MODEL: 48V http://www.m-system.co.jp/ 48V SPECIFICATIONS ES-9311 Rev.13 Page 1/5 Bargraph Indicators 48 Series BARGRAPH INDICATOR Functions & Features
- Displaying a process variable in graphic bargraph of 101 LED segments
- Clear LED
- High-density mounting 100
ORDERING INFORMATION
- Code number: 48V-[1][2][3][4]-[5] Specify a code from below for each [1] through [5]. (e.g. 48V-2RRVA-R)
- Special input range (For codes Z & 0)
- Scale (e.g. 0 – 100 %) [1]BARGRAPHS 1: Single 2: Dual [2] LED COLOR R: Red Y: Amber G: Green Dual (left/right) RR: Red / Red YY: Amber / Amber GG: Green / Green RY: Red / Amber RG: Red / Green YR: Amber / Red YG: Amber / Green GR: Green / Red GY: Green / Amber [3] MOUNTING DIRECTION V: Vertical H: Horizontal [4] INPUT Current A: 4 – 20 mA DC (Input resistance 10 Ω) B: 2 – 10 mA DC (Input resistance 20 Ω) C: 1 – 5 mA DC (Input resistance 39 Ω) D: 0 – 20 mA DC (Input resistance 10 Ω) E: 0 – 16 mA DC (Input resistance 12 Ω) F: 0 – 10 mA DC (Input resistance 20 Ω) G: 0 – 1 mA DC (Input resistance 200 Ω) H: 10 – 50 mA DC (Input resistance 3.9 Ω) Z: Specify current (See INPUT SPECIFICATIONS) Voltage 3: 0 – 1 V DC (Input resistance 100 kΩ) 4: 0 – 10 V DC (Input resistance 330 kΩ) 5: 0 – 5 V DC (Input resistance 250 kΩ) 6: 1 – 5 V DC (Input resistance 250 kΩ) 0: Specify voltage (See INPUT SPECIFICATIONS) [5] POWER INPUT AC Power K: 85 – 132 V AC (Operational voltage range 85 – 132 V, 47 – 63 Hz) L: 170 – 264 V AC (Operational voltage range 170 – 264 V, 47 – 63 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±15 %, ripple 10 %p-p max.) GENERAL SPECIFICATIONS Construction: Panel flush mounting Connection: M3 screw terminals (torque 0.6 N·m) Screw terminal: Chromated brass Housing material: ABS resin Isolation: Input 1 to input 2 to power Scale plate: Aluminium (white scale & characters on black base) Scale
- Characters including decimal points: Max. 6 charac. (48V-1, vertical mount.) Max. 4 charac. (48V-2, vertical mount.) Max. 4 charac. (48V-1, horizontal mount.) Max. 4 charac. (48V-2, horizontal mount.)
- Divisions: 22 – 54.9
- Engineering unit: Max. 8 charac. (48V-1, vertical mount.) Max. 5 charac. (48V-2, vertical mount.) Max. 8 charac. (48V-1, horizontal mount.)
MODEL: 48V http://www.m-system.co.jp/ 48V SPECIFICATIONS ES-9311 Rev.13 Page 2/5 Max. 3 charac. (48V-2, horizontal mount.) If there is only one engineering unit with dual bargraph type, the position and maximum number of characters for single type are applied. Bargraph: 101-segment LED, 100 mm (3.96”) long, 1.5 mm (.06”) wide INPUT SPECIFICATIONS ■ DC Current: 0 – 50 mA DC; input resistor incorporated Minimum span: 1 mA 0 % input: 0 mA DC ■ DC Voltage: 0 – 10 V DC Minimum span: 1 V 0 % input: 0 V DC INSTALLATION Power consumption
- AC: Approx. 3.5 VA (single) or 5.5 VA (dual)
- DC: Approx. 2 W (single) or 4 W (dual) Operating temperature: 0 to 50°C (32 to 122°F) Operating humidity: 40 to 80 % RH (non-condensing) Mounting: Panel flush mounting Weight: 290 g (0.64 lbs) for 48V-1, DC powered 320 g (0.71 lbs) for 48V-1, AC powered 340 g (0.75 lbs) for 48V-2, DC powered 370 g (0.82 lbs) for 48V-2, AC powered PERFORMANCE in percentage of span Accuracy: ±1 % ±1 digit Response time: 0.5 sec. Insulation resistance: ≥ 50 MΩ with 500 V DC (input or power to ground) Dielectric strength:
2000 V AC @1 minute (input or power to ground)
1500 V AC @ 1 minute (input to AC power)
500 V AC @ 1 minute (input to DC power)
500 V AC @ 1 minute (input 1 to input 2)
MODEL: 48V http://www.m-system.co.jp/ 48V SPECIFICATIONS ES-9311 Rev.13 Page 3/5 STANDARD SCALE & UNIT EXAMPLES 1.1 1.2 1.29 1.2 1.3 1.2 1.5 1.8 1.99 0 0 0 0 1.5 2.5 2.59 1.5 1.5 2.5 3.5 4.5 5.49 5.5 10.9 1.5 2.5 2.6 Pattern 1 1 .1 ≤ SPAN < 1 .3 22 through 25.9 Span of Scale Range Standard Divisions Standard Scales Pattern 2 1 .3 ≤ SPAN < 2.0 26 through 39.9 Pattern 3 2.0 ≤ SPAN < 2.6 40 through 51 .9 Pattern 4 2.6 ≤ SPAN < 5.5 26 through 54.9 Pattern 5 5.5 ≤ SPAN < 11 .0 27 .5 through 54.9
20 Ratio 20 20 10 5
Enginnering unit : %, °C, Nm 3/h, m 3/h, t/h, km 3/h, kg/h, l/h, Pa, kPa, abs, ppm, pH, psi, kg/cm 2G, N/m 2, N/cm 2, lb/h, J, kJ, Nl, m 3, lbs, Ω, μΩ, 1° Span of Scale Range = (Full Scale – Zero Scale) × 10 n where n = integer (Determine ‘n’ so that the span of scale range is 1 .1 or greater than 1 .1, and smaller than 11 .0.) [Example 1] Scale range 0 to 100 Span of Scale Range = (100 – 0) × 10 -1 = 10 Span of 10 falls into Pattern 5 according to the above table. Number of divisions is calculated from the Span of Scale Range multiplied by the ratio (10 × 5). The scale range 0 to 100 is provided with 50 divisions. [Example 2] Scale range -10 to +10 Span of Scale Range = (10 – (-10)) × 10 -1 = 2 Span of 2 falls into Pattern 3 according to the above table. Number of divisions is calculated from the Span of Scale Range multiplied by the ratio (2 × 20). The scale range -10 to +10 is provided with 40 divisions. ■ DIVISIONS Number of divisions depends upon the scale range. STANDARD SCALES & DIVISIONS (example) Example 1 100 Unit Example 2 Unit
MODEL: 48V http://www.m-system.co.jp/ 48V SPECIFICATIONS ES-9311 Rev.13 Page 4/5 EXTERNAL VIEW 50 40 30 20 10 0 10 20 30 40 50 50 40 30 20 10 0 10 20 30 40 50 m m3/h Tag No. Label ■VERTICAL MOUNTING 50 40 30 20 10 0 10 20 30 40 50 Input 1 Input 1 Input 2 Input 2
- Single ■HORIZONTAL MOUNTING
- Single
- Dual
- Dual m3/h – – – Tag No. Label *Engineering units longer than 3 characters are indicated here. Remark: If there is only one engineering unit with dual bargraph type, the position and maximum number of characters for single bargraph type are applied. CONNECTION DIAGRAM INPUT DC POWER AC POWER U V ■48V-1 INPUT 1 INPUT 2 DC POWER AC POWER U V ■48V-2 EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 144 (5.67) BEZEL 36 (1.42) 41 (1.61) 135 (5.31) 164 (6.46) 9 (.35) 20 (.79) 139 (5.47) 138.1 (5.44) 138.1 (5.44) 144 (5.67) 9.4 (.37) M3 (.12) SCREW BEZEL
MODEL: 48V http://www.m-system.co.jp/ 48V SPECIFICATIONS ES-9311 Rev.13 Page 5/5 PANEL CUTOUT unit: mm 139.5 L 139.5 164 min. L Note 1. A bezel is required between units for high-density mounting. Note 2. Observe at the minimum of 5 cm above and below the units for heat dissipation. Note 1. A bezel is required between units for high-density mounting. L = (38 x n) (n: number of units) (n: number of units) ■ VERTICAL MOUNTING ■ HORIZONTAL MOUNTING Panel thickness: 1.6 – 5.5 mmPanel thickness: 1.6 – 5.5 mm 139.5 Specifications are subject to change without notice.