MODEL: 49AV2 49AV2 SPECIFICATIONS ES-9333 Rev.9 Page 1/5 http://www.m-system.co.jp/ Bargraph Indicators 49 Series BARGRAPH INDICATING ALARM Functions & Features
- Bargraph and digital displays
- DIN size
- Easy-to-read tri-color LED indicator Typical Applications
- Indicator for various signals
- Available to use alarm with display 60 80 100 V SET MODE M-SYSTEM HH H L LL SPAN POINT ZERO mm (inch) 117(4.61) (3.78) 96(3.78) MODEL: 49AV2-[1]W1[2]-[3]
ORDERING INFORMATION
- Code number: 49AV2-[1]W1[2]-[3] Specify a code from below for each of [1] through [3]. (e.g. 49AV2-4W13-M)
- Special input range (For codes Z & 0)
- Digital meter scale (e.g. 0.0 – 150.0)
- Use Ordering Information Sheet (No. ESU-9333). Factory setting will be used if not otherwise specified. [1] ALARM OUTPUT 0: None 2: 2 points 4: 4 points BAR LED COLOR W: 3 colors (red, green, amber) DIGITAL DISPLAY 1: With [2] INPUT Current A: 4 – 20 mA DC (Input resistance 10 Ω) D: 0 – 20 mA DC (Input resistance 10 Ω) G: 0 – 1 mA DC (Input resistance 200 Ω) Z: Specify current (See INPUT SPECIFICATIONS) ( 0 % input must be 0 mA.) Voltage 3: 0 – 1 V DC (Input resistance 1 MΩ min.) 4: 0 – 10 V DC (Input resistance 1 MΩ min.) 5: 0 – 5 V DC (Input resistance 1 MΩ min.) 6: 1 – 5 V DC (Input resistance 1 MΩ min.) 0: Specify voltage (See INPUT SPECIFICATIONS) ( 0 % input must be 0 V.) [3] POWER INPUT AC Power M: 85 – 264 V AC (Operational voltage range 85 – 264 V, 50/60 Hz DC Power R: 24 V DC (Operational voltage range 24 V ±15 %, ripple 10 %p-p max.) GENERAL SPECIFICATIONS Construction: Panel flush mounting Connection: M4 screw terminals Housing material: ABS resin Isolation: Input to alarm output to power Zero adjustment: -10 to +10 % (front) Span adjustment: 90 to 110 % (front) Scale plate: Aluminium (white scale & characters on black base) H & L alarm output delay: 0 sec. (factory setting; fieldselectable between 0 and 15 sec. by 1 sec. increments) Setpoint adjustment 2 points: H [L setpoint ] to 100 % L 0 to [H setpoint] 4 points: HH [H setpoint] to 100 % H [L setpoint] to [HH setpoint] L [LL setpoint] to [H setpoint] LL 0 to [L setpoint] Read rate: 12.5/s Moving average sample number: 4 (factory setting; field selectable among 1, 2, 4, 8 or 16) ■ BARGRAPH LED: 51-segment LED Scale length: 89 mm (3.50”) long, angle 120° Display range: 0 to 100 (scaling function not available) ■ DIGITAL DISPLAYS LED: 7-segment red LED, character 10 mm (.39”) high Number of digits: 4 digits Setting range: -1999 to 9999 (Min. 3 significant digits)
MODEL: 49AV2 49AV2 SPECIFICATIONS ES-9333 Rev.9 Page 2/5 http://www.m-system.co.jp/ Minimum scale value: 120 (3 digits, the decimal point position disregarded) Factory setting: 0.0 to 100.0 Display range: the ranges from -1999 to 9999 and from -10 to +110 % of input span (The indicator blinks while displaying "Lo" when the input is below -10% and "Hi" when the input is over 110%) Decimal point position: 10–1, 10–2, 10–3 or none Zero indication: Higher-digit zeros are suppressed Engineering unit indication: Sticker label attached; %, m, N/m2, m3/h, mm, ℃, Pa, A, pH, m3, Nm3/h, t/h, ℓ/h, kg/h, kPa, abs, ppm, psi, kg/cm2G, N/cm2, lb/h, J, kJ, Nℓ, lbs, Ω, μΩ, 1°, km3/h, Sm3 INPUT SPECIFICATIONS ■ DC Current: 0 – 50 mA DC; input resistor incorporated Minimum span: 1 mA ■ DC Voltage: 0 – 10 V DC Minimum span: 1 V Input resistance: ≥ 1 MΩ OUTPUT SPECIFICATIONS ■ Alarm Output: Relay contact Rated load: 250 V AC @3 A (cos ø = 1)
30 V DC @3 A (resistive load)
Maximum switching voltage: 300 V AC, 50 V DC Maximum switching power: 750 VA, 90 W Minimum load: 5 V DC @100 mA Mechanical life: ≥ 2 × 107 cycles (rate 300 cycles/min.) 0 50 100 GO 0 50 100 L H HH LL GO Input (%) Input (%) L Setpoint H Setpoint H Output L Output (3–4)ON (3–5)ON (3–4)ON (3–5)ONHH Output H Output LL Output L Output
- Alarm Output Code 4 Terminals 3 – 5, 10 – 12 turn on at a loss of power.
- Alarm Output Code 2 Alarm Trip Operation Terminal No. in parentheses (7–14)ON (10–11)ON (10–12)ON (3–6)ON (7–14)ON (10–13)ON (10–11)ON (10–12)ON INSTALLATION Power consumption
- AC: Approx. 7 VA
- DC: Approx. 6 W Operating temperature: 0 to 45°C (32 to 113°F) Operating humidity: 40 to 80 %RH (non-condensing) Mounting: Panel flush mounting Weight: 500 g (1.1 lb) PERFORMANCE in percentage of span Accuracy Bargraph: ±2 % Digital indicator: ±0.5 % Setpoint accuracy Bargraph: ±2 % Digital indicator: ±0.5 % Response time: 0.5 sec. Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength:
2000 V AC @1 minute (input to power)
1500 V AC @ 1 minute (input to alarm output)
1500 V AC @ 1 minute (alarm output to power)
2000 V AC @ 1 minute (input or alarm output or power to
ground)
MODEL: 49AV2 49AV2 SPECIFICATIONS ES-9333 Rev.9 Page 3/5 http://www.m-system.co.jp/ EXTERNAL VIEW 60 80 100 V SETMODE M-SYSTEM HH H L LL SPAN POINT ZERO HH H * SPAN POINT ZERO : Hi / Hi Setting & Indicator : Hi Setting & Indicator : Span Adjust. Indicator : Decimal Point Position Set. Ind. : Zero Adjust. Indicator LL : Lo Setting & Indicator : Lo / Lo Setting & Indicator SET UP DOWN MODE : Setting ENTER Button : UP Button : DOWN Button : MODE Selector Bargraph Digital Meter Note 1: HH, H, L, LL Settings are not available with model 49AV2-0. * “H” and “L” indicators are replaced with “2” and “1” with the 49AV2-0. “2” and “1” determine where the bargraph color changes. Note 2: HH, LL Settings are not available with model 49AV2-2. red Hi or 2 Lo or 1 green amber Hi < Input Hi or 2 Lo or 1 green amber Lo < Input < Hi Hi or 2 Lo or 1 amber Input < Lo Mulit-Color Indication Pattern 1 red Hi or 2 Lo or 1 red red Hi < Input Hi or 2 Lo or 1 green green Lo < Input < Hi Hi or 2 Lo or 1 amber Input < LoPattern 2
MODEL: 49AV2 49AV2 SPECIFICATIONS ES-9333 Rev.9 Page 4/5 http://www.m-system.co.jp/ CONNECTION DIAGRAM INPUT POWER U(+) V(–) INPUT POWER U(+) V(–) Hc Ha Hb Lc La Lb Gc Ga INPUT POWER U(+) V(–) HHa HHb Ha LLa 3 10 Hc, HHc Lc, LLc LLb La Gc Ga
- 49AV2-0
- 49AV2-2 • 49AV2-4 LOAD Inductive Load (Coil) Varistor or CR Circuit DC Powered LOAD Inductive Load (Coil) Diode, Varistor or CR Circuit
- Relay Protection AC Powered U EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 60 80 100 V SETMODE M-SYSTEM HH H L LL SPAN POINT ZERO 96 (3.78) approx. 16 (.63)10 (.39) 91 (3.58) 91 (3.58) 115 (4.53) 14–M4 SCREW PANEL CUTOUT unit: mm L +1 (3.66) 0 (3.62) Panel thickness 1.6 – 5.5 mm where N : number of units
MODEL: 49AV2 49AV2 SPECIFICATIONS ES-9333 Rev.9 Page 5/5 http://www.m-system.co.jp/ Specifications are subject to change without notice.