Edition • 2023-07-21T16:27:56+02:00 Temperature measuring amplifier 1-channel IM34-14EX-CDRI The 1-channel Ex-area temperature measur- ing amplifier IM34-14Ex-CDRi is designed to evaluate the temperature-dependent changes of Ni100/Pt100 RTDs and thermocouples types B, E, J, K, L, N, R, S, T and to output them as temperature-linear current signals 0/4…20 mA. Furthermore, resistors, poten- tiometers or low voltages can be mapped lin- early as current signals in a range between -160…+160 mV. The device is equipped with an analog output of 0/4…20 mA; In addition, three relay outputs for limit values are available. The measured value can be viewed on a 2-line display. The measured value is permanently written to a ring buffer with space for 8000 values. The writing process is stopped with a prede- fined trigger event, like for example "limit val- ue exceeded". After that, the stored signal se- quence can be read out. The device can be parametrized and config- ured via PC (FDT / DTM). For this, connect the device to the PC via the 3.5 mm jack on the front (the matching transmission cable IM-PROG III can be ordered separately from TURCK). In addition, a basic scope of pa- rameters can be set via buttons and display on the front as well as via the HART capable power interface The signals are transformed according to ITS 90/IEC 584 for thermocouples and according to IEC 751 for Pt100 RTDs and provided tem- perature linear at the current output. Cold junction compensation of thermocouples is either realized via an externally connected Pt100/Ni100 resistor, via temperature mea- sured inside the amplifier or via an individually adjustable constant temperature value. ■ Parameterized via PC (FDT/DTM), front- panel switch or HART ■ Ring buffer for up to 8000 measured val- ues ■ Display ■ Input for Pt100/ Ni100 resistors, variable resistors, thermocouples and millivolt sig- nals ■ Complete galvanic isolation ■ Input reverse-polarity protected ■ ATEX, IECEx, CFMUS, TR CU, KOSHA ■ Installation in zone 2
Edition • 2023-07-21T16:27:56+02:00 Type IM34-14EX-CDRI ID 7506634 Operating voltage 20…250 VAC Frequency 40…70 Hz Operating voltage 20…125 VDC Power consumption ð 3 W Input circuits Intrinsically safe acc. to EN 60079 Thermocouple Ni100 Pt100 mV signals Pt100 (IEC 751), 2, 3 and 4-wire technology Ni100 (DIN 43760), 2, 3 and 4-wire technology Probe current ð 0.2 mA Thermocouples B, E, J, K, N, R, S, T (ITS 90/IEC 584), L (DIN 43710) Potentiometer input Nominal resistance 0…1.5 kò Voltage input -0.160…+0.160 VDC Output circuits Output current 0/4…20 mA Load resistance current output ð 0.6 kò Fault current 0 / 22 mA adjustable Output circuits (digital) 3 x relays (NO) Output switching voltage relay ð 30 VDC / ð 250 VAC Switching current per output ð 2 A Switching capacity per output ð 500 VA/60 W Switching frequency ð 10 Hz Output Adjustable output mode Response characteristic Rise time (10…90 %) ð 1000 ms Fall time (90…10 %) ð 1000 ms Reference temperature 23 °C Measuring accuracy current output (including linearity, hysteresis and repeatability) ± 5 µA Temperature drift analog output 0.0025 %/K Measuring accuracy RTD input (including linearity, hys- teresis and repeatability) ± 50 mò Temperature drift RTD input ± 3 mò/K Measuring accuracy TC input (including linearity, hys- teresis and repeatability) ± 15 µV Temperature drift TC input ± 3.2 µV/K (of 320 mV) Cold junction compensation error 2-wire < 100mò after line compensation 3-wire < 100mò with asymmetrical wiring 4-wire < 50mò with cold junction compensation < 2 K Galvanic isolation Test voltage 2.5 kV RMS Dimensions Output relay – Load curve Output relay – Electrical lifetime
Edition • 2023-07-21T16:27:56+02:00 Important note For Ex-applications the values specified in the corre- sponding Ex certificates (ATEX, IECEx, UL, etc.) ap- ply. Ex approval acc. to conformity certificate TÜV 05 ATEX 2877 Application area II (1) GD Ignition protection category [EEx ia] IIC Ex approval acc. to conformity certificate TÜV 05 ATEX 2889 X Application area II 3 G Ignition protection type EEx nA nC [nL] Characteristic linear Displays/Operating elements Operational readiness Green Switching state Yellow Error indication red Mechanical data Protection class IP20 Flammability class acc. to UL 94 V-0 Ambient temperature -25…+70 °C -25 ... +60 °C für FM Storage temperature -40…+80 °C Dimensions 104 x 27 x 110 mm Weight 248 g Mounting instructions DIN rail (NS35) or panel Housing material Polycarbonate/ABS Electrical connection 4 × 5-pin removable terminal blocks, reverse polarity protected, screw terminal Terminal cross-section 1 × 2.5 mm²/2 × 1.5 mm² Tightening torque 0.5 Nm
Edition • 2023-07-21T16:27:56+02:00 Accessories Type code Ident-No. Dimension drawing IM-CC-5X2BU/2BK 7504031 Cage clamp terminals for IM modules (Ex-devices with 27 mm overall width); includes: 2 pcs. 5-pin blue terminals and 2 pcs. 5-pin black terminals. IM-PROG III 7525111 USB-compatible programming adapter for the FDT/DTM- based parametrization of HART-capable Turck devices; gal- vanic separation between the device to be parametrized and the PC