60C MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 4

Technical content

MODEL: 60C 60C SPECIFICATIONS ES-6602 Rev.10 Page 1/4 http://www.m-system.co.jp/ Field Network Modules 60-UNIT Series ANALOG I/O MODULE (CC-Link) Functions & Features

  • Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with CC-Link
  • Saving power and I/O wiring inside an instrumentation panel 1234567890 1234567890 1234567890 (2.83) (3.15) mm (inch) 153 (6.02) MODEL: 60C-[1][2]-[3][4]

ORDERING INFORMATION

  • Code number: 60C-[1][2]-[3][4] Specify a code from below for each [1] through [4]. (e.g. 60C-161-K/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01) [1] NO. OF CHANNELS 04: 4 points 08: 8 points 16: 16 points [2] I/O TYPE 1: Input 2: Output [3] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 66 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) [4] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel

RELATED PRODUCTS

  • Special cable (model: MCN34) PACKAGE INCLUDES...
  • Terminating resistor (110 Ω, 0.5 W) GENERAL SPECIFICATIONS Construction: Plug-in Connection CC-Link: Euro type connector terminal (applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm) I/O: 34-pin connector (OMRON XG4A-3434) Power input: M3.5 screw terminal Screw terminal: Chromated steel (standard) or stainless steel Housing material: Flame-resistant resin (black) Isolation: I/O to CC-Link to power to FG1 Power indicator: Green LED turns on with power supplied. CC-Link COMMUNICATION CC-Link: Conforms to Version 1.10 Station type: Remote device station Station No. setting: Rotary switch; 1 – 64 Number of occupied stations: 60C-04 1 station 60C-08 2 stations 60C-16 4 stations Remote I/O (RX, RY) is fixed to 32 points. Baud rate setting: Rotary switch (156kbps(factory setting), 625kbps, 2.5Mbps, 5Mbps, 10Mbps) Transmission cable: Approved for CC-Link L RUN indicator: Red LED turns on in an normal condition. L ERR. indicator: Red LED turns on or flashes in an abnormality; off with wire breakdown. SD indicator: Red LED turns on when transmitting. RD indicator: Red LED turns on when receiving.

MODEL: 60C 60C SPECIFICATIONS ES-6602 Rev.10 Page 2/4 http://www.m-system.co.jp/ INPUT SPECIFICATIONS ■ Analog Input Input range: 1 – 5 V DC Input resistance: ≥ 1 MΩ 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. A/D conversion output: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC 0 1 2 3 4 5 6 7 8 9101112131415 RWr n+0 SIGN BIT INPUT 1 A/D CONVERSION DATA RWr n+1 SIGN BIT INPUT 2 A/D CONVERSION DATA RWr n+2 SIGN BIT INPUT 3 A/D CONVERSION DATA RWr n+3 SIGN BIT INPUT 4 A/D CONVERSION DATA RWr n+7 SIGN BIT INPUT 8 A/D CONVERSION DATA RWr n+11 SIGN BIT INPUT 12 A/D CONVERSION DATA RWr n+15 SIGN BIT INPUT 16 A/D CONVERSION DATA RWr n+0 through RWr n+3 for 4 inputs. RWr n+0 through RWr n+7 for 8 inputs. RWr n+0 through RWr n+15 for 16 inputs. ■ A/D CONVERSION DATA

  • Input Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT

1 Input 1 2 COM

3 Input 2 4 COM

5 Input 3 6 COM

7 Input 4 8 COM

9 Input 5 10 COM

11 Input 6 12 COM

13 Input 7 14 COM

15 Input 8 16 COM

17 Input 9 18 COM

19 Input 10 20 COM

21 Input 11 22 COM

23 Input 12 24 COM

25 Input 13 26 COM

27 Input 14 28 COM

29 Input 15 30 COM

31 Input 16 32 COM

33 No connection 34 No connection

Input 1 – 4 for 4 points, 1 – 8 for 8 points. OUTPUT SPECIFICATIONS ■ Analog Output Output must be isolated with signal conditioners. When the transmission line is open, the last value sampled before failure is held. Output range: 1 – 5 V DC Load resistance: 20 kΩ minimum 10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable. D/A conversion output: Signed binary Signal range 0 – 100 % is converted into hexadecimal 0000 – 2710 (0 – 10000). -15 to 0 % is a negative range represented by 2's complements. Overall range is represented by hexadecimal FA24 – 2CEC 0 1 2 3 4 5 6 7 8 9101112131415 RWw n+0 SIGN BIT OUTPUT 1 D/A CONVERSION DATA RWw n+1 SIGN BIT OUTPUT 2 D/A CONVERSION DATA RWw n+2 SIGN BIT OUTPUT 3 D/A CONVERSION DATA RWw n+3 SIGN BIT OUTPUT 4 D/A CONVERSION DATA RWw n+7 SIGN BIT OUTPUT 8 D/A CONVERSION DATA RWw n+11 SIGN BIT OUTPUT 12 D/A CONVERSION DATA RWw n+15 SIGN BIT OUTPUT 16 D/A CONVERSION DATA RWw n+0 through RWw n+3 for 4 outputs. RWw n+0 through RWw n+7 for 8 outputs. RWw n+0 through RWw n+15 for 16 outputs. ■ D/A CONVERSION DATA

MODEL: 60C 60C SPECIFICATIONS ES-6602 Rev.10 Page 3/4 http://www.m-system.co.jp/ w Output Connector Pin Assignment PIN NO. ASSIGNMENT PIN NO. ASSIGNMENT

1 Output 1 2 COM

3 Output 2 4 COM

5 Output 3 6 COM

7 Output 4 8 COM

9 Output 5 10 COM

11 Output 6 12 COM

13 Output 7 14 COM

15 Output 8 16 COM

17 Output 9 18 COM

19 Output 10 20 COM

21 Output 11 22 COM

23 Output 12 24 COM

25 Output 13 26 COM

27 Output 14 28 COM

29 Output 15 30 COM

31 Output 16 32 COM

Output 1 – 4 for 4 points, 1 – 8 for 8 points. INSTALLATION Power consumption

  • AC: Approx. 4 VA
  • DC: Approx. 4 W (160 mA) Operating temperature: -5 to +55°C (23 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Atmosphere: No corrosive gas or heavy dust Mounting: Surface or DIN rail Weight: 450 g (0.99 lb) PERFORMANCE in percentage of span A/D conversion: ±0.1 % D/A conversion: ±0.1 % Temp. coefficient: ±0.015 %/°C (±0.008 %/°F) Permissible power failure duration: ≤ 10 msec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 1500 V AC @ 1 minute (input or output to CC-Link to power)

2000 V AC @ 1 minute (input or output or CC-Link or power

to FG1) EXTERNAL VIEW CN1 Modular Jack for Factory Calibration I/O Connector Euro Type Connector Terminal for CC-Link L RUN L ERR. SD RD PWR 4321 9 8 76 5 4321 9 8 76 5 4321 9 8 76 Baud Rate Setting Station No. Setting Power LED Status Indicator LED

MODEL: 60C 60C SPECIFICATIONS ES-6602 Rev.10 Page 4/4 http://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) (.55) 38 (1.50) 80 (3.15) (.79) CLAMP (top & bottom) DIN RAIL 35mm wide

  • When mounting, no extra space is needed between units. 80 (3.15) 60 (2.36) 72 (2.83) 7.8 (.31) 2–4.5 (.18) dia. MTG HOLE 25 (.98) deep 14–M3.5 SCREW 12 5614 11 110 15 SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM A / D or D / A Conv. I / O CPU CC-Link INTERFACE SERIAL TRANSMISSION LINE Modular Jack for Factory Calibration MODULAR JACK ROTARY SW INDICATOR LED U(+) V(–) POWER FG1 8 To Other CC-Link Devices Terminator COMMUNICATION MODULE I/O CONNECTOR DA DB DG SLD FG *Attach the terminating resistor when the module is at the termination of a transmission line. To 10-RACK, 18-RACK etc. ■ COMMUNICATION CABLE CONNECTIONS DA DB DG SLD FG MASTER UNIT DA DB DG SLD FG ANALOG I/O MODULE DA DB DG SLD FG I/O UNIT TERMINATOR blue white yellow Specifications are subject to change without notice.