F402 GAMEWELL-FCI | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 2

Technical content

Features

  • Two Style B (Class B) Initiating Device Circuits (IDCs).
  • One Style Y (Class B) Notification Appliance Circuit (NAC).
  • 24 VDC.
  • NAC synchronization features: – Provides synchronization of standard ANSI audible signals as required by NFPA 72 – Provides synchronization of ADA compliant strobes per NFPA 72 (4-4.4.1). – Selectable for System Sensor, Wheelock, and Gentex protocols. – Selective Silence feature allows manual silencing of horns while strobes continue to flash on the same NAC.
  • Silent or Audible Walk Test operation mode commanded from the front keypad, with automatic return to normal after one hour of inactivity.
  • Alarm verification selectable per zone.
  • Each zone may be programmed for supervisory or fire; each zone has separate red and yellow LEDs.
  • Disable switches provided for each zone.
  • NACs programmable for: Silence Inhibit, Auto Silence, Strobe Synchronization, Selective Silence (horn/strobe mute), Temporal or Steady signal, Silenceable or Nonsilenceable.
  • Form-C Alarm and Trouble relays.
  • 3.0 amps total usable current.
  • Optional dress panel (P/N DP-FLEX).
  • Piezo sounder for alarm, trouble, supervisory, and maintenance.
  • Control buttons: ACK (Acknowledge), Alarm Silence, Reset, Walktest, Zone Enable/Disable (one per zone).
  • LED indicators: Fire Alarm (one per zone), Supervisory (one per zone), Trouble (one per zone), Maintenance (one per zone), AC Power, NAC Disable, Zone Disable, NAC Fault, System Trouble, Power Trouble, Walktest, Alarm Silence, Earth Fault (on circuit board), Battery Fault (on circuit board), Charger Fault (on circuit board). Listings Listings and approvals below apply to the basic Flex 402 panel. In some cases, certain modules may not be listed by certain approval agencies, or listing may be in process. Consult factory for latest listing status.
  • UL Listed: file S521.
  • CSFM approved: file 7165-1288-180.
  • MEA approved: file 366-04-E. Flex 402 Two-Zone Fire Alarm Control Panel g2402ph1.jpg

Flex 402 Two-Zone FACP CS-2402 09/01/06Page 2 of 2 Specifications and wiring information are provided for information only and are believed to be accurate. Gamewell-FCI assumes no responsibility for their use. Data and design are subject to change without notice. Installation and wiring instructions shipped with the product shall always be used for actual installation. For more information, contact Gamewell-FCI. Gamewell-FCI

12 Clintonville Road

Northford, CT 06472-1610 Phone: 203-484-7161 Fax: 203-484-7118 www.gamewell-fci.com A Honeywell Company © 2006 Gamewell-FCI Specifications AC power, TB8 120 VAC, 50/60 Hz, 2.3 A. Wire size: minimum 14 AWG (2.0 mm²) with 600 V insulation. Battery (sealed lead-acid only), J8 Maximum charging circuit: normal flat charge 27.6 VDC @ 0.8 A. Maximum battery charger capacity: 18 AH battery. Two 7 AH batteries can be housed in the FACP cabinet. Larger batteries require a separate battery box such as the BB-17F. Initiating device circuits, TB3 Alarm zones 1&2. Power-limited circuitry. Operation: all zones Style B (Class B). Normal operating voltage: nominal 22 VDC. Alarm current: 15 mA minimum. Standby current: 4 mA. Short circuit current: 40 mA maximum. Maximum loop resistance: 100 ohms. End-of-line resistor: 4.7K ohm, 1/2 watt (P/N 71252). Notification appliance circuits, TB2 One NAC on Flex 402. Power-limited circuitry. Normal operating voltage: nominal 24 VDC. Maximum signaling current: 2.5 A total with standard transform. End-of-line resistor: 4.7K ohm, 1/2 watt (P/N 71252). Form-C relays Trouble relay TB5 (fail-safe). Alarm relay TB6. Contact ratings: 2.0 A @ 30 VAC (resistive). Auxiliary outputs Resettable power, TB1 Power-limiting circuitry. Operating voltage: nominal 24 VDC. Maximum available current: 500 mA, appropriate for powering four-wire smoke detectors. Note: Total current for resettable power and one NAC must not exceed 3 A for the Flex 402. Cabinet dimensions Door: 15.342" (38.97 cm) high x 14.677" (37.28 cm) wide x 0.375" (0.95 cm) deep. Backbox: 15.0" (38.10 cm) high x 14.5" (36.83 cm) wide x 3.0" (7.62 cm) deep. Backbox Mounting The cabinet can be surface-mounted. The door is removable during installa- tion by opening and lifting it off the hinges. The cabinet mounts using two key slots at the top of the backbox and two additional 0.250" diameter holes at the bottom.

Ordering Information

F402 Two-zone conventional FACP . BB-17F Battery box, required to house two batteries greater than 7 AH, to a maximum of 18 AH. DP-FLEX Dress panel. TR-1-R Trim ring for semi-flush mounting. 52194 Flex 402 Installation and Maintenance Manual. i³™ is a trademark and Gamewell® is a registered trademark of Honeywell International Inc.