 30 5 7 9 10 11 Trip time in seconds 1.5 1.35 1.35 Typical time/current characteristics Interphase barriers / Dimensions 99.06 78.23 thickness 1 mm/.039 in. 3.90 3.08 69.85 2.75 72.39 2.85 typ. typ. typ. typ. Typical terminal barrier Special terminal barrier This is a metric design and millimeter dimensions take precedence ( mm )inch Accessories 19.6 37.3 2.8 16.7 19.2 52.4 Toggle guard for 8350-A... Y 307 381 01 2.52 1.47 .772 .657 .110 .157 .756 2.06 Splash cover (IP65) for 1, 2, 3 pole (only for configuration C/D) X 222 444 01 1 pole X 222 444 11 2 pole X 222 444 21 3 pole ONONON ONONON ONONON 67.5 56.5 52.4 22.25 2.66 2.05 1.38 2.22 .354 .876 2.91 Shock directions All dimensions without tolerances are for reference only. In the interest of improved design, performance and cost effectiveness the right to make changes in these specifications without notice is reserved.Product markings may not be exactly as the ordering codes. Errors and omissions excepted.