6811470 TURCK | Alldatasheet
Document overview
- Manufacturer or author: Provided By alldatasheet.com(free datasheet download site)
- PDF pages: 6
Technical content
Edition • 2023-07-21T16:01:47+02:00 BL compact™ multiprotocol fieldbus station for Industrial Ether- net
8 Digital PNP Outputs
BLCEN-4M12MT-8DO-0.5A-P Type BLCEN-4M12MT-8DO-0.5A-P ID 6811470 Nominal system voltage 24 VDC System power supply Via auxiliary power Voltage supply connection 2 x M12, 5-pin Admissible range Vi 11…30 VDC Nominal current Vi 125 mA Max. current Vi 1 A Admissible range Vo 11…30 VDC Nominal current Vo 100 mA Max. current Vo 4 A Fieldbus transmission rate 10/100 Mbps Adjustment transmission rate Automatic detection Fieldbus address range 1…92 0 (192.168.1.254) 93 (BOOTP) 94 (DHCP) 95 (PGM) 96 (PGM-DHCP) *recommended for PROFINET 97…98 (manufacturer specific) Fieldbus addressing 2 decimally coded rotary switches Fieldbus connection technology 2 × M12 4-pole, D-coded Protocol detection automatic Web server Integrated Service interface Ethernet Vendor ID 48 Product type 12 Product code 11470 ■ On-machine Compact fieldbus I/O block ■ EtherNet/IP™, Modbus® TCP, or PROFINET slave ■ Integrated Ethernet Switch ■ 10 Mbps / 100 Mbps supported ■ Two 4-pole M12, D-coded, connectors for fieldbus connection ■ 2 rotary switches for node address ■ IP67, IP69K ■ M12 I/O connectors ■ LEDs indicating status and diagnostics ■ Electronics galvanically separated from the field level via optocouplers ■ 8 digital PNP outputs, 24 VDC ■ Max. 0.5A per output
Edition • 2023-07-21T16:01:47+02:00 Modbus TCP Addressing Static IP, BOOTP, DHCP Supported function codes FC1, FC2, FC3, FC4, FC5, FC6, FC15, FC16, FC23 Number of TCP connections 6 Input Data Size max. 2 register Input register start address 0 (0x0000 hex) Output Data Size max. 1 register Output register start address 2048 (0x0800 hex) Ethernet/IP Addressing acc. to EtherNet/IP specification Device Level Ring (DLR) supported Class 1 connections (CIP) 6 Input Assembly Instance 103 Input Data Size 2 INT Output Assembly Instance 104 Output Data Size 1 INT Configuration Assembly Instance 106 Configuration Size 0 Comm Format Data - INT PROFINET Addressing DCP Conformance class B (RT) MinCycleTime 1 ms Diagnostics acc. to PROFINET alarm handling Topology detection supported Automatic addressing supported Media Redundancy Protocol (MRP) supported Output Data Size max. 2 BYTE Digital outputs Output type PNP Type of output diagnostics Channel diagnostics Sensor supply (VSENS) 24 VDC Output current per channel 0.5 A Output voltage 24 VDC from supply voltage Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive > 48 ò Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes
Edition • 2023-07-21T16:01:47+02:00 Dimensions 113 x 71 x 32.5 mm Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque Weight 390 ± 20 g Housing material Glass-filled nylon, nickel plated brass connectors Housing color Black Material screw Nickel-plated brass Material label Polyester with polycarbonate overlay Ground label material Nickel plated brass Protection class IP67 IP69K Ambient temperature -40…+70 °C Storage temperature -40…+85 °C Relative humidity 15 to 95% (non-condensing) Vibration test Acc. to IEC 61131-2 - up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility Acc. to IEC 61131-2 MTTF 147 years MTTF note acc. to SN 29500 (Ed. 99) 20 °C Approvals and certificates CE, cULus
Edition • 2023-07-21T16:01:47+02:00 Pinning and wiring diagram Ethernet Fieldbus cable (IP67 example): RSSD RSSD 441-2M ID number U-02482 or RSSD-RSSD-441-2M/S2174 ID number 6914218 Pin Assignment (M12, D-code) Digital Outputs Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment Wiring Diagram Auxiliary Power Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no. U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment
Edition • 2023-07-21T16:01:47+02:00 Station LED status LED Color Status Description IOs OFF No power RED ON Low power or station error RED FLASHING (1 Hz) I/O module configuration error RED FLASHING (4 Hz) No I/O module bus communication GREEN ON Station ok GREEN FLASHING Force mode active BUS OFF Power Off GREEN ON Connected to Master GREEN FLASHING Ready GREEN FLASHING 3x (1Hz) ARGEE Running RED ON Error RED FLASHING WINK YELLOW ON DHCP/BOOTP Search OFF No Link GREEN ON Link GREEN FLASHING Traffic LNK/ACT YELLOW ON 100 Mbit Linked I/O LED status LED Color Status Description D * OFF No diagnostics active RED ON Station error/ module bus communication failure RED FLASHING (0.5Hz) Diagnostics active DO channel OFF Status of channel x = „0“ (OFF), no diagnostics active 0...7 GREEN ON Status of channel x = „1“ (ON) RED ON Short circuit / overload on channel x * D LED also indicates gateway diagnostics
Edition • 2023-07-21T16:01:47+02:00 Process Data Mapping of Each Protocol EtherNet/IP™ I/O & Diagnostics Data Mapping INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 Module number reporting diagnostic dataDiagnostics
1 Replace Sta-
- Diagnostics Active - - - - -
2 Over Current
Slot 1 (ref. Byte 3 - - - - - - - - OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DO 17 DO 16 DO 15 DO 14 DO 13 DO 12 DO 11 DO 10
Legend: CFG Configuration Error FCE Force Mode Active COM Communication Failure SC Short Circuit / Overcurrent DIA Diagnostics Active VI VI Voltage DO Digital Output VO VO Voltage Modbus® TCP Register Mapping REG Bit 15 Bit 14 Bit 13 Bit 12 Bit 11 Bit 10 Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Status (RO) 0x0000 - FCE - - CFG COM VI low - VO low - - - - - - DIA Outputs (RW) 0x0800 - - - - - - - - DO 17 DO 16 DO 15 DO 14 DO 13 DO 12 DO 11 DO 10 I/O Diag. (RO) 0xA000 - - - - - - - - SCDO SCDO SCDO SCDO SCDO SCDO SCDO SCDO PROFINET® Process Data BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0