Technical content
Power Entry Modules with Line Filter 5220https://www.schurter.com /PG06 EMC Products IEC Appliance Inlet C14 with Filter, Fuseholder 1- or 2-pole Screw-on from front side with 2-pole fuseholder Snap-in mounting from front side with 2-pole fuseholder See below: Approvals and Compliances C14 70° C
Description
- Panel mount : Snap-in or screw-on mounting front side - 3 Functions : Appliance Inlet Protection class I , Fuseholder for fuse-links 5 x 20 mm 2-pole , Line filter in standard and medical version - Quick connect terminals 6.3 x 0.8 mm Unique Selling Proposition - Ultra-compact design - Recessed faston connectors - High quality filter case made of stainless steel - Highly resistant since potted filter Characteristics - All single elements are already wired - Plug removal necessary for fuse-link replacement - Suitable for use in medical equipment according to IEC/UL 60601-1 (1 MOOP , 1 MOPP) For applications according IEC/UL 62368-1 we recommend variants with bleed resistor References Alternative: version without line filter 6220 Alternative: version with V-Lock KFA Weblinks pdf data sheet, html datasheet, General Product Information, Approvals, Distributor-Stock-Check, Accessories, Detailed request for product Technical Data Ratings IEC 1 - 10 A @ Ta 40 °C / 250 VAC; 50 Hz Ratings UL/CSA 1 - 10 A @ Ta 40 °C / 250 VAC; 60 Hz Leakage Current standard < 0.5 mA (250 V / 60 Hz) medical < 5 µA (250 V / 60 Hz) Dielectric Strength > 1.7 kVDC between L-N > 2.7 kVDC between L/N-PE Test voltage (2 sec) Allowable Operation Tempe- rature -25 °C to 85 °C Climatic Category 25/085/21 acc. to IEC 60068-1 IP-Protection front side IP40 acc. to IEC 60529 Protection Class Suitable for appliances with protection class I acc. to IEC 61140 Terminal Quick connect terminals 6.3 x 0.8 mm Panel Thickness S Screw: max 8 mm Mounting screw torque max 0.5 Nm Snap-in: 0.8 mm to 3 mm Material: Housing Thermoplastic, black, UL 94V-0 Appliance inlet/-outlet C14 acc. to IEC 60320-1, UL 60320-1, CSA C22.2 no. 60320-1 (for cold conditions) pin-temperature 70 °C, 10 A, Protection Class I Fuseholder 2-pole, Shocksafe category PC2 acc. to IEC 60127-6, for fuse-links 5 x 20 mm Rated Power Acceptance @ Ta 23 °C 5 x 20: 1.6 W (2-pole) Power Acceptance @ Ta > 23°C Admissible power acceptance at higher ambient temperature see derating cur- ves Line Filter Standard and Medical Version, IEC 60939-2, UL 60939-3, CSA C22.2 no. Technical Details MTBF > 2'300'000 h acc. to MIL-HB-217 F Approvals and Compliances Detailed information on product approvals, code requirements, usage instructions and detailed test conditions can be looked up in Details about Approvals SCHURTER products are designed for use in industrial environments. They have approvals from independent testing bodies according to national and international standards. Products with specific characteristics and requirements such as required in the automotive sector according to IATF 16949, medical technology according to ISO 13485 or in the aerospace industry can be offered exclusively with customer-specific, individual agree- ments by SCHURTER.
Power Entry Modules with Line Filter5220 https://www.schurter.com /PG06 EMC Products Approvals The approval mark is used by the testing authorities to certify compliance with the safety requirements placed on electronic products. Approval Reference Type: 5220 Approval Logo Certificates Certification Body Description VDE Approvals VDE Certificate Number: 101307 UL Approvals UL UL File Number: E495089 Product standards Product standards that are referenced Organization Design Standard Description Designed according to IEC 60320-1 Appliance couplers for household and similar general purposes Designed according to IEC 60939-2 Passive filters for suppressing electromagnetic interference Designed according to IEC 60127-6 Miniature fuses. Part 6. Fuse-holders for miniature fuse-links Designed according to UL 60320-1 Standard for Attachment Plugs and Receptacles Designed according to UL 60939-3 Electromagnetic interference filters Designed according to CSA C22.2 no. 60320-1 General Use Receptacles, Attachment Plugs, and Similar Wiring Devices Designed according to CSA C22.2 no. 8 Electromagnetic interference (EMI) filters Application standards Application standards where the product can be used Organization Design Standard Description Designed for applications acc. IEC/UL 62368-1 Audio/video, information and communication technology equipment - Part 1: Safety requirements Designed for applications acc. IEC 60601-1 Medical electrical equipment - Part 1: General requirements for basic safety and essential performance Designed for applications acc. IEC 60335-1 Safety of electrical appliances for household and similar purposes. Meets the requirements for appliances in unattended use. This includes the enhanced requirements of glow wire tests acc. to IEC 60695-2-11 or -12 & -13. Compliances The product complies with following Guide Lines Identification Details Initiator Description CE declaration of conformity SCHURTER AG The CE marking declares that the product complies with the applicable requirements laid down in the harmonisation of Community legislation on its affixing in accordance with EU Regulation 765/2008. UKCA declaration of conformity SCHURTER AG The UKCA marking declares that the product complies with the applicable requirements laid down in the British Amendment of Regulation (EC) 765/2008. RoHS SCHURTER AG Directive RoHS 2011/65/EU, Amendment (EU) 2015/863 China RoHS SCHURTER AG The law SJ / T 11363-2006 (China RoHS) has been in force since 1 March 2007. It is similar to the EU directive RoHS. REACH SCHURTER AG On 1 June 2007, Regulation (EC) No 1907/2006 on the Registration, Evaluation, Authorization and Restriction of Chemicals 1 (abbreviated as "REACH") entered into force. White Paper Glow wire test SCHURTER AG Meets the requirements of IEC 60335-1 for appliances in unattended use. This includes the enhanced requirements of glow wire tests acc. to IEC Medical Equipment SCHURTER AG Suitable for use in medical equipment according to IEC/UL 60601-1 (1 MOOP , 1 MOPP)
Power Entry Modules with Line Filter 5220https://www.schurter.com /PG06 EMC Products Dimension [mm] Screw-on mounting type 5220 ø 6.3x90˚ ø 3.5 +0.50 0max.R3 +0.50 043.6 5 2.5 ±0.2 9 Snap-in mounting type 5220 +0.20 0max.R3 +0.20 043.8 5 3.5 9±0.2 Technical Data of Filter-Components Rated Current [A] Filter-Type Inductances L [mH] Capacitance CX [nF] Capacitance CY [nF] R [MΩ] 1 Standard version 2 x 11 47 2.2 - 2 Standard version 2 x 4 47 2.2 - 4 Standard version 2 x 1.6 47 2.2 - 6 Standard version 2 x 0.7 47 2.2 - 8 Standard version 2 x 0.6 47 2.2 - 10 Standard version 2 x 0.4 47 2.2 -
1 Medical Version (M5) 2 x 11 47 - 1
2 Medical Version (M5) 2 x 4 47 - 1
4 Medical Version (M5) 2 x 1.6 47 - 1 6 Medical Version (M5) 2 x 0.7 47 - 1 8 Medical Version (M5) 2 x 0.6 47 - 1 10 Medical Version (M5) 2 x 0.4 47 - 1 10 Standard and Medical Version 2 x 11 47 2.2 1
Power Entry Modules with Line Filter5220 https://www.schurter.com /PG06 EMC Products Diagrams
5220 Standard Version
L PE N Cx Cy Cy PE’ 1) 2)F1 1) Line 2) Load
5220 Medical Version (M5)
L PE N Cx PE’ 1) 2)F1 R 1) Line 2) Load Derating Curves 2-pole Admissible power acceptance in Watt 02 04 06 08 0 100 0.2 0.0 I = << In I = 0.7 In I = 1.0 In 1.6 0.6 0.4 0.8 1.2 1.0 1.4 Ambient air temperature Ta °C Attenuation Loss - - - - 50Ω differential mode _____ 50Ω common mode Standard version 1 A 2 A 4 A 6 A 8 A 10 A
Power Entry Modules with Line Filter 5220https://www.schurter.com /PG06 EMC Products Medical version (M5) 1 A 2 A 4 A 6 A 8 A 10 A All Variants Rated Current [A] Filter-Type Panel mounting Fuseholder Order Number 1 Standard version Snap-in 2-pole 5220.0143.1 █ 2 Standard version Snap-in 2-pole 5220.0243.1 █ 4 Standard version Snap-in 2-pole 5220.0443.1 6 Standard version Snap-in 2-pole 5220.0643.1 █ 8 Standard version Snap-in 2-pole 5220.0843.1 10 Standard version Snap-in 2-pole 5220.1043.1 █ 1 Standard version Screw 2-pole 5220.0123.1 2 Standard version Screw 2-pole 5220.0223.1 █ 4 Standard version Screw 2-pole 5220.0423.1 █ 6 Standard version Screw 2-pole 5220.0623.1 █ 8 Standard version Screw 2-pole 5220.0823.1 10 Standard version Screw 2-pole 5220.1023.1 █ 1 Medical Version (M5) Snap-in 2-pole 5220.0143.3 2 Medical Version (M5) Snap-in 2-pole 5220.0243.3 █ 4 Medical Version (M5) Snap-in 2-pole 5220.0443.3 █ 6 Medical Version (M5) Snap-in 2-pole 5220.0643.3 █ 8 Medical Version (M5) Snap-in 2-pole 5220.0843.3 10 Medical Version (M5) Snap-in 2-pole 5220.1043.3 █ 1 Medical Version (M5) Screw 2-pole 5220.0123.3 █ 2 Medical Version (M5) Screw 2-pole 5220.0223.3 █ 4 Medical Version (M5) Screw 2-pole 5220.0423.3 █ 6 Medical Version (M5) Screw 2-pole 5220.0623.3 █ 8 Medical Version (M5) Screw 2-pole 5220.0823.3 10 Medical Version (M5) Screw 2-pole 5220.1023.3 █ █ Most Popular. Availability for all products can be searched real-time:https://www.schurter.com/en/Stock-Check/Stock-Check- SCHURTER Packaging unit 10 Pcs
Power Entry Modules with Line Filter5220 https://www.schurter.com /PG06 EMC Products Accessories 0859.0047 RC320 Rear Cover for Power Entry Module Cord retaining kits Cord retaining strain relief Countersunk, B 4700.0002 Mating Outlets/Connectors Category / Description Appliance Outlet Overview complete 4787, Mounting: Screw-on mounting, Appliance Outlet: IEC Solder terminals, 10 A, Suitable for appliances with pro- tection class I 4787 4788, Mounting: Snap-in version, Appliance Outlet: IEC Solder / Quick Connect, 10 A, Suitable for appliances with protection class I 4788 IEC Appliance Outlet F or H, Screw-on Mounting, Front Side, Solder, PCB or Quick-connect Terminal 5091 Connector Overview complete
4782 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13 4782
4785 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13 4785
4300-06 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C13 4300-06
4781 Mounting: Power Cord, Cable, Connector: IEC C15 4781
4784 Mounting: Power Cord, 3 x 1 mm² / 3 x 18 AWG, Cable, Connector: IEC C15 4784
... The specifications, descriptions and illustrations indicated in this document are based on current information. All content is subject to modifications and amendments. Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability and test each product selected for their own applications. 04.01.2022