MODEL: 60S 60S SPECIFICATIONS ES-6612 Rev.3 Page 1/5 http://www.m-system.co.jp/ Field Network Modules 60-UNIT Series ANALOG I/O MODULE (Multiplex Transmission System) Functions & Features
- Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with Multiplex Transmission System
- Saving power and I/O wiring inside an instrumentation panel (2.83) 80 (3.15) mm (inch) 1234567890 1234567890 153 (6.02) MODEL: 60S-16[1]-[2][3]
ORDERING INFORMATION
- Code number: 60S-16[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. 60S-161-K/Q)
- Specify the specification for option code /Q (e.g. /C01/S01) NO. OF CHANNELS 16: 16 points [1] I/O TYPE 1: Input 2: Output [2] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel
RELATED PRODUCTS
- Special cable (model: MCN34) GENERAL SPECIFICATIONS Construction: Plug-in Connection SIN-NET, RUN contact output: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: 34-pin connector (OMRON XG4A-3434) Power input: M3.5 screw terminals Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: I/O to SIN-NET to RUN contact output to power to FG1 Power indicator: Red LED turns ON in normal conditions; OFF when the voltage level becomes low. RUN indicator: Red LED turns ON when the selfdiagnosis proves normal, OFF in an abnormality. ■ RUN Contact Output: Contact opens at error Rated load: 30 V DC @ 0.4 A (resistive load) Maximum switching voltage: 125 V DC Maximum switching power: 60 W Minimum load: 10 mV DC @ 1 mA Mechanical life: 5 x 107 cycles Self-diagnosis Communication: The receiver modules detect loss of communication and wire break. CPU: Watch-dog timer Memory: Sum check Power voltage: Detects when the voltage supply to the CPU drops.
MODEL: 60S 60S SPECIFICATIONS ES-6612 Rev.3 Page 2/5 http://www.m-system.co.jp/ COMMUNICATION Configuration: Multi-drop Standard: Conforms to EIA RS-422 Communication: 2-wire, half-duplex Transmission speed: 125 kbps Control procedure: SDLC Data encoding: NRZ Protocol: SIN-NET (M-System's) Error check: CRC Transmission distance: 500 m Transmission media: Twisted-pair cable CPEV-0.9 dia. Station No.: Rotary switch Terminator: Incorporated (remove jumper pin with those modules not located at the end of transmission line) INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
- Input Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT
1 Input 1 2 COM
3 Input 2 4 COM
5 Input 3 6 COM
7 Input 4 8 COM
9 Input 5 10 COM
11 Input 6 12 COM
13 Input 7 14 COM
15 Input 8 16 COM
17 Input 9 18 COM
19 Input 10 20 COM
21 Input 11 22 COM
23 Input 12 24 COM
25 Input 13 26 COM
27 Input 14 28 COM
29 Input 15 30 COM
31 Input 16 32 COM
33 No connection 34 No connection
■ Analog Output Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
- Output Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT
1 Output 1 2 COM
3 Output 2 4 COM
5 Output 3 6 COM
7 Output 4 8 COM
9 Output 5 10 COM
11 Output 6 12 COM
13 Output 7 14 COM
15 Output 8 16 COM
17 Output 9 18 COM
19 Output 10 20 COM
21 Output 11 22 COM
23 Output 12 24 COM
25 Output 13 26 COM
27 Output 14 28 COM
29 Output 15 30 COM
31 Output 16 32 COM
- AC: Approx. 4 VA
- DC: Approx. 4 W (160 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input or output to SIN-NET to RUN contact output to power)
2000 V AC @ 1 minute (input or output or SIN-NET or RUN
contact output or power to FG1)
MODEL: 60S 60S SPECIFICATIONS ES-6612 Rev.3 Page 3/5 http://www.m-system.co.jp/ DESCRIPTIONS ■ RUN Contact Output (LED) Behaviors
- Input module The LED for the Input Modules turns ON when the network is on-line. When there is an abnormality in the network, the LED turns OFF. The network is reconfigured after an abnormality.
- Output module The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding Input Module. When there is an abnormality in the network or there is no data receiving, the LED turns OFF. ■ Station Number (Address) A) 1 input module and X output modules: Match the address for input and output modules. B) Computer interface: Set address numbers to correspond with the computer as output module. ■ Transmission Time Integrate all the transmission time for each process input module in the system.
- Analog input 16 points: 24.0 msec. An analog module does not transmit all its signals in serial but does 1 point per each cycle. For example, when 1 contact input module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32 point contact signal and 1 point analog signal are transmitted in turn. One cycle time is therefore calculated as: 32 points × 1.5 msec. + 24 msec. = 72 msec. This method is beneficial for giving a priority to contact signals which vary rapidly. ■ Applicable models for use with 60S Input Module
- 60S-162 (Ao 16 points)
- DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)
MODEL: 60S 60S SPECIFICATIONS ES-6612 Rev.3 Page 4/5 http://www.m-system.co.jp/ 60S DLA1DLA1 1234 567 89 1234 56 7 89 DAL4 DAL4 60S 60SDLA1 DLA1 1234 56 7 89 1234 56 7 89 1234 56 7 89 1234 56 7 89 22LA1 DLA1 DLA160S 1234 56 7 89 1234 56 7 89 /square7 TRANSMISSION LINE CONFIGURATION The multi-drop transmission line containing 22LA1, DLA1 and 60S modules should meet the following conditions. Contact M-System's sales office or representatives when designing. A) 10 kilometers at maximum in total system. B) 60S module plus DLA1 units: One multitransmission line containing a 60S module can consist of a maximum of 16 units within the total distance of 500 m. C) 60S modules, DLA1 units plus Repeater (model: DAL4): DAL4 units can expand the total distance. (6 DAL4 units max.) D) 60S module, 22LA1 module plus DLA1 units: The total distance of a section consisting of 60S and 22LA1 modules is less than 500 meters. They can be connected to DLA1 units via a DLA1-7 unit. (Eight DLA1-7 units max.) EXTERNAL VIEW CN1 I/O Connector Power Indicator LED RUN Indicator LED Station No. Setting Rotary Switches Modular Jack for Factory Calibration SIN-NET Terminals Terminals for Terminating Resistor RUN Contact Output PWR RUN '&%$#" '&%$#" PU-2x SA1 SA2
MODEL: 60S 60S SPECIFICATIONS ES-6612 Rev.3 Page 5/5 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) (.55) 38 (1.50) 80 (3.15) (.79) CLAMP (top & bottom) DIN RAIL 35mm wide
- When mounting, no extra space is needed between units. 80 (3.15) 60 (2.36) 72 (2.83) 7.8 (.31) 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW 12 5614 11 110 15 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM A Control CircuitB C D E F Ry TERMINATING RESISTOR TWISTED PAIR RUN CONTACT OUTPUT Transceiver Circuit *1. When the unit is located at the end of transmission line via twisted-pair cable (= no cross-wiring), short across terminals C – D with the jumper pin (or wire) provided with the unit. Remove the jumper pin for the one not located at the end. JUMPER PIN *1 TO OTHER SIN-NET DEVICES SERIAL TRANSMISSION LINE Modular Jack for Factory Calibration MODULAR JACK Station No. Setting Rotary SWLED A/D or D/A Converter I/O CONNECTOR Transmission POWER U(+) V(−) GROUNDING FG1 To 10-RACK, 18-RACK etc. Isolation Specifications are subject to change without notice.