47LAC MSYSTEM | Alldatasheet

Document overview

  • Manufacturer or author: Provided By ALLDATASHEET.COM(FREE DATASHEET DOWNLOAD SITE)
  • PDF pages: 7

Technical content

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 1/7 https://www.m-system.co.jp/ Digital Panel Meters 47 Series AC INPUT DIGITAL PANEL METER (4½ digit, LED display type, true RMS sensing) Functions & Features

  • 4 1/2 digit AC input digital panel meter
  • 1/8 DIN size
  • Moving average function to suppress the display flickering
  • Max. and Min. value display
  • IP66 front panel
  • Separable terminal block
  • Rear terminal cover for safety strapped to the meter Alar m/ Scale/ Max/Min Shift Up Zro Spn D/P Tch Fnc Min Max HH H P L LL (1.89) mm (inch) 96 (3.78) 98.5 (3.88) MODEL: 47LAC-[1][2][3][4]-[5][6]

ORDERING INFORMATION

  • Code number: 47LAC-[1][2][3][4]-[5][6] Specify a code from below for each of [1] through [6]. (e.g. 47LAC-101G-M2/Q)
  • Specify the specification for option code /Q (e.g. /C01/S01/SET) [1] INPUT 1: AC current 2: AC voltage [2] DC OUTPUT 0: Without Current A: 4 – 20 mA DC (Load resistance 550 Ω max.) D: 0 – 20 mA DC (Load resistance 550 Ω max.) Voltage 4: 0 – 10 V DC (Load resistance 10 kΩ min.) 5: 0 – 5 V DC (Load resistance 5000 Ω min.) 6: 1 – 5 V DC (Load resistance 5000 Ω min.) 4W: -10 – +10 V DC (Load resistance 10 kΩ min.) [3] ALARM OUTPUT 0: None 1: N.O. relay contact, 4 points 2: SPDT relay contact, 2 points [4] DISPLAY COLOR R: Red YR: Orange G: Green BG: Bluegreen B: Blue W: White [5] POWER INPUT AC Power M2: 100 – 240 V AC (Operational voltage range 85 – 264 V, 50/60 Hz) DC Power R: 24 V DC (Operational voltage range 24 V ±10 %, ripple 10 %p-p max.) P: 110 V DC (Operational voltage range 85 – 150 V, ripple 10 %p-p max.) [6] OPTIONS blank: none /Q: With options (specify the specification) SPECIFICATIONS OF OPTION: Q (multiple selections) COATING (For the detail, refer to M-System's web site.) Moving parts and indicators are not coated. /C01: Silicone coating /C02: Polyurethane coating /C03: Rubber coating TERMINAL SCREW MATERIAL /S01: Stainless steel EX-FACTORY SETTING /SET: Preset according to the Ordering Information Sheet (No. ESU-9511) GENERAL SPECIFICATIONS Construction: Panel flush mounting Degree of protection: IP66; applicable to the front of the panel meter mounted according to the specified panel cutout Connection: M3 separable screw terminal (torque 0.6 N·m) Screw terminal: Nickel-plated steel (standard) or stainless steel Housing material: Flame-resistant resin (gray) Isolation: Input to DC output to HH output or H output to L output or LL output to power Input waveform RMS sensing: Up to 15 % of 3rd harmonic content Setting: (Front button)
  • Scaled range

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 2/7 https://www.m-system.co.jp/

  • Input type
  • Alarm setpoint
  • Hysteresis (deadband)
  • Moving average
  • Others (Refer to the instruction manual for details) Read rate: 40 times/sec. (25 msec.) Averaging: None or moving average Lockout setting: Prohibiting certain operations; protecting settings DISPLAY Display: 16 mm (.63) high, 4 ½ digits, 7-segment LED Display range: -19999 to 19999 Decimal point position: 10–1, 10–2, 10–3, 10–4 or none Zero indication: Higher-digit zeros are suppressed. Over-range indication: ‘-19999’ or ‘19999’ blinking for display values out of the scaled range. ‘S.ERR’ and ‘Max’ blinking when the input signal is out of the usable range. Alarm status indication LL indicator: Green turns on when the LL alarm is tripped. L indicator: Green turns on when the L alarm is tripped. H indicator: Red turns on when the H alarm is tripped. HH indicator: Red turns on when the HH alarm is tripped. P indicator: Amber turns on when none of the other alarms is tripped. Note: Only ‘P’ turns on with no-alarm-output type. ‘LL’ or ‘HH’ does not turn on with dual-alarm-output type. All setpoints can be independently set either for Hi or Lo alarm trip. Function indicators: Zro, Spn, D/P, Tch, Fnc, Min, Max Display mode status and operation status, amber ON or blink Engineering unit indication: Sticker label attached DC, AC, mV, V, kV, μA, mA, A, kA, mW, W, kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ, cm, mm, m, m/sec, mm/min, cm/min, m/min, m/h, m/s2, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m3, m3/sec, m3/min, m3/h, Nm3/h, N·m, N/m2, g, kg, kg/h, N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J, kJ, MJ, rpm, sec, min, min-1, pH, %, ppm, etc. INPUT SPECIFICATIONS Frequency: 40 Hz – 1 kHz Overload capacity: 200 % of the selected measuring range Default value AC current input: Measuring range 0 – 200 mA AC voltage input: Measuring range 0 – 10 V ■ INPUT CODE: 1 TYPE IND MEASURING RANGE OPERATIONAL RANGE INPUT IMPEDANCE A2 0 – 2 mA 0 – 2.2 mA 100 Ω A20 0 – 20 mA 0 – 22 mA 1 Ω A200 0 – 200 mA 0 – 220 mA 1 Ω ■ INPUT CODE: 2 TYPE IND MEASURING RANGE OPERATIONAL RANGE INPUT IMPEDANCE V0.1 0 – 0.1 V 0 – 0.11 V ≥ 100 kΩ V1 0 – 1 V 0 – 1 .1 V ≥ 100 kΩ V10 0 – 10 V 0 – 11 V ≥ 1 MΩ OUTPUT SPECIFICATIONS ■ DC Output
  • DC Current Operational range: -5 – +105 %
  • DC Voltage Operational range: -5 – +105 % ■ Alarm Output: Relay contact Rated load: 250 V AC @ 3 A (cos ø = 1)

30 V DC @ 3 A (resistive load)

Maximum switching voltage: 250 V AC, 30 V DC Maximum switching power: 750 VA, 90 W (resistive load) Minimum load: 5 V DC @ 10 mA Mechanical life: ≥ 5 × 106 cycles (rate 180 cycles/min.) INSTALLATION Power consumption

  • AC: Approx. 6.5VA
  • DC: Approx. 3 W Operating temperature: -10 to +55°C (14 to 131°F) Operating humidity: 30 to 90 %RH (non-condensing) Mounting: Panel flush mounting Weight: 300 g (0.66 lb) PERFORMANCE in percentage of max. span Accuracy Display: ±0.5 % ±20 digits (input 5 – 100 %) Output: ±0.1 % (DC output = display + output) Temp. coefficient: ±0.05 %/°C (±0.03 %/°F) Input resolution: Max. 16 bits Output resolution: Max. 14 bits Response time: ≤ 0.5 sec. (alarm output: 0 – 100 % at 90 % setpoint) ≤ 0.5 sec. (DC output: 0 – 90 %) Line voltage effect: ±0.1 % over voltage range Insulation resistance: ≥ 100 MΩ with 500 V DC Dielectric strength: 2000 V AC @ 1 minute (input to DC output to HH output or H output to L output or LL output to power to ground)

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 3/7 https://www.m-system.co.jp/ STANDARDS & APPROVALS EU conformity: EMC Directive EMI EN 61000-6-4 EMS EN 61000-6-2 Low Voltage Directive EN 61010-1 Measurement Category II (alarm output) Installation Category II (power) Pollution degree 2 Input or DC output to alarm output to power: Reinforced insulation (300 V) Input to DC output: Basic insulation (300 V) RoHS Directive Protection against access to the terminal blocks: Finger protection (VDE 0660-514) EXTERNAL VIEW (4) Max/Min Button (5) Alarm/ Button (6) Scale/ Button (7) Shift Button (8) Up Button (1) Main Display (2) Alarm Indicators (3) Function Indicators Alarm/ Scale/Max/Min Shift Up Zro HH H P L LL Spn D/P Tch Fnc Min Max

  • COMPONENT IDENTIFICATION No. COMPONENT FUNCTION (1) Main display Indicates present values, setting values and status of the unit. (2) Alarm indicators Indicate alarm status of the input signal. (3) Function indicators Indicate the status in each setting mode. (4) Max/Min button Used to switch the main display to show the present values, maximum values or minimum values etc. (5) Alarm/ button Used to con/f_i rm alarm setting value and to move on to the alarm and other setting modes; or to shift through setting items in each setting mode. (6) Scale/ button Used to move on to the scaling and other setting modes; or to shift through setting items in each setting mode. (7) Shift button Used to move on to the setting standby status of each setting mode and shift through display digits in each setting mode. (8) Up button Used to execute/cancel Forced Zero or to select setting values in each setting mode. Note: Refer to the operating manual for details on each function.

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 4/7 https://www.m-system.co.jp/ EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch) 96 (3.78) 48 (1.89) 103 (4.06) 95 (3.74) 2 (.08) 47 (1.85) 98.5 (3.88) 45 (1.77) 91.5 (3.60) 4–M3 SCREW ■ REAR VIEW

  • No Alarm Output • Alarm Output ■ FRONT VIEW ■ SIDE VIEW ■ TOP VIEW 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 20–M3 SCREW TERMINAL 2–M3 SCREW 10–M3 SCREW TERMINAL 6.6 (.26)

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 5/7 https://www.m-system.co.jp/ MOUNTING REQUIREMENTS unit: mm + 0.8 – 0 + 0.6 – 0 min. 120 min. 75 Panel thickness: 1.6 to 8.0 mm

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 6/7 https://www.m-system.co.jp/ SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM POWER U(+) V(–) LOAD Inductive Load (Coil) Varistor or CR Circuit

  • DC Powered LOAD Inductive Load (Coil) Diode, Varistor or CR Circuit ■ Relay Protection
  • AC Powered ■ ALARM OUTPUT CODE 1: N.O. contact, 4 points Ry Ry Ry Ry POWER U(+) Lc (COM ) Lb (NC) La (NO) Hc (COM ) Hb (NC) Ha (NO) V(–) ■ ALARM OUTPUT CODE 2: SPDT contact, 2 points Ry Ry Lc, LLc LLa La Hc, HHc Ha HHa LL OUTPUT L OUTPUT H OUTPUT L OUTPUT H OUTPUT HH OUTPUT POWER U(+) V(–) ■ ALARM OUTPUT CODE 0: No alarm output Digital Computation Display / Setting A/D Converter DC OUTPUT Isolation Output Driver Digital Computation DC OUTPUT Isolation Output Driver Digital Computation DC OUTPUT Isolation Output Driver Display / Setting A/D Converter Display / Setting A/D Converter INPUT H L COM INPUT H L COM INPUT H L COM Note: The section enclosed by broken line is only with DC output option. U

MODEL: 47LAC 47LAC SPECIFICATIONS ES-9511 Rev.13 Page 7/7 https://www.m-system.co.jp/

  • Input Terminal Assignments INPUT TYPE MEASURING INPUT (indicator) RANGE TERM INALS A2 0 – 2mA 2 – 3 A20 0 – 20mA 1 – 3A200 0 – 200 mA V0.1 0 – 0.1 V 2 – 3V1 0 – 1V V10 0 – 10V 1 – 3 Specifications are subject to change without notice.