6440AXXSZS-AC90 SCHNEIDER | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 3
Technical content
Relay, SE Relays, solid state, SPST NO, 40A, 48…530 VAC, 90...280 VAC Uc, SCR AC zero cross, screw terminal Main Range Legacy Product Type Solid state relay Maximum output current 40 A AC Mounting Support Panel Network Number of Phases 1 phase Output Voltage 48...530 V AC Control Circuit Voltage 90...280 V AC Complementary Input Impedance 13000 Ohm Holding Current 250 mA Input Current Limits 11 mA at 120 V AC typical 20 mA at 240 V AC Switch Function SPST Contacts Type and Composition NO Protection Technology Current limiter Tightening Torque 10 lb.in for input 20 lb.in for output Connections Terminals Input screw clamp terminal, 1 Output screw clamp terminals, 1 Screw Type M3.5 Local Signalling for input status 1 LED (green) Switching Device SCR output Zero voltage switching Maximum Peak Voltage 800 V Surge Current 625 A 16.6 ms Must Release Voltage 10 V Voltage Drop <1.6 V on-state AC Power Factor with maximum load Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications Jul 27, 2021
Insulating Resistance 1 GΩ Thermal Resistance 0.9 °C/W Maximum I²t for fusing 1250 A².s 8.3 ms Leakage Current 10 mA at off-state DV/Dt 500 V/µs off-state at maximum rated voltage Response Time 8.33 ms (turn-on) 8.33 ms (turn-off) Dielectric Strength 4000 V between input and ground
4000 V between output and ground
4000 V between input and output
Height 1.39 in (35.3 mm) Width 1.85 in (47.1 mm) Depth 2.30 in (58.4 mm) Product Weight 3.05 oz (86.5 g) Environment Product Certifications UL CSA CE IP Degree of Protection IP20 Ambient Air Temperature for Operation Ambient Air Temperature for Storage -40…257 °F (-40…125 °C) Ordering and shipping details GTIN 03606480277504 Offer Sustainability California proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov REACh Regulation REACh Declaration EU RoHS Directive Pro-active compliance (Product out of EU RoHS legal scope) EU RoHS Declaration Mercury free Yes RoHS exemption information Yes China RoHS Regulation China RoHS declaration WEEE The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Connections and Wiring Diagrams