Edition • 2023-07-21T16:31:28+02:00 Isolating switching amplifier 1-channel IM12-DI03-1S-2T-S/24VDC/CC Sensors according to EN 60947-5-6 (NAMUR) or potential-free contacts can be connected to the IM12-DI03-1S-2T-S/24VDC/CC isolat- ing switching amplifier. The device can be in- stalled in zone 2. The device can be switched between 1-channel operation with signal dou- bling or 1-channel operation with alarm mes- sage output using DIP switches. The output circuits are equipped with two potential-free transistors. The device complies with the re- quirements of NE21. The devices feature DIP switches on the front. This allows to select between the output mode, the input circuit monitoring, as well as toggle between signal duplication and 1-chan- nel operation. When using mechanical con- tacts, either line monitoring must be switched off or the contact must be wired with resistors (see wiring diagram). The green LED indicates operational readi- ness. An error in the input circuit causes the red LED to flash according to NE44. Then, the transistor of the corresponding output circuit locks. The device can be used in safety circuits up to SIL2 (high and low demand according to IEC 61508). The device is equipped with removable spring type terminals. ■ Transistor output (ð 10 kHz) ■ Switchable between: Alarm output or sig- nal doubling ■ Output mode adjustable (open-cir- cuit/closed current mode) ■ Input circuits monitored for wire break/ short circuit (ON/OFF switchable) ■ Complete galvanic isolation ■ Input reverse-polarity protected ■ Removable spring type terminals ■ ATEX use in Zone 2, cUL ■ SIL 2

Edition • 2023-07-21T16:31:28+02:00 Type IM12-DI03-1S-2T-S/24VDC/CC ID 7580034 Operating voltage 10…30 VDC Power dissipation, typical ð 1.03 W NAMUR input NAMUR EN 60947-5-6 Input circuit monitoring on/off switchable No-load voltage 8.2 VDC Short-circuit current 8.2 mA Input resistance 1 kò Cable resistance ð 50 ò Switch-on threshold 1.75 mA Switch-off threshold 1.55 mA Wire breakage threshold ð 0.06 mA Short-circuit threshold ï 6.4 mA Output circuits Semicondutor output circuit(s) Output circuits (digital) 2 x transistor (potential-free, short-circuit proof) Switching voltage ð 30 VDC Switching current per output ð 0.1 A Switching frequency ð 10000 Hz Voltage drop ð 1.1 V at 20 mA, ð 1.8 V at 50 mA, ð 2.7 V at 100 mA Galvanic isolation Input 1 to output 1 375 V peak value acc. to EN 60079-11 Input 1 to supply 375 V peak value acc. to EN 60079-11 Output 2 to supply 100 V RMS acc. to EN 50178 and EN 61010-1 Important note For Ex-applications the values specified in the corre- sponding Ex certificates (ATEX, IECEx, UL, etc.) ap- ply. Important note If the device is used in applications to achieve func- tional safety according to IEC 61508, the safety manual must be used. Information in the data sheet are not valid for functional safety. Use in SIL safety circuits SIL 2 acc. to IEC 61508 Dimensions

Edition • 2023-07-21T16:31:28+02:00 Mechanical data Protection class IP20 Flammability class acc. to UL 94 V-0 Dimensions 120 x 12.5 x 128 mm Weight 1 g Mounting instructions DIN rail (NS35) Housing material Polycarbonate/ABS Electrical connection Removable spring-type terminals, 2-pin Terminal cross-section 0.2…2.5 mm² (AWG: 24…14) Environmental conditions Operating height Up to 2000 m above sea level Pollution degree II Surge/Overvoltage cate- gory II (EN 61010-1) Standards used Voltage resistance and insulation EN 50178 EN 61010-1 EN 50155 GL VI-7-2 Shock EN 61373 class B EN 50155 GL VI-7-2 EN 60068-2-6 EN 60068-2-27 Temperature EN 60068-2-1 Ad EN 50155 GL VI-7-2 EN 60068-2-2 Bd EN 60068-2-1 Air humidity EN 60068-2-38 EMC EN 50155 GL VI-7-2 NE21 EN 61326-1 EN 61326-3-1 EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-11 EN 61000-4-29 EN 55011 EN 55016 EN 50121-3-2 EN 61000-6-2

Edition • 2023-07-21T16:31:28+02:00 Accessories Type code Ident-No. Dimension drawing WM1 WIDER- STANDSMODUL

0912101 The resistor module WM1 meets the requirements for line

monitoring between a mechanical contact and a TURCK signal processor. The input circuit of the signal processor is designed for sensors acc. to EN60947-5-6 (NAMUR) and equipped with a wire-break and short-circuit monitoring func- tion. IMX12-SC-2X-4BK 7580940 Screw terminals for IM(X)12 modules; included in delivery: 4 pcs. of 2-pin black terminals IMX12-CC-2X-4BK 7580942 Spring terminals for IM(X)12 modules; included in delivery: 4 pcs. black terminals, 2-pin