Product: 6179 Teck90 1000V, 4+G C #3/0+6 Str BC, XLPE Ins M4, PVC Jkt, AIA Armor, Blk PVC Jkt, CSA HL SUN RES -40C Product Description Teck90 1000V, 4+G Conductor 3/0+6AWG (19x10H) Bare Copper, XLPE Insulation M4 Color Code, PVC Inner Jacket, Aluminum Interlock Armor, Black PVC Outer Jacket, CSA HL SUN RES -40C Technical Specifications Product Overview Suitable Applications: CEC Power and Control Applications up to 600V Construction Details Conductor Element No. of Elements Size Stranding Material Conductor(s) 4 3/0 AWG 19x10 BC - Bare Copper Ground Wire 1 4 AWG 7x12 BC - Bare Copper Insulation Element Material Nom. Thickness Nom. Insulation Diameter Color Code Conductor(s) XLP, XLPO, XLPE (Thermoset) 0.080 in (2.0 mm) 0.622 in (15.8 mm) Black, White, Red, Blue Ground Wire No Insulation Outer Shield Material No Shield Inner Jacket Material Nom. Thickness Nom. Diameter Ripcord Color PVC - Polyvinyl Chloride 0.083 in (2.1 mm) 1.665 in (42.29 mm) Yes Black Armor Armor Type & Material Armor Thickness Diameter Over Armor AIA - Aluminum Interlock Armor 0.040 in (1.0 mm) 1.945 in (49.40 mm) Outer Jacket Material Nom. Thickness Nom. Diameter PVC - Polyvinyl Chloride 0.053 in (1.3 mm) 2.051 in (52.10 mm) Overall Cable Diameter (Nominal): 2.051 in (52.10 mm)

Electrical Characteristics

Element Nom. Conductor DCR Max. Current Conductor(s) 0.0644 Ohm/1000ft 24 Amps per Conductor at 30ºC Ground Wire 0.403 Ohm/1000ft (1.32 Ohm/km) 95 Amps per Conductor at 30ºC Voltage

1000 V (TECK 90)

Mechanical Characteristics Temperature UL Temperature Operating 90°C -40°C To +90°C Bend Radius Stationary Min. Installation Min. 16.408 in (416.76 mm) 16.408 in (416.76 mm) Max. Pull Tension: 8533.8 lbs (3870.9 kg) Bulk Cable Weight: 3231 lbs/1000ft Standards and Compliance Environmental Suitability: Indoor, Outdoor, Sunlight Resistance, UV Resistance CEC / C(UL) Compliance: TECK 90, HL History Update and Revision: Revision Number: 0.191 Revision Date: 12-22-2023 © 2024 Belden, Inc All Rights Reserved. Although Belden makes every reasonable effort to ensure their accuracy at the time of this publication, information and specifications described here in are subject to error or omission and to change without notice, and the listing of such information and specifications does not ensure product availability. Belden provides the information and specifications herein on an "ASIS" basis, with no representations or warranties, whether express, statutory or implied. In no event will Belden be liable for any damages (including consequential, indirect, incidental, special, punitive, or exemplary damages) whatsoever, even if Belden has been advised of the possibility of such damages, whether in an action under contract, negligence or any other theory, arising out of or in connection with the use, or inability to use, the information or specifications described herein. All sales of Belden products are subject to Belden's standard terms and conditions of sale. Belden believes this product to be in compliance with all applicable environmental programs as listed in the data sheet. The information provided is correct to the best of Belden's knowledge, information and belief at the date of its publication. This information is designed only as a general guide for the safe handling, storage, and any other operation of the product itself or the one that it becomes a part of. The Product Disclosure is not to be considered a warranty or quality specification. Regulatory information is for guidance purposes only. Product users are responsible for determining the applicability of legislation and regulations based on their individual usage of the product.