Part number: 567346 Data sheet Feature Value Dimensions W x L x H 50 mm x 107 mm x 55 mm Type code CPX Device-specific diagnostics Channel-oriented and module-oriented diagnostics Undervoltage/short circuit of modules Diagnostic memory CPU data 32 MB flash

32 MB RAM

400 MHz processor

Configuration support CODESYS V2.3 Parameterization CODESYS V2.3 Additional functions Diagnostic functions RS232 communication function Control elements Rotary switch for RUN/Stop Programming, operating language DE, EN Programming, file handling support yes Baud rate 10/100 bit/s as per IEEE 802.3 (10BaseT) or 802.3u (100BaseTx) Processing time Approx. 200 µs/1 k instruction Data interface RS232 interface Sub-D, 9-pin, socket Galvanically isolated Intrinsic current consumption at nominal operating voltage Typ. 85 mA IP address setting DHCP Via CODESYS Via MMI Function blocks Read CPX module diagnostics CPX diagnostic status Copy CPX diagnostic trace and others Flag 30 kB remanent data

8 MB global data memory

Nominal operating voltage DC load voltage Without pneumatics: 18 ... 30V 24 V With pneumatics type MPA: 18 ... 30 V Nominal operating voltage DC 24 V Power failure buffering 10 ms Programming software CODESYS provided by Festo V2.3 6/14/21 - Subject to change - Festo AG & Co. KG 1/2

Programming language as per IEC 61131-3 KOP AWL ST FUP AS Additionally CFC Program memory 4 MB user program Corrosion resistance class (CRC) 2 - Moderate corrosion stress Storage temperature -20 °C ... 70 °C Relative air humidity 95 % Non-condensing Degree of protection IP65 IP67 Ambient temperature -5 °C ... 50 °C Product weight 155 g Ethernet, number 1 Ethernet, data transmission speed 10/100 Mbit/s Ethernet, supported protocols TCP/IP , EasyIP , Modbus® TCP Ethernet, connector plug RJ45 Socket 8-pin Protocol CODESYS level 2 EasyIP Modbus® TCP TCP/IP Ethernet interface RJ 45 (socket, 8-pin) LED display (bus-specific) TP: link/traffic LED display (product-specific) ERR: PLC runtime error M: modify/forcing active PL: load supply PS: electronics supply, sensor supply RUN: PLC status SF: system fault STOP: PLC status Note on materials RoHS-compliant Housing material PA-reinforced PC 6/14/21 - Subject to change - Festo AG & Co. KG 2/2