Technical content
Features
– 9-pos. D-SUB connector for plugging onto the controller board – Optical fiber connection via F-SMA connectors – 500 kbaud or 2 Mbaud data transmission rate – Optical path diagnostics – Extended diagnostic options – Voltage supply through the INTERBUS interface – Supports paths with optical transmission Please observe the Optical Fiber Installation Guidelines ( D BG BI B SS Y SF O CA S S E M B L Y ) . Figure 1 IBS OPTOSUB-MA/M/R-LK-OPC
1 Diagnostic indicators
2 Threaded joint for the D-SUB connector
3 9-pos. D-SUB male connector
4 Connection for F-SMA connectors
/G31 /G34 /G33 /G35 /G35 /G37 /G31 /G41 /G30 /G30 /G31 /G32 Optical Fiber Converter With a Data Transmission Rate of 500 kbaud or 2 Mbaud
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 2 5571D Connector Pin Assignment Incoming Remote Bus (9-pos. D-SUB)) Outgoing Remote Bus (F-SMA Connectors)) Figure 2 Position of the connectors Pin Signal Designation
1 DO Data, sending direction
2 DI Data, receiving direction
3 GND GND (pin 3 and pin 4 internally
jumpered)4G N D
5 VCCI 5V DC supply, electrically
isolated (is only required for RBST connector detection) 6 /DO Negated data, sending direction 7 /DI Negated data, receiving direction
8 VCC 5 V DC supply
9 RBST Connector detection (pin 5 and
pin 9 are internally jumpered) Connector Direction Wire Color IN Receive data Black OUT Send data Orange /G35 /G35 /G37 /G31 /G41 /G30 /G30 /G33 /G4F /G75 /G74 /G67 /G6F /G69 /G6E /G67 /G20 /G72 /G65 /G6D /G6F /G74 /G65 /G20 /G62 /G75 /G73 /G20 /G52 /G65 /G6D /G6F /G74 /G65 /G20 /G4F /G55 /G54 /G49 /G6E /G63 /G6F /G6D /G69 /G6E /G67 /G20 /G72 /G65 /G6D /G6F /G74 /G65 /G20 /G62 /G75 /G73 /G20 /G52 /G65 /G6D /G6F /G74 /G65 /G20 /G49 /G4E /G49 /G4E /G4F /G55 /G54
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 5571D 3 Local Diagnostic and Status Indicators Des. Color Meaning IB DIAG Green INTERBUS diagnostics ON: Supply voltage present, bus active, no module error Flashing at 0.5 Hz: Supply voltage present, bus not active Flashing at 2 Hz: Supply voltage present, module error (bus can be active or not active) OFF: Supply voltage not present FO1 Yellow Status of the incoming optical fiber path ON: If the previous device has optical path diagnostics, the system reserve of the optical transmission has dropped. OFF: Incoming optical fiber path is OK or the previous device does not have optical path diagnostics.
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 4 5571D Special Features Supports Paths with Optical Transmission
1 Adjustment of optical transmission power:
– Automatic recognition of the control function on other modules – Additional diagnostics for optical transmission
2 Confirmation of optical system quality:
– No need for an optical cable measuring device – Early error detection through I/O error message to the higher-level control or computer system and diagnostic display on the device – Long-term monitoring of the transmission path is possible
3 Optical path diagnostics
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 5571D 5 Installation Figure 3 Connection examples Connecting the Converter to the Controller Board
- Insert the converter into the INTERBUS interface of your controller board. Tighten the two screws manually with a bladed type screwdriver (e.g., SZF 1-0,6X3,5) through the openings above and below the diagnostics display. An external voltage supply is not required for the converter. The converter is supplied via the INTERBUS interface. Connecting Optical Fibers Please refer to the Optical Fiber Installation Guidelines DB GB IBS SYS FOC ASSEMBLY when assembling polymer fiber cables. Recommended F-SMA connector with bending protection: PSM-SET-FSMA/4-KT. Fit both wires of the polymer fiber cables with F-SMA connectors. Plug the F-SMA connectors into the connections provided and secure the connection with the cap nuts. Please note that you must always connect sender and receiver with one another. The label for the optical fiber connection (black arrow/orange arrow) corresponds to the color of the optical fiber cables. Connect the individual optical fiber cables between adjacent terminals according to their color (e.g., orange cable for orange connections). /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G4F /G55 /G54 /G46 /G4F /G20 /G31 /G49 /G42 /G44 /G49 /G41 /G47 /G49 /G4E /G4F /G55 /G54 /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G49 /G4E /G49 /G4E /G54 /G45 /G52 /G42 /G55 /G53 /G37 /G35 /G35 /G37 /G31 /G41 /G30 /G30 /G32 /G49 /G42 /G53 /G20 /G52 /G4C /G20 /G32 /G34 /G20 /G42 /G4B /G20 /G52 /G42 /G2D /G4C /G4B /G32 /G34 /G20 /G56 /G20 /G44 /G43 /G46 /G55 /G53 /G45 /G46 /G55 /G53 /G45 /G49 /G4E /G54 /G45 /G52 /G42 /G55 /G53 /G2D /G53 /G20 /G4D /G6F /G64 /G75 /G6C /G65 /G20 /G49 /G64 /G65 /G6E /G74 /G2E /G3A /G20 /G31 /G38 /G35 /G46 /G55 /G53 /G45 /G49 /G4E /G54 /G45 /G52 /G42 /G55 /G53 /G2D /G53 /G46 /G55 /G53 /G45 /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G49 /G4E /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G4F /G55 /G54 /G49 /G42 /G53 /G20 /G53 /G54 /G20 /G28 /G5A /G46 /G29 /G20 /G32 /G34 /G20 /G42 /G4B /G4D /G2D /G4C /G4B /G2D /G4F /G50 /G43 /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G4F /G55 /G54 /G46 /G4F /G20 /G31 /G49 /G42 /G44 /G49 /G41 /G47 /G49 /G4E /G4F /G55 /G54 /G52 /G45 /G4D /G4F /G54 /G45 /G20 /G49 /G4E /G49 /G4E /G54 /G45 /G52 /G42 /G55 /G53 /G43 /G6F /G6E /G74 /G72 /G6F /G6C /G6C /G65 /G72 /G62 /G6F /G61 /G72 /G64 /G43 /G6F /G6E /G74 /G72 /G6F /G6C /G6C /G65 /G72 /G62 /G6F /G61 /G72 /G64
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 6 5571D Compatibility With Controller Boards You can connect the converter to the following controller boards. Order Designation Order No. Plug-in Converter Remark IBS 24 ETH DSC/I-T 27 22 92 0 yes IBS 24 RFC/486DX/ETH/-T 27 23 00 0 yes IBS ABB DSC/SL/MEMC/I-T 27 22 89 4 yes IBS BA DSC/I-T 27 23 04 2 yes IBS GE 90-70 SC/I-T 27 22 84 9 yes IBS ISA FC/486DX/I-T 27 22 08 5 no IBS ISA FC/DI/I-T 27 25 11 8 no IBS ISA FC/I-T 27 22 02 7 no IBS ISA SC/486DX/I-T 27 23 94 5 no IBS MEA SC/I-T 27 25 59 0 yes IBS PC 104 SC-T 27 21 70 1 – Connection is not present. IBS PC ISA SC/I-T 27 19 23 4 no IBS PLC5 DSC/I-T 27 19 02 7 yes IBS S5 DSC/I-T 27 52 00 0 yes IBS S7 300 DSC-T 27 19 97 5 no IBS ST 24 RFC-T 27 25 52 9 yes Observe the maximum power of the power supply unit used.IBS STME 24 RFC-T 27 25 51 6 yes IBS USC/4-EVA 27 46 25 2 – Connection is not present. IBS VME3H SC/I-T 27 22 86 5 yes IBS VME6H SC/I-T 27 22 85 2 yes IBS VME6H SC/RI/I-T 27 22 83 6 yes IBS S7 400 DSC/I-T 27 19 96 2 yes IBS S7 400 ETH DSC/I-T 27 31 10 2 yes
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 5571D 7 Programming Data Housing Dimensions Figure 4 Dimensions ID code 08 hex Length code 00 hex Process data channel 0 bits Input address area 0 bytes Output address area 0 bytes Parameter channel (PCP) 0 bytes Register length (bus) 0 bytes /G35 /G35 /G37 /G31 /G41 /G30 /G30 /G34 /G49 /G42 /G53 /G20 /G4F /G50 /G54 /G4F /G53 /G55 /G42 /G2D /G4D /G41 /G2F /G4D /G2F /G52 /G2D /G4C /G4B /G2D /G4F /G50 /G43 /G30 /G30 /G30 /G31 /G30 /G32 /G30 /G33 /G30 /G34 /G30 /G35 /G30 /G36 /G30 /G37 /G30 /G38 /G30 /G39 /G31 /G30 /G4F /G72 /G64 /G2E /G20 /G4E /G6F /G2E /G3A /G20 /G32 /G37 /G20 /G33 /G32 /G20 /G36 /G33 /G35 /G4D /G6F /G64 /G75 /G6C /G65 /G20 /G49 /G64 /G65 /G6E /G74 /G2E /G3A /G20 /G30 /G38 /G34 /G32 /G20 /G6D /G6D /G31 /G2E /G36 /G35 /G34 /G22 /G36 /G31 /G20 /G6D /G6D /G32 /G2E /G34 /G30 /G32 /G22 /G33 /G36 /G20 /G6D /G6D /G31 /G2E /G34 /G31 /G37 /G22 /G35 /G32 /G20 /G6D /G6D /G32 /G2E /G30 /G34 /G37 /G22 /G35 /G39 /G20 /G6D /G6D /G32 /G2E /G33 /G32 /G33 /G22 /G36 /G35 /G20 /G6D /G6D /G32 /G2E /G35 /G35 /G39 /G22
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 8 5571D Technical Data General Data Degree of protection IP 20 Ambient temperature Operation: 0 °C to +55°C (32°F to +131°F) Storage: -20°C to +70°C (-4°F to +158°F) Air and creepance distances DIN VDE 0110-1:1989-01 Supply Voltage Nominal voltage 5 V DC Permissible range 4.75 V DC to 5.25 V DC Current consumption IBS OPTOSUB-MA/M/R-LK-OPC 200 mA, maximum IBS OPTOSUB-MA/M/R-LK-OPC-2MBD 220 mA, maximum Permissible line length The module should only be connected directly to the controller board. Surge protection No Protection against polarity reversal No INTERBUS Interface Incoming remote bus 9-pos. D-SUB male connector Differential voltage interface according to RS-485 Outgoing remote bus F-SMA connector Optical fiber (polymer fiber 980/1000 µm) Data transmission rate IBS OPTOSUB-MA/M/R-LK-OPC 500 kbaud IBS OPTOSUB-MA/M/R-LK-OPC-2MBD 2 Mbaud Wavelength 650 nm, typical Optical output power for operation at 0°C to +55°C (32°F to 131°F) -2.0 dBm ≥ Popt ≥ -6.2 dBm Optical output power after voltage reset at 0°C to +55°C (32°F to +131°F) -3.5 dBm ≥ Popt ≥ -7.7 dBm Optical receiver responsivity at 0°C to +55°C (32°F to 131°F) ≤ -20 dBm
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 5571D 9 Optical overrange at 0°C to +55°C (32°F to 131°F) > -2.0 dBm Power reduction resulting from the wavelength drift Taken into consideration System reserve > 3 dBm Bit error rate 10 -9 INTERBUS Interface Optical Fiber Cable Cable type Step index Fiber (core/cladding diameter) 980/1000 µm Numerical aperture 0.47 Attenuation (50 m [164.042 ft.] fiber measured with 660 nm LED source) ≤ 230 dB/km Transmission length between IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) and INTERBUS devices with 50 m (164.042 ft.) system without optical path diagnostics 1 m, minimum, to 35 m (3.281 ft. to 114.829 ft.) Transmission length between IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) and INTERBUS devices with 70 m (229.659 ft.) system or all INTERBUS devices with optical path diagnostics 1 m, minimum, to 50 m (3.281 ft. to 164.042 ft.) Connector type F-SMA standard (type 905 acc. to IEC 60874-2) I/O Error Message MAU error Yes
IBS OPTOSUB-MA/M/R-LK-OPC(-2MBD) 10 5571D © Phoenix Contact 07/2001 Subject to technical modification TNR 90 00 17 6 Phoenix Contact GmbH & Co Flachsmarktstr. 8
32825 Blomberg
+ 49 - 52 35 - 3 00 + 49 - 52 35 - 34 12 00 www.phoenixcontact.com Ordering Data Description Order Designation Order No. Optical fiber converter with a transmission speed of 500 kbaud IBS OPTOSUB-MA/M/R-LK-OPC 27 32 63 5 Optical fiber converter with a transmission speed of 2 Mbaud IBS OPTOSUB-MA/M/R-LK-OPC 2MBD 27 31 45 8 F-SMA connector set for polymer fiber cables with bending protection (4 pieces) PSM-SET-FSMA/4-KT. 27 99 72 0 Polymer fiber cables for use in humid climates, duplex, 980/100 µm, installation PSM-LWL-KDHEAVY-980/1000 27 44 31 9 Polymer fiber cable with increased alternating bending ability (flexible cable tracks, industrial robots) for indoor use PSM-LWL/KDFLEX-980/1000 27 99 74 6 Optical fiber data line: Polymer fiber cable, duplex, 980/1000 µm, red, welding-splash-resistant in standard applications; sold by the meter, cable is not pre-assembled PSM-LWL-RUGGED-980/1000 27 44 32 2 Optical fiber data line (flexible): Polymer fiber cable, duplex, 980/1000 µm, dark red, welding-splash-resistant in standard applications; tested for flexible cable tracks, sold by the meter cable is not pre-assembled PSM-LWL-RUGGED-FLEX-980/ 1000 27 44 33 5 Optical Fiber Installation Guidelines DB GB IBS SYS FOC ASSEMBLY 94 23 43 9 Bladed type screwdriver SZF 1-0,6X3,5 12 04 51 7