60F MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

MODEL: 60F 60F SPECIFICATIONS ES-6610 Rev.3 Page 1/4 http://www.m-system.co.jp/ Field Network Modules 60-UNIT Series ANALOG I/O MODULE (Fuji Electric T-Link use) Functions & Features

  • Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with T-Link
  • Saving power and I/O wiring inside an instrumentation panel (2.83) 80 (3.15) mm JODI 1234567890 1234567890 153 (6.02) MODEL: 60F-16[1]-[2][3]

ORDERING INFORMATION

  • Code number: 60F-16[1]-[2][3] Specify a code from below for each [1] through [3]. (e.g. 60F-161-K/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) NO. OF CHANNELS 16: 16 points [1] I/O TYPE 1: Input 2: Output [2] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [3] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel

RELATED PRODUCTS

  • Special cable (model: MCN34) GENERAL SPECIFICATIONS Construction: Plug-in Connection T-Link: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: 34-pin connector (OMRON XG4A-3434) Power input: M3.5 screw terminal Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: I/O to T-Link to power to FG1 Power indicator: Green LED turns on with power supplied. T-Link SPECIFICATIONS Configuration: Multi-drop Communication: Half-duplex Baud rate: 500 kbps Transmission media/distance: KPEV-SB 0.75 mm2 × 1 pair, 700 m T-KPEV-SB, 1.25 mm2 × 1 pair, 1000 m Station No.: Rotary switch; 00 - 99 (Factory default setting: 00) L RUN indicator: Red LED ON at normal communication L ERR. indicator: Red LED ON/blinking at communication abnormality L I/O indicator: Red LED blinking at normal I/O L COM indicator: RED LED blinking at T-Link normal communication ■ NUMBER OF CONNECTABLE UNITS WITH T-Link Up to a maximum of 32 T-Link devices can be connected in a single T-Link system. There is a limit of 100 words in processor memory. Make sure that the configured word area to be occupied does not exceed the 100-word range. (According to the Fuji Electric MICREX-F Users Manual) It is necessary to consider these criteria when connecting to this device. The below describes the number of words occupied per device by number of modules.
  • For input 16 / output 16 modules: 16

MODEL: 60F 60F SPECIFICATIONS ES-6610 Rev.3 Page 2/4 http://www.m-system.co.jp/ INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. A/D conversion output: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC

  • Input Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT

1 Input 1 2 COM

3 Input 2 4 COM

5 Input 3 6 COM

7 Input 4 8 COM

9 Input 5 10 COM

11 Input 6 12 COM

13 Input 7 14 COM

15 Input 8 16 COM

17 Input 9 18 COM

19 Input 10 20 COM

21 Input 11 22 COM

23 Input 12 24 COM

25 Input 13 26 COM

27 Input 14 28 COM

29 Input 15 30 COM

31 Input 16 32 COM

33 No connection 34 No connection

■ Analog Output Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. D/A conversion output: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC

  • Output Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT

1 Output 1 2 COM

3 Output 2 4 COM

5 Output 3 6 COM

7 Output 4 8 COM

9 Output 5 10 COM

11 Output 6 12 COM

13 Output 7 14 COM

15 Output 8 16 COM

17 Output 9 18 COM

19 Output 10 20 COM

21 Output 11 22 COM

23 Output 12 24 COM

25 Output 13 26 COM

27 Output 14 28 COM

29 Output 15 30 COM

31 Output 16 32 COM

  • AC: Approx. 3 VA
  • DC: Approx. 4 W (160 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input or output to T-Link to power)

2000 V AC @ 1 minute (input or output or T-Link or power to

FG1)

MODEL: 60F 60F SPECIFICATIONS ES-6610 Rev.3 Page 3/4 http://www.m-system.co.jp/ EXTERNAL VIEW CN1 L RUN L ERR. L I/O L COM PWR 4321 9 8 76 5 4321 9 8 76 I/O Connector Euro Type Connector Terminal for T-Link Operating Status Indicator LED Power Indicator LED Station No. Setting Rotary Switches Modular Jack for Factory Calibration EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) (.55) 38 (1.50) 80 (3.15) (.79) CLAMP (top & bottom) DIN RAIL 35mm wide

  • When mounting, no extra space is needed between units. 80 (3.15) 60 (2.36) 72 (2.83) 7.8 (.31) 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW 12 5614 11 110 15 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM POWER Transmission To 10-RACK, 18-RACK etc. V − GROUNDING FG1 I/O Connector SHIELDED TWISTED-PAIR To other T-Link devices JUMPER PIN* A/D or D/A ConverterI/O Side CPU SERIAL TRANSMISSION LINE Modular Jack for Factory Calibration MODULAR JACK CPU For T-Link Transmission SD RT RT− TERMINATING RESISTOR Indicator LED Station No. Setting Rotary Switches * When the unit is located at the end of transmission line via twisted-pair cable (= no cross-wiring), short across terminals RT+, RT- with the jumper pin (or wire) provided with the unit. Remove the jumper pin for the one not located at the end. Note: Use T1, T2, SD terminals for cross-wiring.

MODEL: 60F 60F SPECIFICATIONS ES-6610 Rev.3 Page 4/4 http://www.m-system.co.jp/ Specifications are subject to change without notice.