61F-GP-NX OMRON | Alldatasheet
Document overview
- Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
- PDF pages: 15
Technical content
Floatless Level Switch (Compact, Plug-in Type) 61F-GP-N@ Space-saving Design Ideal for Control Panel Downsizing. Easy Maintenance.
- Compact: 49.4 × 38 × 84 mm (H×W×D). Easy identification of operating status with LED operation indicator. Independent DPDT contacts on 11-Pin Models. CE marking and UL/CSA compliance. Refer to Safety Precautions for Floatless Level Controllers. ■Model Number Legend ■Ordering Information Note: When ordering, specify the desired operating voltage at the end of the model number. 1. No. of Pins 2. Type N: 11 pins N8: 8 pins Blank: General-purpose L 2KM: Long-distance (for 2 km) L 4KM: Long-distance (for 4 km) H: High-sensitivity D: Low-sensitivity R: Two-wire T: High-temperature Position of LED indicator 61F-GP-@@ Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km) Model Model Model 11-pin 61F-GP-N 61F-GP-NL 2KM 61F-GP-NL 4KM Type High-sensitivity Low-sensitivity Two-wire Model Model Model 11-pin 61F-GP-NH 61F-GP-ND 61F-GP-NR Type Tropical environments High-temperature Model Model 8-pin 61F-GP-N-TDL 61F-GP-NT Type General-purpose Long-distance (for 2 km) Long-distance (for 4 km) Model Model Model 8-pin 61F-GP-N8 61F-GP-N8L 2KM 61F-GP-N8L 4KM Type High-sensitivity Low-sensitivity Two-wire Model Model Model 8-pin 61F-GP-N8H 61F-GP-N8D 61F-GP-N8R 61F-GP-N8HY Example: 61F-GP-N [220 VAC] Desired supply voltage
61F-GP-N@ ■Compact Plug-in Models (11-pin Type) Specifications Note: 1. The length when using completely insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as the cable diameter or number of conductors becomes larger. For details, refer to Safety Precautions for Floatless Level Controllers. 2. The insulation resistance and dielectric strength indicate values between power terminals and Electrode terminals, between power terminals and contact terminals, and between Electrode terminals and contact terminals. For details, refer to Safety Precautions for Floatless Level Controllers. 3. Possible to use with 15 kΩ or less, however, this may cause reset failure. 4. 61F-GP-NH High-sensitivity Controller uses advanced operation. When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter- nal relay will not operate. When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal relay will operate. If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation. Item General-purpose Controller 61F-GP-N High- temperature Controller 61F-GP-NT Long-distance Controllers 61F-GP-NL 2KM (for 2 km) 61F-GP-NL 4KM (for 4 km) High-sensitivity Controller 61F-GP-NH (see note 4) Low-sensitivity Controller 61F-GP-ND Two-wire Controller 61F-GP-NR Controlling materials and operating condi- tions For control of ordi- nary purified water or sewage water For control of ordi- nary purified water or sewage where operating ambient temperature is high. For control of ordi- nary purified water in cases where the distance between sewage pumps and water tanks or between receiver tanks and supply tanks is long or where remote con- trol is required. For control of liq- uids with high spe- cific resistance such as distilled water For control of liq- uids with low spe- cific resistance such as salt water, sewage water, acid chemicals, al- kali chemicals For control of ordi- nary purified water or sewage water used in combina- tion with Two-wire Electrode Holder (incorporating a resistor of 6.8 kΩ) Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz Operating voltage range 85% to 110% of rated voltage Interelectrode voltage 8 VAC Interelectrode current Approx. 1 mA AC max. Approx. 0.12 mA AC max. Approx. 1 mA AC max. Power consumption Approx. 3.5 VA max. Interelectrode operate resistance 0 to approx. 4 kΩ 0 to approx. 4 kΩ 0 to approx. 1.3 kΩ (for 2 km) 0 to approx. 0.5 kΩ (for 4 km) Approx . 10 kΩ to approx. 40 kΩ (see note 3) 0 to approx. 1.3 kΩ 0 to approx. 2 kΩ Interelectrode release resistance Approx. 15 k to Approx. 15 k to 4 k to ∞Ω (for 2 km) 2.5 k to ∞Ω (for 4 km) Approx. 100 k to Approx. 4 k to ∞Ω Approx. 15 k to Response time Operate:80 ms max. Release:160 ms max. Cable length (see note 1) 1 km max. 600 m max. 2 km max. 4 km max. 50 m max. 1 km max. 800 m max. Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4)
3 A, 250 VAC (Resistive load)
Ambient temperature Operating:–10 to 55°C (–10 to 70°C for high-temperature controller) Ambient humidity Operating:45% to 85% RH Insulation resistance (see note 2) 100 MΩ min. (at 500 VDC) Dielectric strength (see note 2) 2000 VAC, 50/60 Hz for 1 min. Life expectancy Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. Weight Approx. 155 g Accessories Hold-down clip PFC-N8
61F-GP-N@ Internal Circuit Diagrams Note: When applying a self-holding circuit, short between terminals 5 and 6 and use terminal 7 as E2. 61F-GP-N/-NT/-NL/-ND 61F-GP-NR61F-GP-NH 3 9 14 1011 U 24 V 8 V Control circuit S0 S1 E3 E1 Ta1 Tc1 Tb1 867 U Ta2 Tc2 Tb2 3 9 14 1011 U 24 V 8 V Control circuit S0 S1 E3 E1 Ta1 Tc1 Tb1 867 U Ta2 Tc2 Tb2 3 9 14 1011 U 24 V 8 V Control circuit S0 S1 E3 E1 Ta1 Tc1 Tb1 U Power supply Power supply Power supply (See note.) (See note.)
61F-GP-N@ ■Connections Automatic Water Supply Control Automatic Drainage Control Compact, Plug-in Type 61F-GP-N Dimensions: page 14 Automatic Water Supply and Drainage Control Water supply source MCCB RS M T Commercial Voltage 61F-GP-N PS-3S Stop 3 9 P Start
8 VPower
0 V U
U U
24 V Control
(See note.) 876 5 10 11 1 2 Contac- tor Water tank Motor protection relay Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF113A (Front-connecting) PL11 (Rear-connecting) Connect terminal 1 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. Connections Reservoir MCCB RS M T Commercial Voltage 61F-GP-N PS-3S P 8 V U U (See note.) 876 5 10 11 1 2 Start Stop Contac- tor Power supply Motor protection relay Waste- water tank Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF113A (Front-connecting) PL11 (Rear-connecting) Connect terminal 1 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. Connections P Water supply (Indicator ON)Pump OFF Pump ON (Indicator OFF) The pump stops when the water level reaches E1 (indicator ON) and starts when the water level drops below E2 (indicator OFF). Principles of Operation Water drainage (Indicator ON) Pump OFF Pump ON (Indicator OFF) P The pump starts when the water level reaches E1 (indicator ON) and stops when the water level drops below E2 (indicator OFF). Principles of Operation
61F-GP-N@ Liquid Level Indication Liquid Level Indication (Connection Example) Compact, Plug-in Type 61F-GP-N Dimensions: page 14 Water supply source Intermediate Upper limit Lower limit MCCB RS M T Commercial Voltage P PS-4S U U 61F-GP-N Lower limit Intermediate Upper limit 5 678
0 V 24 V
U U U 61F-GP-N 5678 8 V U U U 61F-GP-N 5678 8 V U (See note.) Water tank Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the common Electrode (the longest Electrode, terminal 4). Connections
- Terminals 6 and 7, and terminals 10 and 11 on the lower -limit 61F-GP-N are shorted when the water level reaches E3 (indicator ON). Terminals 6 and 7, and terminals 10 and 11 on the intermediate 61F-GP-N are shorted when the water level reaches E2 (indicator ON). Terminals 6 and 7, and terminals 10 and 11 on the upper-limit 61F-GP-N are shorted when the water level reaches E1 (indicator ON). Principles of Operation
61F-GP-N@ Replacing 61F-G3N Functions Replacing 61F-G3N Functions (Automatic Water Supply Control with Abnormal Water Increase and Water Shortage Alarms) Compact, Plug-in Type 61F-GP-N Dimensions: page 14 Contactor Water supply source Stop Full tank Start Water shortage MCCB RS M T Commercial Voltage Water shortage Pump control Full tank P PS-5S 61F-GP-N 5 678 (See note.) Upper limitLower limit Alarm Water tank Motor protection relay Note: The power supply phases (terminals 3 to 9) can be matched to use the same ground for the common Electrode (the longest Electrode, terminal 4). Connections Upper limit Lower limit Pump OFF Pump ON 1 indicator ON) (U2 indicator ON) (U2 indicator OFF) (U3 indicator OFF) BLH BLL P Water supply The pump stops when the water level reaches E2 (U2 indicator ON) and starts when the water level drops below E3 (U2 indicator OFF). If the water level rises to E1 for any reason, the upper-limit indicator turns ON and the alarm sounds (U 1 indicator ON). If the water level drops below E4 for any reason, the lower-limit indicator turns ON and the alarm sounds (U 3 indicator OFF). Principles of Operation
61F-GP-N@ Automatic Water Supply Control Automatic Drainage Control Two-Wire Connections Automatic Water Supply and Drainage Control Compact, Plug-in Type 61F-GP-NR Dimensions: page 14 U U Water supply source Stop Start MCCB RS M T Commercial Voltage 61F-GP-NR (See note.) P R Contac- tor Water tank Motor protection relay Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF113 (Front-connecting) PL11 (Rear-connecting) Connect terminal 1 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. With 2-wire connections, only two wires are required between the 61F-GP-NR and Electrode Holder, but three wires are required for the Electrodes. The Electrode Holder must be specified for 2-wire connections. (Resistance R is built into Electrode Holders for 2-Wire Connections.) Connections U U Reservoir MCCB RS M T 61F-GP-NR (See note.) P R 8 V T Commercial Voltage Power supply Motor protection relay Waste- water tankNote: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF113 (Front-connecting) PL11 (Rear-connecting) Connect terminal 11 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. With 2-wire connections, only two wires are required between the 61F-GP-NR and Electrode Holder, but three wires are required for the Electrodes. The Electrode Holder must be specified for 2-wire connections. (Resistance R is built into Electrode Holders for 2-Wire Connections.) Connections P Water supply (Indicator ON)Pump OFF Pump ON (Indicator OFF) The pump stops when the water level reaches E1 (indicator ON) and starts when the water level drops below E2 (indicator OFF). Principles of Operation Water drainage (Indicator ON) Pump OFF Pump ON (Indicator OFF) P The pump starts when the water level reaches E1 (indicator ON) and stops when the water level drops below E2 (indicator OFF). Principles of Operation
61F-GP-N@ ■Connection with Three-phase Four-line Circuit When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams. Line voltage (R-S, S-T, or R-T): 380 or 415 VAC Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC 61F-GP-N@ 220 or 240 VAC Note: 1. The diagram shows the connections for the water supply. When draining, change the connection from terminal 1 to terminal 11. 2. Be sure to ground terminal 4. Power source 380 or 415 VAC R S T N * M Water tank Stop Start P Electromagnetic switch A Water supply source Source voltage: between 3 and 9 61F-GP-N 0 V 220 or 240 V 8 V
24 V Control circuit
U U 786 5 2 111 10 U 3 9 (See note 1) (See note 2.)
61F-GP-N@ ■Compact Plug-in Models (8-pin Type) Specifications Note: 1. The length when using completely-insulated, 600-V, 3-conductor (0.75 mm2) cabtire cables. Usable cable lengths will become shorter as the cable diameter or number of conductors becomes larger. 2. The insulation resistance and dielectric strength indicate val ues between power terminals and Electrode terminals, between powe r ter- minals and contact terminals, and between Electrode terminals and contact terminals. 3. Possible to use with 15 kΩ or less, however, this may cause reset failure. 4. 61F-GP-N8H/-N8Y High-sensitivity Controllers use advanced operation. When the power supply voltage is applied, if there are some liquids between the electrodes (ground and operation electrodes), the inter- nal relay will not operate. When the power supply voltage is applied, if there are no liquids between the electrodes (ground and operation electrodes), the internal relay will operate. If the advanced operation does not satisfy applications, consider using 61F-N8HY controller which uses sequential operation. Item General-purpose Controller 61F-GP-N8 61F-GP-N8Y (see note 4) Long-distance Controllers 61F-GP-N8L 2KM (for 2 km) 61F-GP-N8L 4KM (for 4 km) High-sensitivity Controllers 61F-GP-N8H 61F-GP-N8HY (see note 4) Low-sensitivity Controller 61F-GP-N8D Two-wire Controller 61F-GP-N8R Variable Sensitivity Controller 61F-GP-N8-V50 Controlling mate- rials and operat- ing conditions For control of ordi- nary purified water or sewage water For control of ordi- nary purified water in cases where the distance between sewage pumps and water tanks or be- tween receiver tanks and supply tanks is long or where remote con- trol is required. For control of liq- uids with high spe- cific resistance such as distilled water For control of liq- uids with low spe- cific resistance such as salt water, sewage water, acid chemicals, alkali chemicals For control of ordi- nary purified water or sewage water used in combina- tion with Two-wire Electrode Holder (incorporating a re- sistor of 6.8 kΩ) For control of cases where variable sen- sitivity control is re- quired such as detection of froth on the surface of a liq- uid, control of soil moisture content, or detection of de- gree of water pollu- tion Supply voltage 24, 100, 110, 120, 200, 220, 230 or 240 VAC; 50/60 Hz 24, 110, 220 or
240 VAC; 50/60 Hz
85% to 110% of rated voltage Interelectrode voltage
8 VAC 24 VAC 8 VAC 24 VAC
Approx. 1 mA AC max. Approx. 0.4 mA AC max. Approx. 1 mA AC max. Approx. 3 mA AC max. Power consump- tion Approx. 3.5 VA max. Interelectrode op- erate resistance 0 to approx. 4 kΩ 0 to 1.3 kΩ (for 2k m ) 0 to 0.5 kΩ (for 4k m ) Approx. 15 kΩ to approx . 70 kΩ (see note 3) 0 to approx. 1.3 kΩ 0 to approx. 2 kΩ 0 to 50 kΩ (Vari- able) Interelectrode re- lease resistance Approx. 15 k to ∞Ω 4 k to ∞Ω (for 2 km) 2.5 k to ∞Ω (for 4 km) Approx. 300 k to Approx. 4 k to ∞Ω Approx. 15 k to ∞Ω Operating resis- tance +50 kΩ max. Response time Operate: 80 ms max. Release: 160 ms max. Cable length (see note 1) 1 km max. 2 km max. 4 km max. 50 m max. 1 km max. 800 m max. 50 m max. Control output 1 A, 250 VAC (Inductive load: cosφ = 0.4) Operating: –10 to 55°C Ambient humidity Operating: 45% to 85% RH Insulation resis- tance (see note 2) 100 MΩ min. (at 500 VDC) Dielectric strength (see note 2) 2000 VAC, 50/60 Hz for 1 min. Life expectancy Electrical: 100,000 operations min. Mechanical: 5,000,000 operations min. Weight Approx. 155 g Accessories Hold-down clip PFC-N8
61F-GP-N@ Internal Circuit Diagrams 24 V 24 V Control circuit Power supply Control circuit24 V Power supply
8 V (see note)
61F-GP-N8/-N8L/-N8D/-N8HY 61F-GP-N8H 61F-GP-N8R 24 V 8 V Power supply Control circuit 2 4 3 61F-GP-N8Y 24 V 8 V Control circuit Power supply Note: 24 V for the 61F-GP-N8HY . Control circuit24 V Power supply 24 V 61F-GP-N8-V50
61F-GP-N@ Automatic Water Supply Control Automatic Drainage Control Automatic Water Supply and Drainage Control Compact, Plug-in Type 61F-GP-N8 Dimensions: page 14 Water supply source MCCB RS M T Commercial Voltage 61F-GP-N8 PS-3S Stop P Start
8 V0 V
U U U (See note.) 218 7 3456 Water tank Contac- tor Power supply Motor protection relay Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF083A (Front-connecting) PL08 (Rear-connecting) Connect terminal 2 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. Connections Reservoir MCCB RS M T 61F-GP-N8 P U U U 24 V (See note.) 3456 PS-3S E2E3 Start Stop 218 7 Control circuit Contac- tor Power supply Motor protection relay Waste- water tank Commercial Voltage Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connection Sockets PF083A (Front-connecting) PL08 (Rear-connecting) Connect terminal 3 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. Connections P Water supply (Indicator ON)Pump OFF Pump ON (Indicator OFF) The pump stops when the water level reaches E1 (indicator ON) and starts when the water level drops below E2 (indicator OFF). Principles of Operation Water drainage (Indicator ON) Pump OFF Pump ON (Indicator OFF) P Principles of Operation The pump starts when the water level reaches E1 (indicator ON) and stops when the water level drops below E2 (indicator OFF).
61F-GP-N@ Water Supply Automatic Drainage Two-Wire Connections Automatic Water Supply and Drainage Control Compact, Plug-in Type 61F-GP-N8R Dimensions: page 14 U U A Water supply source Stop Start MCCB RS M T 61F-GP-N8R 7 8 1 2 P R (See note.) Water tank Contac- tor Commercial Voltage Power supply Motor protection relay Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connect terminal 2 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. With 2-wire connections, only two wires are required between the 61F-GP-N8R and Electrode Holder, but three wires are required for the Electrodes. The Electrode Holder must be specified for 2-wire connections. (Resistance R is built into Electrode Holders for 2-Wire Connections.) Connections E2E3 U U A Reservoir MCCB RS M T 61F-GP-N8R (See note.) 7 8 1 2 P R Note: Be sure to ground the common Electrode E3 (the longest Electrode). Connect terminal 3 to the contactor’s coil terminal. Note: The power supply depends on the specifications of the model. With 2-wire connections, only two wires are required between the 61F-GP-N8R and Electrode Holder, but three wires are required for the Electrodes. The Electrode Holder must be specified for 2-wire connections. (Resistance R is built into Electrode Holders for 2-Wire Connections.) Connections P Water supply (Indicator ON)Pump OFF Pump ON (Indicator OFF) The pump stops when the water level reaches E1 (indicator ON) and starts when the water level drops below E2 (indicator OFF). Principles of Operation Water drainage (Indicator ON) Pump OFF Pump ON (Indicator OFF) P The pump starts when the water level reaches E1 (indicator ON) and stops when the water level drops below E2 (indicator OFF). Principles of Operation
61F-GP-N@ ■Connection with Three-phase Four-line Circuit When supplying power from N-phase to the Controller in three-phase four-line circuit, refer to the following diagrams. Line voltage (R-S, S-T, or R-T): 380 or 415 VAC Phase voltage (N-R, N-S, or N-T): 220 or 240 VAC 61F-GP-N8@, 220 or 240 VAC Note: Be sure to ground terminal 1. Power source 380 to 415 VAC R S T N * M Water tank Stop StartE2 P Electromagnetic switch Transformer U 24 V 8 V A U Control circuit Water supply source
61F-GP-N@ Dimensions Note: All units are in millimeters unless otherwise indicated. ■Safety Precautions Refer to Safety Precautions for All Level Controllers. 49.4 38 70 61F-GP-N PF113A 101 61F-GP-N, -NT, -NL, -NH, -ND, -NR, -N -TDL, -N14, -N15, -NH3 When mounting a Display Unit to a PF113A Surface-mounting Socket, secure the PF113A with the groove facing toward the bottom and then connect the 61F-GP-N the PFC-N8 accessory. PFC-N8 Note: PFC-N8 Mounting Bracket (provided with the Level Controller) t = 0.3 4.5 Approx. 38 70 49.4 61F-GP-N8 PF083A 61F-GP-N8, -N8L, -N8H, -N8HY, -N8D, -N8R Use a PFC-N8 Mounting Bracket to mount the Level Controller to a PF083A Rail-mounted Socket. PFC-N8 Note: PFC-N8 Mounting Bracket (provided with the Level Controller) 4.5 t=0.36 Approx. In the interest of product improvement, specifications are subject to change without notice. ALL DIMENSIONS SHOWN ARE IN MILLIMETERS. To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
Read and Understand This Catalog Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you have any questions or comments. Warranty and Limitations of Liability WARRANTY OMRON's exclusive warranty is that the products are free from defects in materials and workmanship for a period of one year (or other period if specified) from date of sale by OMRON. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THE PRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HAS DETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED. LIMITATIONS OF LIABILITY OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS, WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON'S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR. Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products. This information by itself is not sufficient for a complete determination of the suitability of the products in combination with the end product, machine, system, or other application or use. The following are some examples of applications for which particular attention must be given. This is not intended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the uses listed may be suitable for the products: Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions or uses not described in this catalog. Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medical equipment, amusement machines, vehicles, safety equipment, and installations subject to separate industry or government regulations. Systems, machines, and equipment that could present a risk to life or property. Please know and observe all prohibitions of use applicable to the products. NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM. PROGRAMMABLE PRODUCTS OMRON shall not be responsible for the user's programming of a programmable product, or any consequence thereof. Disclaimers CHANGE IN SPECIFICATIONS Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our practice to change model numbers when published ratings or features are changed, or when significant construction changes are made. However, some specifications of the products may be changed without any notice. When in doubt, special model numbers may be assigned to fix or establish key specifications for your application on your request. Please consult with your OMRON representative at any time to confirm actual specifications of purchased products. DIMENSIONS AND WEIGHTS Dimensions and weights are nominal and are not to be used for manufacturing purposes, even when tolerances are shown. PERFORMANCE DATA Performance data given in this catalog is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON’s test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability. ERRORS AND OMISSIONS The information in this document has been carefully checked and is believed to be accurate; however, no responsibility is assumed for clerical, typographical, or proofreading errors, or omissions. 2012.9 In the interest of product improvement, specifications are subject to change without notice. OMRON Corporation Industrial Automation Company http://www.ia.omron.com/ (c)Copyright OMRON Corporation 2012 All Right Reserved.