Edition • 2023-07-21T15:59:40+02:00 BL compact™ fieldbus station for PROFIBUS-DP
8 Configurable Digital PNP Channels
Type BLCDP-4M12VMT-8XSG-PD ID 6811189 Nominal system voltage 24 VDC System power supply Via auxiliary power Voltage supply connection 2 x M12, 5-pin Admissible range Vi 18…30 VDC Nominal current Vi 200 mA Max. current Vi 1 A Admissible range Vo 18…30 VDC Nominal current Vo 100 mA Max. current Vo 4 A Electrical isolation The inputs and outputs of the 8XSG I/O cards are supplied via a common ground. Therefore, it is rec- ommend not to use this module for safety or emer- gency stop applications. Fieldbus transmission rate 9.6 kbps …12 Mbps Adjustment transmission rate Automatic detection Fieldbus address range 0...99 Fieldbus addressing 2 decimally coded rotary switches Fieldbus connection technology 2 × M12 5-pole, reverse keyed Fieldbus termination external Service interface RS232 interface Digital inputs from 8XSG Input type PNP Type of input diagnostics Channel diagnostics Sensor supply (VSENS) 24 VDC, 100 mA short-circuit limiting Low level signal voltage < 4.5 VDC High level signal voltage 7 ... 30 VDC Low level signal current < 1.5 mA Input delay 0.25 or 2.5 (configurable) ms ■ On-machine Compact fieldbus I/O block ■ PROFIBUS-DP slave ■ 9.6 kbps … 12 Mbps ■ Two 5-pole M12, reverse-keyed, connec- tors for fieldbus connection ■ 2 rotary switches for node address ■ IP67, IP69K ■ All exposed metal is stainless steel ■ LEDs indicating status and diagnostics ■ Electronics galvanically separated from the field level via optocouplers ■ 8 Configurable digital PNP channels, 24 VDC ■ Max. 0.5A per channel ■ Channel diagnostics ■ Selection of filtering times (Input delay) ■ Invertible inputs
Edition • 2023-07-21T15:59:40+02:00 Digital outputs from 8XSG Output type PNP Type of output diagnostics Channel diagnostics Sensor supply (VSENS) 24 VDC Output current per channel 0.5 A Output voltage 24 VDC from supply voltage Output delay 3 ms Load type resistive, inductive, lamp load Load resistance, resistive > 48 ò Load resistance, inductive < 1.2 H Lamp load < 3 W Switching frequency, resistive < 200 Hz Switching frequency, inductive < 2 Hz Switching frequency, lamp load < 20 Hz Short-circuit protection yes Dimensions 113 x 71 x 32.5 mm Mounting 2 × 5.4 mm diameter holes, 1.7 Nm torque Weight 390 ± 20 g Housing material Glass-filled nylon, 316L stainless steel connectors Housing color Black Material screw 303 stainless steel Material label Polyester with polycarbonate overlay Ground label material 304 Stainless Steel Protection class IP67 IP69K Ambient temperature -40…+70 °C Storage temperature -40…+85 °C Relative humidity 15 to 95% (non-condensing) Vibration test Acc. to IEC 61131-2 - up to 20 g (at 10 up to 150 Hz) For mounting on base plate or machinery Shock test according to IEC 61131-2 Electromagnetic compatibility Acc. to IEC 61131-2 Approvals and certificates CE, cULus
Edition • 2023-07-21T15:59:40+02:00 Pinning and wiring diagram PROFIBUS-DP Fieldbus cable (example): RSSW RKSW 455-2M ident-no. U0350 or RSSW-RKSW455-2M ident-no. 6602222 Pin Assignment (M12, B-Code) Digital Inputs and Outputs Extension cable (example): RK 4.4T-2-RS 4.4T ident-no. U2445 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment Auxiliary Power Extension cable (example): RKC 4.4T-2-RSC 4.4T ident-no. U5264 or RKC4.4T-2-RSC4.4T/TEL ident-no. 6625208 Pin Assignment
Edition • 2023-07-21T15:59:40+02:00 Station LED status LED Color Status Description IOs OFF No power RED ON Low power or station error RED FLASHING (1 Hz) I/O module configuration error RED FLASHING (4 Hz) No I/O module bus communication GREEN ON Station ok GREEN FLASHING Force mode active OFF No field bus communication GREEN ON Field bus communication active GREEN FLASHING (1 Hz) No field bus communication active, device status OK RED ON Bus error at the gateway; no data exchange BUS RED FLASHING Faulty PROFIBUS-DP address OFF No field bus communication GREEN ON Field bus communication active GREEN FLASHING (1 Hz) No field bus communication active, device status OK RED ON Bus error at the gateway; no data exchange BUS RED FLASHING Faulty PROFIBUS-DP address I/O LED status LED Color Status Description D * OFF No diagnostics active RED ON Station error/ module bus communication failure RED FLASHING (0.5Hz) Diagnostics active XSG channels 0...7 OFF Channel status x = “0“ (OFF), no diagnostics active GREEN ON Channel status x = “1“ (ON) RED ON Short-circuit at output RED FLASHING (2 Hz) Short-circuit sensor supply * D LED also indicates gateway diagnostics
Edition • 2023-07-21T15:59:40+02:00 I/O Data Map INPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DI 7 DI 6 DI 5 DI 4 DI 3 DI 2 DI 1 DI 0
C3P2 C2P2 C1P2 C0P2 C3P4 C2P4 C1P4 C0P4 1 - - - - - - - - OUTPUT BYTE Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0 DO 7 DO 6 DO 5 DO 4 DO 3 DO 2 DO 1 DO 0
C3P2 C2P2 C1P2 C0P2 C3P4 C2P4 C1P4 C0P4 1 - - - - - - - -