Technical content
The engineer's choice
1 General
Rotational direction looking at rotor clockwise Airflow direction Air intake over struts Bearing system Sleeve bearing Mounting position any Balancing grade 2,5
2 Mechanics
2.1 General
Width 119,0 mm Height 119,0 mm Depth 38,0 mm Diameter 0,0 mm Weight 0,520 kg Housing material Metal Impeller material Metal Max. torque when mounted across both mounting flanges wire outlet corner: 160 Ncm remaining corners: 160 Ncm Screw size ISO 4762 - M3 degreased, without an additional brace and without washer
2.2 Connections
Electrical connection Plug Length of lead wire see drawing Tolerance Length of tube see drawing Tolerance Wire gauge (AWG) Insulation diameter Plug see drawing Contact see drawing
3 Operating Data
3.1 Electrical Operating Data
conditions: Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; Motor axis horizontal;warm-up time before measuring 5 minutes (unless otherwise specified). In the intake and outlet area should not be any solid obstruction within 0,5 m. ∆p = 0: corresp. to free air flow (see section 3.4) I: corresp. to RMS line current Features Condition Symbol Values Frequency ∆p = 0 f 50 Hz 60 Hz Nominal voltage ∆p = 0 UN 115,0 V 115,0 V Tolerance Power consumption ∆p = 0 P 10,0 W 9,0 W Tolerance +- 10,0 % +- 10,0 % Speed ∆p = 0 n 1.850 1/min 1.700 1/min Tolerance +- 14,0 % +- 14,0 %
3.2 Operating Data - Electrical Interface -Output
3.3 Electrical Features
Locked rotor protection Impedance Locked rotor current at Un
3.4 Aerodynamic
conditions: Measured with a double chamber intake rig acc. to DIN EN ISO 5801. Normal air density = 1,2 kg/m3; Temperature 23°C +/- 3°C; In the intake and outlet area should not be any solid obstruction within 0,5 m. The information is only valid under the specified test conditions and may be changed by the installation conditions. If there are deviations from the standard test conditions, the characteristic values must be checked under the installed conditions. a.) Operation condition: 1.850 1/min at free air flow Frequency: 50 Hz Max. free-air flow (∆p = 0 / = max.) 102,0 m3/h Max. static pressure (∆p = max. / =0) 26 Pa b.) Operation condition: 1.700 1/min at free air flow Frequency: 60 Hz Max. free-air flow (∆p = 0 / = max.) 95,0 m3/h Max. static pressure (∆p = max. / =0) 19 Pa
3.5 Sound Data
conditions: Sound pressure level: 1 Meter distance between microphone and the air intake. Sound power level: Acc. to DIN 45635 part 38 (ISO 10302) Measured in a semianchoic chamber with a background noise level of Lp(A) < 5 dB(A) For further measurement conditions see section 3.4 a.) Operation condition: 1.850 1/min at free air flow Frequency: 50 Hz Optimal operating point 50,0 m3/h @ 13 Pa Sound power level at the optimal operating point 4,4 bel(A) Sound pressure level at free air flow, measured in rubber bands 33,0 dB(A) b.) Operation condition: 1.700 1/min at free air flow Frequency: 60 Hz Optimal operating point 44,0 m3/h @ 10 Pa Sound power level at the optimal operating point 4,5 bel(A) Sound pressure level at free air flow, measured in rubber bands 34,0 dB(A)
4 Environment
4.1 General
Min. permitted ambient temperature TU min. -10 °C / 50 Hz -10 °C / 60 Hz Max. permitted ambient temperature TU max. 70 °C / 50 Hz 75 °C / 60 Hz Min. permitted storage temperature TL min. -40 °C Max. permitted storage temperature TL max. 80 °C
4.2 Climatic requirements *)
Humidity requirements humid heat, constant; according to DIN EN 60068-2- 78, 14 days Water exposure None Dust requirements None Salt fog requirements None *) Permittet application area: The product is intended for use in sheltered rooms with controlled temperature and controlled humidity. Directly exposure to water must be avoided. Pollution degree 1 (according DIN EN 60664-1) There is either no pollution or it occurs only dry, non-conductive pollution. The pollution has no negative impact.
5 Safety
5.1 Electrical Safety
DIN EN 60950 (VDE 0805) and DIN EN 60335 (VDE 0700) A.) Type test Measuring conditions: After 48h of storage at 95% R.H. and 25°C. No arcing or breakdown is allowed! All connections together to ground. 1000 VAC / 1 Min. B.) Routine test Measuring conditions: At indoor climate. No arcing or breakdown is allowed! All connections together to ground. 1500 VAC / 1 Sec. Isolation resistance Measuring conditions: After 48h of storage at 95% R.H. and 25°C measured with U=500 VDC for 1 min. RI > 50 MOhm clearance / creepage distance 2,0 mm / 1,1 mm Protection class I
5.2 Approval Tests
UL Yes / UL507, Electric Fans VDE Yes / Approval acc. to EN 60950 (VDE 0805) - Information technology equipment CSA Yes / C22.2 No. 113 Fans and Ventilators CCC Yes / GB 12350 Safety Requirements for small Power Motors The approval tests are observed to: U approval max.: 115 V / f: 60 Hz @ TU approval max.: 75 °C
6 Reliability
6.1 General
Life expectancy L10 at TU = 40 °C 57.500 h / 50 Hz 60.000 h / 60 Hz Life expectancy L10 at TU max. 27.500 h / 50 Hz 27.500 h / 60 Hz