Edition • 2023-07-21T16:29:57+02:00 Cabinet Guard Internal and External Sensors IM12-CCM03-MTIS-3T-IOLC/24V/CC The cabinet guard IM12-CCM03-MTIS-3T- IOLC/24V/CC monitors preset environmental limits inside the control cabinet. The environ- mental conditions are detected by an integrat- ed humidity or temperature sensor, a bright- ness sensor and a triangulation sensor that detects an incorrectly closed cabinet door. When exceeding or falling below the set limit values, an error message appears on the LED display or is reported via the switching outputs and the IO link interface to the host control system. The device is supplied with 24 VDC The teaching is done manually on the device; extended parameterization is carried out via the IO-Link interface. The device is equipped with 8 cage clamp ter- minals for connecting the power supply and switching outputs and can be mounted on a DIN rail acc. to EN 60715. Furthermore, the device has 4 front-mounted LEDs to display the operating status (green), the error message (red) and the states of the switching outputs (2 × yellow). The device is equipped with removable spring-type terminals. ■ Two potential-free contacts ■ Temperature detection ■ Moisture detection ■ Detection of distance to cabinet door ■ IO-Link parameterizable ■ Connection of two devices via CAN bus ■ Galvanic isolation of outputs (A1/A2) ■ Removable cage clamp terminals

Edition • 2023-07-21T16:29:57+02:00 Type IM12-CCM03-MTIS-3T-IOLC/24V/CC ID 7570101 Nominal voltage 24 VDC Operating voltage 10…30 VDC Power consumption ð 0.5 W Installed sensors CCM Triangulation sensor 40…500 mm Humidity sensor 10…90 % rel. hum. Temperature sensor -25 °C…+70 °C Dry contact Reference temperature 23 °C Output circuits Semicondutor output circuit(s) Output circuits (digital) 2 x transistor (potential-free) NO/NC Switching voltage ð 30 VDC Switching current per output ð 0.1 A Voltage drop ð 1 V Moisture Sensor Accuracy max. ± 4.5 % relative humidity in the range 10…90 % Repeat accuracy 0.2 % RF Temperature Sensor Max. accuracy ±2 °C Repeat accuracy 0.16 °C Distance Sensor Beam angle 6 ° Measuring range 40…500 mm Relative accuracy ±50 mm In the range of ð 500 mm Temperature coefficient +/- 30 mm in the range of ð 500 mm at -25°C ð T ð 70°C +/- 15 mm in the range of ð 500 mm at 0 °C ð T ð 50 °C Max. linearity error ð 2 % of full scale Displays/Operating elements Operational readiness Green Switching state Yellow Error indication red Dimensions

Edition • 2023-07-21T16:29:57+02:00 Mechanical data Protection class IP20 Flammability class acc. to UL 94 V-0 Ambient temperature -25…+60 °C Storage temperature -25…+80 °C Dimensions 120 x 12.5 x 128 mm Weight 164 g Mounting instructions DIN rail (NS35) Housing material Polycarbonate/ABS Electrical connection Removable spring-type terminals, 2-pin Terminal cross-section 0.2…2.5 mm² (AWG: 24…14) Environmental conditions Operating height Up to 2000 m above sea level Pollution degree II Standards used Voltage resistance and insulation EN 50178 EN 61010-1 Shock EN 60068-2-6 EN 60068-2-27 Temperature EN 60068-2-1 Ad EN 60068-2-2 Bd EN 60068-2-1 Air humidity EN 60068-2-38 EMC EN 61000-4-2 EN 61000-4-3 EN 61000-4-4 EN 61000-4-5 EN 61000-4-6 EN 61000-4-8 Emission CISPR16

Edition • 2023-07-21T16:29:57+02:00 Accessories Type code Ident-No. Dimension drawing USB-2-IOL-0002 6825482 IO-Link Master with integrated USB port