FC-2224 GAMEWELL-FCI | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

DESCRIPTION

The FC-2224 Fire Alarm Control panel is a proven, versa- tile, two-zone control with space to accommodate an op- tional digital communicator. It meets the requirements of NFPA Standard 72 for Central Station, Protected Premises, and Remote (DACT) Supervising Station Fire Alarm Sys- tems. It is Listed to UL Standard 864, inherently power lim- ited and meets all UL transient immunity requirements. The many features of the FC-2224 control provide a cost effective approach to systems design, and allow a great de- gree of flexibility in one enclosure. These features include two (2) Class B, Style B initiating circuits and two (2) Class B, Style Y notification appliance circuits, rated at 1.25 amps each. Notification appliance circuits can be configured as silenceable or non-silenceable. DIP switch programming is used throughout, eliminating the need for computers and associated software. A time delay of 30, 60, or 90 seconds is available for waterflow switches. The control is housed in a red steel enclosure with a win- dow offering a view of LEDs displaying the status of vital functions. The surface mounted enclosure, with its slim ap- pearance (3 3/8-inch depth) is designed to blend with any en- vironment. Space is available for two (2) B-7R batteries. Supervision of vital components, plug-in modules, func- tional switches and standby batteries is provided. The optional digital communicator includes a wide range of selectable transmission formats to communicate to most central stations. Other features of the communicator are: A line-active indicator for each of two phone lines, “Kiss-Off” signal LED, dual “low telephone voltage detect” circuitry and programmable event codes per format. The FC-2224 is programmable for AC power loss delay required for DACT operation. An optional serial annunciator driver allows remote alarm annunciation to as many as four (4) Model FC-2866 remote annunciators. Other optional modules include the FC-2880 I/O module which provides 34 pre-defined open collector outputs that can be used to drive LEDs or relays. AGENCY APPROV ALS UL S1869 CSFM Approved

FEATURES

/c183Inherently Power Limited /c183DIP Switch Programming /c183Choice of Output Patterns Including ANSI S3.41 /c183Programmable Time Delay for Waterflow Switches /c183Periodic Trouble Reminder /c183Walk Test Feature /c183Optional Digital Communicator with Multiple Reporting Formats /c183Serial Annunciator Output (Optional) /c183Surface Mount Technology FC-2224 TWO-ZONE PANEL CONVENTIONAL FIRE ALARM CONTROL

16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099

9020-0483/Ver. 1.5 Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control In- struments, Inc. for their use. Specifications subject to change without notice. © 2000 All Rights Reserved An ISO 9001 Certified Company

CHARACTERISTICS AND DIMENSIONS Supervisory current \` .050 amp. Alarm current .250 amp. Operating temperature 32 - 120o F (0 - 49o C) Relative humidity 85% (non-condensing) Dimensions 15 1/8”H x 12 13/16” W x 3 3/8” D (38.4 cm x 33 cm x 8.5 cm)

ORDERING INFORMATION

Part Number Model Description 150-00001 FC-2224 Two-zone Control, 120 V AC 151-00001 FC-2884 Serial Driver Module 151-00003 FC-2880 /c197 Annunciator Driver Module 151-00004 FC-2866 /c197 Remote Zone Annunciator w/reset and silence switches 151-00005 FC-2104 Digital Alarm Communicator Transmitter 151-00019 2190 Cabinet for FC-2104 DACT (optional) 151-00017 5230 Programmer for FC-2104 DACT 151-00018 7860 Cable w/spade lugs for connection to Telco RJ31X plug. (Optional) 151-00020 Quick connect cable to connect

5230 Programmer to FC-2104 DACT

151-00007 FC-2224PC Replacement PC board

7628 UL Listed EOL resistor

151-00011 120 V AC Transformer (replacement) 151-00012 230 V AC, 50 Hz Transformer (optional) /c197Requires one (1) FC-2884 FC-2104 DACT reporting formats are: SIA 8 or 20 SK 3/1 1,400 or 2,300 Hz Contact ID SK 4/2 BFSK 1,400 or 2,300 Hz FC-2880 Annunciator Driver Module FC-2866 Remote Zone Annunciator FC-2104 Digital Alarm Communicator Transmitter FC-2884 Serial Driver Module