MODEL: 61A 61A SPECIFICATIONS ES-6639 Rev.2 Page 1/3 http://www.m-system.co.jp/ Field Network Modules 61-UNIT Series ANALOG I/O MODULE (conforms to AnyWire wiring saving system) Functions & Features

  • Interfacing analog I/O signals from/to Mini-M or Pico-M modules with AnyWire wiring saving systems
  • Saving power and I/O wiring inside an instrumentation panel mm (inch) (1.97) 100 (3.94) 115 (4.53) MODEL: 61A-[1][2]-[3][4]

ORDERING INFORMATION

  • Code number: 61A-[1][2]-[3][4] Specify a code from below for each [1] through [4]. (e.g. 61A-161-K/Q)
  • Specify the specification for option code /Q (e.g. /C01) [1] NO. OF CHANNELS 04: 4 points 08: 8 points 16: 16 points [2] I/O TYPE 1: Input 2: Output [3] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) (Specify power suffix code R (24 V DC) when the UNIT is to be combined with the M8BS2.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating

RELATED PRODUCTS

  • Installation Base (model: M2BS2)
  • Installation Base (model: M8BS2) GENERAL SPECIFICATIONS Construction: Plug-in Connection AnyWire: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: Via Installation Base (model: MxBS2) Power input: Via Installation Base (model: MxBS2) Housing material: Flame-resistant resin (black) Isolation: I/O to AnyWire to power Power indicator: Green LED turns on with power supplied. AnyWire SPECIFICATIONS Network: Conforms to AnyWire wiring saving system Transmission media
  • General-purpose 2-core / 4-core cable (0.75 - 1.25 mm2)
  • General-purpose wiring (0.75 - 1.25 mm2) etc. Station No.: DIP switch; 00 - 3F Transmission clock / maximum transmission distance (configurable with DIP switch(es))
  • 7.8 kHz / 800 m (874.9 yds)
  • 15.6 kHz / 500 m (546.8 yds)
  • 31.3 kHz / 200 m (218.7 yds)
  • 62.5 kHz / 100 m (109.4 yds) RDY indicator: Red LED ON at normal operating LINK indicator: Red LED blinking at normal operating INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ (Each input must be isolated by signal conditioners. Non- isolated modules such as M2BW and M8BW are not usable.) A/D conversion Moving averaging: 4 samples Sampling rate: 160 ms A/D conversion output: Signed binary

MODEL: 61A 61A SPECIFICATIONS ES-6639 Rev.2 Page 2/3 http://www.m-system.co.jp/ Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC OUTPUT SPECIFICATIONS ■ Analog Output Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum (Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW and M8BW are not usable. ) D/A conversion input: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC INSTALLATION Power consumption

  • AC: Approx. 4 VA
  • DC: Approx. 4 W (160 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Installation Base (model: MxBS2) Weight: 250 g (0.55 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (I/O to AnyWire to power) EXTERNAL VIEW PWR RDY LINK D E Modular Jack for Factory Calibration Power Indicator LED Transmission Setting Euro Type Connector Terminal for AnyWire Status Indicator LED

MODEL: 61A 61A SPECIFICATIONS ES-6639 Rev.2 Page 3/3 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS unit: mm (inch) (1.50) (.47) 80 (3.15) 100 (3.94) 2–M3 SCREWS SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM A/D or D/A ConverterI/O Side CPU SERIAL TRANSMISSION LINE Modular Jack for Factory Calibration MODULAR JACK To Installation Base D G G DTo other AnyWire devices * Refer to the manual of the AnyWire device to be connected for explanations how to connect the device. AnyWire Interface Indicator LED Transmission Setting I/O & POWER CONNECTOR Specifications are subject to change without notice.