A B C D E F H I J K L M N O P Q R S T UE43-4AR2D2 | UE43-4AR SAFETY RELAYS Illustration may differ
Ordering information
Type Part no. UE43-4AR2D2 6034772 Other models and accessories www.sick.com/UE43-4AR Detailed technical data Safety-related parameters Safety integrity level SIL3 (IEC 61508) SILCL3 (EN 62061) Category Category 4 (EN ISO 13849) Performance level PL e (EN ISO 13849) B10d parameter 3 x 105 switching cycles (AC-15, 230 V, I = 5 A) 2 x 106 switching cycles (DC-15, 230 V, I = 2 A) 7 x 106 switching cycles (DC-13, 24 V, I = 1 A) PFHD (mean probability of a dangerous fail- ure per hour) 1.30 x 10-8 (EN ISO 13849) TM (mission time) 20 years (EN ISO 13849) Stop category 0 (EN 60204-1) Interfaces Connection type Fixed screw terminals Number of enable current (N/O) contacts 4, relevant for safety Electrical data Operating data Voltage supply A1, A2 Output circuit > 25 V AC / 60 V DC, Output cir- cuit ≤ 25 V AC / 60 V DC PELV, PELV or SELV Supply voltage Vs A1, A2 Residual ripple (≤ 2.4 Vpp) 1) Power consumption (≤ 2.8 VA (AC)) (≤ 1.3 W (DC)) Overvoltage category II 1) In DC operation, within the limits of VS.
2 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE43-4AR2D2 | UE43-4AR SAFETY RELAYS Rated insulation voltage Ui 300 V AC Rated impulse withstand voltage Uimp 4 kV Test voltage 2 kV (50 Hz) (EN 60439-1) 1) In DC operation, within the limits of VS. Control voltage: S11 Control voltage 22 V DC (19.2 V DC ... 40 V DC) Control current ≤ 250 mA Input circuits: S12, S52, S22 Input current ≤ 100 mA Cable resistance ≤ 70 Ω Input circuits: S34 Input current 5 mA Cable resistance ≤ 25 Ω Reset time Automatic ≤ 350 ms Electrical output circuits: 13/14, 23/24, 33/34, 41/42 Response time (≤ 10 ms) 1) Number of enable current (N/O) contacts 4, relevant for safety Contact type Positively driven Contact material Silver alloy, gold flashed Switching voltage Enable current contact 5 V AC/DC ... 300 V AC/DC Current-carrying capacity per OSSD Enable current contact 10 mA ... 8 A Usage category AC-15/DC-13 (EN 60947-5-1) Rated operating current (voltage) 4 A (230 V AC) 360 switching cycles/h
4 A (24 V DC) 3600 switching cycles/h
Switching frequency ≤ 3600/h Mechanical life (relay contacts) 1 x 107 switching cycles Electrical life (relay contacts) 1 x 106 switching cycles 1) K1/K2. Mechanical data Dimensions (W x H x D) 22.5 mm x 114 mm x 96.5 mm Weight 0.27 kg Classifications ECl@ss 5.0 27371990 ECl@ss 5.1.4 27371990 ECl@ss 6.0 27371819 2018-09-11 15:13:28 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 3
A B C D E F H I J K L M N O P Q R S T UE43-4AR2D2 | UE43-4AR SAFETY RELAYS ECl@ss 6.2 27371819 ECl@ss 7.0 27371819 ECl@ss 8.0 27371819 ECl@ss 8.1 27371819 ECl@ss 9.0 27371819 ETIM 5.0 EC001449 ETIM 6.0 EC001449 UNSPSC 16.0901 41113704 Dimensional drawing (Dimensions in mm (inch)) Safety relay (3.25) 82.5 (3.67) 93.3 (3.8) 96.5 (1.9) 48.3 (2.63) 66.7 (2.48) (4.24) 107.6 (2.96) 75.3 (0.89) 22.5 (3.69) 93.6 (4.49) 114
4 SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK Online data sheet | 2018-09-11 15:13:28
Subject to change without notice
UE43-4AR2D2 | UE43-4AR SAFETY RELAYS Connection diagram Power Reset CH 1 CH 2 Control-Logic A2 S34 13 23 33 43 14 24 34 44 S21 S11 S12 S52 S22 – + + –+ 2018-09-11 15:13:28 | Online data sheet Subject to change without notice SENS:CONTROL - SAFE CONTROL SOLUTIONS | SICK 5
SICK AG | Waldkirch | Germany | www.sick.com SICK At A GlAnCe SICK is one of the leading manufacturers of intelligent sensors and sensor solutions for industrial applica- tions. A unique range of products and services creates the perfect basis for controlling processes securely and efficiently, protecting individuals from accidents and preventing damage to the environment. We have extensive experience in a wide range of industries and understand their processes and require- ments. With intelligent sensors, we can deliver exactly what our customers need. In application centers in Europe, Asia and North America, system solutions are tested and optimized in accordance with customer specifications. All this makes us a reliable supplier and development partner. Comprehensive services complete our offering: SICK lifetime Services provide support throughout the ma- chine life cycle and ensure safety and productivity. For us, that is “Sensor Intelligence.” WOrldWIde preSenCe: Contacts and other locations – www.sick.com